This Statement of Need outlines the procurement of a 20 TON Split AC System for equipment purchase only. The Contracting Entity (CE) is responsible for furnishing all supervision, labor, transportation, materials, tools, incidentals, equipment, and quality assurance necessary to purchase the specified 20 TON Split AC Unit.

The required equipment consists of three main components: (1) Outdoor Unit (Condenser) with a nominal capacity of 20 TON (240,000 BTU/h), operating at 208/230V three-phase 60Hz, featuring dual scroll compressors, three fans, and efficiency ratings up to 11.2 EER/14.8 IEER, with dimensions of approximately 44-3/4" H x 83-7/8" W x 38-3/8" D and weighing 926 lbs; (2) Inside Unit (Air Handler) with matching 20 TON capacity, 5HP motor at 1725 RPM standard speed, 18-inch blower diameter and width, 16.5 FT² coil face area, 4-row deep coil with 15 fins per inch, dual thermal expansion valves (BBIZE-12.5-GA), and 20 x 25 x 1 filter size, operating at 230V three-phase 60Hz; and (3) Commercial Heat Element Kit for the air handler unit rated at 208/230V three-phase 60Hz. All electrical components are compatible with standard commercial three-phase power systems.

View the file

Other files

File Type Posted
Solicitation Amendment - FA301626Q00460001.pdf PDF
IMG_0227.jpeg JPEG file
Heating Element for AHU B41.jpg JPG image
Name Plate AHU B41.jpg JPG image
IMG_0226.jpeg JPEG file
IMG_0225.jpeg JPEG file
Pic4.jpg JPG image
SOO-B41 PURCHASE AC SPLIT SYSTEM.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF NEED

Equipment Only: 20 TON Split AC System

PROJECT SCOPE: CE shall furnish all supervision; labor, transportation materials, tools, incidentals, equipment, and quality assurance to purchase 20TON Split AC Unit.

SCOPE OF MATERIAL. Purchasing 20TON Split AC Unit.

Material that will be purchased is as follows:

Outdoor Unit (Condenser):

Nominal Capacity: 20 TON (240,000 BTU/h) Voltage: 208/230V – 3 Phase – 60HZ Refrigerant TYPE: R-454B Compressors: 2-Stage (Dual) Scroll Compressors Fans: 3 Efficiency: Up to 11.2 EER / 14.8 IEER Dimensions: ~44-3/4” H x 83-7/8” W x 38- 3/8” D Weight: 926lbs Minimum Circuit Ampacity (MCA): 91A Maximum Fuse/Breaker: 110 A

Inside Unit (Air Handler):

Nominal Capacity: 20 TON (240,000 BTU/h) Motor Horsepower: Standard (1725 RPM) 5HP Blower Diameter: 18 in.

Blower Width: 18 in Blower Shaft Size: 1 in Motor Sheave Size: VP56 1- 1/8” in Belt Type and Size: B51 Coil Face Area 16.5 FT^2 Coil Tube Diameter: 3/8” in Coil Rows Deep: 4 in Fins Per Inch: 15 Refrigerant Control – Thermal Expansion Valve: BBIZE – 12.5 – GA Refrigerant Control – Thermal Expansion Valves No. 2 Filter Size: 20 x 25 x 1 Gauge Top: 18 in

Gauge Side: 16 in Gauge Bottom: 18 in Gauge – Door Covers: 20 in Voltage: 230V Frequency: 60HZ Number of Phases: 3

Commercial Heat Element Kit

For Air Handler Unit: 20 TON Voltage: 208/230V – 3 Phase – 60HZ