SystemSensor_Heat_200Series_DataSheet_A05-0362.pdf
PDF 304 KB Posted
- Attached to
- FIRE ALARM SYS REPLACEMENT SERVICE - SKAGWAY AK Federal contract opportunity
- Solicitation number
- 140P9723Q0077
About this file
This document contains a product datasheet for SystemSensor's 200 Series intelligent plug-in smoke and heat detectors as well as details for a related federal contract opportunity with the National Park Service.
The datasheet provides specifications for SystemSensor's photoelectric, ionization, and thermal detector models as well as compatible mounting bases and accessories. Detector features include low-profile designs, analog communications, adjustable sensitivity settings, and dual LEDs. Thermal detectors offer fixed-temperature and rate-of-rise heat detection. The opportunity notice is for replacement of the fire alarm system in Skagway, Alaska and seeks contractor support for installation, maintenance, and repair services. The solicitation number is 140P9723Q0077 with responses due to the National Park Service Alaska Region.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P9723Q0077_Amd_0001.pdf | ||
| System-Smoke-Detectors-AppGuide-SPAG91.pdf | ||
| SilentKnight_PullStations_DataSheet.pdf | ||
| Sol_140P9723Q0077.pdf | ||
| B03_DL_WD_2015-5685_Rev_19.pdf | ||
| KLGO_Pantheon_Saloon___Red_Front_FireAlarm_plans.pdf | ||
| Bldg_Device_Inventories.zip | ZIP file | |
| SK-Photo_DataSheet_350118.pdf | ||
| SilentKnight_6808_hbt-fire-351608-C.pdf | ||
| SilentKnight_SwiftGateway_WSK-WGI_DataSheet.pdf | ||
| B08_SOW.pdf | ||
| B08_RFQ_Content.pdf | ||
| Swift_AVbase_DataSheet.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Agency Listings
200 Series Intelligent Low-Profile Plug-In Detectors
The System Sensor 200 Series intelligent plug-in smoke detectors with integral communication provide point location for alarm communication and selective maintenance.
Features
• Sleek, low-profile design
• Analog communications
• Low standby current
• Rotary address switches
• Superior EMI protection
• Dual LEDs for 360° visibility
| 200 | Series | smoke | detectors | are | intelligent | (addressable) | detectors | ||||
| with | point | ID | capability | that | enable | each | detector | address | to | be | set |
| with | decade | address | switches | to | provide | exact | detector | locations. | |||
| The | sensitivity | of | 200 | Series | detectors | can | be | programmed | using | the | |
| control | panel | software | to | suit | the | environment. | In | addition, | detector | ||
| sensitivity | is | continually | monitored | and | reported | to | the | panel. |
| The System Sensor 2251B | photoelectric | detector’s | unique | optical | ||||||
| sensing | chamber | is | engineered | to | sense | smoke | produced | by | a | wide |
| range | of | combustion | sources. | Dual | electronic | thermistors | add | 135°F | ||
| fixed | temperature | thermal | sensing | on | the | 2251TB | model. | The | ||
| 2251BR | is | a | remote | test | capable | detector | for | use | with | DNR(W) |
| duct | smoke | detectors. |
| The Acclimate ™ | 2251TMB | photoelectric | detector | includes | thermal | ||||||
| detection | at | 135°F. | It | uses | advanced | onboard | software | to | combine | ||
| the | signals | from | the | photo | and | thermal | elements | to | create | a | true |
| multi-criteria | detector | capable | of | rejecting | nuisance | sources, | but | still | |||
| responding | quickly | to | real | fires. | In | addition, | the | Acclimate | detector | ||
| can | adjust | its | sensitivity | according | to | its | environment. |
| The 1251B | ionization | detector | incorporates | a | unique | single-source, | |||
| dual-chamber | design | to | respond | quickly | and | dependably | to | a | broad |
| range | of | fires. |
| Both | the 5251B and 5251RB | detectors | use | an | innovative | thermistor | |||
| sensing | circuit | to | produce | 135°F | fixed | and | rate-of-rise | thermal | detection |
| in | low-profile | packages. | The | 5251H | model | provides | fixed | high- | |
| temperature | detection | at | 190°F. | These | thermal | detectors | provide | cost- | |
| effective, | intelligent | property | protection | in | a | variety | of | applications. |
For exact certification listings for each model, please reference the respective agency Web site.
| 3825 | Ohio | Avenue | • | St. | Charles, | IL | 60174 |
| Phone: | 800-SENSOR2 | • | Fax: | 630-377-6495 |
| ©2011 | System | Sensor. | |||||||
| Product | specifications | subject | to | change | without | notice. | Visit | systemsensor.com | for |
| current | product | information, | including | the | latest | version | of | this | data | sheet. |
| A05-0362-006 | • | 8/11 | • | #2653 |
Ordering Information Part No. Description
2251B* Photoelectric smoke detector
| 2251BR* Photoelectric | smoke | detector, | remote | test | capable, | |
| for | use | with | DNR(W) | duct | smoke | detectors |
2251TB* Photoelectric smoke detector with thermal
2251TMB* Acclimate™ multi-criteria smoke detector
1251B* Ionization smoke detector
5251B* Fixed temperature thermal detector
5251RB* Rate-of-rise thermal detector
5251H* High temperature thermal detector
Bases
B501* 4” Flangeless mounting base
B501BP* 4” Flangeless mounting base bulk pack
B210LP* 6” Flanged mounting base
B210LPBP* 6” Flanged mounting base bulk pack
| B200SR* Standard | sounder | base | |
| (compatible | with | B501BH | series) |
B200S* Intelligent addressable sounder base
B224RB* Relay base
B224BI* Isolator base
Accessories
SMB600 Surface Mounting Kit (flanged)
F110 Accessory Flange Ring for 6” Base
F110BP Accessory Flange Ring for 6” Base Bulk Pack
F210 Accessory New Smaller Flange Ring for 6” Base
RA100Z Remote LED annunciator
M02-04-01 Detector test magnet
M02-09-00 Telescoping test magnet
XR2B Detector removal tool (T55-127-000 included)
XP-4 Extension for XR2B (5 to 15 ft)
T55-127-000 Detector removal head
BCK-200B Black detector kit (10 pack)**
WCK-2008 White detector kit (10 pack)**
Accessories
200 Series Intelligent Detector Specifications Physical/Operating Specifications
Height 2.0 inches (51 mm)
Diameter 6.1 inches (155 mm) installed in B210LP base; 4.1 inches (104 mm) installed in B501 base
Shipping Weight Heat: 4.8 oz (136 g); Photo/Photo with Heat: 5.2 oz (147 g); Ion: 5.4 oz (153 g)
| Operating Temperature Range Ion/Photo: | 32°F | to | 120°F | (0°C | to | 49°C) | ||
| Photo | with | Thermal: | 32°F | to | 100°F | (0°C | to | 38°C) |
| Thermal: | –4°F | to | 100°F | (–20°C | to | 38°C) | ||
| High | Temperature: | –4°F | to | 150°F | (–20°C | to | 66°C) |
| UL-Listed Velocity Range Ion: | 0 | to | 1,200 | fpm | (0 | to | 6.1 | m/sec) | |||||||
| Photo/Photo | with | Thermal: | 0 | to | 4,000 | fpm | (0 | to | 20 | m/sec) | (suitable | for | installation | in | ducts) |
Operating Humidity Range 10% to 93% non-condensing
| Thermal Ratings Fixed | Temperature | Setpoint: | 135°F | (57°C) |
| Rate-of-Rise | Detection: | 15°F/min. | (8.3°C/min.) | |
| High | Temperature | Heat: | 190°F | (88°C) |
Electrical Specifications
Voltage Range 15 to 32 VDC peak
| Standby Current (max. avg.) 300 | µA | @ | 24 | VDC | (one | communication | every | 5 | seconds | with | LED | enabled) | |||
| Photo/Photo | with | Thermal: | 300 | µA | @ | 24 | VDC | (one | communication | every | 5 | seconds | with | LED | enabled) |
LED Current (max.) 6.5 mA @ 24 VDC (on)
RA100Z
Remote LED Annunciator
XR2B
Detector
Removal Tool
| Head | also | sold | separately |
| (part | no. | T55-127-000) |
* Add “A” for ULC listed product (e.g., 2251BA)
| ** | The | BCK-200B | and | WCK-200B | are | only | applicable | to | the | B210LP | flanged | style | |
| mounting | base | and | may | only | be | used | with | 2251B | (photoelectric) | and | 1251B | ||
| (ionization) | smoke | detectors. |
File details come from the government source that posted it. Updated .