SUPPLYSPEC - PDU.docx

DOCX document 16 KB Posted

Attached to
PD-60-0099; AVDB Dell Server Tech Refresh
Solicitation number
N64498-26-SIMACQ-PD-60-0099
Issued by

About this file

This file is a specification document for Schneider Electric Power Distribution Units (PDUs) required as part of a federal procurement. The document outlines detailed technical specifications for PDU equipment that the Naval Surface Warfare Center, Philadelphia Division (NSWCPD) is seeking to procure alongside three Dell PowerEdge servers under Sources Sought notice N64498-26-SIMACQ-PD-60-0099.

The specification document provides engineering requirements and performance standards for the PDU units, ensuring compatibility and functionality with the Dell server infrastructure being refreshed. Interested vendors and contractors are required to submit capability statements addressing their ability to provide equipment meeting these specifications by the 06:00 PM EST deadline on September 21, 2026. Responses must be submitted electronically to jenny.e.tomeo.civ@us.navy.mil with the solicitation number in the subject line. This is a market research effort conducted by the Department of the Navy Naval Sea Systems Command for planning purposes only, with no payment offered for responses and all submissions becoming Government property. Proprietary information submitted will be protected in accordance with applicable regulations.

View the file

Other files

File Type Posted
Sources Sought_Notice Code 60 Dell Severs_SAPCOM.docx DOCX document
SUPPLYSPEC - 2 Servers for Database.docx DOCX document
SUPPLYSPEC - 1 Server for Process Management (1).docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Standalone Tech Refresh Server Specifications/Requirements

Item 0003 Quantity: 1

Rackmount Power Distribution Unit (PDU) shall have the following specifications:

1. Power Specifications:

a. Input Current: 30 ampere

b. Input Voltage: 200V AC, 208V AC

c. Input Frequency: 50/60Hz

d. Load Capacity: 5000 watt / 4992 VA

e. Output Voltage: 200V AC, 208V AC

2. Protection:

a. Must have circuit breaker protection

3. Receptacle/Plug Specifications:

a. Must include minimum of thirty six IEC 60320 C13 receptacles

b. Must include minimum of six IEC 60320 C19 receptacles

c. Must include a NEMA L6-30P input plug with a cord of minimum 2.5m in length

4. Form factor:

a. Must be Rackmount of type 0U form factor

5. Features:

a. Must have user-interactive LCD interface

b. Must have metering capability

c. Must have remote monitoring capability

File details come from the government source that posted it. Updated .