This is a Fire Sprinkler System Specification Sheet prepared by Maddox Engineering, Inc. for the Tigerville Fire Department, located at 2605 SC Highway 414 in Travelers Rest, South Carolina (Greenville County). The project involves the installation of a wet pipe automatic fire sprinkler system in an existing two-story fire station. The system design covers two hazard areas: Area 1 (Light Hazard) protecting offices, restrooms, corridors, training rooms, break rooms, dayrooms, game rooms, and bunk rooms at a density of 0.10 gpm/ft² over 1,500 square feet with 100 gpm outside hose demand; and Area 2 (Ordinary Hazard Group 1) protecting truck bays, storage, mechanical spaces, yard equipment, fluid rooms, and gear rooms at a density of 0.15 gpm/ft² over 1,500 square feet with 250 gpm outside hose demand. The contractor shall install underground piping from the municipal water supply to the building and complete the wet pipe sprinkler system installation in accordance with NFPA 13-2019, IBC 2021, and IFC 2021 standards.
The project is based on water supply flow test data conducted on December 1, 2020, by Mason Fraize of BRRWC, showing a static pressure of 150 psi, residual pressure of 82 psi, and flow of 1,384 gpm from a municipal dead-end water supply through a 6-inch pipe located 20 feet horizontally from the building riser. The site is classified as Seismic Design Category C with a Site Classification D and seismic coefficient SS of 0.306. The specification sheet was prepared by Warren E. Maddox, P.E., of Maddox Engineering, Inc., and dated April 29, 2026, with revision number 0. No fire pump or on-site water storage is included in this design. The County of Greenville seeks a single-point-of-responsibility contractor to design, permit, install, test, and accept both the fire sprinkler system and a complete fire alarm system as part of the related contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Fire_Alarm_and_Fire_Sprinkler_Systems.pdf | ||
| 2025-08_Tigerville_FD_3-17-2026.pdf | ||
| Sample_Services_Agreement.pdf | ||
| COG_Sub_W9_.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Sprinkler System Specification Sheet (Per §40-10-250)
Project Data
Project name: Tigerville Fire Department
Location in South Carolina:
Address (street # & name): 2605 SC Hwy 414 State Project: Yes No
City: Travelers Rest, 29690 County: Greenville State Project #:
Water Supply Information (Flow test data must be less than 1 year old per §40-10-250(A)(1))
Date test conducted: 12/1/20 Static pressure (psi): 150 Residual pressure (psi): 82 Flow (gpm): 1384
Distances of test gauges relative to the base of the riser: Horizontal (ft): 20 Vertical (elevation difference in ft): 0
Source of water supply: Municipal dead-end Municipal circulation existing fire pump Other: Pipe Size (in.): 6
Test data by/from: Name: Mason Fraize Title: Tester
Organization: BRRWC Phone: 864-895-1719
Fire pump: New Existing
No Pump
Rated Capacity (gpm): Churn Pressure (psi):
Rated Pressure (psi): Pressure @ 150% flow (psi):
On-site water storage: Yes No New Existing Tank Other: Capacity (gal):
NFPA Hazard Classification (Attach continuation page when necessary)
Area #
Hazard Class or Code Reference
Description of Hazard Protected (including occupancy use group, and details of storage arrangement as applicable (including commodity class, rack arrangement/type, ceiling and storage height.))
1 Light Offices, restrooms, corridors, Training room, break room, dayroom, game room, bunk rooms, etc.
2 OH1 Truck Bays, Storage, Mechanical, Yard EQ., Fluid Rm., Gear Rm., etc.
Design Parameters
(Attach additional continuation pages when necessary)
Area # System Type Density(gpm/ft2)/Area(ft2), or Other (Reference code sections) Inside Hose (gpm) Outside Hose (gpm)
1 Wet 0.10 / 1500 0 100
2 Wet 0.15 / 1500 0 250
Seismic Design Data: SS= 0.306 Site Classification= D Seismic Design Category= C Codes and Standards (Attach continuation page when necessary)
Applicable Codes, Standards, & Editions (i.e. 2018 IBC, 2016 NFPA 13, etc.) for the Scope of Work on the Fire Sprinkler System
NFPA 13 – 2019, IBC – 2021, IFC - 2021
Scope of work (i.e. sprinkler system A.G. from 1'-0" A.F.F., U.G. from tap to 5'-0" outside, etc.) and notes (attach continuation page when necessary):
Contractor to install underground piping to the building and a wet pipe sprinkler system for the building.
Specifier's Information
Name: Warren E. Maddox P.E.
Certificate of Authorization
Professional Engineer’s Seal
Engineering services provided through a firm: Yes No
Firm name: Maddox Engineering, Inc.
Address: PO Box 26266
City: Greenville
State: SC Zip: 29616
Phone: 864-334-1875 Fax: NA
E-mail: warren@maddoxeng.pro
Revision No.: 0
Form Version: July 1, 2021
Page1of 1 Signature:
Date: 4/29/26