TECH LIBRARY 1 SVPP Supplier Manuals Phoenix Contact 2814100.pdf
PDF 70 KB Posted
- Attached to
- Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL Federal contract opportunity
- Solicitation number
- FA4610-22-R-0001
About this file
This request for proposal solicits offers for launch operations support contract services. Offerors must provide facilities support, engineering, and mission integration services to support space launch operations at Vandenberg Air Force Base in California. Responses are due no later than 27 January 2022. The resulting contract will be awarded by the 30th Space Wing and governed under NAICS code 561210 with a small business size standard of $41.5 million. The performance work statement and its appendices describe the required services in detail.
View the file
Other files for this federal contract opportunity
Show all 50
Launch Operations Support Contract (LOSC) Request for Proposal (RFP) – FINAL has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
https://www.phoenixcontact.com/us/products/2814100
10/25/2016 Page 1 / 4
Temperature measuring transducer - MCR-T-UI-NC - 2814100 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download)
MCR-T module, programmable temperature measuring transducer, unconfigured, for thermocouple sensors and resistance thermometers, with 2, 3, or 4-wire system
The illustration shows version MCR-
T-UI
Why buy this product
Freely programmable via MCR/PI-CONF-WIN
With transistor switching output
Inverse output signal ranges as an option
For resistance thermometers and thermocouples
Measure differential temperatures
Key Commercial Data Packing unit 1 STK
GTIN
GTIN 4017918139421
Weight per Piece (excluding packing) 140.500 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Dimensions
10/25/2016 Page 2 / 4
Temperature measuring transducer - MCR-T-UI-NC - 2814100 Technical data
Dimensions Width 17.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions Ambient temperature (operation) -20 °C ... 65 °C
Input data Configurable/programmable Yes, unconfigured
Sensor types (RTD) that can be used Pt, Ni, Cu sensors
Sensor types that can be used (TC) U, T, L, J, E, K, N, S, R, B, C, W, HK
Linear resistance measuring range 0 Ω ... 8000 Ω (freely adjustable, min. measuring range 100 Ω)
Sensor input current 250 µA (resistance thermometer)
Temperature measuring range Depending on sensor type used
Connection method 2, 3, 4-wire
Protective circuit Transient protection
Surge protection 30 V DC
Connection method Pluggable screw connection
Output data Output name Voltage output / current output
Configurable/programmable Yes, unconfigured
Voltage output signal 0 V ... 10 V
0 V ... 5 V
-5 V ... 5 V
-10 V ... 10 V
10 V ... 0 V
5 V ... 0 V
10 V ... -10 V
5 V ... -5 V
1 V ... 5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. output voltage ± 12 V
Max. output current 24 mA
Output voltage range with wire break -12 V ... 12 V
Output current range with wire break 0 A ... 24 mA
10/25/2016 Page 3 / 4
Temperature measuring transducer - MCR-T-UI-NC - 2814100 Technical data
Output data Output voltage range with overrange/underrange -12 V ... 12 V
Output current range with overrange/underrange 0 A ... 24 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 500 Ω
Ripple < 20 mVPP
Protective circuit Transient protection
D/A resolution ± 12 bit
Switching output Output name Transistor output, pnp
Output description Can carry a load of 100 mA, switches supply voltage (not protected against short-circuit); locked in case of order-specific configuration, otherwise freely programmable through MCR/PI-CONF-WIN
Output voltage range 18 V DC ... 30 V DC (switches supply voltage, not short-circuit resistant)
Continuous load current 100 mA
Power supply Supply voltage range 18 V DC ... 30 V DC
Max. current consumption ≤ 60 mA
Typical current consumption 40 mA
Connection data Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Stripping length 8 mm
Screw thread M3
General Maximum transmission error ≤ 0.1 % (of maximum range, ±6 mV or ±12 µA at output)
Maximum temperature coefficient ≤ 0.01 %/K
Temperature coefficient, typical 0.005 %/K
Cold point error, max. ≤ 3 K
Typical cold point errors 1.5 K
Test voltage input/output 1 kV (50 Hz, 1 min.)
Test voltage input/power supply 1 kV (50 Hz, 1 min.)
10/25/2016 Page 4 / 4
Temperature measuring transducer - MCR-T-UI-NC - 2814100 Technical data
General Color green
Housing material Polyamide PA non-reinforced
Mounting position any
Conformance CE-compliant
UL, USA/Canada Class I, Div. 2, Groups A, B, C, D or Non-Hazardous Locations
GL Germanischer Lloyd
Standards and Regulations Connection in acc. with standard CUL
Conformance CE-compliant
UL, USA/Canada Class I, Div. 2, Groups A, B, C, D or Non-Hazardous Locations
GL Germanischer Lloyd
Environmental Product Compliance China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Drawings
Dimensional drawing
17,5
,5
Circuit diagram
Phoenix Contact 2016 © - all rights reserved http://www.phoenixcontact.com