TFD_FSSSS_4-29-26.pdf
PDF 211 KB Posted
- Attached to
- Fire Sprinkler System
- Solicitation number
- RFP #27006
- Issued by
- Greenville County, South Carolina
About this file
This Fire Sprinkler System Specification Sheet documents the design requirements for a new automatic fire sprinkler system installation at the Tigerville Fire Department, located at 2605 SC Highway 414 in Travelers Rest, Greenville County, South Carolina. The County of Greenville is seeking sealed proposals from qualified fire sprinkler contractors to design, permit, install, test, and commission the system in an existing two-story fire station. The project encompasses underground piping to the building and a complete wet pipe sprinkler system designed to NFPA 13-2019, IBC 2021, and IFC 2021 standards. The system will serve two hazard areas: Area 1 (Light Hazard) covering approximately 1,500 square feet of offices, restrooms, corridors, training rooms, break rooms, dayrooms, game rooms, and bunk rooms, and Area 2 (Ordinary Hazard OH1) covering approximately 1,500 square feet of truck bays, storage, mechanical spaces, yard equipment areas, fluid rooms, and gear rooms. The design parameters specify wet pipe systems with densities of 0.10 gpm/ft² for Area 1 and 0.15 gpm/ft² for Area 2, with outside hose demands of 100 gpm and 250 gpm respectively.
Water supply for the system is sourced from a municipal dead-end connection with flow test data dated December 1, 2020, showing a static pressure of 150 psi, residual pressure of 82 psi, and flow of 1,384 gpm at 20 feet horizontal distance from the riser base. The project does not include an on-site fire pump, relying instead on the municipal water supply. Seismic design data indicates Site Classification D with a Seismic Design Category of C (SS=0.306). The specification sheet was prepared by Warren E. Maddox, P.E., of Maddox Engineering, Inc., located in Greenville, South Carolina, with a revision date of April 29, 2026, and carries a signature date confirming professional engineering authorization and oversight.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Fire_Sprinkler_System.pdf | ||
| 2025-08_Tigerville_FD_3-17-2026.pdf | ||
| COG_Sub_W9_.pdf | ||
| Sample_Services_Agreement.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Sprinkler System Specification Sheet (Per §40-10-250)
Project Data
Project name: Tigerville Fire Department
Location in South Carolina:
Address (street # & name): 2605 SC Hwy 414 State Project: Yes No
City: Travelers Rest, 29690 County: Greenville State Project #:
Water Supply Information (Flow test data must be less than 1 year old per §40-10-250(A)(1))
Date test conducted: 12/1/20 Static pressure (psi): 150 Residual pressure (psi): 82 Flow (gpm): 1384
Distances of test gauges relative to the base of the riser: Horizontal (ft): 20 Vertical (elevation difference in ft): 0
Source of water supply: Municipal dead-end Municipal circulation existing fire pump Other: Pipe Size (in.): 6
Test data by/from: Name: Mason Fraize Title: Tester
Organization: BRRWC Phone: 864-895-1719
Fire pump: New Existing
No Pump
Rated Capacity (gpm): Churn Pressure (psi):
Rated Pressure (psi): Pressure @ 150% flow (psi):
On-site water storage: Yes No New Existing Tank Other: Capacity (gal):
NFPA Hazard Classification (Attach continuation page when necessary)
Area #
Hazard Class or Code Reference
Description of Hazard Protected (including occupancy use group, and details of storage arrangement as applicable (including commodity class, rack arrangement/type, ceiling and storage height.))
1 Light Offices, restrooms, corridors, Training room, break room, dayroom, game room, bunk rooms, etc.
2 OH1 Truck Bays, Storage, Mechanical, Yard EQ., Fluid Rm., Gear Rm., etc.
Design Parameters
(Attach additional continuation pages when necessary)
Area # System Type Density(gpm/ft2)/Area(ft2), or Other (Reference code sections) Inside Hose (gpm) Outside Hose (gpm)
1 Wet 0.10 / 1500 0 100
2 Wet 0.15 / 1500 0 250
Seismic Design Data: SS= 0.306 Site Classification= D Seismic Design Category= C Codes and Standards (Attach continuation page when necessary)
Applicable Codes, Standards, & Editions (i.e. 2018 IBC, 2016 NFPA 13, etc.) for the Scope of Work on the Fire Sprinkler System
NFPA 13 – 2019, IBC – 2021, IFC - 2021
Scope of work (i.e. sprinkler system A.G. from 1'-0" A.F.F., U.G. from tap to 5'-0" outside, etc.) and notes (attach continuation page when necessary):
Contractor to install underground piping to the building and a wet pipe sprinkler system for the building.
Specifier's Information
Name: Warren E. Maddox P.E.
Certificate of Authorization
Professional Engineer’s Seal
Engineering services provided through a firm: Yes No
Firm name: Maddox Engineering, Inc.
Address: PO Box 26266
City: Greenville
State: SC Zip: 29616
Phone: 864-334-1875 Fax: NA
E-mail: warren@maddoxeng.pro
Revision No.: 0
Form Version: July 1, 2021
Page1of 1 Signature:
Date: 4/29/26