This is a Statement of Requirements document specifying technical requirements for one 270 VDC Load Bank for the Department of the Air Force Air Combat Command under solicitation FA480025QA031.

The required load bank must have a maximum operating voltage of 270VDC, maximum current rating of 254 Amps, and maximum power rating of 69 kW. The unit must be constructed of Zintec coated 2mm steel with powder coated outer panel (RAL7003), featuring 3kW Incoloy 270V resistors with ±5% tolerance. Key specifications include forced air cooling with horizontal fan, IP55-rated electrical chamber and IP20-rated heat chamber, operating temperature range of 0-40°C, and case dimensions of 1140mm x 670mm x 1140mm high (45" x 26" x 45") weighing 179kg. The unit requires single phase 110V AC and 240V AC auxiliary power, includes digital panel meters for voltage (0-300VDC) and current (0-300A), and features six load channel switches, temperature indicators, and control circuitry with start/stop functionality. Quotes are due by 5:00 PM Eastern Time on February 20, 2025.

View the file

Other files for this federal contract opportunity

Other files attached to 270 VDC Load Bank, newest first.
File Type Posted
Load Bank 270 VDC.pdf PDF
RFQ Instructions Load Bank 270 VDC 1.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF REQUIREMENTS

For

270 VDC Load Bank

1 MXS/MXMG

Quantity: One 270 VDC Load Bank

Max operating voltage: 270VDC

Max current rating: 254 Amps

Max power rating: 69 kW

DC Cable Set Burton connector type: 270R-1100-000

Resistor Type: 3kW Incoloy 270V resistors; Tolerance +/-5%

Construction: Zintec coated 2mm steel

Finish: Powder coated outer panel; RAL7003

Auxiliary mains: Single phase 110V AC, 50/60Hz, Single phase 240V AC, 50/60Hz

Cooling: Forced air cooling, horizontal fan

Environmental Protection: Rating - Electrical chamber IP55, Heat chamber IP20

Movement: Swivel castors, forklift pockets, lifting eyes

Temperature: Operating: 0 – 40 ℃, 0 - 104 ℉, Storage: 0 – 80 ℃, 0 - 176 ℉

Current Shunt: 6A:1mV; Accuracy: ± 0.5%

Voltage Measurement: Fused direct terminal connection points

Case Size: 1140mm x 670mm x 1140mm High, 45” x 26” x 45”

Case weight: 179kg, 400lb

Lifting Eyes: 4×M12 long shank collared eyebolts

Test sockets: 4mm, 28VDC +ve & -ve, 270VDC +ve & -ve, Current 6A:1mV

Auxiliary sockets: IEC 60309 Blue 240V 50Hz with IP65 protective cap, IEC 60309 Yellow 120V 60Hz with IP65 protective cap

Digital Panel Voltmeter: 0-300VDC

Digital Panel Ammeter: 0-300A

Load channel switches: Channel 1 to 6: Amber illuminated IP65 rocker switches Mains switch: Green illuminated IP65 rocker switch

LED indicators: Over Temperature, 28V Circuit enabled

28V switch: 2 position rotary switch

Green Start button: Latching enabling of control circuit

Red Stop button: De-energises control circuit