These structural engineering documents are for the Greenville County Clerk's TAB Products Mobile Shelving System Seismic Anchorage project located at 301 University Ridge in Greenville, South Carolina. The documents detail technical specifications for seismic anchorage of a mobile shelving system, including precise installation requirements for expansion anchors, track mounting, and carriage connections. The project involves structural engineering work focused on ensuring the mobile shelving system is properly secured according to the 2019 International Building Code, with specific design criteria including seismic parameters like Ss = 0.314g and Sds = 0.324g.
The technical specifications mandate specific installation protocols, including the use of Hilti Kwik Bolt-TZ2 expansion anchors with special inspection requirements, non-shrink grout applications, and precise mounting techniques for anti-tip tracks, standard tracks, fixed carriages, and seismic stop angles. Materials specifications include ASTM A36 steel shapes, ASTM A1011 shelving shapes, and requirements for machine bolts. The documents emphasize contractor responsibilities for field verification, coordination, and compliance with local building authorities, with special inspections to be performed by a certified independent inspection company hired by the project owner.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. SCOPE OF WORK: STRUCTURAL ENGINEERING WORK FOR THIS PROJECT IS THE DESIGN OF THE SEISMIC
ANCHORAGE OF THE STATIC SHELVING.
2. FIELD VERIFICATION: FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO CONSTRUCTION.
PROMPTLY NOTIFY ARCHITECT (STRUCTURAL ENGINEER) IN CASE OF DISCREPANCIES.
3. DESIGN INTENT: CONTRACT DOCUMENTS INDICATE DESIGN INTENT FOR STRUCTURE IN ITS COMPLETED
STATE. THEY DO NOT INDICATE METHOD OF CONSTRUCTION. PROMPTLY NOTIFY ARCHITECT
(STRUCTURAL ENGINEER), PRIOR TO PROCEEDING WITH WORK, IF DESIGN INTENT REQUIRES FURTHER CLARIFICATION. ALL WORK SHALL BE IN CONFORMANCE WITH THE INTERNATIONAL BUILDING CODE (IBC)
2019 EDITION INCLUDING ALL AMENDMENTS.
4. NON-STRUCTURAL COMPONENT DESIGN CRITERIA:
• Ss = 0.314g
• Sds = 0.324g
• ap = 1.0
• Rp = 2.5
• Ωo = 2.0
• Ip = 1.0
• z/h = 0.5
5. STRUCTURAL STEEL: ALL STEEL SHAPES AND PLATES SHALL BE ASTM A36 UNLESS NOTED OTHERWISE.
ALL SHELVING SHAPES SHALL CONFORM TO ASTM A1011. ALL MACHINE BOLTS SHALL CONFORM TO ASTM
A307, AND ALL THROUGH BOLTS SHALL CONFORM TO ASTM F1554 GR. 36.
6. DEVIATIONS: MODIFICATIONS AND SUBSTITUTIONS TO APPROVED STRUCTURAL DRAWINGS MUST BE ACCEPTED IN WRITING BY ARCHITECT (STRUCTURAL ENGINEER) AND APPROVED BY GOVERNING CODE AUTHORITY. NO DEVIATION, MODIFICATION OR SUBSTITUTION WILL BE ACCEPTED VIA SHOP DRAWING
REVIEW.
7. COORDINATION RESPONSIBILITY: CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF WORK
INCLUDING THAT OF SUB-CONTRACTOR TRADES.
8. SUBMITTALS: SUBMIT TO ARCHITECT (STRUCTURAL ENGINEER) AS INDICATED ON STRUCTURAL DRAWINGS AND SPECIFICATIONS. GENERAL CONTRACTOR SHALL REVIEW SUBMITTAL FOR COMPLETENESS AND
COMPLIANCE WITH CONTRACT DOCUMENTS PRIOR TO SUBMISSION.
A. REQUEST FOR INFORMATION (RFI) SUBMITTALS: ACCOMPANY RFI'S WITH PARTIAL STRUCTURAL
MEMBERS. COPY PARTIAL PLAN FROM STRUCTURAL DRAWINGS AND INDICATE GRID LINE
LOCATIONS AND FLOOR LEVEL. ALSO PROVIDE PROPERLY DRAWN ENGINEERING SKETCHES
ILLUSTRATING ISSUES AND CONTRACTORS PROPOSED SOLUTIONS. PHOTOGRAPHS ARE NOT
ACCEPTABLE SUBSTITUTIONS TO ENGINEERING SKETCHES.
9. CONTRACTOR DOCUMENTS USE: REVIEW CONTRACT DOCUMENTS IN THEIR ENTIRETY BEFORE
PERFORMING STRUCTURAL RELATED WORK AND BEFORE DEVELOPING SHOP DRAWINGS. BRING
DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE ARCHITECT (STRUCTURAL ENGINEER) BEFORE
STARTING WORK.
A. SCALING OF DRAWINGS: NOT PERMITTED.
B. ADDITIONAL STRUCTURAL REQUIREMENTS: SEE SPECIFICATIONS.
C. BUILDING GEOMETRY: SEE ARCHITECTURAL DRAWINGS FOR BUILDING GEOMETRY INCLUDING, BUT
NOT LIMITED TO, TOP OF FLOOR AND ROOF ELEVATIONS, DEPRESSIONS, SLOPES, CURBS, DRAINS, TRENCHES, SLAB AND DECK EDGE LOCATIONS, WALL OVERALL DIMENSIONS, AND SIZE AND
LOCATIONS OF OPENINGS IN FLOORS, ROOF, AND WALLS.
D. NON-STRUCTURAL ITEMS REQUIRING SPECIAL PROVISIONS: SEE ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR NON-STRUCTURAL ITEMS REQUIRING SPECIAL
PROVISIONS DURING CONSTRUCTION. THEY INCLUDE, BUT ARE NOT LIMITED TO, NON-STRUCTURAL WALLS, SIZE AND LOCATIONS OF OPENINGS AND SLEEVES PENETRATING STRUCTURE, SIZE AND LOCATION OF CONCRETE CURBS AND PADS, AND SIZE AND LOCATION OF PIPING, DUCTWORK, AND
EQUIPMENT ANCHORAGE MOUNTED OR SUSPENDED FROM STRUCTURE. VERIFY EXACT SIZE AND
LOCATION OF EQUIPMENT WITH EQUIPMENT MANUFACTURER.
10. MATERIALS: FURNISH AND INSTALL IN COMPLIANCE WITH LEGALLY CONSTITUTED PUBLISH AUTHORITIES HAVING JURISDICTION INCLUDING COUNTY AND LOCAL ORDINANCES AND SAFETY ORDERS OF STATE INDUSTRIAL ACCIDENT COMMISSION, OSHA. THE ARCHITECT, STRUCTURAL ENGINEER OF RECORD, AND THE OWNER DO NOT ACCEPT ANY RESPONSIBILITY FOR THE CONTRACTOR'S FAILURE TO COMPLY WITH
THESE REQUIREMENTS.
11. PENETRATIONS, EMBEDMENTS, AND OPENINGS IN STRUCTURAL MEMBERS: NO PENETRATION, EMBEDMENT, OPENING, SLEEVE, PIPE, OR CONDUIT SHALL OCCUR IN STRUCTURAL MEMBERS INCLUDING FOOTINGS, SLABS, WALLS, COLUMNS, AND BEAMS UNLESS SPECIALLY SHOWN OR INDICATED ON
STRUCTURAL DRAWINGS.
12. TYPICAL DETAILS: DETAILS ARE APPLICABLE THROUGHOUT PROJECT WHEREVER THE DESCRIBED CONDITION OCCURS AND MAY OR MAY NOT BE SPECIFICALLY REFERENCED ON STRUCTURAL DRAWINGS.
CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING THESE DETAILS AND UNDERSTANDING EXTENT OF THEIR
APPLICATION PRIOR TO PERFORMING WORK.
13. PROCEDURES OF CONSTRUCTION: CONTRACTOR IS RESPONSIBLE FOR PROCEDURES OF CONSTRUCTION COMPLYING WITH NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES. SITE VISITS (INCLUDING
STRUCTURAL OBSERVATION) BY ARCHITECT (STRUCTURAL ENGINEER) DO NOT CONSTITUTE
SUPERVISIONS OF METHODS OF CONSTRUCTION.
A. PROTECTION OF UTILITIES: LOCATE EXISTING UTILITIES, INCLUDING THOSE NOT SHOWN ON
CONTRACT DOCUMENTS, AND PROTECT THEM FROM DAMAGE. CONTRACTOR BEARS EXPENSE OF
REPAIR OR REPLACEMENT OF UTILITIES IN CONJUNCTIONS WITH EXECUTION OF WORK.
B. EXCAVATION: PROTECT STRUCTURE, ADJACENT STRUCTURES, ADJACENT PROPERTIES, STREETS, AND UTILITIES DURING EXCAVATION UTILIZING LAGGING, SHORING, UNDERPINNING AT SIDES AND
RELATED PROCEDURES AS MAY BE REQUIRED. PROVIDE NECESSARY SUPPORTS FOR SOIL
EXCAVATIONS. CONTRACTOR AND AFFECTED TRADES SHALL REFER TO GEOTECHNICAL REPORT
FOR MORE INFORMATION.
C. PROTECTION OF STRUCTURE: PROVIDE NECESSARY MEASURES TO PROTECT STRUCTURE DURING
EXECUTION OF WORK.
D. CONTRACTOR PROPOSED REVISIONS: WHERE A REVISION OF STRUCTURAL DESIGN OR
CONNECTION IS PROPOSED BY CONTRACTOR TO ACCOMMODATE CONSTRUCTION TOLERANCES,
CONSTRUCTION SEQUENCE AND/OR DIMENSION MODIFICATIONS, CONTRACTOR SHALL RETAIN A
LICENSED STRUCTURAL ENGINEER TO PERFORM DESIGN. SUBMIT STAMPED AND SIGNED DESIGN
DRAWINGS AND CALCULATIONS TO THE ARCHITECT (STRUCTURAL ENGINEER) FOR REVIEW AND
THE GOVERNING CODE AUTHORITY FOR APPROVAL.
E. SHORING, BRACING, AND OTHER TEMPORARY SUPPORTS: DESIGN AND ERECT SHORING, BRACING, AND OTHER TEMPORARY SUPPORTS WHERE STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH
AND AS REQUIRED FOR SAFE ERECTION. ENSURE FLOOR, ROOF, AND WALL MEMBERS ARE
SECURELY SHORED AND BRACED DURING CONSTRUCTION.
F. TEMPORARY LOADING: ENSURE CONSTRUCTION LOADS DO NOT EXCEED INDICATED DESIGN LIVE
LOAD VALUES. NOTIFY AFFECTED SUB-CONTRACTOR TRADES OF THESE DESIGN LOAD LIMITS.
ABBREVIATIONS
@ = AT
AB = ANCHOR BOLT
ABV = ABOVE
ALT = ALTERNATE
AWA = ALIGN WITH ABOVE
BLW = BELOW
BM = BEAM
BRG = BEARING
BS = BOTH SIDES
BTM = BOTTOM
BTWN = BETWEEN
CBC = CALIFORNIA BUILDING CODE
CL = CENTER LINE
CLR = CLEAR
CONC = CONCRETE
DIA = DIAMETER
(E) = EXISTING
EA = EACH
EFF = EFFECTIVE
EMBED = EMBEDMENT
EW = EACH WAY
EXT = EXTERIOR
F.F. = FINISH FLOOR
FT = FEET
GA = GAGE (GAUGE)
GALV. = GALVANIZED
HORIZ = HORIZONTAL
LBS = POUNDS
LWC = LIGHT WEIGHT CONCRETE
IN = INCH
INFO = INFORMATION
MAX = MAXIMUM
MFR = MANUFACTURER
MIN = MINIMUM
NWC = NORMAL WEIGHT CONCRETE
NA = NOT APPLICABLE
OC = ON CENTER
SIM = SIMILAR
SDSTS = SELF DRILLING SELF TAPPING SCREW
SMS = SHEET METAL SCREW
SQ = SQUARE
STD = STANDARD
TYP = TYPICAL
UNO = UNLESS NOTED OTHERWISE
VERT = VERTICAL
W/ = WITH
W/O = WITHOUT
SPECIAL INSPECTION NOTES
1. NOTICE TO THE APPLICANT/OWNER/OWNERS'S AGENT/ ARCHITECT OR ENGINEER: BY USING THESE PERMITTED CONSTRUCTION DRAWINGS FOR CONSTRUCTION/INSTALLATION OF THE WORK SPECIFIED
HEREIN, YOU AGREE TO COMPLY WITH THE REQUIREMENTS OF THE LOCAL BUILDING
DEPARTMENTS/BUILDING AUTHORITY FOR SPECIAL INSPECTIONS, STRUCTURAL OBSERVATIONS,
CONSTRUCTION MATERIALS TESTING AND OFF-SITE FABRICATION OF BUILDING COMPONENTS, CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS AND, AS REQUIRED BY THE CALIFORNIA CONSTRUCTION
CODES.
2. NOTICE TO THE CONTRACTOR/BUILDER/INSTALLER/SUB-CONTRACTOR/OWNER-BUILDER: BY USING THESE PERMITTED CONSTRUCTION DRAWINGS FOR CONSTRUCTION/INSTALLATION OF WORK SPECIFIED HEREIN, YOU ACKNOWLEDGE AND ARE AWARE OF, THE REQUIREMENTS CONTAINED IN THE STATEMENT OF
SPECIAL INSPECTIONS. YOU AGREE TO COMPLY WITH REQUIREMENTS OF THE CITY OR COUNTY FOR SPECIAL INSPECTIONS, STRUCTURAL OBSERVATIONS, CONSTRUCTION MATERIALS TESTING AND OFF-SITE FABRICATION OF BUILDING COMPONENTS, CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS AND, AS REQUIRED BY THE GOVERNING BUILDING CONSTRUCTION CODES. THE SPECIAL INSPECTOR MUST BE CERTIFIED BY THE BUILDING AUTHORITY, IN THE CATEGORY OF WORK REQUIRED TO HAVE SPECIAL INSPECTION. THE CONSTRUCTION MATERIALS TESTING LABORATORY MUST BE APPROVED BY THE CITY
OR COUNTY FOR TESTING MATERIALS, SYSTEMS, COMPONENTS, AND EQUIPMENT. THE SPECIAL
INSPECTIONS IDENTIFIED ON PLANS ARE IN ADDITION TO, AND NOT SUBSTITUTE FOR THOSE INSPECTIONS
REQUIRED TO BE PREFORMED BY THE CITY'S BUILDING INSPECTOR.
3. ALL INSPECTION, SPECIAL OR OTHERWISE, REQUIRED BY THE BUILDING CODES, LOCAL BUILDING DEPARTMENTS, OR SPECIFIED ON PLANS SHALL BE COMPLETED BY AN INDEPENDENT INSPECTION COMPANY CERTIFIED BY THE BUILDING AUTHORITY AND ACCEPTED/APPROVED BY THE ENGINEER OF RECORD. JOBSITE VISITS BY THE ENGINEER DO NOT CONSTITUTE OFFICIAL INSPECTION OR SUPERVISION
OF THE WORK.
4. SPECIAL INSPECTOR SHALL BE HIRED BY THE OWNER TO PROVIDE SPECIAL INSPECTIONS AS REQUIRED
PER THE PLANS.
5. SPECIAL INSPECTOR: A QUALIFIED PERSON, EMPLOYED BY THE OWNER, WHO HAS DEMONSTRATED COMPETENCE TO THE SATISFACTION OF THE BUILDING OFFICIAL FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION. DUTIES INCLUDE VISUAL INSPECTIONS AND FIELD MEASUREMENTS OR MATERIALS, OBTAINING SPECIMENS FOR TESTS AND
RELATED ACTIONS INCLUDING PREPARATION OF REPORTS.
6. CONTINUOUS INSPECTION: ON SITE INSPECTION BY THE SPECIAL INSPECTOR ON A CONTINUOUS BASIS
OBSERVING ALL WORK REQUIRING SPECIAL INSPECTION.
7. PERIODIC INSPECTION: INTERMITTENT INSPECTION AS PERMITTED BY THE PLAN, SPECIFIED AT PRE- DETERMINED INTERVALS OR MORE FREQUENTLY AS WORK PROGRESSES. NO SIGNIFICANT ELEMENTS OR AREAS SHALL BE COVERED BY ADDITIONAL WORK UNTIL APPROVED BY THE BUILDING OFFICIAL AND/OR
SPECIAL INSPECTOR.
PROPRIETARY ANCHORS AND FASTENERS
1. ANCHORAGE:
A. EPOXY ANCHORS: SHALL NOT BE USED.
B. MECHANICAL ANCHORS: HILTI KWIK BOLT - TZ2 EXPANSION ANCHORS ICC ESR-4266
2. FASTENERS:
A. SELF-DRILLING METAL SCREWS (INDICATED AS "SCREWS" OR "SMS" ON DRAWINGS): MINIMUM
0.292-INCH HEAD DIAMETER SELF-DRILLING/SELF-TAPPING STEEL SCREWS COMPLYING WITH ICC ES
REPORT. MINIMUM YIELD STRESS, FY=33 KSI.
3. INSTALLATION: SEE MANUFACTURER'S WRITTEN INSTRUCTIONS AND REFERENCED ICC ES REPORT.
A. MATERIALS NOT TO BE PENETRATED BY FASTENERS OR ANCHORS: POST-TENSIONED CONCRETE
AND PRECAST CONCRETE, PRESTRESSED CONCRETE UNLESS SPECIFICALLY DETAILED HEREIN OR
AS ACCEPTED IN WITTING BY ARCHITECT (STRUCTURAL ENGINEER). WHEN INSTALLATION IS
PERMITTED, LOCATE PRESTRESSING AND POST-TENSIONED TENDONS ACCURATELY PRIOR TO
INSTALLATION.
B. DRILLING HOLES IN EXISTING CONCRETE OR MASONRY FOR ANCHORS: USE NON-PNEUMATIC, ROTARY HAMMER TOOLS WITH ANSI COMPLIANT NON-REBAR CUTTING DRILL BITS TO DRILL HOLES
OR PROPER TOLERANCE. LOCATE EXISTING REBAR INCLUDING PRESTRESSING AND POST-
TENSIONING TENDONS USING NON-HAZARDOUS, NON-DESTRUCTIVE METHODS WITH ACCURATE
LOCATION TOLERANCES (PLUS OR MINUS ONE INCH PRIOR TO DRILLING HOLES TO AVOID CUTTING
OR DAMAGING EXISTING REINFORCING OR PRESTRESSING/POST-TENSIONING TENDONS. HOLES
SHALL BE THOROUGHLY CLEANED PER THE MANUFACTURERS WITTING RECOMMENDATIONS PRIOR
TO INSTALLATION OF ANCHORS.
C. DELETERIOUS MATERIALS: KEEP ANCHORS, INCLUDING HOLES FOR DRILL AND MECHANICAL
ANCHORS FREE OF DUST, GREASE, AND OTHER MATERIALS THAT IMPAIR MECHANICAL BOND.
4. TESTING FOR EXPANSION ANCHORS:
A. SPECIAL INSPECTION: SPECIAL INSPECTOR WILL PERFORM CONTINUOUS SPECIAL INSPECTION
DURING INSTALLATION.
B. TEST QUANTITY: INSPECTOR SHALL TEST 50% OF ANCHORS USED FOR EQUIPMENT/NON-
STRUCTURAL COMPONENT ANCHORAGE.
C. TEST LOADS FOR: HILTI KB-TZ2 (ICC-ES ESR-4266)
• INSTALLATION TORQUE FOR 1/4" EXPANSION ANCHOR: 4 FT-LBS
• INSTALLATION TORQUE FOR 1/2" EXPANSION ANCHOR: 50 FT-LBS
D. TESTING METHOD:
• TORQUE WRENCH METHOD: THE ANCHORS SHALL BE TESTED BY THE USE OF A
CALIBRATED WRENCH. THE APPLICABLE TEST LOAD SHALL BE REACHED WITHIN ONE-HALF
TURN OF THE NUT.
E. FAILED ANCHORS: IF ANY ANCHOR(S) FAIL IN TESTING, TESTING OF REMAINING ANCHORS OF THE
SAME SIZE AND CATEGORY NOT PREVIOUSLY TESTED SHALL BE COMPLETED.
5. POST-INSTALLED ANCHORAGE: CONTRACTOR SHALL INSTALL ANCHORAGE AT ALL LOCATIONS
ILLUSTRATED IN THE CONSTRUCTION DOCUMENTS. POST-INSTALLED ANCHORS SHALL CONFORM TO THE
IBC REQUIREMENTS, AND BE INSPECTED BY A SPECIAL INSPECTOR SPECIAL.
30" MIN
PER MFR
ANTI TIP
TRACK, TYP
S2 TYP
S2
S2
MOBILE CARRIAGE TYP
FIXED CARRIAGE
FIXED CARRIAGE
ANCHORAGE
LOCATION, TYP
30" MIN
PER MFR
SEISMIC STOP ANGLE, TYP
E Q
E Q
E Q
E Q
ANTI TIP
TRACK, TYP
S2 TYP
S2
S2
MOBILE CARRIAGE TYP
FIXED CARRIAGE
FIXED CARRIAGE
ANCHORAGE
LOCATION, TYP
SEISMIC STOP ANGLE, TYP
30" MIN
PER MFR
30" MIN
PER MFR
E Q
E Q
E Q
E Q
(E) 3" LIGHT WEIGHT CONCRETE
TOPPING OVER 2" METAL DECK
(f'm = 3,000 PSI MIN), V.I.F.
NOTES:
1. CHECK OF THE EXISTING CONCRETE TOPPING OVER METAL DECK AND
FLOOR FRAMING IS BY OTHERS.
2. MAX SHELVING HEIGHT = 76-1/4 INCHES.
3. SEE DETAIL 2 ON THIS SHEET FOR SHELVING CONNECTION TO CARRIAGE.
STANDARD
TRACK
S2
TYP
TYP
STANDARD
TRACK
S2
TYP
TYP
SHELVING UPRIGHT BEYOND
BOTTOM SHELF SUPPORT
SIDE CHANNEL
BOT SHELF SUPPORT W/
(2) #12 SDSTS AT EACH
END AND EACH SIDE (8
SCREWS TOTAL)
BOTTOM SHELF
PROJECT INFORMATION:
PLAN REVISIONS
CONSULTANT:
SHEET NUMBER
SHEET
REV:
DATE:
SHEET TITLE:
605 Fourth Street Mayville, WI 53050
PROJECT NUMBER:
41593 WINCHESTER RD, SUITE 200
TEMECULA, CA 92590
PH: (805) 345-0378
S1
NOTES, DETAIL, AND PLAN
LAYOUT
GREENVILLE COUNTY CLERK-
TAB PRODUCTS MOBILE
SHELVING SYSTEM SEISMIC
ANCHORAGE
9/13/2022
301 UNIVERSITY RIDGE
GREENVILLE, SC 29601
17-5000.11
1/2" = 1'-0"
MOBILE SHELVING SYSTEM LAYOUT
No.: Revision: Date:
6" = 1'-0"
SHELF TO CARRIAGE CONNECTION
010-013-22
DATE SIGNED: 9/13/2022
Trent Line
(2) 1/4" DIA. BOLT AT 2-3/4" ON CENTER
CROSS CHANNELS
10 GA ANTI-TIP CHANNEL x 4" LONG
ASTM 653, GR 50
1/4" DIA. HILTI KWIK BOLT-TZ2
EXPANSION ANCHOR WITH 1-1/2"
EFFECTIVE EMBEDMENT AT 12" ON
CENTER AND 3-1/2" FROM EACH END
OR TRACK SPLICE (SPECIAL
INSPECTIONS REQUIRED)
1/2" MIN NON-
SHRINK GROUT
CENTERLINE OF WHEEL
AND AXLE DRIVE
WHEEL
CONT ANTI-TIP
ALUMINUM TRACK
1/4" DIA HILTI KB3 FLUSH
MOUNTED ANCHOR AT 36" ON
CENTER W/ 1-1/4" EMBEDMENT
(FILL ALL HOLES)
CONTINUOUS SIDE
CHANNELS
WHEEL ASSEMBLY
NOTES:
1. CONTRACTOR TO SHALL LOCATE EXISTING REINFORCING LOCATIONS AND DEPTHS PRIOR TO DRILLING FOR THE INSTALLATION OF EXPANSION ANCHORS. CONTRACTOR SHALL NOT DAMAGE EXISTING REINFORCING.
2. GUIDE WHEELS ARE REQUIRED AT EACH ANTI-TIP TRACK.
3. THE HILTI KB3 FLUSH MOUNTED ANCHORS SHOWN ARE USED FOR THE INSTALLATION AND LEVELING THE ANTI-TIP TRACK AND ARE NOT CONSIDERED PART OF THE ANCHORAGE DESIGN OR LOAD PATH USED FOR ANCHORAGE. THE HILTI KBTZ ANCHORS SHOWN HAVE BEEN DESIGNED FOR THE UPLIFT AND SHEAR DESIGN FORCES TO EACH ANTI-TIP TRACK.
(E) 3" THICK MIN. LWC OVER
METAL DECK
(f'c = 3,000 PSI MIN)
(E) REINF. WHERE
OCCURS SEE NOTE 1
CROSS CHANNELS
1/4" DIA HILTI KB3
FLUSH MOUNTED
ANCHOR AS REQ.
FOR INSTALLATION
ONLY, TYP
1/2" NON-SHRINK GROUT
CENTERLINE OF WHEEL
AND AXLE DRIVE
WHEEL
CONT TRACK W/ NEOPRENE
CONT SIDE CHANNELS
NOTES:
1. CONTRACTOR TO SHALL LOCATE EXISTING REINFORCING LOCATIONS AND DEPTHS PRIOR TO DRILLING FOR THE INSTALLATION OF EXPANSION ANCHORS. CONTRACTOR SHALL NOT DAMAGE EXISTING REINFORCING.
2. STANDARD TRACKS ARE NOT USED FOR THE ANCHORAGE OF THE SHELVING SYSTEM. THE HILTI KB3 FLUSH MOUNTED ANCHORS SHOWN ARE USED FOR THE INSTALLATION AND LEVELING OF THE STANDARD TRACK AND ARE NOT CONSIDERED PART OF THE ANCHORAGE DESIGN OR LOAD PATH USED FOR ANCHORAGE.
(E) REINF. WHERE
OCCURS SEE NOTE 1
CROSS CHANNEL BEYONDCONT SIDE
CHANNEL, TYP
L5"x3"x1/4" w/ (2) 1/2" DIA. HILTI KWIK BOLT-TZ2
EXPANSION ANCHORS W/ 1-1/2" EFFECTIVE
EMBEDMENT
(SEE PLAN FOR LOCATION)
(SPECIAL INSPECTIONS REQUIRED)
#12 SELF DRILLING SELF TAPPING
SCREW, (2 EA END TYP)
0' - 1"
CARRIAGE WIDTH PER MFR
0' - 1"
(E) 3" THICK MIN. LWC
OVER METAL DECK
(f'c = 3,000 PSI MIN)
0' - 1"
0' - 2"
TYP
TYPTYP
(E) REINF. WHERE
OCCURS SEE NOTE 1
NOTES:
1. CONTRACTOR TO SHALL LOCATE EXISTING REINFORCING LOCATIONS AND DEPTHS PRIOR TO DRILLING FOR THE INSTALLATION OF EXPANSION ANCHORS. CONTRACTOR SHALL NOT DAMAGE EXISTING REINFORCING.
EQ EQ
0' - 1"
MOBILE CARRIAGE
L5x3x1/4 (LLV) x 2'-2" LENGTH WITH
(5) 1/2" DIA. HILTI KWIK BOLT-TZ2
EXPANSION ANCHORS AT 6" ON
CENTER AND 1" FROM EA END W/
1-1/2" EFFECTIVE EMBEDMENT
(SPECIAL INSPECTIONS REQUIRED)
SHELVING
TRACK BEYOND WHERE OCCURS
WHEELS BEYOND WHERE
OCCURS
(E) 3" THICK MIN. LWC
OVER METAL DECK
(f'c = 3,000 PSI MIN)
NOTES:
1. CONTRACTOR TO SHALL LOCATE EXISTING REINFORCING LOCATIONS AND DEPTHS PRIOR TO DRILLING FOR THE INSTALLATION OF EXPANSION ANCHORS. CONTRACTOR SHALL NOT DAMAGE EXISTING REINFORCING.
(E) REINF. WHERE
OCCURS SEE NOTE 10' - 1"
PROJECT INFORMATION:
PLAN REVISIONS
CONSULTANT:
SHEET NUMBER
SHEET
REV:
DATE:
SHEET TITLE:
605 Fourth Street Mayville, WI 53050
PROJECT NUMBER:
41593 WINCHESTER RD, SUITE 200
TEMECULA, CA 92590
PH: (805) 345-0378
S2
DETAILS
GREENVILLE COUNTY CLERK-
TAB PRODUCTS MOBILE
SHELVING SYSTEM SEISMIC
ANCHORAGE
9/13/2022
301 UNIVERSITY RIDGE
GREENVILLE, SC 29601
17-5000.11
No.: Revision: Date:
3" = 1'-0"
ANTI-TIP TRACK ANCHORAGE
3" = 1'-0"
STANDARD TRACK SECTION
3" = 1'-0"
FIXED CARRIAGE ANCHORAGE
3" = 1'-0"
SEISMIC STOP ANGLE ANCHORAGE
010-013-22
DATE SIGNED: 9/13/2022
| Sheets |
| S1 - NOTES, DETAIL, AND PLAN LAYOUT |
| S2 - DETAILS |
File details come from the government source that posted it. Updated .