TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1756-IF8I_-en-e.pdf

PDF 7 MB Posted

Attached to
Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL Federal contract opportunity
Solicitation number
FA4610-22-R-0001
Issued by
Department of the Air Force Space Command

About this file

This announcement is a request for proposal for the Launch Operations Support Contract at Vandenberg Air Force Base in California. The RFP seeks to procure launch operations support services including mission planning, payload processing, launch processing, and range operations. Interested contractors must submit proposals by January 27, 2022. The North American Industry Classification System code for this effort is 561210 Facilities Support Services, with a small business size standard of $41.5 million. Attachments to the RFP include the performance work statement, security requirements, Department of Labor wage determinations for various labor categories, and contract data requirements. Exhibits specify data item descriptions and deliverables. Additional documents provide guidance on staffing plans, subcontracting, organizational conflict of interest mitigation, and proposal sections. Questions regarding the RFP are due by January 4, 2022. The 30th Space Wing at Vandenberg Air Force Base is the issuing agency.

View the file

Other files for this federal contract opportunity

Other files attached to Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL, newest first.
File Type Posted
L-1_Contractor Staffing Plan and Matrix_30Aug22.xlsx XLSX spreadsheet
TECH LIBRARY Workload Data Information for CLINs X003_X004.docx DOCX document
Conformed Solicitation Amendment - FA461022R00010005.pdf PDF
L-5_Section M dtd 19Nov21_Revised_02Feb2022.pdf PDF
RFP Amendment 0003 FA461022R00010003 SF30 signed 20220125.pdf PDF
RFP Amendment - FA461022R00010002 SF30 signed 20220118.pdf PDF
Amend 0001 Conformed SF33 - FA461022R00010001_20220112.pdf PDF
Atch 6_LOSC_DD254_7Jan2022.pdf PDF
Atch 11 Appendix D - Job Descriptions_redacted_11Jan2022.pdf PDF
Atch 11 2019-2024 CBA_Redacted_w_Appendix A_12Jan2022.pdf PDF
L-5_Section M dtd 19Nov21_Revised_11Jan2022.pdf PDF
22R0001 LOSC RFP QandA Consolidated.pdf PDF
Atch 1_LOSC PWS_dtd 09Dec2021_Final.pdf PDF
Atch 2_Appendix A_Property and Equipment Responibility List_Final_9Dec2021.xlsx XLSX spreadsheet
Atch 2_Appendix K_Compliance documents_Final_9Dec2021.pdf PDF
Atch 9 SCA WD 2015-5647_Rev 13_20211020.pdf PDF
Atch 10 SCA WD 1986-0431 Rev 54_20210219.pdf PDF
Exhibit A_CDRL_A003_Test Inspection Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A007_P-E Certification Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A013_Backflow Prevention Systems Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A017_Lead-Based Abatement Plan_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A022_Accident Incident Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A025_Generator Testing and Maint Report_Final_9Dec2021.pdf PDF
Exhibit B_LOSC_DID_Combined_9Dec2021.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Everight Alliance S1A_datasheet_022610.pdf PDF
TECH LIBRARY 1 System and Overview ACGAL020S000001_A.pdf PDF
TECH LIBRARY 5-HPGSA-PV-230-VTE-20210121.pdf PDF
TECH LIBRARY 8-LOSC Service Calls 1Jul19_30Jun20.pdf PDF
TECH LIBRARY 9-TA rollup WLF.pdf PDF
TECH LIBRARY 11-Workload Factor Hours_OY2.pdf PDF
TECH LIBRARY 13-CDRL_A001_Submittal example.pdf PDF
TECH LIBRARY 13-CDRL_A003_Testing and Certification_example.pdf PDF
TECH LIBRARY 13-CDRL_A024_Work Order Status Report_example.pdf PDF
TECH LIBRARY 13-CDRL_A010 Daily Maintenance And Repair Schedule_example.pdf PDF
TECH LIBRARY 13-CDRL_A014_Cathodic Protection Tracker_example.pdf PDF
L-5_Section M dtd 19Nov21_Final_9Dec2021.pdf PDF
Atch 6_LOSC_DD254_9Dec2021.pdf PDF
Atch 11 Appendix B - Wage Rate Tables (2019-2024)_Redacted.pdf PDF
Exhibit A_CDRL_A002_GFP Inventory Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A010_Daily Maintenance and Repair Schedule_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A014_Cathodic Protection Booklet_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A020_Contract Funds Status Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A027_Facility Assessment Report_Final_9Dec2021.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1444-um001_-en-p.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1407-CGCM-DLR.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1444-td001_-en-p.pdf PDF
TECH LIBRARY 1 Drawings - As Builts - ACGAL020S000002_E1.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Everight Alliance S1AmanualRev022610V13.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Phoenix Contact 2814100.pdf PDF
TECH LIBRARY 10-Fences_Gates_WLF.pdf PDF
Show all 50

Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Data 1756 ControlLogix I/O Specifications 1756 Series Catalog Numbers

The ControlLogix® architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers.

Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.

Topic Page

Available 1756 I/O Modules 2

ControlLogix I/O Accessories 244

Additional Resources 246

Available 1756 I/O Modules

You can select these types of digital I/O modules.

Digital I/O Type Description

Diagnostic These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number.

Electronic fusing These modules have internal electronic fusing to prevent too much current from flowing through the module. These modules have an E at the end of the catalog number.

Individually isolated These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.

I/O Type Cat. No. Page Cat. No. Page

AC digital 1756-IA8D

1756-IA16

1756-IA16I

1756-IA32

1756-IM16I

1756-IN16

1756-LSC8XIB8I

1756-OA8D

1756-OA8E

1756-OA16

1756-OA16I

1756-ON8

DC digital 1756-IB16

1756-IB16D

1756-IB16I

1756-IB16IF

1756-IB16IOSE

1756-IB32

1756-IC16

1756-IG16

1756-IH16I

1756-IH16ISOE

1756-IV16

1756-IV32

1756-OB8

1756-OB8EI

1756-OB8I

1756-OB16D

1756-OB16E

1756-OB16I

1756-OB16IEF

1756-OB16IEFS

1756-OB16IS

1756-OB32

1756-OC8

1756-OG16

1756-OH8I

1756-OV16E

1756-OV32E

Contact 1756-OW16I

1756-OX8I

Analog 1756-IF6CIS

1756-IF6I

1756-IF8

1756-IF8I

1756-IF16

1756-IF4FXOF2F

1756-IR6I

1756-IRT8I

1756-IR12

1756-IT6I

1756-IT6I2

1756-IT16

1756-OF4

1756-OF6CI

1756-OF6VI

1756-OF8

1756-OF8I

HART interface 1756-IF8H

1756-IF8IH

1756-IF16H

1756-OF8H

1756-OF8IH

Specialty 1756-CFM

1756-HSC

1756-LSC8XIB8I

1756-PLS

2 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

1756-IA8D

ControlLogix 120V AC diagnostic input module

Table 1 - Diagnostic Specifications - 1756-IA8D

Attribute 1756-IA8D

Open wire Off-state leakage current 1.5 mA min

Loss of power Transition range 46…85V AC

Timestamp of diagnostics ±1 ms

Table 2 - Technical Specifications - 1756-IA8D

Attribute 1756-IA8D

Inputs 8 diagnostic (4 points/group)

Voltage category 120V AC 50/60 Hz

Operating voltage range(1) 79…132V AC, 47…63 Hz

Input voltage, nom 120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms

Current draw @ 5.1V 100 mA

Current draw @ 24V 3 mA

Total backplane power 0.58 W

Power dissipation, max 4.5 W @ 60 °C (140 °F)

+5V

47 kΩ, 1/2 W, 5% Resistor

47 kΩ, 1/2 W 5% Resistor

Not Used

L2-0

L2-0

L2-0

L2-0

L2-1

L2-1

L2-1

L2-1

L2-1

L1-0 Loss of Field Power

IN-0

IN-1

IN-2

IN-3

IN-4

IN-5

IN-6

IN-7

L1-1 Loss of Field Power

Daisy Chain to Other RTBs

Group

Group 0

Group 1Group 1

L2

L1

ControlLogix Backplane Interface

ControlLogix Backplane Interface

Display

Simplified Schematic

Input

Display Open Wire

GND

GND

+5V

AC INPUT

ST

FLT

0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7 O K

1756-IA8D

Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 3

Thermal dissipation 15.35 BTU/hr

Off-state voltage, max 20V

Off-state current, max 2.5 mA

On-state current, min 5 mA @ 74V AC

On-state current, max 16 mA @ 132V AC

Inrush current, max 250 mA

Input impedance, max 8.25 kΩ @ 132V AC, 60 Hz

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBNH

1756-TBSH

RTB keying User-defined mechanical

Slot width 1

Wire category 1(2)

North American temperature code T4A

Enclosure type None (open-style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.

(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 3 - Environmental Specifications - 1756-IA8D

Attribute 1756-IA8D

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Table 2 - Technical Specifications - 1756-IA8D (Continued)

Attribute 1756-IA8D 4 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 Hz sine-wave 80% AM from 150 kHz…80 MHz

Table 4 - Certifications - 1756-IA8D

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IA8D

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

Table 3 - Environmental Specifications - 1756-IA8D (Continued)

Attribute 1756-IA8D Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 5 http://www.ab.com

1756-IA16

ControlLogix 120V AC input module

Table 5 - Technical Specifications - 1756-IA16

Attribute 1756-IA16

Inputs 16 (8 points/group)

Voltage category 120V AC 50/60 Hz

Operating voltage range(1) 74…132V AC, 47…63 Hz

Input voltage, nom 120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms

Current draw @ 5.1V 100 mA

Current draw @ 24V 2 mA

Total backplane power 0.58 W

Power dissipation, max 5.8 W @ 60 °C (140 °F)

Thermal dissipation 18.41 BTU/hr

Off-state voltage, max 20V

Off-state current, max 2.5 mA

On-state current, min 5 mA @ 74V AC

On-state current, max 13 mA @ 132V AC

L2 L1

Daisy Chain to Other RTBs

Group 0

Group 0

Group 1Group 1

IN-1

IN-3

IN-5

IN-7

L2-0

IN-9

IN-11

IN-13

IN-15

L2-1

IN-0

IN-2

IN-4

IN-6

L2-0

IN-8

IN-10

IN-12

IN-14

L2-1

Simplified Schematic

ControlLogix Backplane Interface

Display

+5V

L2-0

IN-O

GND

AC INPUT

ST

FLT

0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7 O K

1756-IA16

6 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Inrush current, max 250 mA peak (decaying to <37% in 22 ms, without activation)

Input impedance, max 10.15 kΩ @ 132V AC, 60 Hz

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1400V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBNH

1756-TBSH

RTB keying User-defined mechanical

Slot width 1

Wire category 1(2)

North American temperature code T4

Enclosure type None (open-style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.

(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 6 - Environmental Specifications - 1756-IA16

Attribute 1756-IA16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Table 5 - Technical Specifications - 1756-IA16 (Continued)

Attribute 1756-IA16 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 7

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand

IEEE C37.90.1

3 kV

Table 7 - Certifications - 1756-IA16

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IA16

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Table 6 - Environmental Specifications - 1756-IA16 (Continued)

Attribute 1756-IA16 8 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

1756-IA16I

ControlLogix 120V AC isolated input module

Table 8 - Technical Specifications - 1756-IA16I

Attribute 1756-IA16I

Inputs 16 individually isolated

Voltage category 120V AC 50/60 Hz

Operating voltage range(1) 79…132V AC, 47…63 Hz

Input voltage, nom 120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms

Current draw @ 5.1V 125 mA

Current draw @ 24V 3 mA

Total backplane power 0.71 W

Power dissipation, max 4.9 W @ 60 °C (140 °F)

Thermal dissipation 16.71 BTU/hr

Off-state voltage, max 20V

Nonisolated Wiring

Isolated Wiring

Daisy Chain to Other RTBs

L2-0 L2-0 L2-1

L2-2

L2-3

L2-8

L2-4

L2-5

L2-6

L2-7

Not Used

L2-9

L2-10

L2-11

L2-12

L2-13 L2-14

L2-15

L2-15

IN-0

IN-1

IN-2

IN-3

IN-8

IN-4

IN-5

IN-6

IN-7

Not Used

IN-9

IN-10

IN-11

IN-12

IN-13

IN-14

IN-15

Not Used

L2-2

L2-4

L2

L1

L1-0

L1-2

L1-4

Jumper Bar (Cut to Length)

ControlLogix Backplane Interface

Display

Simplified Schematic

+5V

L2-0

IN-O

GND

Additional jumper bars are available as cat. no. 1756-JMPR.

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O K

AC INPUT

1756-IA161

Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 9

Off-state current, max 2.5 mA

On-state current, min 5 mA @ 79V AC, 47…63 Hz

On-state current, max 15 mA @ 132V AC, 47…63 Hz

Inrush current, max 250 mA

Input impedance, max 8.8 kΩ @ 132V AC, 60 Hz

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 125V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1200V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1(2)

North American temperature code T4A

Enclosure type None (open-style)

(1) UL certification for 120V 50/60 Hz nominal. Rockwell Automation specified to 74…132V, 47…63 Hz.

(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 9 - Environmental Specifications - 1756-IA16I

Attribute 1756-IA16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Table 8 - Technical Specifications - 1756-IA16I (Continued)

Attribute 1756-IA16I 10 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand

IEEE C37.90.1

3 kV

Table 10 - Certifications - 1756-IA16I

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IA16I

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Table 9 - Environmental Specifications - 1756-IA16I (Continued)

Attribute 1756-IA16I Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 11

1756-IA32

ControlLogix AC (74…132V) input module

Table 11 - Technical Specifications - 1756-IA32

Attribute 1756-IA32

Inputs 32 (16 points/group)

Voltage category 120V AC 50/60 Hz

Operating voltage range 74…132V AC, 47…63 Hz

Input voltage, nom 120V AC 50/60 Hz

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 1.5 ms nom/10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 1 ms nom/8 ms max + filter time User-selectable filter time: 9 or 18 ms

Current draw @ 5.1V 165 mA

Current draw @ 24V 2 mA

Total backplane power 0.9 W

Power dissipation, max 6.1 W @ 60 °C (140 °F)

Thermal dissipation 20.8 BTU/hr

Off-state voltage, max 20V

Off-state current, max 2.5 mA

On-state current, min 5 mA @ 74V AC

On-state current, max 15 mA @ 132V AC

IN-0

IN-2

IN-4

IN-6

IN-8

IN-10

IN-12

IN-14

IN-16

IN-18

IN-20

IN-22

IN-24

IN-26

IN-28

IN-30

L2-1

L2-0

IN-1

IN-3

IN-5

IN-7

IN-9

IN-11

IN-13

IN-15

L2-0

IN-17

IN-19

IN-21

IN-23

IN-25

IN-27

IN-29

IN-31

L2-1

L1

L2

Daisy Chain to Other RTBs

1 puorG1 puorG

0 puorG0 puorG

Simplified Schematic

ControlLogix Backplane Interface

Display

+5V

L2-0

IN-O

GND

AC INPUT

O K

ST 0 1 2 3 4 5 6 7

ST 8 9

0 21 3 4 5

1 1 1 11

ST 6 7

8 09 1 2 3

1 2 2 221 1

ST 4 5

6 87 9 0 1

2 2 2 332 2

1756-IA32

12 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Inrush current, max 390 mA

Input impedance, max 14.0 kΩ @ 132V AC, 60 Hz

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1(1)

North American temperature code T4

Enclosure type None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 12 - Environmental Specifications - 1756-IA32

Attribute 1756-IA32

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Table 11 - Technical Specifications - 1756-IA32 (Continued)

Attribute 1756-IA32 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 13

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Table 13 - Certifications - 1756-IA32

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IA32

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Table 12 - Environmental Specifications - 1756-IA32 (Continued)

Attribute 1756-IA32 14 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

1756-IB16

ControlLogix DC (10…31.2V) input module

Table 14 - Technical Specifications - 1756-IB16

Attribute 1756-IB16

Inputs 16 (8 points/group)

Voltage category 12/24V DC sink

Operating voltage range 10…31.2V DC

Input voltage, nom 24V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 290 μs nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 700 μs nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms

Current draw @ 5.1V 100 mA

Current draw @ 24V 2 mA

Total backplane power 0.56 W

Power dissipation, max 5.1 W @ 60 °C (140 °F)

Thermal dissipation 17.39 BTU/hr

Off-state voltage, max 5V

Off-state current, max 1.5 mA

On-state current, min 2 mA @ 10V DC

On-state current, max 10 mA @ 31.2V DC

IN-9

IN-11

IN-13

IN-15

GND-1

IN-1

IN-3

IN-5

IN-7

GND-0

IN-8

IN-10

IN-12

IN14

GND-1

IN-0

IN-2

IN-4

IN-6

GND-0

Daisy Chain to Other RTBs

Group 0

Group 0

Group 1Group 1

DC COM

ControlLogix Backplane Interface

Simplified Schematic

Display

GND

GND-0

IN-0

+5V

DC INPUT

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O K

1756-IB16

Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 15

Inrush current, max 250 mA peak (decaying to < 37% in 22 ms, without activation)

Input impedance, max 3.12 kΩ @ 31.2V DC

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBNH

1756-TBSH

RTB keying User-defined mechanical

Slot width 1

Wire category 1(1)

North American temperature code T3C

IEC temperature code T3

Enclosure type None (open-style)

Reverse polarity protection Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 15 - Environmental Specifications - 1756-IB16

Attribute 1756-IB16

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Table 14 - Technical Specifications - 1756-IB16 (Continued)

Attribute 1756-IB16 16 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Radiated RF immunity

IEC 61000-4-3

10V/m with 1kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand

IEEE C37.90.1

3 kV

Table 16 - Certifications - 1756-IB16

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with:

• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

• EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Table 15 - Environmental Specifications - 1756-IB16 (Continued)

Attribute 1756-IB16 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 17

1756-IB16D

ControlLogix DC (10…30V) diagnostic input module

Table 17 - Diagnostic Specifications - 1756-IB16D

Attribute 1756-IB16D

Open wire Off-state leakage current 1.2 mA min

Timestamp of diagnostics ±1 ms

Table 18 - Technical Specifications - 1756-IB16D

Attribute 1756-IB16D

Inputs 16 diagnostic (4 points/group)

Voltage category 12/24V DC sink

Operating voltage range 10…30V DC

Input voltage, nom 24V DC

Leakage Resistor

Leakage Resistor

Daisy Chain to Other RTBs

Group 0

Group 1

Group 2

Group 3

Group

Group

Group

Group

IN-0

IN-1

IN-2

IN-3

IN-8

IN-4

IN-5

IN-6

IN-7

Not Used

IN-9

IN-10

IN-11

IN-12

IN-13

IN-14

IN-15

Not Used

GND-0

GND-0

GND-0

GND-0

GND-2

GND-1

GND-1

GND-1

GND-1

Not Used

GND-2

GND-2

GND-2

GND-3

GND-3

GND-3

GND-3

GND-3

DC COM

ControlLogix Backplane Interface

Simplified Schematic

Display

GND

Open Wire

GND-0

IN-0

Input +5V

FLT 8 9 10 11 12 13 14 15

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O K

FLT 0 1 2 3 4 5 6 7

DC INPUT

DIAGNOSTIC

Recommended Leakage Resistor Size 1/4 W, 5% Supply Voltage

3.9K 10V DC

5.6K 12V DC

15K 24V DC

20K 30V DC

1756-IB16D

18 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 340 μs nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms

Hardware delay: 740 μs nom/4 ms max + filter time User-selectable filter time: 0, 1, 9, or 18 ms

Current draw @ 5.1V 150 mA

Current draw @ 24V 3 mA

Total backplane power 0.84 W

Power dissipation, max 5.8 W @ 60 °C (140 °F)

Thermal dissipation 19.78 BTU/hr

Off-state voltage, max 5V

Off-state current, max 1.5 mA

On-state current, min 2 mA @ 10V DC

On-state current, max 13 mA @ 30V DC

Inrush current, max 250 mA

Input impedance, max 2.31 kΩ @ 30V DC

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1(1)

North American temperature code T3C

IEC temperature code T3

Enclosure type None (open-style)

Reverse polarity protection Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 18 - Technical Specifications - 1756-IB16D (Continued)

Attribute 1756-IB16D Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 19

Table 19 - Environmental Specifications - 1756-IB16D

Attribute 1756-IB16D

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz 20 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Table 20 - Certifications - 1756-IB16D

Certifications(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16D

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Ex European Union 94/9/EC ATEX Directive, compliant with:

• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

• EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 21

1756-IB16I

ControlLogix DC (10…30V) isolated input module

1 2

3 4

5 6

7 8

01 9

21 11

41 31

61 51

81 71

02 91

22 12

42 32

62 52

82 72

03 92

23 13

43 33

63 53

Nonisolated Wiring

Isolated Wiring

Daisy Chain to Other RTBs

GND-0

GND-1

GND-2

GND-3

GND-8

GND-4

GND-5

GND-6

GND-7

Not Used

GND-9

GND-10

GND-11

GND-12

GND-13

GND-14

GND-15

GND-15

IN-0

IN-1

IN-2

IN-3

IN-8

IN-4

IN-5

IN-6

IN-7

Not Used

IN-9

IN-10

IN-11

IN-12

IN-13

IN-14

IN-15

Not Used

DC-5 (-)

DC (-)

Jumper Bar (Cut to Length)

DC-6 (-)

DC-5 (+)

DC-6 (+)

DC (+)

DC-0 (+)

DC-1 (+)

DC-0 (-)

DC-1 (-)

Source Input Wiring

Sink Input Wiring

ControlLogix Backplane Interface

Simplified Schematic

Display

GND-0

GND

IN-0

+5V

Additional jumper bars are available as cat. no. 1756-JMPR.

DC INPUT

ST 0 1 2 3 4 5 6 7

ST 8 9 10 1112 13 14 15

O K

1756-IB161

22 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Table 21 - Technical Specifications - 1756-IB16I

Attribute 1756-IB16I

Inputs 16 individually isolated

Voltage category 12/24V DC sink/source

Operating voltage range 10…30V DC

Input voltage, nom 24V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms

Current draw @ 5.1V 100 mA

Current draw @ 24V 3 mA

Total backplane power 0.58 W

Power dissipation, max 5 W @ 60 °C (140 °F)

Thermal dissipation 17.05 BTU/hr

Off-state voltage, max 5V

Off-state current, max 1.5 mA

On-state current, min 2 mA @ 10V DC

On-state current, max 10 mA @ 30V DC

Inrush current, max 250 mA peak (decaying to < 37% in 22 ms, without activation)

Input impedance, max 3 kΩ @ 30V DC

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1(1)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

North American temperature code T4

IEC temperature code T4

Enclosure type None (open-style)

Reverse polarity protection Yes Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 23

Table 22 - Environmental Specifications - 1756-IB16I

Attribute 1756-IB16I

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 1, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand

IEEE C37.90.1

3 kV 24 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Table 23 - Certifications - 1756-IB16I

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16I

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with:

• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 25

1756-IB16IF

ControlLogix DC (10…30V) sinking or sourcing, isolated, fast input module

01 9

21 11

41 31

61 51

81 71

02 91

22 12

42 32

62 52

82 72

03 92

23 13

43 33

63 53

GND-0

GND-1

GND-2

GND-3

GND-4

GND-5

GND-6

GND-7

Not Used

IN-0

IN-1

IN-2

IN-3

IN-4

IN-5

IN-6

IN-7

Not Used Not Used

DC-5 (-)

DC (-)

DC-6 (-)

DC-5 (+)

DC-6 (+)

DC (+)

DC-1 (+)

DC-2 (+)

DC-1 (-)

DC-2 (-)

GND-8

GND-9

GND-10

GND-11

GND-12

GND-13

GND-14

GND-15

GND-15

IN-8

IN-9

IN-10

IN-11

IN-12

IN-13

IN-14

IN-15

Simplified Schematic

ControlLogix Backplane Interface

Display

GND-x

IN-x

1756-IB16IF

Current Limiter

Daisy Chain to Other RTBs

Source Input Wiring

Jumper Bar Cut to Length

Nonisolated Wiring

Isolated Wiring

Sink Input Wiring

Additional jumper bars may be purchased by using catalog number 1756-JMPR.

DC INPUT

PEER DEVICE

O0 1 2 3 4 5 6 7

8 9 10 11 12 13 14 15 K

ST

ST

Opto-isolator 26 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Table 24 - Technical Specifications - 1756-IB16IF

Attribute 1756-IB16IF

Inputs 16 individually isolated

Voltage category 12/24V DC sink/source

Operating voltage range 10…30V DC

Input voltage, nom 24V DC

Input delay time (screw to backplane) Off to On On to Off

14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs 14 μs nom/23 μs max + user-configurable filter time of 0…30,000 μs

Current draw @ 5.1V 275 mA

Current draw @ 24V 3 mA

Total backplane power 1.47 W

Power dissipation 3.8 W @ 60 °C (140 °F)

Thermal dissipation 12.97 BTU/hr

Off-state voltage, max 5V

Off-state current, max 1.5 mA

On-state current, min 2 mA @ 10V DC

On-state current, max 5 mA @ 30V DC

Input impedance, max 6 kΩ @ 30V DC

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ± 4 μs for inputs < 4 kHz ± 13 μs for inputs > 4 kHz

Isolation voltage 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input

Module keying Electronic, software configurable

Removable terminal block housing 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1 on signal ports(1)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

North American temperature code T4A

IEC temperature code T4

Enclosure type None (open-style)

Reverse polarity protection Yes Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 27

Table 25 - Environmental Specifications - 1756-IB16IF

Attribute 1756-IB16IF

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Emissions CISPR 1, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz 28 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Table 26 - Certifications - 1756-IB16IF

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16IF

c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with:

• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 29

1756-IB16ISOE

ControlLogix DC (10…55V) sequence of events input module

Table 27 - Technical Specifications - 1756-IB16ISOE

Attribute 1756-IB16ISOE

Inputs 16 individually isolated, sequence of events

Voltage category 24/48V DC sink/source

Operating voltage range 10…55V DC

Input voltage, nom 24V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 10 μs nom/20 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 μs (FIFO) or 625 μs (Coordinated System Time per point) Hardware delay: 25 μs nom/50 μs max + firmware scan: up to 25 μs + filter time: 0…50 ms + ASIC delay: 175 μs (FIFO) or 625 μs (Coordinated System Time per point)

Current draw @ 5.1V 320 mA

Current draw @ 24V 2 mA

Total backplane power 1.7 W

Power dissipation, max 5.5 W @ 60 °C (140 °F)

Thermal dissipation 17.22 BTU/hr

Nonisolated Wiring

Isolated Wiring

Daisy Chain to Other RTBs

DC (-)

Jumper Bar (Cut to Length)

)+( 6-CD)-( 6-CD

DC (+)

DC-0 (+)

DC-1 (+)

DC-0 (-)

DC-5 (-)

IN-0

IN-1

IN-2

IN-3

IN-8

IN-4

IN-5

IN-6

IN-7

Not Used

IN-9

IN-10

IN-11

IN-12

IN-13

IN-14

IN-15

Not Used

GND-0

GND-1

GND-2

GND-3

GND-8

GND-4

GND-5

GND-6

GND-7

Not Used

GND-9

GND-10

GND-11

GND-12

GND-13

GND-14

GND-15

GND-15

DC-5 (+)

Sink Input Wiring

Source Input WiringSource Input Wiring

Sink Input WiringControlLogix Backplane

Interface

Simplified Schematic

Display

GND-0

IN-0

Electronic Current Limit Circuit

+5V

Additional jumper bars are available as cat. no. 1756-JMPR.

SOE INPUT

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O K

1756-IB16ISOE

30 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

Off-state voltage, max 5V

Off-state current, max 1.5 mA

On-state current, min 2.0 mA @ 9V DC

On-state current, nom 4.5 mA @ 24…31V DC

On-state current, max 5.1 mA @ 48…55V DC

Input impedance, max 10.8 kΩ @ 55V DC

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±100 μs

Isolation voltage 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1(1)

North American temperature code T4

IEC temperature code T4

Enclosure type None (open-style)

Reverse polarity protection Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 28 - Environmental Specifications - 1756-IB16ISOE

Attribute 1756-IB16ISOE

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max 60 °C (140 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50 g

Table 27 - Technical Specifications - 1756-IB16ISOE (Continued)

Attribute 1756-IB16ISOE Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 31

Emissions CISPR 11, Class A

ESD immunity

IEC 61000-4-2

6 kV contact discharges 8 kV air discharges

Radiated RF immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80… 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4

±4 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Oscillatory surge withstand

IEEE C37.90.1

2.5 kV

Table 29 - Certifications - 1756-IB16ISOE

Certification(1)

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16ISOE

UL UL Listed Industrial Control Equipment. See UL File E65584.

CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE European Union 2004/108/IEC EMC Directive, compliant with:

• EN 61326-1; Meas./Control/Lab., Industrial Requirements

• EN 61000-6-2; Industrial Immunity

• EN 61000-6-4; Industrial Emissions

• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex European Union 94/9/EC ATEX Directive, compliant with:

• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

• EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

KC Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Table 28 - Environmental Specifications - 1756-IB16ISOE (Continued)

Attribute 1756-IB16ISOE 32 Rockwell Automation Publication 1756-TD002I-EN-E - June 2015

1756-IB32

ControlLogix DC (10…31.2V) input module

Table 30 - Technical Specifications - 1756-IB32

Attribute 1756-IB32

Inputs 32 (16 points/group)

Voltage category 12/24V DC sink

Operating voltage range 10…31.2V DC

Input voltage, nom 24V DC

Input delay time (screw to backplane) Off to On

On to Off

Hardware delay: 380 μs max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 420 μs max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms

Current draw @ 5.1V 120 mA

Current draw @ 24V 2 mA

Total backplane power 0.66 W

Power dissipation, max 6.2 W @ 60 °C (140 °F)

Thermal dissipation 21.1 BTU/hr @ 60 °C (140 °F)

Off-state voltage, max 5V

Off-state current, max 2.27 mA

On-state current, min 4.8 mA @ 10V DC

On-state current, max 5.5 mA @ 31.2V DC

Inrush current, max 250 mA (decaying to < 37% in 22 ms, without activation)

Daisy Chain to Other RTBs

DC COM

0 puorG0 puorG

1 puorG1 puorG

IN-1

IN-3

IN-5

IN-7

GND-0

IN-9

IN-11

IN-13

IN-15

GND-1

IN-17

IN-19

IN-21

IN-23

IN-25

IN-27

IN-29

IN-31

IN-0

IN-2

IN-4

IN-6

GND-0

IN-8

IN-10

IN-12

IN-14

GND-1

IN-16

IN-18

IN-20

IN-22

IN-24

IN-26

IN-28

IN-30

ControlLogix Backplane Interface

Simplified Schematic

Display

GND-0

GND

IN-0

+5V

DC INPUT

O K

ST 0 1 2 3 4 5 6 7

ST 8 9

0 21 3 4 5

1 1 1 11

ST 6 7

8 09 1 2 3

1 2 2 221 1

ST 4 5

6 87 9 0 1

2 2 2 332 2

Current Limiter

1756-IB32

Rockwell Automation Publication 1756-TD002I-EN-E - June 2015 33

Input impedance, max 5.67 kΩ @ 31.2V DC

Cyclic update time 200 μs…750 ms

Change of state Software configurable

Timestamp of inputs ±200 μs

Isolation voltage 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s

Module keying Electronic, software configurable

Removable terminal block 1756-TBCH

1756-TBS6H

RTB keying User-defined mechanical

Slot width 1

Wire category 1 - on signal ports(1)

North American temperature code T4

IEC temperature code T4

Enclosure type None (open-style)

Reverse polarity protection Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual.