SilentKnight_6808_hbt-fire-351608-C.pdf
PDF 160 KB Posted
- Attached to
- FIRE ALARM SYS REPLACEMENT SERVICE - SKAGWAY AK Federal contract opportunity
- Solicitation number
- 140P9723Q0077
About this file
This document provides product specifications and ordering information for the SilentKnight 6808 intelligent fire alarm control panel and compatible devices. The 6808 is a replacement for the 5808 panel and features a single SLC loop supporting up to 99 addressable detectors, four Flexput output circuits, a dual-line digital alarm communicator, and connectivity for up to 17 sites. Compatible devices include remote annunciators, printer interfaces, power supplies, addressable smoke, heat and pull stations, and the SWIFT wireless gateway and devices. The related federal contract opportunity is a solicitation from the National Park Service Alaska Region seeking replacement of a fire alarm system in Skagway, Alaska. The solicitation number is 140P9723Q0077.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P9723Q0077_Amd_0001.pdf | ||
| Bldg_Device_Inventories.zip | ZIP file | |
| SK-Photo_DataSheet_350118.pdf | ||
| SilentKnight_SwiftGateway_WSK-WGI_DataSheet.pdf | ||
| B03_DL_WD_2015-5685_Rev_19.pdf | ||
| SystemSensor_Heat_200Series_DataSheet_A05-0362.pdf | ||
| KLGO_Pantheon_Saloon___Red_Front_FireAlarm_plans.pdf | ||
| System-Smoke-Detectors-AppGuide-SPAG91.pdf | ||
| SilentKnight_PullStations_DataSheet.pdf | ||
| Sol_140P9723Q0077.pdf | ||
| B08_SOW.pdf | ||
| B08_RFQ_Content.pdf | ||
| Swift_AVbase_DataSheet.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Intelligent Fire Alarm Control Panel with Communicator
The 6808 is the latest intelligent addressable FACP (Fire Alarm Control Panel) from Silent Knight and is a direct replacement for the 5808 FACP. The 6808 has one SLC (signaling line circuit) loop for connecting addressable detectors, which can support 99 System Sensor® SK sensors and 99 SK modules or 127 Hochiki® SD devices per loop.
A common communications and annunciation link allows up to 17 panels to be connected via copper or fiber optic cable. A designated panel is configured as the communicator for all panels in the link for convenient single-point communications.
The built-in digital alarm communicator/transmitter (DACT) is dual technology, IP and POTS. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available.
The 6808 has four onboard Flexput® circuits that can be configured as notification outputs or auxiliary power. There are four types of Aux power available: door holder, constant power, resettable power and sounder sync power. The 6808 also has form-C trouble relay, and two programmable form-C relays, along with powerful features such as drift compensation, pre-trouble maintenance alert, a built-in sensor test to comply with NFPA 72 calibration testing requirements, and a calibration trouble alert.
The 6808 supports a variety of devices, including 6860, 5860, or 6855 remote annunciators, 5824 serial/parallel printer interface modules (for printing system reports), 5895XL power modules, and SK, SWIFT® wireless, or SD devices.
FEATURES AND BENEFITS
• Complies with UL 864 10th Edition
• Built-in support for up to 99 IDP/SK detectors and 99 IDP/SK modules or 127 SD SLC devices
• Four Flexput circuits (3 amps max) for NAC outputs or auxiliary power
• Selectable strobe synchronization for Amseco®, System Sensor, Wheelock®, and Gentex® devices
• 250 software zones and 250 output groups for flexible design options
• Built-in dual phone line, digital alarm communicator/ transmitter (DACT) with IP and optional cellular technologies
• Four line LCD display with 20 characters per line
• Built-in USB interface for quick and easy programming
• JumpStart® auto programming reduces installation time
• 13 preset notification cadence patterns (including ANSI® 3.41)
• Allows up to 20 SBUS devices
• Two programmable relays and one fixed trouble relay
• Convenient field-upgradeable firmware
• Supports up to four SWIFT wireless gateways which can foster up to 49 wireless devices each
• Connectivity for up to 17 sites
• Network card allows copper network connection with a multi-mode or single-mode fiber connection
• Programmable date setting for Daylight Savings Time
• History file with 1,000 event capacity
• Can be surface or flush-mounted
The 6808 features a built-in SLC circuit, four Flexput® circuits, dual-line DACT, powerful software features, and connectivity for up to 17 panels.
Page 2 of 4 — 351608:C • 3/10/2022
USER INTERFACE
LED INDICATORS
• General Alarm (Red)
• Supervisory (Yellow)
• System Trouble (Yellow)
• System Silenced (Yellow
• System Power (Green)
KEYPAD
• 12-key numeric pad
• Acknowledge
• Alarm Silence
• System Reset
• F1-F4 Programmable Function Keys
PROGRAMMING
The 6808 system offers several options to simplify and expedite programming. JumpStart auto programming minimizes programming required to start a new system. The built-in keypad, or the remote annunciators give on-site access to current system programming. System programming can also be accomplished using the Windows®-based Honeywell Fire Software Suite (HFSS).
ORDERING INFORMATION
6808: Addressable fire alarm control panel, red
COMPATIBLE SBUS DEVICES
6860: 4x40 LCD remote fire annunciator with four programmable buttons, red
5860: 4x20 LCD remote fire annunciator, gray
5860R: 4x20 LCD remote fire annunciator, red
6855: 4x20 LCD remote fire annunciator, red
5865-3: LED annunciators can display up to 30 LEDs (15 red and 15 yellow)
5865-4: LED annunciators can display up to 30 LEDs (15 red and 15 yellow). Key switches for silence and reset, and a system trouble
LED
5880: LED I/O module with 40 programmable LED outputs and eight supervised dry contact inputs
5883: Relay interface. Provides 10 Form C relays
5824: Serial/Parallel printer interface module for printer connection
SK COMPATIBLE ADDRESSABLE DEVICES
Note: SK and SD devices cannot be mixed in the same system. Refer to the Device Compatibility Document and SLC Wiring Manual for more information.
SK-ACCLIMATE: Multi criteria photoelectric smoke detector with thermal 135°F fixed temperature
SK-BEAM: Reflected beam smoke detector without test feature
SK-BEAM-T: Reflected beam smoke detector with test feature
OSI-RI-SK: Reflected beam smoke detector, SK protocol
SK-CONTROL: Supervised control module
SK-CONTROL-6: Six circuit supervised control module
SK-DUCT: Photoelectric duct smoke detector with extended air speed range
SK-FIRE-CO: Four criteria fire and carbon monoxide detector
SK-FIRE-CO-W: Four criteria fire and carbon monoxide detector, white
SK-HEAT: Fixed thermal detector (135°F)
SK-HEAT-W: Fixed thermal detector (135°F), white
SK-HEAT-ROR: Fixed rate of rise detector
SK-HEAT-HT: Fixed high temperature thermal detector (190°F)
SK-HEAT-HT-W: Fixed high temperature thermal detector (190°F), white
SK-HEAT-ROR-W: Fixed rate of rise detector, white
SK-ISO: Fault isolator module
SK-MINIMON: Mini monitor module
SK-MONITOR: Monitor module
SK-MONITOR-2: Dual input monitor module
SK-MON-10: 10- input monitor module
SK-PHOTO: Photoelectric smoke detector
SK-PHOTO-W: Photoelectric smoke detector, white
SK-PHOTO-R: Photoelectric detector with remote test capability
SK-PHOTO-R-W: Photoelectric detector with remote test capability, white
SK-PHOTO-T: Photoelectric smoke detector with fixed thermal heat (135°F)
SK-PHOTO-T-W: Photoelectric smoke detector with fixed thermal heat (135°F), white
SK-PTIR-W: Multi criteria photoelectric smoke detector with thermal 135°F fixed temperature, white
SK-PULL-SA Addressable single action pull station
SK-PULL-DA: Addressable dual action pull station
SK-RELAY: Addressable relay module
SK-RELAY-6: Addressable Six relay control module
SK-RELAYMON-2: Addressable Dual relay/monitor module
SK-ZONE: Addressable zone interface module
SK-ZONE-6: Six zone interface module
SK BASES
B210LP: 6" mounting base
B501: 4" Flangeless mounting base
B200S: Intelligent sounder base
B200S-LF: Low-frequency intelligent sounder base
B224RB: Relay base
B224BI: Isolator base
SD COMPATIBLE ADDRESSABLE DEVICES
Note: SK and SD devices cannot be mixed in the same system.
SD505-6AB: Addressable 6" base
SD505-6IB: Addressable 6" short circuit isolator base
SD505-6RB: Addressable 6" relay base
SD505-6SB: Addressable 6" sounder base
SD500-AIM: Addressable input module (switch input)
SD500-ANM: Addressable notification module
SD500-ARM: Addressable relay module
SD505-DTS-K: Remote test switch/LED indicator for the
SD505-DUCTR
SD505-DUCT: Addressable Duct Smoke Detector
SD505-DUCTR: Addressable Duct Detector housing with relay base
Page 3 of 4 — 351608:C • 3/10/2022
SD505-HEAT: Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C)
SD500-LIM: Addressable Line isolator module
SD500-MIM: Addressable Mini input monitor module (switch input)
SD505-PHOTO: Photoelectric smoke detector
SD500-PS/-PSDA: Addressable Single or dual action pull station
SD500-SDM: Addressable smoke detector module
SWIFT WIRELESS DEVICES
Note: SWIFT is only compatible with System Sensor (SK) devices. It is not compatible with Hochiki (SD) devices.
WSK-WGI: Wireless gateway
WSK-PHOTO: Wireless photoelectric smoke detector with B501W base
WSK-PHOTO-T: Wireless photoelectric smoke detector with fixed thermal detection (135°F) and B501W base
W-SYNC: Wireless sync module
WSK-HEAT: Wireless, fixed heat detector (135°F) with B501W base
WSK-HEAT-ROR: Wireless rate-of-rise heat detector and B501W base
WSK-MONITOR: Wireless monitor module
WSK-RELAY: Wireless relay module
WSK-PULL-DA: Wireless pull station
WAV-CRL, WAV-CWL: Wireless AV bases
W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools
SWIFT Tools: Programming and diagnostic utility for the wireless gateway and devices. Available for download from www.farenhyt.com
SYSTEM EXPANDERS
5895XL: 6A power supply with six Flexput circuits and two Form C relays 5496: 6A NAC power expander with four power-limited output circuits
OPTIONAL COMMUNICATORS
HWF2A-COM: Digital Cellular Fire Alarm Communicator and Internet Panel, AT&T
HWF2V-COM: Digital Cellular Fire Alarm Communicator and Internet Panel, Verizon
IPGSM-4G: Dual path fire alarm communicator, cellular and/or IP (primary or backup, selectable)
SK-IP -2: Remote reporting via the Internet. Requires a VisorALARM® receiver at the central station
MISCELLANEOUS ACCESSORIES
SK-NIC: Network Interface Card. Provides a common communications link for the 6808
SK-NIC-KIT: Installation Accessory Kit
SK-FML: Fiber-Optic Multi Mode, transmitter and receiver
SK-FSL: Fiber-Optic Single Mode
RBB: Remote battery box accessory cabinet
SK-SCK: Seismic compliance kit to fasten batteries to the fire panel
SOFTWARE SOLUTIONS
SKST: Silent Knight Selection Tool provides the installer or design architect with a Windows®-based software system configuration tool to create a detailed bill of material (BOM) and battery calculations
HFSS: Honeywell Fire Software Suite provides remote and local panel programming, detector status, event history and additional data. Databases can be uploaded/downloaded via the panel’s USB port using a flash drive. Requires a PC running Microsoft® Windows®.
6808 TECHNICAL SPECIFICATIONS
351608 | C | 04-22 ©2022 Honeywell International Inc.
Flexput®, Honeywell®, JumpStart®, Silent Knight®, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc.
Amseco® is a registered trademark of Potter Electric Signal Company, LLC. Gentex® is a registered trademark of Gentex Corporation.
Hochiki® is a registered trademark of Hochiki Corporation. Wheelock® is a trademark of Cooper Technologies Company. ANSI® is a registered trademark of the American National Standards Institute, Inc. VisorALARM® is a registered trademark of the Teldat Corporation. Microsoft® and Windows® are registered trademarks of Microsoft Corporation.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.
Country of origin: USA
Honeywell Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161 www.silentknight.com
SYSTEM CAPACITY
Intelligent Signaling Line Circuits: 1
Addressable device capacity: 198 (SK) or
127 (SD)
Programmable software zones: 250
Output circuits: 4 (expandable)
SBUS Devices: 20 (12 annunciators, 8 LED modules)
ELECTRICAL
AC Power: 120 VAC, 60 Hz, 3.3 A
Standby Current: 190 mA
Alarm Current: 250 mA
Flexput Circuits: Terminal block provides connections for (four Class B or two Class A) NACs or auxiliary power. Power-limited, supervised circuitry. Maximum current per circuit: 3 A. Cannot exceed 6A total for all circuits. End-of-line resistor: 4.7k ohm, ½ watt for Class B NACs
Communication Loop: Supervised and power-limited, Class A or Class B, 32VDC, 150mA
Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.5 A @ 27.4 VDC (resistive), Form C
Battery: Cabinet holds maximum of two 18 AH batteries
Battery Charger Capacity: 17-55 AH
PHYSICAL
Dimensions: 16.4” W x 26.4” H x 4.1” D
(41.66cm W x 67.06cm H x 10.41cm D)
Weight: 45 lbs. (20.4 kg.)
Color: Red
TEMPERATURE AND HUMIDITY
RANGES
This system meets NFPA requirements for operation at 0 – 49°C (32– 120°F) and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.
NFPA STANDARDS
The 6808 complies with the following NFPA 72 Fire Alarms Systems requirements: NFPA
13, NFPA 15, NFPA 16, NFPA 70, NFPA 72
Central station; remote Signaling; Local Protective Signaling Systems; Auxiliary Protected Premises Unit; Water Deluge releasing service. Suitable for automatic, manual, waterflow, sprinkler supervisory (DACT non-coded) signaling services
AGENCY LISTINGS AND
APPROVALS
UL Listed: S2766
CSFM: 7165-0559:0502
FDNY: COA# 6246
FM Approved
Seismic: (CA) VMA-45894-05C
File details come from the government source that posted it. Updated .