Covington - TE-10 Infrared Testing.pdf

PDF 18 KB Posted

Attached to
Operations and Maintenance Services for IRS Covington, KY Facility
Solicitation number
TIRMS10R00006
Issued by

About this file

Technical Exhibit 10

View the file

Other files

File Type Posted
Covington Site Visit Sign In.pdf PDF
VENDOR QUESTIONS with answers COVINGTON.pdf PDF
TIRMS10R00006 7-14-10.pdf PDF
TIRMS10R00006-A0002 1 .rtf RTF text file
Covington PWS 7-14-10.pdf PDF
Wage Determination 6-22-10 Kenton.pdf PDF
HSPD_12_PIV Procedures Manual.pdf PDF
TE3.pdf PDF
TIRMS10R00006 Amendment 2.pdf PDF
TIRMS10R00006-A0001 1 .pdf PDF
Covington - TE-5 CMMS Inventory Changes 11-4-09.xls XLS spreadsheet
Key personnel Program Manager attachment.rtf RTF text file
QASP Covington.pdf PDF
Covington - TE 12 Non-Conformance Notification for Rework.pdf PDF
Covington - TE-9 Standards and Regulations.pdf PDF
Covington - TE-3 New PWS_12_9_09.xls XLS spreadsheet
Wage Determination Covington.pdf PDF
Key personnel CMMS Administrator attachment.rtf RTF text file
Key personnel Supervisory attachment.rtf RTF text file
Covington - TE-2 Facility Components and Equipment.pdf PDF
Covington - TE-11 Certification Requirements.pdf PDF
Covington - TE-4 PM Requirements.pdf PDF
NOTICE TO CONTRACTORS Covington.pdf PDF
Covington Offeror's letter.pdf PDF
Covington - TE-8 Terminology.pdf PDF
Covington - TE-6 reports_changes_included.pdf PDF
TIRMS10R00006.pdf PDF
Covington - TE-1 Facility Location Data.pdf PDF
Covington - TE-7 GFME 1-19-10.xls XLS spreadsheet
Performance Work Statement.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Cincinnati Service Center 201 W. River Center Blvd Covington, KY 41011 IRS Building Delegations Performance Work Statement

TECHNICAL EXHIBIT TE -10

Infrared Testing Requirements

IRS PM

CHECK DESCRIPTION FREQUENCY

E-26 Molded Case Breakers Less than 600 Volts and Greater than 400 amps One time in three years

E-28 Motor Starters Less Than 100 Hp One time in three years

E-30A Switchboards, Medium Voltage, (per cubicle) One time in three years

E-30B Switchboards Low Voltage, (per cubicle), One time in three years

E-37C Bus Duct, Low Voltage, & Connectors Copper - Per disconnect One time in three years

E-37D Bus Duct, Low Voltage, & Connectors Copper - Per 10 foot bus duct section

One time in three years

E-36 Automatic Transfer Switch One time in three years

E-33A High Voltage Network and, Power Type Transformer Dry Type Transformer - - Power Type Annual

E-33B High Voltage Network and, Power Type Transformer Dry Type Transformer - - Network Type Annual

E-34A Disconnects or Isolating Switch, Per Switch, Under 200 amps >600 VOLTS Annual

E-34B Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - 200 To 500 Amps Annual

E-34C Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - Over 500 Amps Annual

E-37A Bus Duct, Low Voltage, & Connectors Aluminum - Per disconnect Annual

E-37B Bus Duct, Low Voltage, & Connectors Aluminum - Per 10 foot bus duct section

Annual

E-37AA Bus Duct, Metal Enclosed, & Connectors Aluminum: - Per disconnect Annual

E37BB Bus Duct, Metal Enclosed, & Connectors Aluminum: - Per 10 foot bus duct section Annual

E-37CC Bus Duct, Metal Enclosed, & Connectors Aluminum: - Outdoors: Per disconnect Annual

E-37DD Bus Duct, Metal Enclosed, & Connectors Aluminum: - Outdoors: Per 10 foot bus duct section Annual

E-59 Uninterruptible Power System, Static Annual

E-35A Motor Control Center (MCC), under 100 hp - - 5 or fewer starters Annual

E-35B Motor Control Center (MCC), under 100 hp - - Each additional motor starter Annual

E-58 Power Distribution Unit Annual