N42158-22-Q-0016 ATTACHMENT 1
TECHNICAL CAPABILITY CERTIFICATIONS
Vendor shall self-certify that the equipment and services proposed either meets or does not meet the Government’s minimum requirements specified in the associated Statement of Work (SOW) reference by initialing in the “YES” or “NO” area of the chart below.
Any deviation to the Government specifications shall be identified as such – A detailed explanation shall be provided for each negative response.
Note: In order to be considered for award, the table must be completed in its entirety and submitted with your quotation in accordance with FAR 52.212-1 Instructions of Offerors ADDENDUM.
In order to be considered technically acceptable, this form must be completed in its entirety.
Vendor shall certify that his product meets or does not meet each specification listed above by initialing in the applicable YES or NO box beside each specification.
Print Name Signature
Vendor’s Certification is as of __________________.
Date
Company Name
Technical Capabilities Statement Item #1 Specifications for One (1) Diesel Pump for JP-5 Shall be provided with the following capabilities, features, and specifications: YES NO Pump must be diesel powered.
Pump must provide 150 GPM (minimum) at 50 PSIG discharge pressure. Limit
RPM of motor is 1500 RPM (maximum).
Pump must be able to prime automatically and quickly for suction lifts of up to 28 feet without use of foot valves.
Pump must have a 40-gallon (minimum) diesel fuel tank Pump must be a separate compact unit mounted on a trailer type chassis with integral fuel tank.
The total weight including all fluids must be stenciled on the unit with minimum 1” high letters.
Pump must be capable of continuous operation.
Maximum working pressure of pump unit shall be 50 PSIG Hose connections: 3” suction and 2” discharge (Camlok).
Pump unit shall have discharge pressure gage (0 – 100 PSIG minimum range).
Pump unit shall have winterization features such as water jacket heaters and lube oil sump heaters to ensure rapid starting during freezing conditions.
Pump shall be cleaned and dry for JP-5 fuel service Provide one 3” suction hose 20’ length with male/female Camlok end fittings suitable for JP-5 fuel service.
Hose ends shall be blanked/capped to prevent debris from entering hose.