TECH LIBRARY 13-CDRL_A003_Testing and Certification_example.pdf

PDF 844 KB Posted

Attached to
Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL Federal contract opportunity
Solicitation number
FA4610-22-R-0001
Issued by
Department of the Air Force Space Command

About this file

This document contains a final request for proposal for the Launch Operations Support Contract at Vandenberg Air Force Base in California. The solicitation seeks proposals to provide facilities support services including maintenance and inspection of roofs, ladders, pressure vessels, and cranes/hoists. Interested offerors must submit proposals by 27 January 2022. The North American Industry Classification System code for this effort is 561210 with a small business size standard of $41.5 million. The incumbent contractor's performance will be evaluated based on inspection reports and test results included in the technical library files for various facilities and equipment. Award is expected to be made in 2022 to provide launch operations support through 2027.

View the file

Other files for this federal contract opportunity

Other files attached to Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL, newest first.
File Type Posted
Solicitation Amendment FA461022R00010005 SF 30.pdf PDF
RFP Amendment 0003 Conf SF33 - FA461022R00010003.pdf PDF
L-4_Section L dtd 19Nov21_Revised_18Jan2022.pdf PDF
Atch 2_Appendix A_Property and Equipment Responibility List_Final_6Jan2022.xlsx XLSX spreadsheet
Atch 7 DB WD CA20210018_Mod 28_20211203_12Jan2022.pdf PDF
Atch 10 SCA WD 1986-0431 Rev 54_20210219_12Jan2022.pdf PDF
Atch 11 CBA-2019-12949_12Jan2022.pdf PDF
L-4_Section L dtd 19Nov21_Revised_10Jan2022.pdf PDF
Solicitation Amendment FA461022R00010001_20220112(S).pdf PDF
TECH LIBRARY 0 List of documents_Tech Ref Library_07Jan2022.pdf PDF
L-1_Contractor Staffing Plan and Matrix_Final_9Dec2021.xlsx XLSX spreadsheet
L-3 _OCI_MitigationPlanChecklist_Final_9Dec2021.pdf PDF
L-4_Section L dtd 19Nov21_Final_9Dec2021.pdf PDF
Atch 2_Appendix C_D_E_F_Final_9Dec2021.pdf PDF
Atch 2_Appendix H_Acronyms and Abbreviations_Final_9Dec2021.pdf PDF
Atch 3_LOSC_GFP Attachment (cover page)_9Dec2021.docx DOCX document
Atch 8 SCA WD 2015-5637_Rev 19_20211020.pdf PDF
Exhibit A_CDRL_A004_Power Plant Operation and Maintenance Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A008_P-E Responsibility List_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A018_Contract Work Breakdown Structure_Final_9Dec2021.pdf PDF
TECH LIBRARY 0 List of documents Tech Ref Library_09DEC21.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1756-um540_-en-p 1756-IRT8I.pdf PDF
TECH LIBRARY 1 Func Desc Instrux - HMI - ACGAL020S000003_B.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1756-IB32 Contact Input Module.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals EthosEnergy Customer Support Services.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Axiomatic corrected current-converter.pdf PDF
TECH LIBRARY 3-8310-PV-182-VTE-20210225.pdf PDF
TECH LIBRARY 12-Pillar Point Outfall Storm Drain Inspection Checklist example.pdf PDF
TECH LIBRARY 13-CDRL_A004_Power_example.pdf PDF
TECH LIBRARY 13-CDRL_A015_Solid Waste Report_example.pdf PDF
Atch 1_LOSC PWS_dtd 09Dec2021_Final.pdf PDF
Atch 2_Appendix A_Property and Equipment Responibility List_Final_9Dec2021.xlsx XLSX spreadsheet
Atch 2_Appendix K_Compliance documents_Final_9Dec2021.pdf PDF
Atch 9 SCA WD 2015-5647_Rev 13_20211020.pdf PDF
Atch 10 SCA WD 1986-0431 Rev 54_20210219.pdf PDF
Exhibit A_CDRL_A003_Test Inspection Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A007_P-E Certification Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A013_Backflow Prevention Systems Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A017_Lead-Based Abatement Plan_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A022_Accident Incident Report_Final_9Dec2021.pdf PDF
Exhibit A_CDRL_A025_Generator Testing and Maint Report_Final_9Dec2021.pdf PDF
Exhibit B_LOSC_DID_Combined_9Dec2021.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Rockwell 1756-IF8I_-en-e.pdf PDF
TECH LIBRARY 1 SVPP Supplier Manuals Everight Alliance S1A_datasheet_022610.pdf PDF
TECH LIBRARY 1 System and Overview ACGAL020S000001_A.pdf PDF
TECH LIBRARY 5-HPGSA-PV-230-VTE-20210121.pdf PDF
TECH LIBRARY 8-LOSC Service Calls 1Jul19_30Jun20.pdf PDF
TECH LIBRARY 9-TA rollup WLF.pdf PDF
TECH LIBRARY 11-Workload Factor Hours_OY2.pdf PDF
TECH LIBRARY 13-CDRL_A001_Submittal example.pdf PDF
Show all 50

Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SAMPLE

LINE FAC NBR DESCRIPTION ADD'L DETAIL TEST NAME TEST DATE DCR RATING NEXT TEST DATE NOTES 1 51 COMM, TMTR RCVR Ground to Air Transmit/Receive Site Annual Inspection 8162018 8162019 + 2 67 WTR FR PMP STN Oak Mtn Fire Pumphouse Annual Inspection 8162018 (-) 8162019 3 175 RDR TMTR COMP BLDG Former AN/MPS-39 MOTR Radar Bldg Annual Inspection 9032018 (+) 9032019 - 4 177 RAD RELAY FCLTY Cable Hut #16 Annual Inspection 9142018 (+) 9142019 + 5 178 RDR TMTR COMP BLDG Weather Tower #80 at Tranq Pk Annual Inspection 10012018 10012019 6 181 MSL/SPACE RSCH TST DOAMS Optical Telescope Annual Inspection 10062018 10062019 - 7 185 ELEC PWR S BLD Tranquillion Pk Generators Annual Inspection 10062018 10062019 + 8 189 AUTO SWITCHING CEN N/A Annual Inspection 10062018 10062019 9 305 AUTO SWITCHING CEN AUTO SWITCHING CEN Annual Inspection 10242018 (+) 10242019 -

10 326 OSS RADAR FACILITY Ocean Surveillance System Site #1 Annual Inspection 10242018 10242019

CDRL A003 Test and Inspection Report

LINE FAC NBR DESCRIPTION ADD'L DETAIL TEST NAME TEST DATE DCR RATING NEXT TEST DATE NOTES

1 763 ROOF EARTHEN BUNKER ROOF ANNUAL INSPECTION 201903 202003

2 1768 ROOF ANNUAL INSPECTION 201903 202003

3 1777 ROOF ANNUAL INSPECTION 201904 - 202004

4 1819 ROOF ANNUAL INSPECTION 201902 - 202002

5 1828 ROOF ANNUAL INSPECTION 201902 + 202002 SURFACE RUST ON FLASHING AND EXHAUST VENT

6 1829 ROOF ANNUAL INSPECTION 201903 + 202003 LEAKS AROUND ROOF JACKS

7 1894 ROOF EARTHEN BUNKER ROOF ANNUAL INSPECTION 201902 + 202002

8 1908 ROOF ANNUAL INSPECTION 201904 + 202004

9 1909F ROOF ANNUAL INSPECTION 201904 + 202004

10 1913 ROOF ANNUAL INSPECTION 201904 + 202004

11 1914 ROOF ANNUAL INSPECTION 201903 + 202003

12 1916 ROOF ANNUAL INSPECTION 201903 + 202003

13 1918 ROOF ANNUAL INSPECTION 201904 + 202004

14 1919 ROOF ANNUAL INSPECTION 201904 + 202004

15 1959 ROOF ANNUAL INSPECTION 201904 + 202004

16 2001 ROOF ANNUAL INSPECTION 201903 + 202003

17 6510 ROOF ANNUAL INSPECTION 201903 + 202003

18 6511 ROOF ANNUAL INSPECTION 201903 + 202003

19 6819 ROOF EARTHEN BUNKER ROOF ANNUAL INSPECTION 201902 + 202002

LINE FAC NBR DESCRIPTION ADD'L DETAIL TEST NAME TEST DATE PASS/FAIL NEXT TEST DATE NOTES 1 1912 ACCESS LADDER EXTERNAL ACCESS LADDER Annual Inspection 201904 PASS 202004 OPTIMAL

LINE NBR FAC NBR LOCATION PV # ITEM DESCRIPTION INSPECTION RATING

INSPECTION

DATE

NEXT

INSPECTION

DATE

SPECIFIC

ISI

TASKS

UNIQUE ISI

LAST

PERFORMED

UNIQUE ISI

NEXT

INSPECTION

DATE

RV

CALIBRATION

REQUIRED?

RV

CALIBRATION

DATE

NEXT RV

CALIBRATI

ON DATE

PG

CALIBRATION

REQUIRED?

PG

CALIBRATION

DATE

NEXT PG

CALIBRATION

DATE

LAST

CERTIFICATION

DATE

NEXT

CERTIFICATION

DATE REJECTABLE ITEM INSPECTION NOTES

1 871 PEMO PV-128 BREATHING AIR TANK PV-128, 338 CF, MONOBLOC DESIGN External Visual Examination Acceptable 201912 202012 UTV 201812 202812 Yes 20190128 20200128 Yes 20191106 20201106 2008 2028 2 871 PEMO PV-129 HORIZONTAL BREATHING AIR VESSEL PV-129, 338 CF, MONOBLOC DESIGN External Visual Examination Rejectable 201912 202012 Yes 20191023 20201023 Yes 20191003 20201003 2008 2028 Relief valve missing calibration tag 3 871 PEMO PV-130 LIQUID AIR TANK PV-130, 400 GAL, HORZ External Visual Examination Acceptable 201912 202012 Yes 20190429 20200429 No N/A N/A 2008 2028 5 974 HSF PV-132 HORIZONTAL N204 VESSEL PV-132, TK-201, 28,000 GAL External Visual Examination Rejectable 201905 202005 UTT 201906 202906 Yes 20181023 20191023 Yes 20190107 20200107 2008 2028 PT-211 missing calibration tag 6 974 HSF PV-133 HORIZONTAL N204 VESSEL PV-133, DEACTIVATED, TK-202, 28,000 GAL External Visual Examination Rejectable 201905 202005 Yes ** ** Yes 20180524 20190524 2008 2028 RV-221 missing calibration tag

7 974 HSF PV-134 HORIZONTAL N204 VESSEL PV-134, DEACTIVATED, TK-203, 28,000 GAL External Visual Examination Rejectable 201905 202005 Yes ** ** Yes 20190129 20200129 2008 2028 PT-231 missing calibration tag, RV-231 missing calibration tag

8 974 HSF PV-135 HORIZONTAL N204 VESSEL PV-135, TK-204, 28,000 GAL External Visual Examination Rejectable 201905 202005 UTT 201906 202906 Yes 20190417 20200417 Yes 20180904 20190904 2008 2028 PT-241 missing calibration tag 9 974 HSF PV-136 HORIZONTAL PV-136, DEACTIVATED, TK-205, 28,000 GAL External Visual Examination Rejectable 201905 202005 Yes 20190417 20200417 Yes 20181121 20191121 2008 2028 PT-251 missing calibration tag

10 974 HSF PV-137 HORIZONTAL N204 VESSEL PV-137, TK-206, 28,000 GAL External Visual Examination Rejectable 201905 202005 UTT 201906 202906 Yes 20190417 20200417 Yes 20180904 20190904 2008 2028 PT-261 missing calibration tag 11 974 HSF PV-143 PRESSURE VESSEL PV-143, SEPARATOR External Visual Examination Rejectable 201905 202005 UTT 2025 Yes 20181210 20191210 Yes 20180711 20190711 2015 2035 Securing nut on top flange not fully engaged 12 974 HSF PV-144 PRESSURE VESSEL PV-144, SEPARATOR External Visual Examination Acceptable 201905 202005 UTT 2025 Yes 20181221 20191221 Yes 20181019 20191019 2015 2035 13 974 HSF PV-145 PRESSURE VESSEL PV-145, 338 CF, MONOBLOC DESIGN External Visual Examination Other 201905 202005 UTT 2025 Yes 20180725 20190725 Yes 20190116 20200116 2008 2028 Dissimilar metals on flange assemblies 14 976 HSF PV-146 PRESSURE VESSEL PV-146, TK-101, 28,000 GAL External Visual Examination Acceptable 201905 202005 UTT 201906 202906 Yes 20180918 20190918 Yes 20180925 20190925 2007 2027 15 976 HSF PV-147 PRESSURE VESSEL PV-147, DEACTIVATED, TK-102, 28,000 GAL External Visual Examination Acceptable 201906 202006 AE/RT 2025 Yes 20180918 20190918 Yes 20190212 20200212 2008 2028 16 976 HSF PV-148 PRESSURE VESSEL PV-148, TK-103, 28,000 GAL External Visual Examination Acceptable 201906 202006 UTT 201906 202906 Yes 20180918 20190918 Yes 20180925 20190925 2015 2035 17 976 HSF PV-149 PRESSURE VESSEL PV-149, TK-104, 28,000 GAL External Visual Examination Rejectable 201906 202006 UTT 201906 202906 Yes ** ** Yes 20180810 20190810 2008 2028 RV-141 missing calibration tag 18 976 HSF PV-156 PRESSURE VESSEL PV-156, SEPARATOR External Visual Examination Acceptable 201906 202006 UTT 2025 Yes 20181210 20191210 Yes 20181205 20191205 2015 2035 19 976 HSF PV-157 PRESSURE VESSEL PV-157, SEPARATOR External Visual Examination Rejectable 201906 202006 UTT 2025 Yes 20181004 20191004 Yes 20180621 20190621 2015 2035 RV-181 single bolt lacking engagement 20 976 HSF PV-158 PRESSURE VESSEL PV-158, 338 CF, MONOBLOC DESIGN External Visual Examination Other 201906 202006 RT 2022 Yes 20180816 20190816 Yes 20190510 20200510 2007 2027 Dissimilar metals on flange assemblies

21 976 HSF PV-150 PRESSURE VESSEL PV-150, TK-105, 28,000 GAL External Visual Examination Rejectable 201906 202006 UTT 201906 202906 Yes 20180608 20190608 Yes ** ** 2008 2028 RV-151 single bolt lacking engagement, PI-151 missing calibration tag

22 976 HSF PV-151 PRESSURE VESSEL PV-151, TK-106, 28,000 GAL External Visual Examination Rejectable 201906 202006 UTT 201906 202906 Yes ** ** Yes 20181205 20191205 2008 2028 RV-161 missing calibration tag

23 1559 NVAFB PV-112 PRESSURE VESSEL (PV-112), 310 CF External Visual Examination Rejectable 201912 202012 Yes 20111101 ** Yes 20111101 ** 1995 2015, Overdue

Support equipment not calibrated, RV's not calibrated, no known last inspection since removed from previous LOSC. Damaged gauges, relief valves and gauges expired calibrations, possible leak at valve H-2, anchor lacking engagement.

24 1559 NVAFB PV-113 PRESSURE VESSEL (PV-113), 310 CF External Visual Examination Rejectable 201912 202012 Yes 20111101 ** Yes 20111101 ** 1995 2015, Overdue

Support equipment not calibrated, RV's not calibrated, no known last inspection since removed from previous LOSC. Damaged gauges, relief valves and gauges expired calibrations, possible leak at valve H-2, anchor lacking engagement.

25 1737 PMEL PV-166 PRESSURE VESSEL PV-166, LAYERED VESSEL DESIGN External Visual Examination Acceptable 201911 202011 UTV/RT 2024 Yes 20180123 20190123 Yes 20180123 20190123 2014 2034

26 6670 FUELS LAB PV-175 PRESSURE VESSEL PV-175, LAYERED VESSEL DESIGN External Visual Examination Acceptable 201911 202011 UTV 2024 Yes 20180323 20190323 Yes 20180712 20190712 2014 2034

The pressure gauge had condinsation inside of the slight glass. It is recommended that this gauge be replaced. One of the vessel relief valves was missing a calibration tag

27 8310 NVAFB PV-181 PRESSURE VESSEL PV-181, PROC. & SUPP FACILITY External Visual Examination Acceptable 201903 202003 UTV/RT/MT 2026 Yes 20180502 20190502 Yes 20180502 20190502 2016 2036 28 8310 NVAFB PV-182 PRESSURE VESSEL PV-182, PROC. & SUPP FACILITY External Visual Examination Acceptable 201903 202003 UTT 2020 Yes 20180503 20190503 Yes 20180503 20190503 2010 2030

29 8350 NVAFB PV-188 PRESSURE VESSEL PV-188, 400 CF, HELIUM FARM External Visual Examination Acceptable 201903 202003 Yes 20180711 20190711 No N/A N/A Vessel out of service, under low pressure GN2 purge.

Possible slow leak.

30 8350 NVAFB PV-189 PRESSURE VESSEL PV-189, 400 CF, HELIUM FARM External Visual Examination Acceptable 201903 202003 Yes 20180711 20190711 No N/A N/A Vessel out of service, under low pressure GN2 purge.

31 8350 NVAFB PV-190 PRESSURE VESSEL PV-190, 400 CF, HELIUM FARM External Visual Examination Acceptable 201903 202003 Yes 20180711 20190711 No N/A N/A Vessel out of service, under low pressure GN2 purge.

32 SLC-4E HPGSA PV-222 PRESSURE VESSEL PV 222 GN2, LAYERED VESSEL DESIGN External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Minor leak detected at drain nozzle flange. Leak at panel connection. Foundation offset.

33 SLC-4E HPGSA PV-223 PRESSURE VESSEL PV 223 GN2, LAYERED VESSEL DESIGN External Visual Examination Acceptable 201901 202001

UTT (5YR), RT

(10YR) 2015 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel. Foundation offset.

34 SLC-4E HPGSA PV-224 PRESSURE VESSEL PV 224 GN2, LAYERED VESSEL DESIGN External Visual Examination Other 201901 202001

UTT (5YR), RT

(10YR) 2015 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel. Moderate corrosion on W. Flange.

Foundation offset.

35 SLC-4E HPGSA PV-225 PRESSURE VESSEL PV 225 GN2, LAYERED VESSEL DESIGN External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel.Foundation offset.

36 SLC-4E HPGSA PV-226 PRESSURE VESSEL PV 226 GN2, MONOBLOC WITH SS LINER External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel.Foundation offset.

37 SLC-4E HPGSA PV-227 PRESSURE VESSEL PV 227 GN2, MONOBLOC WITH SS LINER External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel.Foundation offset.

38 SLC-4E HPGSA PV-228 PRESSURE VESSEL PV 228 GN2, MONOBLOC WITH SS LINER External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel.Foundation offset.

39 SLC-4E HPGSA PV-229 PRESSURE VESSEL PV 229 GN2, MONOBLOC WITH SS LINER External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Leak at panel.Foundation offset.

40 SLC-4E HPGSA PV-230 PRESSURE VESSEL PV 230 GN2, MONOBLOC WITH SS LINER External Visual Examination Other 201901 202001 UTT/RT (10YR) 2010 2020 Yes 20190118 20200118 No N/A N/A 2010 2030 Minor leak at bottom nozzle flange connection. Leak at panel.Foundation offset.

** - Unknown due to expired or missing calibration tags

LINE

NBR FAC NBR CRITICALITY LOCATION DESC FILTERED Unit

EQUIPMENT

NUMBER

100%

CAPABILITY

LOAD TEST

DATE

PASS/

FAIL

100%

CAPABILITY

LOAD NEXT TEST

DATE NOTES

5 525 C VAFB CRANE UNIT 12 12 ABQMHCN375 201912 PASS 202012

14 1546 C VAFB CRANE UNIT 23 23 AGDMHCN674 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 15 1546 C VAFB CRANE UNIT 24 24 AGDMHCN675 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 16 1546 C VAFB CRANE UNIT 25 25 AGDMHCN677 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 17 1546 C VAFB CRANE UNIT 26 26 AGDMHCN678 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 19 1555 C VAFB CRANE UNIT 27 27 AGEMHCN680 201911 PASS 202011 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 20 1555 C VAFB CRANE UNIT 28 28 AGEMHCN682 201911 PASS 202011 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

22 1639 NC VAFB CRANE UNIT 33 33 AGLMHCN688 201912 PASS 202012

23 1731 NC VAFB CRANE UNIT 35 35 AGNMHCN690 PERFORMED BY OTHERS (AT USER'S INSISTANCE) 24 1731 NC VAFB CRANE UNIT 36 36 AGNMHCN692 PERFORMED BY OTHERS (AT USER'S INSISTANCE) 25 1731 NC VAFB CRANE UNIT 37 37 AGNMHCN693 PERFORMED BY OTHERS (AT USER'S INSISTANCE)

27 1768 NC VAFB CRANE UNIT 38 38 AGTMHCN695 CRANE IS LOCKED OUT OF SERVICE

28 1783 NC VAFB CRANE UNIT 41 41 AGUMHCN696 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS

33 1800 NC VAFB CRANE UNIT 42 42 AGXMHCN697 201903 PASS 202003

34 1800 NC VAFB CRANE UNIT 43 43 AGXMHCN699 201903 PASS 202003

35 1800 NC VAFB CRANE UNIT 44 44 AGXMHCN700 201902 PASS 202002

36 1806 C VAFB CRANE UNIT 45 45 AGYMHCN702 201908 PASS 202008 THIS CRANE DOES NOT MEET ALL THE 91-710 REQUIREMENTS FOR CRITICAL CRANES 37 1806 C VAFB CRANE UNIT 46 46 AGYMHCN703 201908 PASS 202008 THIS CRANE DOES NOT MEET ALL THE 91-710 REQUIREMENTS FOR CRITICAL CRANES 38 1819 C VAFB CRANE UNIT 48 48 AGZMHCN721 201903 PASS 202003 THIS IS A LIMITED CERTIFICATION DUE TO DEFICIENCIES FOUND IN 91-710 39 1819 C VAFB CRANE UNIT 49 49 AGZMHCN722 201903 PASS 202003 THIS IS A LIMITED CERTIFICATION DUE TO DEFICIENCIES FOUND IN 91-710

40 1819 C VAFB CRANE UNIT 50 50 AGZMHCN750 CRANE IS LOCKED OUT OF SERVICE

41 1819 C VAFB CRANE UNIT 51 51 AGZMHCN751 201908 PASS 202008 LIMITED TRAVEL ON THE ENVELOPE DUE TO OBSTACLES IN THE BAY

42 1824 C VAFB CRANE UNIT 52 52 AHAMHCN752 NO ACCESS

43 1824 C VAFB CRANE UNIT 53 53 AHAMHCN753 NO ACCESS

44 1833 C VAFB CRANE UNIT 54 54 AHCMHCN754 NO ACCESS

45 1833 C VAFB CRANE UNIT 55 55 AHCMHCN755 NO ACCESS

46 1900 C VAFB CRANE UNIT 57 57 AHJMHCN756 CRANE IS LOCKED OUT OF SERVICE

47 1900 C VAFB CRANE UNIT 58 58 AHJMHCN757 201809 PASS 201909

THIS CRANE DOES NOT MEET ALL THE 91-710 REQUIREMENTS FOR CRITICAL CRANES. THIS IS A LIMITED CERTIFICATION.

2019: NO ACCESS AT TIME OF INSPECTION DUE TO FLIGHT HARDWARE IN THE BAY. CUSTOMER WILL SCHEDULE A DATE AS

SOON AS THE BAY IS CLEAR.

48 1900 C VAFB CRANE UNIT 59 59 AHJMHCN758 201809 PASS 201909

2019: NO ACCESS AT TIME OF INSPECTION DUE TO FLIGHT HARDWARE IN THE BAY. CUSTOMER WILL SCHEDULE A DATE AS

SOON AS THE BAY IS CLEAR.

49 1900 C VAFB CRANE UNIT 60 60 AHJMHCN759 201809 PASS 201909

2019: NO ACCESS AT TIME OF INSPECTION DUE TO FLIGHT HARDWARE IN THE BAY. CUSTOMER WILL SCHEDULE A DATE AS

SOON AS THE BAY IS CLEAR.

52 6527 C VAFB CRANE UNIT 65 65 AIVMHCN764 CRANE HAS BEEN LOCKED OUT OF SERVICE. ANNUAL LOCKOUT INSPECTION 54 6601 C VAFB CRANE UNIT 66 66 AIWMHCN765 201910 PASS 202010 PULL CRANE SLOWLY THROUGH THE S CURVES OUTSIDE SO PICKUP SHOES DON'T JUMP OUT OF FEEDRAIL.

55 6601 C VAFB CRANE UNIT 67 67 AIWMHCN767 201907 PASS 202007 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 56 6601 C VAFB CRANE UNIT 68 68 AIWMHCN768 201907 PASS 202007 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

57 6601 NC VAFB CRANE UNIT 69 69 AIWMHCN769 202001 PASS 202101

60 6817 C VAFB CRANE UNIT 70 70 AJCMHCN771 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

61 7425 NC VAFB CRANE UNIT 71 71 AJRMHCN773 CRANE IS LOCKED OUT OF SERVICE

62 7525 C VAFB CRANE UNIT 74 74 AJTMHCN777 201910 PASS 202010 THIS CRANE DOES NOT MEET ALL THE 91-710 REQUIREMENTS FOR CRITICAL CRANES 63 7525 C VAFB CRANE UNIT 75 75 AJTMHCN778 201910 PASS 202010 THIS CRANE DOES NOT MEET ALL THE 91-710 REQUIREMENTS FOR CRITICAL CRANES 67 8415 C VAFB CRANE UNIT 81 81 AKHMHCN792 201903 PASS 202003 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 68 8415 C VAFB CRANE UNIT 82 82 AKHMHCN793 201903 PASS 202003 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 69 8415 C VAFB CRANE UNIT 83 83 AKHMHCN002 201903 PASS 202003 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

70 8425 NC VAFB CRANE UNIT 84 84 AKIMHCN796 201907 PASS 202007

71 8425 NC VAFB CRANE UNIT 85 85 AKIMHCN797 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS 75 9320 C VAFB CRANE UNIT 91 91 AKNMHCN801 201911 PASS 202011 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 76 9320 C VAFB CRANE UNIT 92 92 AKNMHCN802 201911 PASS 202011 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

77 9320 C VAFB CRANE UNIT 93 93 AKNMHCN804 201906 PASS 202006

78 9320 C VAFB CRANE UNIT 94 94 AKNMHCN805 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS 79 9320 C VAFB CRANE UNIT 95 95 AKNMHCN806 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS 80 9320 NC VAFB CRANE UNIT 96 96 AKNMHCN808 201903 PASS 202003 PROOF LOAD TEST WAS COMPLETED DUE TO REPLACEMENT OF DAMAGED WIRE.

81 9320 NC VAFB CRANE UNIT 97 97 AKNMHCN809 201903 PASS 202003

82 9320 NC VAFB CRANE UNIT 98 98 AKNMHCN810 201903 PASS 202003

88 10713 NC VAFB CRANE UNIT 102 102 AKWMHCN002 201909 PASS 202009

89 11439 NC VAFB CRANE UNIT 110 110 AKYMHCN864 201903 PASS 202003

90 11439 NC VAFB CRANE UNIT 111 111 AKYMHCN821 201903 PASS 202003

92 12000 C VAFB CRANE UNIT 114 114 AKZMHCN829 201912 PASS 202012

66 8305 NC VAFB CRANE UNIT 119 119 AJWMHCN833 201903 PASS 202003

8 763 NC VAFB CRANE UNIT 129 129 ADGMHCN834 201907 PASS 202007

9 766 NC VAFB CRANE UNIT 137 137 ADIMHCN839 CRANE NOT IN USE, TAGGED OUT

26 1737 NC VAFB CRANE UNIT 140 140 AGPMHCN840 201912 PASS 202012

18 1555 C VAFB CRANE UNIT 147 147 AGEMHCN844 201911 PASS 202011 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 72 9320 NC VAFB CRANE UNIT 153 153 AKNMHCN848 201912 PASS 202012 MAXIMUM LOAD ON BEAM IS 1740 LBS. MUST NOT EXCEED WITH BOTH UNITS

73 9320 NC VAFB CRANE UNIT 154 154 AKNMHCN849 201912 PASS 202012

58 6710 VAFB CRANE UNIT 155 155 AIZMHCN851 CRANE IS LOCKED OUT OF SERVICE

51 6419 C VAFB CRANE UNIT 157 157 AITMHCN852 201901 PASS 202001 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

13 980 C VAFB CRANE UNIT 162 162 AEPMHCN856 CRANE IS LOCKED OUT OF SERVICE

10 790 NC VAFB CRANE UNIT 174 174 ADQMHCN857 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS 74 9320 NC VAFB CRANE UNIT 185 185 AKNMHCN002 201912 PASS 202012 MAXIMUM LOAD ON BEAM IS 1740 LBS. MUST NOT ESCEED WITH BOTH UNITS 59 6816 C VAFB CRANE UNIT 188 188 AJBMHCN861 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 94 21155 NC VAFB CRANE UNIT 189 189 ALHMHCN862 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS

91 11439 NC VAFB CRANE UNIT 196 196 AKYMHCN864 201907 PASS 202007

95 22312 NC VAFB CRANE UNIT 197 197 ALOMHCN865 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS

29 1784 C VAFB CRANE UNIT 211 211 AGVMHCN866 201912 PASS 202012

30 1784 NC VAFB CRANE UNIT 212 212 AGVMHCN867 201912 PASS 202012

7 660 NC VAFB CRANE UNIT 213 213 ACAMHCN001 201906 PASS 202006

83 10711 NC VAFB CRANE UNIT 215 215 AKVMHCN869 201901 PASS 202001

84 10711 NC VAFB CRANE UNIT 216 216 AKVMHCN870 201910 PASS 202010

85 10711 NC VAFB CRANE UNIT 217 217 AKVMHCN871 201901 PASS 202001

86 10711 NC VAFB CRANE UNIT 221 221 AKVMHCN872 201901 PASS 202001

87 10711 NC VAFB CRANE UNIT 222 222 AKVMHCN001 201901 PASS 202001

96 23215 NC VAFB CRANE UNIT 226 226 ALQMHCN874 201909 PASS 202009

97 23235 NC VAFB CRANE UNIT 227 227 ALXMHCN227 201901 PASS 202001

31 1785 NC VAFB CRANE UNIT 229 229 AGWMHCN875 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS 32 1785 NC VAFB CRANE UNIT 230 230 AGWMHCN876 CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS 64 8250 C VAFB CRANE UNIT 231 231 AJUMHCN877 201903 PASS 202003 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710 65 8250 C VAFB CRANE UNIT 232 232 AJUMHCN878 201903 PASS 202003 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

50 1930 NC VAFB CRANE UNIT 233 233 AHSMHCN879 201908 PASS 202008

3 502 NC VAFB CRANE UNIT 250 250 ABEMHCN880 201909 PASS 202009

4 502 NC VAFB CRANE UNIT 251 251 ABEMHCN881 201909 PASS 202009

11 907 NC VAFB CRANE UNIT 252 252 AEAMHCN882 201905 PASS 202005

53 6601 NC VAFB CRANE UNIT 253 253 AIWMHCN883 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

98 PP12 NC PILLAR POINT CRANE UNIT 255 255 PPAMHCN754 201902 PASS 202002

99 PP17 NC PILLAR POINT CRANE UNIT 256 256 PPFMHCN689 201902 PASS 202002

100 PP17 NC PILLAR POINT CRANE UNIT 257 257 PPFMHCN690 201902 PASS 202002

12 907 NC VAFB CRANE UNIT 307 307 AEAMHCN623 201910 PASS 202010

21 1610 NC VAFB CRANE UNIT 420 420 VB3MHCN001 201905 PASS 202005 DOES NOT MEET ALL REQUIREMENTS FOR CRITICAL CRANES LISTED IN THE 91.710

1 175 VAFB / TRAN PEAK CRANE UNIT CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS

2 178 VAFB / TRAN PEAK CRANE UNIT CRANE HAS BEEN PHYSICALLY REMOVED BY OTHERS

93 12006 NC VAFB CRANE UNIT BCBMHHO001 ELECTRIC HOIST (LOCKED OUT NOT IN USE)

100% CAPABILITY TEST - ANNUAL - CRITICAL ONLY

100% CAPABILITY TEST - 4 YEARS - NON-CRITICAL ONLY

EXAMPLE_LEGEND
ROOFS
LADDERS
PRESSURE VESSELS
CRANES_HOISTS

File details come from the government source that posted it. Updated .