All_Drawings_SDU-7_Tank.pdf
PDF 5 MB Posted
- Solicitation number
- SRR-SCM-2018-00065
About this file
Liquid Waste Operations Salstone Disposal Unit & Tank Drawings
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C-SPP-Z-00015_SDU7_Spec._Rev._J1.pdf | ||
| EOI_-_SDU-7_Onsite_Concrete_Testing.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LATEST
REVISION
C Z 0 0 02C
N/A
C-C2-Z-00014
C-C2-Z-00015
C-C2-Z-00016
COVER SHEET
ABBREVIATIONS
GENERAL STRUCTURAL NOTES
DRAWING TITLEDWG NO.SHT. NO.
C-CY-Z-00010
C-CY-Z-00011
C-CC-Z-00059 FOUNDATION PLAN
C-CC-Z-00060
C-CC-Z-00062 PARTIAL ROOF PLAN
C-CC-Z-00063 WALL AND COLUMN SECTION AND DETAILS
C-CC-Z-00064 TYPICAL ROOF SECTIONS
C-CC-Z-00065
C-CC-Z-00066
C-CC-Z-00067
C-CM-Z-00049
TANK STRUCTURE
GENERAL
COVER SHEET
GENERAL
TANK DESIGN
LAST CADD REV. BY: PSC= 1
DATE: TIME
DRAWING INDEX
0 1"= 1"
C-CC-Z-00068
HDPE/GCL, LEAKAGE DETECTION AND SETTLEMENT MONITORING PLAN
9 C-CY-Z-00012
LEAKAGE DETECTION SYSTEM SECTIONS AND DETAILS
TANK SUBGRADE INTERFACE/LEAKAGE DETECTION SYSTEM
LEAKAGE DETECTION AND SETTLEMENT MONITORING SECTIONS AND DETAILS
MISCELLANEOUS STEEL DETAILS
C-CC-Z-00061 (1 of 5)
C-CC-Z-00061 (2 of 5)
C-CC-Z-00061 (3 of 5)
C-CC-Z-00061 (4 of 5)
C-CC-Z-00061 (5 of 5)
ROOF EMBED AND NOZZLE PLAN
ROOF EMBED AND NOZZLE PLAN
ROOF EMBED AND NOZZLE PLAN
ROOF EMBED AND NOZZLE PLAN
ROOF EMBED AND NOZZLE PLAN
OVERALL ROOF PLAN
PLOT DATE 12-11-17
C-C2-Z-00017 (1 of 3)
C-C2-Z-00017 (2 of 3)
C-C2-Z-00017 (3 of 3)
DRAWN BY (ORIG): IRINA L-T
SDU7
0SDU7
SALTSTONE DISPOSAL UNIT 7
LIQUID WASTE OPERATIONS
ISSUED FOR CONSTRUCTION
STATEMENT OF INSPECTIONS
STATEMENT OF INSPECTIONS
STATEMENT OF INSPECTIONS
SECTIONS AND DETAILS
DETAILS
DETAILS
DETAILS
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A
W.S. # [ ] .
REF FILES YES NO
PSC= 1 Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
T y p e r e v
CHK'D/VERIF'D APRV'D
PROJ.
APRV'DPRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
REVISION
CHK'D/VERIF'D APRV'D
REVISION
DS SDU TANK 7
Z AREA
SALTSTONE DISPOSAL SITE
Z451451-7Z TBD
APPROVALS MAINTAINED IN DCR/EDWS
1"= 1"
REVISION
C C Z 0
NGVD
NIC
NS
NTS NOT TO SCALE
NOT IN CONTRACT
OUT TO OUT
ON CENTER
OUTSIDE DIAMETER
OUTSIDE FACE
OPENING
OPPOSITEOPP
OPNG
O.F.
OD
OC
O TO O
PE
PJF
PSF
PSI
PSIG POUNDS PER SQUARE INCH, GAUGE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
PLATE (STEEL)
PREMOULDED JOINT FILLER
PLAIN END
REQD
REINF
R OR RAD
R RISER
RADIUS
REINFORCED, REINFORCING, REINFORCE
REQUIRED
S
SIM
I-BEAM
SIMILAR
SPANDREL PANEL, STORMPROOF
SPACE OR SPACES,
SPECIFICATIONS
SPACING
SQUARE
SQUARE FOOT, FEET
SQUARE INCH
STAINLESS STEEL
STANDARD
STIFFENERSTIF
STD
SST
SQ IN
SQ FT
SQ
SPG
SPEC, SPECS
STL
STRUCT
SYMM SYMMETRICAL
STRUCTURE
STEEL
TREAD
TOP AND BOTTOM
THREAD
THICKNESS
THROUGH
TOP OF
TOP OF CONCRETE
TOP OF FOOTING
TOP OF GROUT, TOP OF GRATE
T
T&B
THD
THK
THRU
T.O.
TOC
TOF
TOG
TOS
TST
TYP TYPICAL
TOP OF STEEL
TOP OF WALL
TOP OF SLAB
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
WITH
WORKPOINT
WATERSTOP
WELDED WIRE FABRICWWF
WS
WP
W/
BUT NOT SHOWN ON THIS DRAWING.
1.
NOTES:
ABBREVIATIONS
AMERICAN CONCRETE INSTITUTE
ADDITIONAL
ALUMINUM
ALTERNATE
AVERAGE
AT
BETWEEN
BLIND FLANGE
BEAM, BENCHMARK
BOTTOM
BEARING
CENTER TO CENTER
CHECKERED
CONSTRUCTION JOINT
CENTERLINE
CEMENT LINED DUCTILE IRON
CONTROLLED LOW STRENGTH FILL
CLEAR, CLEARANCE
CONTROLLED LOW STRENGTH MATERIAL
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUED, CONTINUOUS, CONTINUATION
CONTRACTOR
COORDINATE
CENTER
CENTERED
COUNTERSUNK
DRAIN
DEFORMED BAR ANCHOR
DOUBLE
DUCTILE IRON
DIAMETER
DIAGONAL
DOWN
DRAWING
DOWEL
EACH, EXHAUST AIR
EACH FACE
ELEVATION
ENGINEER
EQUAL
EQUALLY SPACED
EQUIPMENT
EACH WAY
EXPANSION, EXPOSED
EXPANSION ANCHOR BOLT
EXPANSION JOINT
EXISTING
EXTERIOR
FOUNDATION
FLAT BAR
FINISH GRADE
FLANGE
FIBERGLASS REINFORCED PLASTIC
FOOT OR FEET
FOOTING
GAUGE
GALVANIZED
GRATING
HEADED ANCHOR STUD
HORIZONTAL
HORSEPOWER
HIGH POINT
INVERT ELEVATION
INSIDE FACE
INCH
INVERT
JOINT
ANGLE
POUND
LINEAR FEET
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LOW POINT
MAXIMUM
MACHINE BOLT
MANUFACTURER
MECHANICAL
MANHOLE, MOUNTING HEIGHT
MINIMUM
MOUNTING
MOUNTED
MECHANICAL JOINT
MISCELLANEOUS
MTG
MTD
MJ
MISC
MIN
MH
MFR
MECH
MB
MAX
LONG
LLV
LLH
LF
LB
L
JT
IE
I.F.
IN
INVT
HP
HORIZ
H.A.S.
GA
FTG
FT
FRP
GALV
GRTG
FDN
FB
FG
FLG
EXT
EXST, EXIST
EXP JT
EXP AB
EXP
EW
EQPT
EQL SP
EQL
ENGR
EL
EF
EA
DWL
DWG
DN
DIAG
DIA
DI
DBL
DBA
D
CTSK
CTRD
CTR
COORD
CONTR
CONT
CONSTR
CONN
CONC
COL
CLSM
CLR
CLSF
CLDI
CJ
CHKD
C TO C
BRG
BOT
BM
BF
ALTN
AL
ADDL
AVG
BTWN
I.D. INSIDE DIAMETER
GENERAL
ABBREVIATIONS
DRAWN BY (ORIG): IRINA L-T
2 0 0
N/A
SDU7
N NORTH
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
E EAST
FF FLAT FACE
GCL GEOSYNTHETIC CLAY LINER
HDPE HIGH DENSITY POLYETHYLENE
HOLLOW STRUCTURAL SECTIONHSS
POLY POLYETHYLENE
SCH SCHEDULE
ADJ ADJACENT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ANCHOR BOLTAB
ACI
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AWS
AWWA AMERICAN WATER WORKS ASSOCIATION
AMERICAN WELDING SOCIETY
IBC INTERNATIONAL BUILDING CODE
ICC-ES INTERNATIONAL CODE COUNCIL EVALUATION SERVICE
KIP THOUSAND POUNDS
KCF THOUSAND POUNDS PER CUBIC FEET
MPH MILES PER HOUR
OSHA
(BOTH FEDERAL AND STATE)
OCCUPATIONAL SAFETY AND HEALTH ACT
PCF POUNDS PER CUBIC FEET
SP, SPA
SDU SALTSTONE DISPOSAL UNIT
SRR
SRS
SAVANNAH RIVER REMEDIATION
SAVANNAH RIVER SITE
NATIONAL GEODETIC VERTICAL DATUM
NONSHRINK
T.O.W.
CONTACT STR FOR ABBREVIATIONS USED
STR SUBCONTRACT TECHNICAL REPRESENTATIVE
N/A NOT APPLICABLE
GR GRADE
CL OR CL
PL OR PL
PJP PARTIAL JOINT PENETRATION
LP
HP
SO SLIP-ON
PLOT DATE 12-11-17
PVC POLYVINYL CHLORIDE
PT POINT
RF RAISED FACE
TANK DESIGN
IAPMO-UES
MECHANICAL OFFICIALS UNIFORM EVALUATION SERVICE
INTERNATIONAL ASSOCIATION OF PLUMBING AND
TBD TO BE DETERMINED
SDU7 0
LWO LIQUID WASTE OPERATIONS
ISSUED FOR CONSTRUCTION
CLFL COMPOSITE LOWER FLAMMABILITY LIMIT
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CTF COGNIZANT TECHNICAL FUNCTION
ETC ET CETERA
FS FACTOR OF SAFETY
GWT GROUND WATER TABLE
INT INTERSECTION
LLDPE LINEAR LOW DENSITY POLYETHYLENE
P.T. POST-TENSIONED
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A
PSC= 1 Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
T y p e r e v
CHK'D/VERIF'D APRV'D
PROJ.
APRV'DPRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
REVISION
CHK'D/VERIF'D APRV'D
REVISION
DS SDU TANK 7
Z AREA
SALTSTONE DISPOSAL SITE
1"= 1"
TANK DESIGN
LATEST
REVISION
C C Z 0
GENERAL
GENERAL STRUCTURAL NOTES
DRAWN BY (ORIG): IRINA L-T
N/A
2 0 0
NORMAL HIGH GWT WITH UPLIFT (FS =1.10):
SOIL FRICTION AND WEDGE FAILURE NOT CONSIDERED IN UPLIFT RESISTANCE:
DESIGN GROUND WATER ELEVATION:H.
NATIVE SOIL UNIT WEIGHT:G.
COEFFICIENT OF FRICTION:F.
VERTICAL SURCHARGE:E.
L/240
L/180
L/360
L/240
360 PCF
60 PCF
235 PCF
91 PCF
0.35
120 PCF
2.
1.
ITEM
SECTION
SPECIFICATION
#3
1'-0"
1'-0"
1'-0"
1'-0" 1'-0"
#4 #5 #6 #7 #8 #9 #10 #11
TOP BAR
OTHER BAR
TOP BAR
OTHER BAR
TOP BAR
OTHER BAR
TOP BAR
OTHER BAR
SPACING>6"
SPACING<6"
EMBEDMENT LENGTH
SPACING>6"
SPACING<6"
LAP SPLICE LENGTH
BAR SIZE
GRADE 60 REINFORCING STEEL
S
DS
D1
03314
A53, GRADE B
A500, GRADE B
A36
A992
WHERE L IS THE MEMBER'S SPAN LENGTH
LIVE LOAD
TOTAL LOAD
DEFLECTION CRITERIA FOR FLOOR FRAMING MEMBERS:
EXITS AND STAIRS
FLOOR LIVE LOADS:
FOUNDATIONS
FORMWORK, SHORING AND BRACING
CONCRETE REINFORCING
CONCRETE
DEFERRED SUBMITTALS
EQUIVALENT 2 FEET OF SOIL
DESIGN CRITERIA
STRUCTURAL STEEL AND METAL FABRICATIONS
12.
11.
10.
9.
8.
7.
6.
5.
3.
4.
1.
GENERAL INFORMATION
WELDING
2.
1.
1'-5"
1'-1"
1'-0"
1'-1"
2'-3"
1'-1"
1'-4"
1'-8"
1'-9"
1'-4"
1'-1"
1'-9"
1'-4"
3'-2"
2'-5"
2'-5
1'-11"
4'-3"
3'-3"
2'-0"
1'-7"
3'-3"
6'-9"
2'-11"
5'-2"
8'-3"
6'-4"
3'-4"
2'-7"
6'-4"
4'-11"
2'-7"
2'-0"
9'-3"
7'-2"
4'-1"
3'-2"
7'-2"
5'-6"
3'-2"
2'-5"
10'-5"
8'-0"
5'-1"
3'-11"
8'-0"
6'-2"
3'-11"
3'-0"
11'-7"
8'-11"
6'-1"
4'-8"
8'-11"
6'-10"
4'-8"
3'-7"
2'-6"
1'-4"
1'-0"
1'-7"
1'-2"
2'-3"
5'-2"
4'-0"
2'-3"
1'-9"
CONCRETE DESIGN STRENGTH = 6,000 PSI
5.
4.
3.
2.
SDU7
MODULUS OF SUBGRADE REACTION Ks:D.
PASSIVE:
AT REST:
EQUIVALENT UNDRAINED FLUID PRESSURES:C.
PASSIVE:
AT REST:
EQUIVALENT DRAINED FLUID PRESSURES:B.
40,300 PSF DYNAMIC
30,200 PSF STATIC
GROSS ALLOWABLE SOIL BEARING PRESSURES:A.
SOIL DESIGN PARAMETERS:
OF THESE ITEMS.
SHALL THEN BE FILED BY THE SUBCONTRACTOR AND ACKNOWLEDGED AS ACCEPTED BY SRR PRIOR TO INSTALLATION
ADDITIONALLY, ACCEPTANCE INDICATED ON THE STR'S COMMENT FORM, ALONG WITH THE COMPLETED, FINAL SUBMITTAL
REQUIRED CALCULATIONS AND SUPPORTING DATA AND DRAWINGS FOR REVIEW AND ACCEPTANCE BY THE CTF.
EQUIPMENT, DISTRIBUTION SYSTEM, OR COMPONENT OR ITS ANCHORAGE, THE SUBCONTRACTOR SHALL SUBMIT THE
REQUIREMENTS FOR DESIGNED SYSTEMS. PRIOR TO INSTALLATION OF THE INDICATED STRUCTURAL ELEMENT, STRUCTURAL CALCULATIONS OR SAFETY RELATED SYSTEM INFORMATION FOR REVIEW TO MEET BUILDING PERMITTING
THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS PER IBC SECTION 107.3.4.2 THAT ARE EXPECTED TO CONTAIN
INSTALLATION OF THAT PORTION OF THE WORK.
APPLICATION AND WHICH ARE TO BE SUBMITTED TO THE PERMITTING AGENCY FOR ACCEPTANCE PRIOR TO
DEFERRED SUBMITTALS ARE THOSE PORTIONS OF THE DESIGN WHICH ARE NOT SUBMITTED AT THE TIME OF PERMIT
BARS ARE CONSIDERED TOP BARS.
OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR IN ANY SINGLE POUR. HORIZONTAL WALL
TOP BARS SHALL BE DEFINED AS ANY HORIZONTAL BARS PLACED SUCH THAT MORE THAN 12 INCHES
STATEMENT OF INSPECTIONS
ELEVATION 230
2.
C-CC-Z-00064 TYPICAL ROOF SECTIONS
VERTICAL POST-TENSION BAR ANCHORAGE
SUBCONTRACTOR CALCULATIONS INCLUDING HORIZONTAL PRESTRESSING AND
PRESTRESSED TANK VERTICAL POST-TENSIONING - SDU PRESTRESSING
PLOT DATE 12-11-17
5.
4.
3.
2.
1.
PROCEDURE 109; AND WELDING PROCEDURE GUIDE Y16.3, PROCEDURE 109-G.
WELDING SHALL BE IN ACCORDANCE WITH ENGINEERING STANDARD 05057; WELDING CONTROL PROCEDURE MANUAL Y16.2, BUTT JOINT WELDS SHALL BE COMPLETE JOINT PENETRATION (CJP) UNLESS INDICATED OTHERWISE.
THE EXISTING CONCRETE.
USE INTERMITTENT WELDS AT FIELD WELDS OF EMBED PLATES AND ANGLES TO AVOID SPALLING OR CRACKING OF
REPAIR WELDS FOUND DEFECTIVE IN ACCORDANCE WITH AWS D1.1 SECTION 5.26.
D1.6, STRUCTURAL WELDING CODE - STAINLESS STEEL
D1.1, STRUCTURAL WELDING CODE - STEEL
WELDS SHALL CONFORM TO AMERICAN WELDING SOCIETY (AWS), LATEST EDITION:
7.
6.
5.
4.
3.
2.
1.
2.
1.
4.
3.
2.
1.
C-C2-Z-00017
CONCRETE TANK WITH ANCHORED FLEXIBLE BASE.
FLAT-BOTTOM GROUND SUPPORTED PRESTRESSED
TANK:
LATERAL FORCE-RESISTING SYSTEMS
ACI 350.3-06 AS MODIFIED BY ASCE 7-10.
OF ASCE 7-10. PRESTRESSED TANK SEISMIC LOADS IN ACCORDANCE WITH THE PROVISIONS OF
APPURTENANT STRUCTURES HAVE BEEN ANALYZED USING THE EQUIVALENT LATERAL FORCE PROCEDURES
Ra (ADJUSTED)
R
RESPONSE MODIFICATION COEFFICIENT
I
IBC SEISMIC DESIGN CATEGORY
OCCUPANCY CATEGORY
SITE CLASS
S
S
DESIGN SPECTRAL RESPONSE ACCELERATIONS
S
S
MAPPED SPECTRAL RESPONSE ACCELERATIONS
SRS SDC-2 SEISMIC LOAD:
= 1.0
= III
= 0.18
= C
= 98 MPH
= 126 MPH
DIRECTIONAL
= 1.2
= 3.25
= 1.5
= D
= IV
= D
= 0.170 g
= 0.316 g
= 0.108 g
= 0.305 g
= 1.0 (CONVECTIVE)
= 3.5 (IMPULSIVE)
= 1.5
CONSERVATIVE THAN SDC-2 LOADINGS.
THE TANK STRUCTURE HAS BEEN DESIGNED PER EQUATIONS CONTAINED IN D110-13 WHERE MORE
RESPONSE MODIFICATION FACTOR, R
IMPORTANCE FACTOR, I
AWWA D110-13 SEISMIC LOAD:
86 KCF
THE RADIUS OF THE SDU 7 TANK AT END OF OPERATIONS.
STRUCTURES HAVE BEEN DESIGNED FOR MAXIMUM DIFFERENTIAL SETTLEMENT OF 1.8 INCHES ACROSS
ASTM A615, GRADE 60
2000 PSI
6000 PSI
SDU7 0
7.
6.
5.
AT 15 DEGREES MAXIMUM WITH PRIOR APPROVAL OF THE STR.
WELDING OF REINFORCEMENT BARS IS NOT PERMITTED. FIELD BENDING IS LIMITED TO COLD BENDING ONCE
SHALL CONFORM TO ACI 350.
REINFORCEMENT BARS SHALL BE IN ACCORDANCE WITH ASTM A615/A615M, GRADE 60. SPACING AND POSITIONING
HOOK BAR EMBEDMENTS, UNLESS OTHERWISE NOTED, SHALL SATISFY THE FOLLOWING MINIMUM REQUIREMENTS:
WHERE L IS THE MEMBER'S SPAN LENGTH
LIVE LOAD
TOTAL LOAD
DEFLECTION CRITERIA FOR ROOF FRAMING MEMBERS:
LIVE LOAD (PRIOR TO CLOSURE CAP)
ROOF LOADS:
REFER TO THE DRAWINGS FOR ADDITIONAL AND SPECIFIC STRUCTURE LOADINGS AND REQUIREMENTS.
PERFORMANCE CATEGORY
HAZARD CLASSIFICATION
FUNCTIONAL CLASSIFICATION
PLANT MODIFICATION CLASSIFICATIONS:
M-TC-Z-00009.
ACCORDANCE WITH SALTSTONE FACILITY DISPOSAL UNIT (SDU) #7 TASK REQUIREMENTS AND CRITERIA DOCUMENT
ENGINEERING STANDARD 01060, REVISION 12, AND ENGINEERING STANDARD 01110, REVISION 6. DESIGN IS IN
APPLICABLE CODE: 2012 INTERNATIONAL BUILDING CODE (IBC), AS AMENDED BY SRS MANUAL WSRC-TM-95-1, = SDC-2, LIMIT STATE D
= HC-2
= PS
100 PSF OR 300 LB CONCENTRATED
MATERIALS. ABOVE WIND LOAD CRITERIA APPLY TO TEMPORARILY BRACED CONSTRUCTION.
SEE SPECIFICATIONS FOR DESIGN WIND PRESSURES FOR EXTERIOR COMPONENT AND CLADDING
COMPONENTS AND CLADDING DESIGNED FOR WIND PRESSURE IN ACCORDANCE WITH ASCE 7-10, 30.11, I
OCCUPANCY CATEGORY
INTERNAL PRESSURE COEFFICIENT
EXPOSURE
NOMINAL WIND SPEED (3-SECOND GUST)
BASIC WIND SPEED (3-SECOND GUST)
ASCE 7 METHOD
WIND LOAD:
ROOF STRUCTURE DESIGNED FOR PONDING WATER IN ACCORDANCE WITH ASCE 7-10, 8.4.F.
VACUUM PRESSUREE.
CRANE LOAD ON FLOORD.
REFERENCE M-TC-Z-00009
THERMAL LOADS:C.
GROUT BLEED WATER WEIGHTB.
GROUT UNIT WEIGHTA.
SPECIAL LOADS:
MATERIAL TO MINIMIZE EJECTION OF FINES.
BOTTOM OF COLUMN FORMWORK SHALL BE DESIGNED TO MATCH SURFACE OF PEDESTAL OR ADD SUITABLE SEAL
FOR BACKFILL OF SECONDARY FOUNDATIONS, CLSM MAY BE USED IN LIEU OF COMMON FILL OR STRUCTURAL FILL.
100 PERCENT OF THE 56 DAY DESIGN STRENGTH AS DETERMINED BY CONCRETE MATURITY PROBES. SEE SPECIFICATIONS.
TEMPORARY SHORING SHALL REMAIN IN PLACE UNTIL ELEVATED CONCRETE FLOOR OR SLABS HAVE REACHED
PERFORM THE WORK SHOWN.
METHODS, BRACING, SHORING, RIGGING, GUYS, SCAFFOLDING, FORMWORK, AND OTHER WORK AIDS REQUIRED TO SAFELY
DURING CONSTRUCTION. SUBCONTRACTOR IS RESPONSIBLE FOR ALL WORK RELATING TO CONSTRUCTION ERECTION
DESIGN SHOWN DOES NOT INCLUDE NECESSARY COMPONENTS OR EQUIPMENT FOR STABILITY OF THE STRUCTURES
STRUCTURES SHOWN ON THE DRAWINGS HAVE BEEN DESIGNED FOR STABILITY UNDER FINAL CONDITIONS ONLY.
AND APPROVED BY CTF.
CONSTRUCTION JOINT DETAILS TO BE UTILIZED FOR CONSTRUCTION INTERRUPTIONS, SHALL BE SUBMITTED FOR REVIEW
SPECIFICALLY NOTED OTHERWISE.
CONTINUOUS WATERSTOP AS SPECIFIED SHALL BE INSTALLED IN ALL CONSTRUCTION JOINTS EXCEPT WHERE
STANDARD PRACTICE" AND ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE".
FABRICATION AND PLACEMENT OF REINFORCING STEEL SHALL BE IN ACCORDANCE WITH CRSI MSP-1 "MANUAL OF
REINFORCING STEEL:
MUD MATS, TYPE II MIX:
TYPICAL, TYPE V MIX:
56-DAY CAST-IN-PLACE CONCRETE STRENGTHS:
- 4" WATER COLUMN
ON 11" BY 29" MINIMUM FOOTPRINT
MAXIMUM TOTAL POINT LOAD 37.4 KIPS
= 100 TON CAPACITY
= 77 PCF
= 110 PCF (CURED)
ACI MINIMUM HOOK EMBEDMENT LENGTH
BAR SIZE
MIN EMBED
#4
6"
#5
7"
#6
9"
#7
10"
#8
11"
#9
13"
#10
14"
3.
2.
1.
REQUIREMENTS FOR SPACING BETWEEN BARS BEING LAP SPLICED:
REINFORCEMENT BENDS AND LAPS, UNLESS OTHERWISE NOTED, SHALL SATISFY THE FOLLOWING MINIMUM
90 DEGREE BENDS, UNLESS OTHERWISE SHOWN, SHALL BE ACI 350-06 STANDARD HOOKS.
2"ALL OTHER CONCRETE SURFACES, UNO
3"WHEN PLACED ON GROUND:
CLEARANCE FOR REINFORCEMENT BARS, UNLESS SHOWN OTHERWISE, SHALL BE:
4.
EMBEDMENT OF THE LARGER BAR.
LAP SPLICE OF BARS OF DIFFERING SIZE SHALL BE THE LARGER OF THE LAP SPLICE FOR THE SMALLER BAR AND
ISSUED FOR CONSTRUCTION
= 30 PSF
INSPECTION, OBSERVATIONS AND TESTING
IN THE STATEMENT OF INSPECTIONS PLAN ON DRAWING C-C2-Z-00017.
STRUCTURAL OBSERVATIONS (SRR FURNISHED) ARE REQUIRED IN ACCORDANCE WITH IBC SECTION 1710 AS INDICATED
INSPECTION (SRR FURNISHED) AS INDICATED IN THE STATEMENT OF INSPECTIONS PLAN ON DRAWING C-C2-Z-00017.
EXPOSED SUBGRADE IS AS ANTICIPATED BY THE SITE SPECIFIC BORINGS, TEST PITS, TESTING AND DATA REPORTS.
PRIOR TO PLACEMENT OF FORMING OR REINFORCING STEEL. THE OBSERVATION SHALL VERIFY THAT THE ACTUAL
ALL FOUNDATION BEARING SURFACES SHALL BE OBSERVED BY THE GEOTECHNICAL ENGINEER OF RECORD OR DESIGNEE
DATED NOVEMBER, 2017.
REFER TO SALTSTONE DISPOSAL UNIT 7 GEOTECHNICAL INVESTIGATION REPORT K-ESR-Z-00008, REV. 0, AND ROUND SHARP EDGES TO SMALL UNIFORM RADIUS.
FINISH EXPOSED SURFACES SMOOTH, SHARP, AND TO WELL-DEFINED LINES. GRIND CUT EDGES SMOOTH AND STRAIGHT
PER MANUFACTURER'S INSTRUCTIONS.
APPLY ZINC CLAD 5 PRIMER BY SHERWIN WILLIAMS FOR TOUCH UP OF DAMAGED GALVANIZED SURFACES. APPLY
NO CUTTING OR BURNING OF STRUCTURAL STEEL IS PERMITTED WITHOUT THE PRIOR APPROVAL OF THE CTF.
NO HOLES OTHER THAN THOSE SPECIFICALLY DETAILED SHALL BE ALLOWED THROUGH STRUCTURAL STEEL MEMBERS.
ITEMS TO BE EMBEDDED IN CONCRETE SHALL BE CLEAN AND FREE OF OIL, DIRT AND PAINT.
HEADED ANCHOR STUDS (H.A.S.)
MACHINE BOLTS (MB)
GALVANIZED STEEL
STEEL
STAINLESS STEEL
ANCHOR BOLTS (AB)
UNLESS SHOWN OTHERWISE
INDICATED OTHERWISE:
BOLTS SHALL BE HIGH STRENGTH BOLTS CONFORMING TO THE FOLLOWING EXCEPT WHERE SPECIFICALLY
AISC 360-10, AND CURRENT OSHA STANDARDS.
STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN CONFORMANCE WITH THE AISC STEEL CONSTRUCTION MANUAL, STEEL PIPE
SQUARE OR RECTANGULAR STEEL TUBING
ANGLES, CHANNELS, PLATES, ETC.
MISCELLANEOUS SHAPES INCLUDING
W-SHAPES
STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:
A108, GR 1010 THROUGH 1020
A307, GR A WITH A563 NUTS, GALVANIZED PER A153
F1554, GR 36 WITH A563 NUTS / A153
F1554, GR 36 WITH A563 NUTS
F593, AISI TYPE 316, CONDITION CW, WITH F594 NUTS
SHEAR PLANE WITH A563 NUTS, GALVANIZED PER A153
F3125, GR A325, TYPE I, THREADS NOT EXCLUDED FROM
STRENGTH, PSI
MINIMUM CONCRETE COMPRESSIVE
MAXIMUM WHEEL LOAD, TONS
2000 3000 4000 5000 6000
36 45 53 60 67
FIELD SHALL USE HAND EXCAVATION AND CAUTION TO PROTECT HDPE ON THE FOUNDATION CLOSE TO TANK.
ARE AT THE DISCRETION OF THE SUBCONTRACTOR.
FORM 3/4 INCH MINIMUM BEVELS AT CONCRETE EDGES UNLESS NOTED OTHERWISE. BEVELED EDGES ON MUDMATS
AND CRSI-PRB ARE ACCEPTABLE.
UNLESS OTHERWISE SPECIFIED, ALLOWANCES PER ACI 301, ACI 117, ACI-SP-66, CRSI MANUAL OF STANDARD PRACTICE, POSSIBLE. ANY PENETRATIONS TO TYPE V CONCRETE AFTER SETTING SHALL BE APPROVED BY THE CTF.
PENETRATIONS (I.E., NAILS, SCREWS, ETC.) TO TYPE V CONCRETE SHALL BE MINIMIZED TO THE MAXIMUM EXTENT
9.
8.
7.
6.
13.
12.
11.
10.
PRESSURES NOT EXCEEDING 100 PSI MAY BE APPLIED AS FOLLOWS:
THE MUD MATS AFTER REACHING THE SPECIFIED COMPRESSIVE STRENGTH. OTHER CONSTRUCTION LOADS WITH CONTACT
COMPRESSIVE STRENGTH OF 3,000 PSI. TIRE CONTACT PRESSURES NOT EXCEEDING 100 PSI MAY BE APPLIED TO
CRANE LOADS SHALL NOT BE IMPOSED ON FOUNDATION SLAB UNTIL CONCRETE HAS REACHED A MINIMUM
SHALL BE EMBEDDED IN THE CONCRETE.
NO ALUMINUM CONDUIT OR PRODUCTS CONTAINING ALUMINUM OR ANY OTHER MATERIAL INJURIOUS TO THE CONCRETE
INSERTS PRIOR TO PLACEMENT OF CONCRETE.
THE SUBCONTRACTOR SHALL COORDINATE PLACEMENT OF OPENINGS, CURBS, DOWELS, SLEEVES, CONDUITS, BOLTS AND
CONCRETE.
ROUGHEN AND CLEAN CONSTRUCTION JOINTS IN WALLS AND SLABS AS SPECIFIED PRIOR TO PLACING ADJACENT
REFERENCE THE STRUCTURAL INSPECTION CRITERIA DOCUMENT C-QIP-Z-00021.
REFERENCE CALCULATIONS SEE C-CLC-Z-00115.
REFERENCE THE CSI SPECIFICATION DOCUMENT SEE C-SPP-Z-00015.
DETAILED OR APPROVED IN WRITING BY THE CTF.
STRUCTURAL MEMBERS SHALL NOT BE CUT OR MODIFIED FOR PIPES, DUCTS, ETC, UNLESS SPECIFICALLY
ABBREVIATIONS USED BUT NOT SHOWN ON THIS DRAWINGS.
DISTRIBUTED BY THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME). CONTACT STR FOR
FOR ABBREVIATIONS NOT LISTED, SEE ASME Y14.38 "ABBREVIATIONS AND ACRONYMS: PUBLICATION AS
5.
4.
3.
2.
1.
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A
PSC= 1 Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
T y p e r e v
CHK'D/VERIF'D APRV'D
PROJ.
APRV'DPRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
REVISION
CHK'D/VERIF'D APRV'D
REVISION
DS SDU TANK 7
Z AREA
SALTSTONE DISPOSAL SITE
C Z 0 0 0 72C
N/A
GENERAL
GENERAL NOTES
GEOTECHNICAL OBSERVATION
STRUCTURAL OBSERVATION
1"= 1" 1 OF 3
SDU7
C-C2-Z-00016 GENERAL STRUCTURAL NOTES
SDU7 0 SR 12-11-17 KW 12-11-17MM 12-11-17ILT 12-11-17
STATEMENT OF INSPECTIONS
STRUCTURAL INSPECTION
STRUCTURAL INSPECTIONS FOR SEISMIC RESISTANCE
SALTSTONE DISPOSAL UNIT 7 BEARING PLATES FOR BRIDGES AND EMBEDDED ANCHOR PLATES FOR PIPING CARRYING HAZARDOUS MATERIAL.A.
INSPECTION, OBSERVATION AND TESTING.
MAIN SYSTEMS REQUIRED TO BE COVERED UNDER PROJECT SPECIAL INSPECTION REQUIREMENTS INCLUDE THE FOLLOWING TOGETHER WITH THEIR CONNECTIONS. REFER TO SPECIFICATION 01810, STRUCTURAL 3.
STRUCTURAL INSPECTIONS REQUIREMENTS FOR SEISMIC RESISTANCE SHALL APPLY TO THE SYSTEMS AND COMPONENTS LISTED IN TABLE 4.2.
STRUCTURAL INSPECTIONS REQUIREMENTS FOR SEISMIC RESISTANCE WILL BE BASED ON IBC SECTION 1705.11 TOGETHER WITH LOCAL AND STATE AMENDMENTS.1.
THE SUBCONTRACTOR WILL BE NOTIFIED ON-SITE OR BY EMAIL WITHIN 24 HOURS UPON FINDING DEFICIENCIES.
GEOTECHNICAL OBSERVATION REPORTS, NOTING ANY DEFICIENCIES IN OBSERVED CONSTRUCTION, WILL BE DELIVERED TO THE SUBCONTRACTOR, CTF, AND SRR QUALITY ASSURANCE FOLLOWING EACH OBSERVATION. 5.
DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR ANY REQUIRED INSPECTIONS OR INSPECTIONS BY SRR.
GEOTECHNICAL OBSERVATION WILL BE PERFORMED BY A REGISTERED PROJECT DESIGN PROFESSIONAL FOR GENERAL CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS. GEOTECHNICAL OBSERVATION 4.
GEOTECHNICAL TESTING REQUIREMENTS ARE LISTED IN TABLE 3.3.
ADDITIONAL GEOTECHNICAL INSPECTION REQUIREMENTS ARE LISTED IN TABLE 1.2.
ALL FOUNDATION BEARING SURFACES SHALL BE INSPECTED UNDER THE SUPERVISION OF A REGISTERED DESIGN PROFESSIONAL PRIOR TO PLACEMENT OF FOUNDATION REINFORCING STEEL.1.
CONTAINED IN THE WORK. THE SUBCONTRACTOR SHALL SCHEDULE AND FACILITATE STRUCTURAL OBSERVATION INCLUDING THE FOLLOWING:
STRUCTURAL OBSERVATION WILL INCLUDE VISUAL OBSERVATION OF THE STRUCTURAL SYSTEM AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE STRUCTURAL SYSTEM FOR EACH STRUCTURE 6.
SITE VISITS WERE MADE AND WHETHER THERE REMAIN ANY STRUCTURAL DEFICIENCIES THAT HAVE NOT BEEN RESOLVED.
AT THE CONCLUSION OF CONSTRUCTION, A WRITTEN STATEMENT WILL BE PROVIDED BY THE STRUCTURAL OBSERVER TO THE CTF AND SRR QUALITY ASSURANCE TO VERIFY THAT THE STRUCTURAL OBSERVATION 5.
THE CONTRACTOR WILL BE NOTIFIED ON-SITE OR BY PHONE OR EMAIL WITHIN 24 HOURS UPON FINDING DEFICIENCIES.
STRUCTURAL OBSERVATION REPORTS, NOTING ANY DEFICIENCIES IN OBSERVED CONSTRUCTION, WILL BE DELIVERED TO THE SUBCONTRACTOR, CTF, AND SRR QUALITY ASSURANCE, FOLLOWING EACH OBSERVATION. 4.
DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR ANY REQUIRED INSPECTIONS BY SRR.
STRUCTURAL OBSERVATION WILL BE PERFORMED BY A REGISTERED PROJECT DESIGN PROFESSIONAL FOR GENERAL CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS. STRUCTURAL OBSERVATION 3.
STRUCTURAL NOTES, DRAWING C-C2-Z-00016 FOR THE BASIC SEISMIC- OR WIND FORCE-RESISTING SYSTEMS FOR THE STRUCTURES INCLUDED IN THE WORK.
ONSITE STRUCTURAL OBSERVATION WILL BE PERFORMED FOR EACH IDENTIFIED SEISMIC FORCE- OR WIND FORCE-RESISTING SYSTEM, INCLUDING FOUNDATIONS AND CONNECTIONS. REFER TO THE GENERAL 2.
STRUCTURAL OBSERVATION WILL BE IN ACCORDANCE WITH IBC SECTION 1704.5 TOGETHER WITH LOCAL AND STATE AMENDMENTS. REFER TO PROJECT SPECIFIC NOTES ON THIS SHEET. 1.
ISSUED FOR CONSTRUCTION
STATEMENT OF INSPECTIONS
DEFINITIONS AND TERMINOLOGY USED IN THIS STATEMENT OF SPECIAL INSPECTIONS.C.
SUBCONTRACTOR'S STATEMENT OF RESPONSIBILITY FOR WORK TO BE PERFORMED ON SYSTEMS DESIGNATED UNDER THE STATEMENT OF SPECIAL INSPECTIONS PLAN FOR WIND OR SEISMIC RESISTANCE.B.
SUBCONTRACTOR'S REQUIREMENTS TO PROVIDE ACCESS TO THE WORK FOR REQUIRED INSPECTIONS, AND TO PROVIDE NOTICE OF REQUIRED INSPECTIONS AND STRUCTURAL OBSERVATION. A.
FOR ADDITIONAL REQUIREMENTS, REFER TO SPECIFICATION SECTION 01810, STRUCTURAL INSPECTION, OBSERVATION AND TESTING. THESE INCLUDE:5.
PROJECT SPECIFIC REQUIREMENTS FOR STRUCTURES ASSIGNED TO IBC SEISMIC DESIGN CATEGORIES C, D, E, OR F ARE CONTAINED IN TABLE 4. 4.
STRUCTURAL COMPONENTS ARE CONTAINED IN TABLE 3.
STANDARD INSPECTION REQUIREMENTS FOR STRUCTURAL COMPONENTS, REGARDLESS OF WIND OR IBC SEISMIC DESIGN CATEGORIES, ARE CONTAINED IN TABLE 2. STANDARD TESTING REQUIREMENTS FOR 3.
STANDARD INSPECTION REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS SUPPORTING THE STRUCTURE ARE CONTAINED IN TABLE 1.2.
PROVIDED FOR COMPLIANCE WITH THE 2012 INTERNATIONAL BUILDING CODE, EXCEPT WHERE OTHERWISE NOTED, THIS INSPECTION IS SRR FURNISHED.
THE STATEMENT OF INSPECTIONS DRAWINGS PROVIDE PROJECT COMPLIANCE WITH THE PROVISIONS OF AWWA D110-13, INCLUDING ACI SP-2 AND 311-4R AS REFERENCED. STRUCTURAL OBSERVATION IS 1.
AND SRR QUALITY ASSURANCE.
AT THE CONCLUSION OF CONSTRUCTION, A FINAL REPORT DOCUMENTING REQUIRED STRUCTURAL INSPECTIONS AND CORRECTION OF PREVIOUSLY NOTED DISCREPANCIES WILL BE SUBMITTED TO CTF, SUBCONTRACTOR, 5.
FOR WHICH REPORTING WILL BE REQUIRED ARE NOTED IN THE TABLES CONTAINED ON THIS STATEMENT OF SPECIAL INSPECTIONS.TEST COMPLETION. INSPECTIONS
STRUCTURAL INSPECTION AND ASSOCIATED TESTING REPORTS WILL BE SUBMITTED TO THE CTF, SUBCONTRACTOR, AND SRR QUALITY ASSURANCE WITHIN ONE WEEK OF INSPECTION OR WITHIN ONE WEEK OF 4.
THE IMMEDIATE ATTENTION OF THE SUBCONTRACTOR FOR CORRECTION.
THE STRUCTURAL INSPECTOR WILL OBSERVE THE INDICATED WORK FOR COMPLIANCE WITH THE APPROVED CONTRACT DOCUMENTS AND SUBMIT RECORDS OF INSPECTION. ALL DISCREPANCIES WILL BE BROUGHT TO 3.
(ICC) CERTIFIED OR OTHERWISE APPROVED BY SRR.
PAY FOR THE SERVICES OF THE AGENCY AS REQUIRED TO PERFORM ALL STRUCTURAL INSPECTION AND ASSOCIATED TESTS. INSPECTORS FOR EACH SYSTEM AND MATERIAL WILL BE INTERNATIONAL CODE COUNCIL
STRUCTURAL INSPECTIONS WILL BE PROVIDED BY A CERTIFIED OR QUALIFIED INSPECTOR AND ASSOCIATED TESTING WILL BE PERFORMED BY AN APPROVED ACCREDITED INDEPENDENT AGENCY. SRR WILL SECURE AND 2.
REFER TO THE TABLES CONTAINED ON THIS DRAWING FOR PROJECT SPECIFIC INSPECTION TYPES AND FREQUENCIES.1.
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A
PSC= 1 Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
T y p e r e v
CHK'D/VERIF'D APRV'D
PROJ.
APRV'DPRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
REVISION
CHK'D/VERIF'D APRV'D
REVISION
DS SDU TANK 7
Z AREA
SALTSTONE DISPOSAL SITE
A
1 2
SRP DRAWING NO.
N/A
B
C
D
E
F
G
H
J
I
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
TITLE
SRP DRAWING NO. SHEET NO.
X
Y
C C Z 0 0 0
VENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
SALTSTONE DISPOSAL SITE
TANK DESIGN
DRAWN BY (ORIG): LAST CADD REV. BY:
DATE:
DRAWING REV.
Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
IRINA L-T
REF FILES YES NO
LEVELS
234567890123 5678901234567890123456789 1234567890123456789 23
1111 1111122222222223333333333 44444444455555555 5 66
5W.S. # [ ] . 6
6 PSC= 96
TIME
18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
O
I
P
Q
R
S
T
U
V
W
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
GENERAL
PLOT DATE 12-11-17
SDU7
STATEMENT OF INSPECTIONS
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
1 2
SRP DRAWING NO.
N/A
18 19 20
A
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
B
C
D
E
F
G
H
J
I
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
TITLE
SRP DRAWING NO. SHEET NO.
Y
C C Z 0 0 0
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
SALTSTONE DISPOSAL SITE
TANK DESIGN
DRAWN BY (ORIG): LAST CADD REV. BY:
DATE:
DRAWING REV.
Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
IRINA L-T
REF FILES YES NO
LEVELS
234567890123 5678901234567890123456789 1234567890123456789 23
1111 1111122222222223333333333 44444444455555555 5 66
5W.S. # [ ] . 6
6 PSC= 96
TIME
GENERAL
PLOT DATE 12-11-17
X
B
C
D
E
F
G
H
J
K
L
M
N
O
I
P
Q
R
S
T
U
V
W
SDU7
STATEMENT OF INSPECTIONS
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
.2
11'-6"
5'-0"
5'-0"
11'-4"11'-4"
T Y
P
T Y
P
RADIAL
4'-3"
RADIAL
4'-3"
150.53°
RADIA
L4'-
3"
RADIA
L4'-
3"
6"
1'-6"
.7
LATEST
REVISION
C C C Z 0
V
G
I.
D
3/64" = 1'-0"
TANK DESIGN
CONCRETE
FOUNDATION PLAN
FOUNDATION PLAN
0 0 5 9
A
C-CC-Z-00065
C-CC-Z-00065
C-CC-Z-00063
C-CC-Z-00065
A C -C
C -Z -0
T Y P
KEY PLAN
NOTES
N
T R
UE
NOR
T H
PLANT NORTH
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
15'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"15'-0"
375'-0" AVG I.D.
C-CC-Z-00063
A
C-C2-Z-00016 GENERAL STRUCTURAL NOTES
C-CY-Z-00010
C-CY-Z-00011
C-CY-Z-00012
C-CC-Z-00063
C-CC-Z-00065
HDPE/GCL, LEAKAGE DETECTION AND
SETTLEMENT MONITORING PLAN
LEAKAGE DETECTION SYSTEM SECTIONS AND
DETAILS
LEAKAGE DETECTION AND SETTLEMENT
MONITORING SECTIONS AND DETAILS
WALL AND COLUMN SECTION AND DETAILS
N/A
SUMP, TYP OF 4
4'-0" SQ x 0'-6" DEEP
CL SUMP, TYP
C-CC-Z-00066 CONCRETE DETAILS
CONCRETE SECTIONS AND DETAILS
EMBED #5
EMBED #8
2'-5"
2'-5"
2'-5"
2'-5"
EMBED #4
EMBED #6
TANK FLOOR EMBED SCHEDULE
DESCRIPTION DETAIL REMARKS
EMBED #
2/C-CC-Z-00067 RECESSED IN SUMP
2 2/C-CC-Z-00067 RECESSED IN SUMP
3 2/C-CC-Z-00067
4 2/C-CC-Z-00067
5 2/C-CC-Z-00067 RECESSED IN SUMP
6 2/C-CC-Z-00067
7 2/C-CC-Z-00067
8 2/C-CC-Z-00067 RECESSED IN SUMP
9 PL 3/4" x 12" x 1'-0"
10 PL 3/4" x 12" x 1'-0"
11 PL 3/4" x 12" x 1'-0"
S
THERMOCOUPLE
THERMOCOUPLE
THERMOCOUPLE
PLOT DATE 12-11-17
8/C-CC-Z-00067
8/C-CC-Z-00067
8/C-CC-Z-00067
EMBED #7
JOINT, TYP
CONSTRUCTION
EMBED #2
S E
M
IS
C
N O T E
S
IS
C N O T E
#3, 4, 6 & 7
TYP @ EMBEDS
C-CC-Z-00066
C-CC-Z-00066
CL SDU7
E 66390.28
N
.5
.53
CL SDU7
150.53°
TYP
92'-0"
TYP
46'-0"
TYP
162'-9 5/8 "
EMBED #3
.53
OF 25
TYP, TOTAL
WALL JT,
3A5A
2A
3B5B
2B
SDU7
SDU6
SDU7
TYP
EL 269.67,
TOC SLAB
FOUNDATION SLAB PLACEMENT
1 2 3
654 7
8 9 10 11
12 13 14
NTS
EMBED #1
6'-9"
EMBED #10
EMBED #9
EMBED #11
C-CC-Z-00068
C-CC-Z-00067
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
PL 3/4" x 42" x 3'-6"
SEE
AND CONVENIENCE PORTS,
SHOTCRETE ENTRY PIPES
IN CORE WALL
T4 THERMOCOUPLE TREE
C-CC-Z-00063
REINFORCING, SEE
2'-0" SLAB FOR
SEE
AND CONVENIENCE PORTS,
SHOTCRETE ENTRY PIPES
IS COMPLETE. WATER CURE ALL SLABS FOR 12 DAYS.
ROWS MAY BE STARTED BEFORE THE PRECEDING ROW
CASTING OF SEQUENTIALLY NUMBERED SEGMENTS. NEW
MAXIMUM OF 14 DAYS SHALL BE ALLOWED BETWEEN 2.
SEQUENCE FOR CASTING INDIVIDUAL SLAB SEGMENTS.
THE NUMBERS SHOWN INDICATE THE REQUIRED 1.
NOTES:
C-CC-Z-00067
C-CC-Z-00068
TYP
TOTAL OF 208,
2'-0" DIA COLUMN,
CONCRETE DETAILS
CONCRETE DETAILS
0 ISSUED FOR CONSTRUCTION
COATED OR HOT-DIP GALVANIZED.
UNLESS OTHERWISE NOTED, EMBED PLATES ARE NOT REQUIRED TO BE 6.
CENTER SHOTCRETE ENTRY PIPES BETWEEN LATERAL CABLING.5.
EMBEDS SHALL BE LEVEL.
HORIZONTAL TOLERANCE FOR ALL EMBEDS SHALL BE (+/-) 1/2" AND 4.
FINISH GRADE.
LINER CONNECTION TO THE WALL FOUNDATION, AND BRINGING BACKFILL TO
COATING AND/OR LINER SYSTEM AND PRIOR TO MAKING EXTERIOR HDPE
PERFORM LIQUID TIGHTNESS TEST AFTER INSTALLATION OF THE INTERIOR 3.
MAXIMUM DEEP.
OF OUTSIDE BASE SLAB BY SAW CUTTING MARK INTO CONCRETE 1/4"
PERMANENTLY MARK POST-TENSIONING BAR LOCATIONS ON VERTICAL SIDE 2.
FORMING REQUIREMENTS FOR THE CONCRETE COREWALL CONSTRUCTION.
REFER TO SECTION 03300, CAST-IN-PLACE CONCRETE, FOR SPECIAL 1.
MISCELLANEOUS:
ADJACENT POURS.
CAST COREWALLS IN 25 WALL SEGMENTS WITH 2 DAY MINIMUM BETWEEN 5.
POST-TENSIONING BLOCKOUTS HAS BEEN PLACED.
SECTIONS SHALL NOT BE POURED UNTIL THE GROUT FOR THE
PRIOR TO THE HORIZONTAL PRESTRESSING OF THE WALL. THE ROOF SLAB
THE CONTRACTOR SHALL COMPLETE THE VERTICAL POST-TENSIONING 4.
BE MAINTAINED PER DRAWING C-C2-Z-00016.
BASE JOINT MOVEMENT AND CLEARANCES FOR REINFORCING BARS SHALL
TOP OF NEOPRENE PADS. FORM SUPPORTS SHALL NOT RESTRICT WALL
SPREADING OF FORMS, SO THAT CONCRETE WILL NOT PENETRATE BELOW
PROVIDE POSITIVE FORM SUPPORTS AT BASE OF WALL TO PREVENT 3.
CONCRETE IN WALL.
DUCT UNITS. SEAL OR REPAIR ALL CRACKS OR DAMAGE PRIOR TO CASTING
PRIOR TO CASTING CONCRETE IN WALL, WATER TEST THE VERTICAL BAR 2.
BOTTOM RUBBER PADS.
STEEL PLATE SUPPORTS. VERTICALS ARE NOT TO REST DIRECTLY ON THE
SUPPORT VERTICAL WALL REINFORCING ON HARD PLASTIC OR STAINLESS 1.
COREWALL:
PERIMETERS.
THE JOINT DETAILS. LAP SPLICES MAY BE SHIFTED OUTSIDE OF COLUMN
INTERSECTING GRID LINES AND BOTTOM REINFORCING NEAR GRID LINES PER
GRID LINES UNLESS OTHERWISE NOTED. LAP TOP REINFORCING ON
SLAB REINFORCING SHALL BE ORIENTED PARALLEL AND PERPENDICULAR TO 7.
JOINTS, SEE DETAIL .
FOR CONCRETE PLACEMENT SEQUENCE AT WATERSTOP AND CONSTRUCTION 6.
APPROVED BY CTF.
CAST 24" BASE SLAB IN 14 SEPARATE POURS, UNLESS OTHERWISE 5.
C-CC-Z-00066.
JOINT WITHIN TOLERANCES SHOWN ON DRAWINGS C-CC-Z-00063 AND
LOCATE CENTERLINE OF WATERSTOP AND LATERAL CABLES AT WALL BASE 4.
SPECIFIED. USE ONLY HAND HELD EQUIPMENT WITHIN 5'-0" OF THE WALL.
MINIMUM COMPACTION OF BACKFILL AROUND TANK BASE SHALL BE AS 3.
MUDMAT OF LEAKAGE DETECTION SYSTEM.
BOTTOM SLAB SHALL BEAR ON POLY SHEETING LAID OVER THE UPPER 2.
C-CY-Z-00010 THRU C-CY-Z-00012.
SYSTEM AS REQUIRED BY SPECIFICATION, AND AS SHOWN ON DRAWINGS
AND OTHER SUBGRADE MATERIALS AND CONSTRUCT LEAKAGE DETECTION
PREPARE CONCRETE MUD MATS, GEOSYNTHETIC CLAY LINER, HDPE LINER, 1.
24" BOTTOM SLAB:
FOR GENERAL STRUCTURAL NOTES SEE DRAWING C-C2-Z-00016. 1.
GENERAL NOTES:
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A
PSC= 1 Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
T y p e r e v
CHK'D/VERIF'D APRV'D
PROJ.
APRV'DPRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
REVISION
CHK'D/VERIF'D APRV'D
REVISION
DS SDU TANK 7
Z AREA
SALTSTONE DISPOSAL SITE
.2
TYP
174'-10 9/16 "
T Y
P
23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"23'-0"
20°
LATEST
REVISION
C C C Z 0
AS SHOWN
0 0 0
CONCRETE
OVERALL ROOF PLAN
DRAWN BY (ORIG): IRINA L-T
KEY PLAN
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
AC
-C
C -Z -0
T Y P
C-CC-Z-00067
C-CC-Z-00065
SCALE 3/64"=1'-0"
N
T R
UE
NOR
T H
PLANT NORTH
N
.5
C-CC-Z-00063
E 66390.28
C-CM-Z-00049 MISCELLANEOUS STEEL DETAILS
T Y
P
TYP
5'-9"
C-CC-Z-00063
C-CC-Z-00067
C-CC-Z-00065
WALL AND COLUMN SECTION AND DETAILS
CONCRETE DETAILS
CONCRETE SECTIONS AND DETAILS
N/A
ROOF PLAN
S
EL 316.58
HP SLAB
NOTES
C-C2-Z-00016 GENERAL STRUCTURAL NOTES
PLOT DATE 12-11-17
CL SDU7
SDU7
TYP
69'-0"
JOINT TYP
CONSTRUCTION
.47
.47
°158.47°
1.5% RADIAL SLOPE, TYP
O D
379'-6" OD
158.47°
BY OTHER
STAIR TOWER
T Y
P
TYP
5'-9"
3B5B
2B
SDU7
SDU6
C-CM-Z-00049
C-CM-Z-00049
SUPPORT
WALKWAY
LP SLAB EL 313.73
TYP
2'-0" DIA COLUMN,
RAILING
2-RAIL GALV STL PERIMETER
TYP OF 4
W/ CURB,
8'-0" x 10'-0" HATCH
C-CC-Z-00063
SDU7
1 2
43 5
ROOF SLAB PLACEMENT
NTS
RADIAL, NOTE 2
1'-9"
RADIA
L, N
OTE 21'-9
RADIAL, NOTE 2
1'-9"
RADIA
L, N
OTE 21'-9
WALL.
TURN CONSTRUCTION JOINTS PERPENDICULAR TO WALL AT INSIDE FACE OF 2.
FOR GENERAL STRUCTURAL NOTES SEE DRAWING C-C2-Z-00016. 1.
TYP
AT EA COLUMN,
8'-0" SQ DROP PANEL
IS COMPLETE. WATER CURE ALL SLABS FOR 12 DAYS.
ROWS MAY BE STARTED BEFORE THE PRECEDING ROW
CASTING OF SEQUENTIALLY NUMBERED SEGMENTS. NEW
MAXIMUM OF 14 DAYS SHALL BE ALLOWED BETWEEN 2.
SEQUENCE FOR CASTING INDIVIDUAL SLAB SEGMENTS.
THE NUMBERS SHOWN INDICATE THE REQUIRED 1.
NOTES:
0 ISSUED FOR CONSTRUCTION
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A
PSC= 1 Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
T y p e r e v
CHK'D/VERIF'D APRV'D
PROJ.
APRV'DPRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
REVISION
CHK'D/VERIF'D APRV'D
REVISION
DS SDU TANK 7
Z AREA
SALTSTONE DISPOSAL SITE
1.7 3°
1.73°
.49°1.94°
1.5°
1'-9
.87°
1.
.1
2.
.0
1.
1.
8'-9"
2'-3"
4'-10•"
2'-7"
4'-5•"
3'-8"
2'-7"
5'-6•"
2'-6"
3'-8"
4'-5"
2'-7"
5'-6•"
" 3
1'-10"1
5'-2"
3'-8" 1'-2"
8" 2
1'-4•"
2'-9"
4'-10"
2'-0"
8'-5" 10'-0" 10'-0" 10'-0" 10'-4"
3'-6"3'-0"
"3'-0"
2'-0"
8'-0•"8'-0" 10'-0" 9'-2" 6'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 11'-6" 11'-6" 5'-3"
5°
0"
0"
0"
0"
0"
2'-0"
1'-
0"
2•
2' -9
9'-0"
NOTES
LEGEND
KEY PLAN
T R
UE
NOR
T H
PLANT NORTH
N
#D4
#P23
#P21
#C7
#P22
#P1
#D5
FOR NOZZLE PENETRATION LOCATIONS AND LEGEND, SEE SHEET 5.1.
TYP
,CHORD
T Y P
C H O R D
C-CC-Z-00067
C-CC-Z-00067
C TANKL
C TANKL
TYP
2'-0" DIA COL,
TYP
SUPPORT EMBED
C INTLC
IN
T
L
C INTL
" #P24
#G5
TA
NKCT
R
PT
#C2
#G1
#V1
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
LATEST
REVISION
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
REFERENCE STANDARDS
REFERENCE DRAWINGS
PROJ.
BLDG. NO.
TITLE
SITE CLEARANCE NO. DESIGN AREA NO. DESIGN GROUP
SCALE SRP DRAWING NO. SHEET NO. LATEST REVISION
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
YVENDOR'S SHOP DRAWINGS, SHALL BEAR OR REFER TO THIS STAMP.
CONTRACTOR. ALL REPRODUCTIONS IN WHOLE OR IN PART, INCLUDING
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
APRV'D
LEVELS
234567890123 5678901234567890123456789 1234567890123456789 23
1111 1111122222222223333333333 44444444455555555 5 66
N/A
C C C Z 0 0 0 0
Z451
Z AREA
„" = 1'-0" N/A 1 OF 5
CONCRETE DETAILS
STAIR TOWER DETAILS
PSC= DRAWN BY (ORIG): LAST CADD REV. BY:
PLOT DATE 12-11-17 TIME DATE:
Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
C-CC-Z-00067
C-CM-Z-00046
SALTSTONE DISPOSAL SITE
CONCRETE
ROOF EMBED AND NOZZLE PLAN
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
y p e r e v
CHK'D/VERIF'D
APRV'D
PROJ.
PRP'D APRV'DLEAD ENG
INITIAL AND DATE
NO.
REV.
CHK'D/VERIF'D
TBD451-7Z DS SDU TANK 7
IRINA L-T
C-CC-Z-00068 CONCRETE DETAILS
87654321
A
B
C
D
E
F
G
H
M A
T C
H
L
IN
E
S
E
MATCH LINE - SEE SHEET 4
1'-9
R
'-4
R
TYP
CHORD
5'-
6"
TYP
5'-6"
TYP
5'-6
T Y P
3'-1 0"
'-1"T
Y P
4' -0
TYP
TYP
RAILING EMBED
5'-9"
T Y P
T Y P
6"
6"
5'-3"
TYP
T Y P
1'
'-9
R
'-0
R
R O O F
S
LA
B
O .F . O
F
W
LL
3B5B
2B
SDU7
SDU6
C L
E
M B E D
P L A T E S
C L
E
M B E D
P L A T E S
E66390.28
0SDU7
#P2
4'-4•"
8'-2"
8'-2"
3' -0 3' -6
16'- 6"
C-CC-Z-00067
31'-10•"
T Y P
DIM TO EDGE OF ROOF SLAB
EA COL
PANEL, TYP AT
8'-0" SQ DROP
LEVEL INDICATOR, TYP
2'-0" DIA COL W/
TYP
STAIR EMBED
TYP
FOR STAIR SEE
C-CM-Z-00046
ISSUED FOR CONSTRUCTION
#G3
SEE PLAN
ROOF HATCH,
8'-0" x 10'-0"
#V2
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
.45° 3.32°
1.29° 1.29°
1.73°
2.22°
.12
1.7
1.7
.0
1.2
1.2 .4
5'-10"
10'-0"10'-0"10'-0"9'-6ƒ"
2'-0"
9'-6"
10'-0"6'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"11'-6"5'-6"
3'-0"
9'-2‚" 8'-0"8'-0" 10'-0"
135°
3'-0"
3'-6"
2'-0"
6'-0"2'-0"
P
3'-7‚" 2'-7"
2'-9"
1'-4•
1.29°
31'-10•"
1'-3"
9'-0"
3'-6"2'-9"
13'-•"
3'-0"
2' -0
9' -0
NOTES
LEGEND
KEY PLAN
T R
UE
NOR
T H
PLANT NORTH
N
#D1
#P3
#P4
#V3
#P5
#P6
#C1
#D2
#P8
#C4
#D3
#P7
#P25
FOR NOZZLE PENETRATION LOCATIONS AND LEGEND, SEE SHEET 5.1.
C-CC-Z-00067
C-CC-Z-00067
TYP
CHORD
LC TANK
LC TANK
C INT
C INT
L
L
C INTL
#G4
#G2
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
TITLE
SRP DRAWING NO. SHEET NO.
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
REF FILES YES NO
LEVELS
234567890123 5678901234567890123456789 1234567890123456789 23
1111 1111122222222223333333333 44444444455555555 5 66
N/A N/A
5W.S. # [ ] . 6
C C C Z 0 0 0
0 2 OF 5
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
SALTSTONE DISPOSAL SITE
TANK DESIGN
CONCRETE
ROOF EMBED AND NOZZLE PLAN
PSC= 96 DRAWN BY (ORIG): LAST CADD REV. BY:
TIME DATE:
DRAWING REV.
Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
TANK
CTR PT
TYP
SUPPORT EMBED
SDU7
IRINA L-T
3B5B
2B
SDU7
SDU6
9 1610 11 12 13 14 15
H
A
B
C
D
E
F
G
M A
T
E
S
E E
T
MATCH LINE - SEE SHEET 3
N .5
PANEL, TYP
8'-0" SQ DROP
2'-0" DIA COL W/
R
R
R O O F
S
LA
B
O .F O F
W
LL
1'- 9"
R
9' -4
R
CL
E
M
BE
D
PL
AT
ES
C L
EM
BE
D
PL
AT
ES
TYP
RAILING EMBED
5'-6"
TYP
4'-3"
1'-5•"
5'-2•"
'-6"
T Y P
T Y P , C H O R D
'-6
T Y P
T Y P
C
H O
R D
"T Y P
TY
P
'-3"
3'-6"
8' -2
8' -2
1'-9"
PLOT DATE 12-11-17
TYP
4'-4† "1
#T3
#T2
C-CC-Z-00067
'-5
#T1
1'-0"
T Y P
C-CM-Z-00046
INDICATOR, TYP
W/ LEVEL
2'-0" DIA COL
TYP
FOR STAIR SEE
TYP
STAIR EMBED
#T4
SEE PLAN
ROOF HATCH,
8'-0" x 10'-0"
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
NO. C00201
CH2M HILL
11'-2ƒ
10'-0"
10'-0"
10'-0"
10'-0"
10'-0"
.1 1°
1.
.1
2.
1.7 3°
1.73
1.7°1.66°.8°
2'-0"
11'-0"11'-0"11'-0"7'-6"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"5'-9"5'-6"
2'-0"
3'-3"
9'-0"9'-0"9'-0"9'-0"5'-9•"5'-9•"1'-6"
2'-0"
31'-10•"
2' -9 "1'-
4•
9'-0"
2'-0"
NOTES
LEGEND
KEY PLAN
#C3
#P9
#P12
#P11
#C6
#P13
#P14
FOR NOZZLE PENETRATION LOCATIONS AND LEGEND, SEE SHEET 5.1.
#C3
#P9
#G6
#P12
#P11
#C6
#P14
#D8
T R
UE
NOR
T H
PLANT NORTH
N
C TANKL
C TANKL
C-CC-Z-00067
C-CC-Z-00067
TYP
LEVEL INDICATOR,
2'-0" DIA COL W/
#D6
TA
NKC
TR
P
T
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
TITLE
SRP DRAWING NO. SHEET NO.
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
REF FILES YES NO
LEVELS
234567890123 567890123456789012345678901234567890123456789 23
1111 1111122222222223333333333444444444455555555 5 66
N/A N/A
5W.S. # [ ] . 6
0 3 OF 5
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
SALTSTONE DISPOSAL SITE
TANK DESIGN
CONCRETE
ROOF EMBED AND NOZZLE PLAN
PSC= 96 DRAWN BY (ORIG): LAST CADD REV. BY:
PLOT DATE 12-11-17 TIME DATE:
DRAWING REV.
Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
SDU7
6 1
IRINA L-T
9 10 11 12 13 14 15 16
S
R
P
N
M
L
K
J
E66390.28
3B5B
2B
SDU7
SDU6
MATCH LINE - SEE SHEET 2
M A
T
E
S
E
1'-
T Y P4
T Y P
C H
O R
D
T Y P
SEE PLAN
ROOF HATCH,
8'-0" x 10'-0"
T Y P
6"
6"
TYP
5'-2•"
TYPCHORD,
5' -6
"TYP
TYP
CHORD,
5'-6
5'-6"
2'-7•"
Y P4
189'-9"
R
ROOF SLAB
189'-0"
R
O.F. OF WALL
181'-9"
R
189'-4"
R
CL EMBED PLATES
CL EMBED PLATES
TYP
RAILING EMBED
TYP
DROP PANEL,
W/ 8'-0" SQ
2'-0" DIA COL
#P10
#G8
1'-9"
1•
TYP
SUPPORT EMBED
#V5
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
1'-4• "2'-9"
1.7
.5 ° 2 .11°
1.7
1.7° 1.66° 1.66° .87°
1.73°
.12
2.22°
4'-4•" 1'-7•"
4'-4"
5'-•"
2'-6"
5'-3"
5'-9"
2'-0"
11'-0" 11'-0" 11'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0"
4'-9"
6'-10•"
4'-7•"
8'-6" 10'-0" 6'-10" 6'-10" 8'-9" 9"
2'-0"
'-5
1/2
31'-10•"
2' -0
9' -0
NOTES
LEGEND
KEY PLAN
T R
UE
NOR
T H
PLANT NORTH
N
J
C TANKL
C TANKL
C-CC-Z-00067
C-CC-Z-00067
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
UNITED STATES DEPARTMENT OF ENERGY
SAVANNAH RIVER SITE
TITLE
SRP DRAWING NO. SHEET NO.
SRP DRAWING NO.
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
REF FILES YES NO
LEVELS
234567890123 5678901234567890123456789 1234567890123456789 23
1111 1111122222222223333333333 44444444455555555 5 66
N/A N/A
5W.S. # [ ] . 6
0 4 OF 5
DRAWING REPRODUCED WITHOUT WRITTEN PERMISSION OF THE PRIME
THE INFORMATION AND KNOW HOW THEREON MAY NOT BE USED NOR THE
THIS DRAWING HAS BEEN FURNISHED BY THE SAVANNAH RIVER SITE.
SALTSTONE DISPOSAL SITE
TANK DESIGN
CONCRETE
ROOF EMBED AND NOZZLE PLAN
PSC= 96 DRAWN BY (ORIG): LAST CADD REV. BY:
PLOT DATE 12-11-17 TIME DATE:
DRAWING REV.
Scale shown on this drawing is only applicable when plotted at 30"x42" (actual drawing size)
TANK
CTR PT
SDU7
6 1
IRINA L-T
MATCH LINE - SEE SHEET 1
M A
T
E
S
E
21 3 4 5 6 7 8
K
L
M
N
P
R
S
N
.5
T Y P
C H
O R
D
T Y P
1 '
9'-
9"
R
9'-
0"
R
O.
F.
OF
WALL
ROOF
SLAB
181'- 9"
R
189' -4"
R
T Y P
C H O R D
'-6
T Y P
5'-6" 5'-6" 2'-11"
T Y P
'-8
5'-9"
TYP
CHORD,
5'-6"
5'-3"
3B5B
2B
SDU7
SDU6
FOR NOZZLE PENETRATION LOCATIONS AND LEGEND, SEE SHEET 5.1.
T Y P
'-3
5'-3"
CL EMBED PLATES
CL EMBED P
LATES
TYP
RAILING EMBED
8'-9"
12'-2" 7'-10" 11"
6'-8"9'-8" 2'-1"
8'-2" 8'-2"
1/
T Y P
C-CC-Z-00067
TYP
8'-0" SQ DROP PANEL,
2'-0" DIA COL W/
TYP
STAIR EMBED
TYP
FOR STAIR SEE
LEVEL INDICATOR, TYP
2'-0" DIA COL W/
C-CM-Z-00046
TYP
SUPPORT EMBED
#P16
#P17
SEE PLAN
ROOF HATCH,
8'-0" x 10'-0"
#C8
#P19
#G7
#P18
#D7 #P20
#P15
#C5
#G9
#V4
CAROLIN
A
S O
U
TH
C E
R T
IF
IC
ATE O
FAUTH
O
R
IZ
A T I
O
N
INC.
DESCRIPTION
NOTES
LEGEND
DETAILNOZZLE # REMARKSNORTH OF CL SOUTH OF C EAST OF C WEST OF CL L L
12" DIA. PASSIVE VENTILATION - PORT #1
12" DIA. PASSIVE VENTILATION - PORT #2
12" DIA. PASSIVE VENTILATION - PORT #3
12" DIA. PASSIVE VENTILATION - PORT #4
3" DIA. GROUT POUR- PORT #1
3" DIA. GROUT POUR- PORT #2
3" DIA. GROUT POUR- PORT #3
3" DIA. GROUT POUR- PORT #4
3" DIA. GROUT POUR- PORT #5
3" DIA. GROUT POUR- PORT #6
3" DIA. GROUT POUR- PORT #7
3" DIA. GROUT POUR- PORT #8
3" DIA. GROUT POUR- PORT #9
36" DIA. DRAIN WATER RETURN- PORT #1
36" DIA. DRAIN WATER RETURN- PORT #2
36" DIA. DRAIN WATER RETURN- PORT #3
36" DIA. DRAIN WATER RETURN- PORT #4
36" DIA. DRAIN WATER RETURN- PORT #5
36" DIA. DRAIN WATER RETURN- PORT #6
36" DIA. DRAIN WATER RETURN- PORT #7
36" DIA. DRAIN WATER RETURN- PORT #8
V1
T1 8" DIA. THERMOCOUPLE TREE - PORT #1
8" DIA. THERMOCOUPLE TREE - PORT #2
8" DIA. THERMOCOUPLE TREE - PORT #3
C1 12" DIA. CAMERA - PORT #1A
12" DIA. CAMERA - PORT #1B
12" DIA. CAMERA - PORT #2A
12" DIA. CAMERA - PORT #2B
12" DIA. CAMERA - PORT #3A
12" DIA. CAMERA - PORT #3B
12" DIA. CAMERA - PORT #4A
12" DIA. CAMERA - PORT #4B
P1 3" DIA. INSPECTION/GROUT - PORT #1
3" DIA. INSPECTION/GROUT - PORT #2
3" DIA. INSPECTION/GROUT - PORT #4
3" DIA. INSPECTION/GROUT - PORT #5
3" DIA. INSPECTION/GROUT - PORT #6
3" DIA. INSPECTION/GROUT - PORT #7
3" DIA. INSPECTION/GROUT - PORT #8
3" DIA. INSPECTION/GROUT - PORT #9
3" DIA. INSPECTION/GROUT - PORT #10
3" DIA. INSPECTION/GROUT - PORT #11
3" DIA. INSPECTION/GROUT - PORT #12
3" DIA. INSPECTION/GROUT - PORT #13
3" DIA. INSPECTION/GROUT - PORT #14
3" DIA. INSPECTION/GROUT - PORT #15
3" DIA. INSPECTION/GROUT - PORT #16
3" DIA. INSPECTION/GROUT - PORT #17
3" DIA. INSPECTION/GROUT - PORT #18
3" DIA. INSPECTION/GROUT - PORT #19
3" DIA. INSPECTION/GROUT - PORT #20
3" DIA. INSPECTION/GROUT - PORT #21
3" DIA. INSPECTION/GROUT - PORT #22
3" DIA. INSPECTION/GROUT - PORT #23
3" DIA. INSPECTION/GROUT - PORT #24
3" DIA. INSP/GROUT/CONDENSATE - PORT #25
3" DIA. INSP/GROUT/CONDENSATE - PORT #3
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
- 5'-1"
123'-9"
51'-8" 124'-8"
5'-0"
5'-0"
55'-1"
55'-1"
183'-10" 5'-0"
55'-1"
55'-1"
5'-0"
1'-6" 78'-0"
1'-6" 78'-0"
78'-0" 1'-6"
78'-0" 1'-6"
1'-6" 78'-0"
1'-6" 78'-0"
78'-0" 1'-6"
78'-0" 1'-6"
10'-7"
59'-11"
44'-7" 60'-2"
123'-9" 89'-11"
10'-7"
59'-11"
2'-0" 11'-6"
V2
V3
V4
V5
G1
G2
G3
G4
G5
G6
G7
G8
G9
D1
D2
D3
D4
D5
D6
D7
D8
T2
T3
C2
C3
C4
C5
C6
C7
C8
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
P22
P23
P24
P25
123'-9"
123'-9"
123'-9"
123'-9"
123'-9"
123'-9"
123'-9"
51'-8"
51'-8"
51'-8"
51'-8"
51'-8"
51'-8"
51'-8"
124'-8"
124'-8"
124'-8"
124'-8"
124'-8"
124'-8"
124'-8"
ROOF PENETRATION SCHEDULE
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/2")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/2")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/2")
C TO MATCH EMBED P C AT FOUNDATION (+/- 1/4")LL
L L
L L
L L
L L
L L
L L
L L
L L
L L
L L
1'-0" 1'-0"
6"
6"
6"
6"
6"
6"
6"
6"
6"
6"
6"
14" DIA. PASSIVE VENTILATION - PORT #5
L
L
L
L
L
L
L
L
L
L
L
3'-1 1/4"
314.21'
314.21'
314.21'
315.96'
315.96'
315.96'
315.96'
314.21'
315.36'
317.39'
183'-10"
183'-10"
183'-10"
314.97'
314.97'
314.97'
314.97'
CLFL MONITOR (SECONDARY)
CLFL MONITOR (PRIMARY)
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
9/C-CC-Z-00067
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
I
Y
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18…