SilentKnight_6808_hbt-fire-351608-C.pdf

PDF 160 KB Posted

Attached to
FIRE ALARM SYS REPLACEMENT SERVICE - SKAGWAY AK Federal contract opportunity
Solicitation number
140P9723Q0077
Issued by
Department of the Interior National Park Service Alaska Region

About this file

This document provides product specifications and ordering information for the SilentKnight 6808 intelligent fire alarm control panel and compatible devices. The 6808 is a replacement for the 5808 panel and features a single SLC loop supporting up to 99 addressable detectors, four Flexput output circuits, a dual-line digital alarm communicator, and connectivity for up to 17 sites. Compatible devices include remote annunciators, printer interfaces, power supplies, addressable smoke, heat and pull stations, and the SWIFT wireless gateway and devices. The related federal contract opportunity is a solicitation from the National Park Service Alaska Region seeking replacement of a fire alarm system in Skagway, Alaska. The solicitation number is 140P9723Q0077.

View the file

Other files for this federal contract opportunity

Other files attached to FIRE ALARM SYS REPLACEMENT SERVICE - SKAGWAY AK, newest first.
File Type Posted
Sol_140P9723Q0077_Amd_0001.pdf PDF
Bldg_Device_Inventories.zip ZIP file
SK-Photo_DataSheet_350118.pdf PDF
SilentKnight_SwiftGateway_WSK-WGI_DataSheet.pdf PDF
B03_DL_WD_2015-5685_Rev_19.pdf PDF
SystemSensor_Heat_200Series_DataSheet_A05-0362.pdf PDF
KLGO_Pantheon_Saloon___Red_Front_FireAlarm_plans.pdf PDF
System-Smoke-Detectors-AppGuide-SPAG91.pdf PDF
SilentKnight_PullStations_DataSheet.pdf PDF
Sol_140P9723Q0077.pdf PDF
B08_SOW.pdf PDF
B08_RFQ_Content.pdf PDF
Swift_AVbase_DataSheet.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Intelligent Fire Alarm Control Panel with Communicator

The 6808 is the latest intelligent addressable FACP (Fire Alarm Control Panel) from Silent Knight and is a direct replacement for the 5808 FACP. The 6808 has one SLC (signaling line circuit) loop for connecting addressable detectors, which can support 99 System Sensor® SK sensors and 99 SK modules or 127 Hochiki® SD devices per loop.

A common communications and annunciation link allows up to 17 panels to be connected via copper or fiber optic cable. A designated panel is configured as the communicator for all panels in the link for convenient single-point communications.

The built-in digital alarm communicator/transmitter (DACT) is dual technology, IP and POTS. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available.

The 6808 has four onboard Flexput® circuits that can be configured as notification outputs or auxiliary power. There are four types of Aux power available: door holder, constant power, resettable power and sounder sync power. The 6808 also has form-C trouble relay, and two programmable form-C relays, along with powerful features such as drift compensation, pre-trouble maintenance alert, a built-in sensor test to comply with NFPA 72 calibration testing requirements, and a calibration trouble alert.

The 6808 supports a variety of devices, including 6860, 5860, or 6855 remote annunciators, 5824 serial/parallel printer interface modules (for printing system reports), 5895XL power modules, and SK, SWIFT® wireless, or SD devices.

FEATURES AND BENEFITS

• Complies with UL 864 10th Edition

• Built-in support for up to 99 IDP/SK detectors and 99 IDP/SK modules or 127 SD SLC devices

• Four Flexput circuits (3 amps max) for NAC outputs or auxiliary power

• Selectable strobe synchronization for Amseco®, System Sensor, Wheelock®, and Gentex® devices

• 250 software zones and 250 output groups for flexible design options

• Built-in dual phone line, digital alarm communicator/ transmitter (DACT) with IP and optional cellular technologies

• Four line LCD display with 20 characters per line

• Built-in USB interface for quick and easy programming

• JumpStart® auto programming reduces installation time

• 13 preset notification cadence patterns (including ANSI® 3.41)

• Allows up to 20 SBUS devices

• Two programmable relays and one fixed trouble relay

• Convenient field-upgradeable firmware

• Supports up to four SWIFT wireless gateways which can foster up to 49 wireless devices each

• Connectivity for up to 17 sites

• Network card allows copper network connection with a multi-mode or single-mode fiber connection

• Programmable date setting for Daylight Savings Time

• History file with 1,000 event capacity

• Can be surface or flush-mounted

The 6808 features a built-in SLC circuit, four Flexput® circuits, dual-line DACT, powerful software features, and connectivity for up to 17 panels.

Page 2 of 4 — 351608:C • 3/10/2022

USER INTERFACE

LED INDICATORS

• General Alarm (Red)

• Supervisory (Yellow)

• System Trouble (Yellow)

• System Silenced (Yellow

• System Power (Green)

KEYPAD

• 12-key numeric pad

• Acknowledge

• Alarm Silence

• System Reset

• F1-F4 Programmable Function Keys

PROGRAMMING

The 6808 system offers several options to simplify and expedite programming. JumpStart auto programming minimizes programming required to start a new system. The built-in keypad, or the remote annunciators give on-site access to current system programming. System programming can also be accomplished using the Windows®-based Honeywell Fire Software Suite (HFSS).

ORDERING INFORMATION

6808: Addressable fire alarm control panel, red

COMPATIBLE SBUS DEVICES

6860: 4x40 LCD remote fire annunciator with four programmable buttons, red

5860: 4x20 LCD remote fire annunciator, gray

5860R: 4x20 LCD remote fire annunciator, red

6855: 4x20 LCD remote fire annunciator, red

5865-3: LED annunciators can display up to 30 LEDs (15 red and 15 yellow)

5865-4: LED annunciators can display up to 30 LEDs (15 red and 15 yellow). Key switches for silence and reset, and a system trouble

LED

5880: LED I/O module with 40 programmable LED outputs and eight supervised dry contact inputs

5883: Relay interface. Provides 10 Form C relays

5824: Serial/Parallel printer interface module for printer connection

SK COMPATIBLE ADDRESSABLE DEVICES

Note: SK and SD devices cannot be mixed in the same system. Refer to the Device Compatibility Document and SLC Wiring Manual for more information.

SK-ACCLIMATE: Multi criteria photoelectric smoke detector with thermal 135°F fixed temperature

SK-BEAM: Reflected beam smoke detector without test feature

SK-BEAM-T: Reflected beam smoke detector with test feature

OSI-RI-SK: Reflected beam smoke detector, SK protocol

SK-CONTROL: Supervised control module

SK-CONTROL-6: Six circuit supervised control module

SK-DUCT: Photoelectric duct smoke detector with extended air speed range

SK-FIRE-CO: Four criteria fire and carbon monoxide detector

SK-FIRE-CO-W: Four criteria fire and carbon monoxide detector, white

SK-HEAT: Fixed thermal detector (135°F)

SK-HEAT-W: Fixed thermal detector (135°F), white

SK-HEAT-ROR: Fixed rate of rise detector

SK-HEAT-HT: Fixed high temperature thermal detector (190°F)

SK-HEAT-HT-W: Fixed high temperature thermal detector (190°F), white

SK-HEAT-ROR-W: Fixed rate of rise detector, white

SK-ISO: Fault isolator module

SK-MINIMON: Mini monitor module

SK-MONITOR: Monitor module

SK-MONITOR-2: Dual input monitor module

SK-MON-10: 10- input monitor module

SK-PHOTO: Photoelectric smoke detector

SK-PHOTO-W: Photoelectric smoke detector, white

SK-PHOTO-R: Photoelectric detector with remote test capability

SK-PHOTO-R-W: Photoelectric detector with remote test capability, white

SK-PHOTO-T: Photoelectric smoke detector with fixed thermal heat (135°F)

SK-PHOTO-T-W: Photoelectric smoke detector with fixed thermal heat (135°F), white

SK-PTIR-W: Multi criteria photoelectric smoke detector with thermal 135°F fixed temperature, white

SK-PULL-SA Addressable single action pull station

SK-PULL-DA: Addressable dual action pull station

SK-RELAY: Addressable relay module

SK-RELAY-6: Addressable Six relay control module

SK-RELAYMON-2: Addressable Dual relay/monitor module

SK-ZONE: Addressable zone interface module

SK-ZONE-6: Six zone interface module

SK BASES

B210LP: 6" mounting base

B501: 4" Flangeless mounting base

B200S: Intelligent sounder base

B200S-LF: Low-frequency intelligent sounder base

B224RB: Relay base

B224BI: Isolator base

SD COMPATIBLE ADDRESSABLE DEVICES

Note: SK and SD devices cannot be mixed in the same system.

SD505-6AB: Addressable 6" base

SD505-6IB: Addressable 6" short circuit isolator base

SD505-6RB: Addressable 6" relay base

SD505-6SB: Addressable 6" sounder base

SD500-AIM: Addressable input module (switch input)

SD500-ANM: Addressable notification module

SD500-ARM: Addressable relay module

SD505-DTS-K: Remote test switch/LED indicator for the

SD505-DUCTR

SD505-DUCT: Addressable Duct Smoke Detector

SD505-DUCTR: Addressable Duct Detector housing with relay base

Page 3 of 4 — 351608:C • 3/10/2022

SD505-HEAT: Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C)

SD500-LIM: Addressable Line isolator module

SD500-MIM: Addressable Mini input monitor module (switch input)

SD505-PHOTO: Photoelectric smoke detector

SD500-PS/-PSDA: Addressable Single or dual action pull station

SD500-SDM: Addressable smoke detector module

SWIFT WIRELESS DEVICES

Note: SWIFT is only compatible with System Sensor (SK) devices. It is not compatible with Hochiki (SD) devices.

WSK-WGI: Wireless gateway

WSK-PHOTO: Wireless photoelectric smoke detector with B501W base

WSK-PHOTO-T: Wireless photoelectric smoke detector with fixed thermal detection (135°F) and B501W base

W-SYNC: Wireless sync module

WSK-HEAT: Wireless, fixed heat detector (135°F) with B501W base

WSK-HEAT-ROR: Wireless rate-of-rise heat detector and B501W base

WSK-MONITOR: Wireless monitor module

WSK-RELAY: Wireless relay module

WSK-PULL-DA: Wireless pull station

WAV-CRL, WAV-CWL: Wireless AV bases

W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools

SWIFT Tools: Programming and diagnostic utility for the wireless gateway and devices. Available for download from www.farenhyt.com

SYSTEM EXPANDERS

5895XL: 6A power supply with six Flexput circuits and two Form C relays 5496: 6A NAC power expander with four power-limited output circuits

OPTIONAL COMMUNICATORS

HWF2A-COM: Digital Cellular Fire Alarm Communicator and Internet Panel, AT&T

HWF2V-COM: Digital Cellular Fire Alarm Communicator and Internet Panel, Verizon

IPGSM-4G: Dual path fire alarm communicator, cellular and/or IP (primary or backup, selectable)

SK-IP -2: Remote reporting via the Internet. Requires a VisorALARM® receiver at the central station

MISCELLANEOUS ACCESSORIES

SK-NIC: Network Interface Card. Provides a common communications link for the 6808

SK-NIC-KIT: Installation Accessory Kit

SK-FML: Fiber-Optic Multi Mode, transmitter and receiver

SK-FSL: Fiber-Optic Single Mode

RBB: Remote battery box accessory cabinet

SK-SCK: Seismic compliance kit to fasten batteries to the fire panel

SOFTWARE SOLUTIONS

SKST: Silent Knight Selection Tool provides the installer or design architect with a Windows®-based software system configuration tool to create a detailed bill of material (BOM) and battery calculations

HFSS: Honeywell Fire Software Suite provides remote and local panel programming, detector status, event history and additional data. Databases can be uploaded/downloaded via the panel’s USB port using a flash drive. Requires a PC running Microsoft® Windows®.

6808 TECHNICAL SPECIFICATIONS

351608 | C | 04-22 ©2022 Honeywell International Inc.

Flexput®, Honeywell®, JumpStart®, Silent Knight®, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc.

Amseco® is a registered trademark of Potter Electric Signal Company, LLC. Gentex® is a registered trademark of Gentex Corporation.

Hochiki® is a registered trademark of Hochiki Corporation. Wheelock® is a trademark of Cooper Technologies Company. ANSI® is a registered trademark of the American National Standards Institute, Inc. VisorALARM® is a registered trademark of the Teldat Corporation. Microsoft® and Windows® are registered trademarks of Microsoft Corporation.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

Country of origin: USA

Honeywell Silent Knight

12 Clintonville Road

Northford, CT 06472-1610

203.484.7161 www.silentknight.com

SYSTEM CAPACITY

Intelligent Signaling Line Circuits: 1

Addressable device capacity: 198 (SK) or

127 (SD)

Programmable software zones: 250

Output circuits: 4 (expandable)

SBUS Devices: 20 (12 annunciators, 8 LED modules)

ELECTRICAL

AC Power: 120 VAC, 60 Hz, 3.3 A

Standby Current: 190 mA

Alarm Current: 250 mA

Flexput Circuits: Terminal block provides connections for (four Class B or two Class A) NACs or auxiliary power. Power-limited, supervised circuitry. Maximum current per circuit: 3 A. Cannot exceed 6A total for all circuits. End-of-line resistor: 4.7k ohm, ½ watt for Class B NACs

Communication Loop: Supervised and power-limited, Class A or Class B, 32VDC, 150mA

Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.5 A @ 27.4 VDC (resistive), Form C

Battery: Cabinet holds maximum of two 18 AH batteries

Battery Charger Capacity: 17-55 AH

PHYSICAL

Dimensions: 16.4” W x 26.4” H x 4.1” D

(41.66cm W x 67.06cm H x 10.41cm D)

Weight: 45 lbs. (20.4 kg.)

Color: Red

TEMPERATURE AND HUMIDITY

RANGES

This system meets NFPA requirements for operation at 0 – 49°C (32– 120°F) and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).

However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity.

Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

NFPA STANDARDS

The 6808 complies with the following NFPA 72 Fire Alarms Systems requirements: NFPA

13, NFPA 15, NFPA 16, NFPA 70, NFPA 72

Central station; remote Signaling; Local Protective Signaling Systems; Auxiliary Protected Premises Unit; Water Deluge releasing service. Suitable for automatic, manual, waterflow, sprinkler supervisory (DACT non-coded) signaling services

AGENCY LISTINGS AND

APPROVALS

UL Listed: S2766

CSFM: 7165-0559:0502

FDNY: COA# 6246

FM Approved

Seismic: (CA) VMA-45894-05C