Statement of Work - Comms Installation of Power Whips for Server Rack Power Feeds.pdf
PDF 144 KB Posted
- Solicitation number
- FA465426Q0012
About this file
Statement of Work Summary: Server Rack Power Feeds Installation
This is a Statement of Work (SOW) for the installation of electrical power feeds to support server rack equipment at Grissom Air Force Base, Indiana. The project consists of two separate installations: Project 1 requires installation of four (4) independent 240V/208V, 30-Amp single-phase power circuits with NEMA L6-30R locking receptacles rated for 250V/30A, each mounted in code-compliant metal junction boxes on server rack rails or structural channels. Project 2 requires installation of two (2) independent 125V, 15-Amp single-phase power circuits with NEMA L5-15R locking receptacles rated for 125V/15A, similarly mounted. Both projects involve approximately 25-foot conduit runs from existing electrical panels or UPS systems using appropriately sized copper wire (minimum 10 AWG), professional code-compliant routing through overhead cable ladders or underfloor spaces, installation of new breakers, and comprehensive testing and grounding verification. Project 1 sources power from an existing Eaton Model 9393 Datacenter UPS (50 kVA, Serial EL201CBC03) requiring installation of four double-pole 30A breakers. Project 2 sources power from Building 427 power panel H and Building 671 XTREME Model M90 UPS (15 kVA, Serial M910241100002), requiring installation of single-pole 15A breakers in two separate locations.
This is a firm, fixed-price (FFP) turnkey installation with all work, testing, and government acceptance required by August 10, 2026. The contractor bears all responsibility for field verification of conditions, breaker compatibility, panel space availability, and exact conduit routing complexity, with a mandatory pre-bid site visit required. Payment will be made in a single lump sum only after 100% completion and formal written government acceptance. Deliverables include four operational NEMA L6-30R receptacles and two L5-15R receptacles, certified testing sheets verifying voltage/polarity/grounding for each run, and an "As-Built" sketch detailing electrical pathways and breaker assignments. The project is subject to 2009 International Building Code, current National Electrical Code (NEC), NFPA 13, Architectural Barriers Act, and Defense Intelligence Agency Construction Security Plan requirements. Contractor personnel require background checks, vehicle passes, and base identification badges, with mandatory escort requirements in Building 427 Datacenter (a secure controlled area). Government POCs are Contracting Officer Cedric Roberts (765-688-2818) and Project Manager Chris Duncan (765-688-4459).
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work (SOW) Installation of 240V/208V 30A and 125V 15A
Server Rack Power Feeds
Grissom Air Force Base, Indiana
July 20, 2026
BACKGROUND: The 434th Communications Squadron (434 CS) is undergoing a scheduled technology refresh of communications equipment in building 427.
To support the deployment of the new core nodes and server switches, the facility requires the installation of dedicated 30-Amp power feeds. A total of four (4) runs are required to support the server rack from an existing uninterruptible power supply (UPS) system.
Because the server racks are separated from the walls to allow walk-around access (front and rear clearance), the contractor must install facility-mounted electrical receptacles directly on the real property structure (e.g., mounted securely to the top or bottom of the server rack rails or under the raised floor tiles immediately adjacent to the racks). The 434 CS will separately acquire and connect the power receptacles/PDUs from the IT equipment to these newly installed receptacles.
A second project is scheduled to take place to accomplish tech refresh of communications equipment in Building 427 DCO and Building 671 communications room. These facilities require the installation of dedicated 15-Amp power feeds. A total of two (2) runs are required to support the server racks. To accommodate for standalone rackmount UPS.
SECURITY: Contractor personnel will require background checks, vehicle passes, and base identification badges to work on Grissom ARB. Background checks can take several weeks and must be initiated immediately upon award. Building 427 Datacenter is a secure controlled area.
Contractor personnel must be escorted at all times while performing work in this facility.
Escorts will be coordinated by the 434 CS Project POCs. Any penetration of fire-rated walls, ceilings, or floors must be properly sealed with approved fire-stopping materials. Any work impacting facility airflow or fire barriers must be coordinated with the Base Fire Inspector.
OBJECTIVES: The contractor shall be responsible for all labor, materials, and equipment required to complete the work described herein, regardless of the site conditions discovered.
This project is a firm, fixed price (FFP) turnkey installation. The contractor is solely responsible for the verification of all field conditions, including but not limited to, breaker panel space and compatibility, routing, pathways for conduits, structural mounting points, and adherence to all referenced codes. The Government will not be liable for any claims resulting from the contractor’s failure to perform due diligence. Refer to the below scope of work & specifications.
Project 1: Specification Area Required Details
Power Requirement 240V/208V, Single-Phase, 30-Amp. (Total estimated load: 37.5 Amps, 7,810 Watts, 9,000 VA).
Quantity Four (4) independent circuit runs.
Receptacle Type NEMA L6-30R (Locking Receptacles) rated for 250V/30A, each mounted in a secure, code-compliant metal junction box. Junction boxes must be mounted on the top or bottom of the server rack or secure structural channels.
Wiring & Distance Approximately 25-foot run from the source electrical/UPS panel to the server racks. Must use appropriately sized copper wire (minimum 10 AWG or as required by code/distance to prevent voltage drop).
Source Panel / UPS existing Eaton Model 9393 Datacenter UPS (50 kVA, Serial Number: EL201CBC03) panel A, B, or C.
Breakers Install four (4) new double-pole 30A breakers in the existing Eaton UPS panel A, B, or C.
Contractor is responsible for verifying breaker brand, location, and type compatibility during the pre-bid site visit.
Routing & Conduit All wiring must be routed professionally and safely using code-compliant conduit (e.g., EMT or Liquid-tight flexible metallic conduit where applicable) utilizing existing overhead cable ladders, under-floor spaces, or drop ceilings as determined during the site visit.
Testing & Grounding Contractor must test all four (4) receptacles for proper phase-to-phase and phase-to-ground voltage, polarity, and grounding. A copy of the test results must be provided to the Government Project Manager.
Project 2: Specification Area Required Details
Power Requirement 125V, Single-Phase, 15-Amp.
Quantity Two (2) independent circuit runs.
Receptacle Type NEMA L5-15R (Locking Receptacles) rated for 125V/15A, each mounted in a secure, code-compliant metal junction box. Junction boxes must be mounted on the top or bottom of the server rack or secure structural channels.
Wiring & Distance Approximately 25-foot run from the source electrical/UPS panel to the server racks. Must use appropriately sized copper wire (minimum 10 AWG or as required by code/distance to prevent voltage drop).
Source Panel / UPS Building 427 – existing power panel H, located in room 1518-1.
Building 671 - existing XTREME Model M90 UPS (15 kVA, Serial Number:
M910241100002) located in room 1701A, feeds panel U located in room 1505-2.
Breakers Install 1 (1) new single-pole 15A breaker in the existing panel H in building 427 mechanical room 1518-1. Install one (1) new single-pole 15A breaker in the existing panel U in building 671 room 1505-2. Contractor is responsible for verifying breaker brand and type compatibility during the pre-bid site visit.
Routing & Conduit All wiring must be routed professionally and safely using code-compliant conduit (e.g., EMT or Liquid-tight flexible metallic conduit where applicable) utilizing existing overhead cable ladders, under-floor spaces, or drop ceilings as determined during the site visit.
Testing & Grounding Contractor must test all two (2) receptacles for proper phase-to-phase and phase-to-ground voltage, polarity, and grounding. A copy of the test results must be provided to the Government Project Manager.
PERIOD OF PERFORMANCE: Due to high operational mission importance and the firm scheduled installation date for the core network equipment, all physical work, testing, and government acceptance must be fully completed on or before August 10, 2026.
MEETINGS: A pre-bid site visit is mandatory for all bidding contractors to verify panel space, breaker compatibility, conduit routing paths, and rack layouts. The stated “25-foot run” is an estimate for informational purposes only. The contractor is responsible for verifying the exact length and complexity of the conduit run required and factoring it into their firm, fixed-price proposal. To schedule a site visit, contact the On-Site Escort Coordinator listed in Section 9.0.
After award, there will be one kick-off meeting after issuance of the Notice to Proceed (NTP) and prior to beginning construction. The kick-off meeting will be used to identify project participants, clarify work schedules and confirm procedures and requirements. There will be one progress meeting each month. Time and location of each meeting will be determined by the CO. All meetings will be on base.
GOVERNMENT FURNISHED INFORMATION: The Government will provide access to the building 427 Datacenter, building 671 roomd, the electrical/UPS panels, and existing cable tray routing paths. The Government (434 CS) is responsible for purchasing and installing the power whips/PDUs that plug into the contractor-installed NEMA L6-30R receptacles.
INSPECTION, ACCEPTANCE, AND INVOICING: This effort is defined as a Firm-Fixed- Price (FFP) service requirement. The Government will not authorize partial, advance, or progress payments for this work. Payment will be made in a single lump sum only after 100% completion of all services, installation, testing, and site cleanup as defined in this Statement of Work. Final payment is contingent upon a final physical inspection and formal written acceptance of the completed work by the designated Government Point of Contact (POC) or Contracting Officer’s Representative (COR). The contractor shall not submit an invoice for payment through the Wide Area Workflow (WAWF) system until formal Government acceptance has been granted.
DELIVERABLES: As stated in the Contract. FFP proposal. Turnkey installation of four (4) operational NEMA L6-30R receptacles and 2 L5-15P receptacles. Certified testing sheet verifying proper voltage, polarity, and grounding for each run. Simple "As-Built" sketch or diagram detailing the electrical run pathways and breaker panel assignments.
REFERENCES: This project shall be defined in accordance all pertinent codes including but not limited to the following:
a. The 2009 International Building Code (IBC) and all related specialty codes
b. The current National Electrical Code (NEC)
c. The National Fire Protection Association code for fire protection (NFPA 13)
d. The Architectural Barriers Act (ABA) for federal facilities
e. Intelligence Community Standard (ICS) 705-1, ICS 705-2 and the ICS Tech Spec
f. Defense Intelligence Agency (DIA) Construction Security Plan – CSW Version
1.0 (November 10, 2010)
GOVERNMENT POINTS OF CONTACT (POC): Subject to change, Contracting Officers (CO): Cedric Roberts