TOP VIEW

SIDE VIEW

CONCRETE EQUIPMENT PAD DETAIL

6" x 6" 10/10 WIRE MESH

FINISH GRADE

NO SCALE

PAD SHOULD BE A

MINIMUM OF 6" LARGER

THAN THE EQUIPMENT

ENCLOSURE ON ALL

SIDES

6" x 6" 10/10

WELDED WIRE MESH

PROVIDE 1", 45 DEGREE

CHAMFER ON ALL SIDES

3000 PSI CONCRETE

EQUIPMENT PAD

4" 6"

REFER TO GENERATOR SHOP

DRAWINGS FOR CONDUIT STUB-UP

LOCATIONS IN THE GENERATOR PAD.

WP GFI

PROVIDE RECEPTACLE AT GENERATOR

4-#10, 1-#10EG, 1" C

40 38 42

TO EP1

100A/3P

(3) 20A/1P

NO SCALE

EMERGENCY GENERATOR SCHEMATIC WIRING DIAGRAM

JJ

DIGITAL CONTROL

PANEL (FURNISHED

WITH GENERATOR)

CONNECT BATTERY

CHARGER

2-#12, 1-#12EG, 1/2"C

2-#12, 1-#12EG, 1/2"C

(10) #18 SHIELDED TWISTED PAIR IN 1"C

OR AS REQUIRED BY MANUFACTURER

EP1/38 (20A/1P C.B., BLOCK HEATER)

EP1/40 (20A/1P C.B., BATTERY CHARGER)

EP1/42 (20A/1P C.B., GFI RECEPTACLE)

INSTALL ANNUNCIATOR PANEL

FURNISHED WITH GENERATOR.

ATS

208Y/120V 100A/3P

CONNECT BLOCK HEATER

4-#2, 1-#8EG, 4" PVC-80,

DB

(1) #18 SHIELDED TWISTED

PAIR IN 1/2 "C FOR

GENERATOR START SIGNAL

(1) ENCLOSED CIRCUIT BREAKERS

IN GENERATOR ENCLOSURE

EMERGENCY GENERATOR

25KW/31.25KVA

208Y/120V

NATURAL GAS

LOCATED OUTSIDE

PROVIDE EMERGENCY STOP BREAK-

GLASS PUSHBUTTON. INSTALL OUTSIDE

OF GENERATOR ROOM OR EXTERNAL

TO THE WEATHERPROOF ENCLOSURE

2-#14, 1/2"C

NO SCALE

DIRECT BURIED CONDUIT DETAIL

TWO DUCTS

40"

MIN.

7 1/2"

GRASS AREAS

BACKFILL WITH NATIVE

MATERIAL IN 6" LIFTS.

COMPACT AFTER EACH

LIFT.

PAVEMENT AREAS

BACKFILL WITH #2

CRUSHED STONE IN 6"

LIFTS. COMPACT AFTER

EACH LIFT.

3" SCREENED TOP SOIL

AROUND CONDUIT

4" SCREENED TOP SOIL

FOR GRASS AREAS.

PAVEMENT AS REQUIRED6" WIDE, RED PLASTIC

TAPE WITH WORDING

"CAUTION BURIED ELECTRIC

LINE BELOW." TAPE SHALL

BE LOCATED 6" BELOW

FINISHED GRADE

FINISH GRADE

PVC CONDUIT

THREADED CAP ON ALL SPARES

TO COUPLING, PULLBOX, PANEL ECT.

PVC TO RIGID ADAPTER

PROVIDE ENGRAVED NAMEPLATE

ON CONDUITFINISHED

FLOOR

WRAP ALL JOINTS 100%

WATERTIGHT

SEAL VAPOR

BARRIER TO

CONDUIT

RIGID HOT DIPPED

GALVANIZED CONDUIT

BACKFILL WITH NATIVE

MATERIAL IN 6" LIFTS.

COMPACT AFTER

EACH LIFT

SAND BED ENVELOPE AS

CALLED FOR ON PLANS.

WHERE CONDUIT STUBS UP UNDER FLOOR MOUNTED EQUIPMENT SUCH

AS SWITCHGEAR, PROVIDE PVC ELBOWS IN LIEU OF RIGID SHOWN.

AT EACH CONDUIT STUB-UP, AFFIX ENGRAVED PLASTIC NAMEPLATE

INDICATING CONDUIT NO. OR CIRCUIT IDENTIFICATION. ATTACH WITH

NYLON CABLE TIE.

NOTES:

NO SCALE

CONDUIT STUB-UP INSIDE BUILDING DETAIL

1.

2.

FT

P A N E L B

O A R

D

D

IS

C O

N N E C T

T H E R

M O

S T A T

L

IG

H T S

W

IT

C H

C A R

D A

C C E S S

V O

IC

E /D

A T A O

U T L E T

D U P L E X R

E C E P T A C L E

6'-8" 6'-0" 5'-0"

4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0"

2'-10"

1'-6" 1'-6" 1'-6"

4'-0" 4'-0"

7'-8"7'-6"

NO SCALE

TYPICAL DEVICE MOUNTING ELEVATIONS

NOTES:

F

IR

E A

L A R

M A U D

IO

/V

IS

U A L

A N D

V

IS

U A L

D E V

IC

E

N U R

S E C

A L L

P R

E /P

O S T

P .A

.C .U

N U R

S E C

A L L

O .R

N U R

S E C

A L L

T Y P

IC

A L

IN LOCATIONS WHERE SIMILAR DEVICES ARE MOUNTED AT THE SAME HEIGHT, DEVICES SHALL BE PROPERLY "GANGED" AND SHALL

HAVE A SINGLE COVER PLATE.

IN LOCATIONS WHERE DIFFERENT DEVICES ARE MOUNTED AT DIFFERENT HEIGHTS WITHIN FOUR FEET OF ONE ANOTHER, DEVICES SHALL BE MOUNTED SUCH THAT THEY HAVE A COMMON CENTERLINE. IF THERE ARE THREE OR MORE DEVICES, THE CONTRACTOR

SHALL REQUEST A DETAIL FROM THE ARCHITECT.

1.

2.

F

IR

E A

L A R

M P U L L S

T A T

IO

N

W A L L M

O U N T E D

T E L E P H O

N E

D U P L E X R

E C E P T A C L E

M E C H R

O O

M G

A R

A G

E S

N U R

S E C

A L L E

M E R

G E N C Y

B A T H R

O O

M

C L O

C K

O U T L E T

D E S K T

O P T

E L E P H O

N E

C A T V

O U T L E T

FINISHED

FLOOR

D O

M E

L

IG

H T

4'-0"

A P A R

T M

E N T L

O A D

C E N T E R

NO SCALE

POWER ONE-LINE RISER DIAGRAM

400A/3P

LVP1

G

200A/3P 100A/3P

EP1

100A/3P

EG-1

25KW/31.25KVA

208Y/120V 3Ø, 4W

NATURAL GAS

ATS-1

250V 100A/3P

(E)MDP

208Y/120V 3Ø, 4W

400A/3P MLO

4-#2, 1-#8EG IN 1¼"C

4-#2, 1-#8EG IN 1¼"C

4-#2, 1-#8EG IN 4" PVC-80, DB

(E)PAD MOUNTED TRANSFORMER

100KVA

208Y/120V SECONDARY

DEMOLITION NOTES:

NO SCALE

NATURAL GAS SERVICE - DEMOLITION SCHEMATIC DETAIL

COORDINATE UPGRADE OF (E) NG METER WITH NYSEG.1

(E) METER

(E) NG SERVICE

(E) NG PIPING

(E) PRESSURE

REGULATOR

DRAWING NOTES:

NO SCALE

NATURAL GAS SERVICE - NEW WORK SCHEMATIC DETAIL

COORDINATE UPGRADE OF (E) NG METER WITH NYSEG.

CONNECT (N) 1½" NG BRANCH TO (E) NG PIPING.

PROVIDE ISOLATION VALVE AND TRANSITION TO PE

GAS PIPING BELOW GRADE. UNDERGROUND NG PIPING

SHALL HAVE 24" OF COVER.

(N) METER

(E) NG SERVICE

(E) NG PIPING

(E) PRESSURE

REGULATOR

(N) 1½" NG PIPING

(E) NG PIPING

TURNER

E N G I N E E R I N G , P C

One Woodbury Boulevard Rochester, NY 14604

585.381.3360 Tel

Project No.

IT IS A VIOLATION OF LAW FOR ANY PERSONS,

UNLESS ACTING UNDER THE DIRECTION OF A

LICENSED PROFESSIONAL ENGINEER, TO ALTER

ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY

LICENSEE WHO ALTERS THIS DOCUMENT IS

REQUIRED BY LAW TO AFFIX HIS OR HER SEAL

AND THE NOTATION "ALTERED BY", FOLLOWED

BY HIS OR HER SIGNATURE AND A SPECIFIC

DESCRIPTION OF THE ALTERATIONS.

Client

Project

Drawing

Issue Date:

Proj. No.

Sheet

Proj. Status:

EP200

ELECTRICAL AND

PLUMBING DETAILS

19223

CORNELL USDA

GENERATOR

CORNELL COOPERATIVE

EXTENSION

19223

01/02/2020

ISSUED FOR BID

Revision Schedule

NO. DESC. DATE

1 PANEL SCHEDULE 2/4/2020

2 EP1 SCHEDULE 2/6/2020

3 OWNER REQUESTED

CHANGES

2/24/2020

4 UTILITY ADDITIONS 8/20/2020

TOTAL EST. DEMAND: 30 A

Receptacle 180 VA 100.00% 180 VA TOTAL CONN.: 40 A

Other 4 VA 100.00% 4 VA TOTAL EST. DEMAND: 10837 VA

Motor 14136 VA 75.00% 10602 VA TOTAL CONN. LOAD: 14376 VA

Lighting 56 VA 90.00% 50 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 34 A 42 A 46 A

TOTAL LOAD: 4064 VA 4924 VA 5388 VA

41 SPACE -- -- 0.00 0.18 1 20 A GEN RECEPTACLE 42

39 SPACE -- -- 0.00 0.50 1 20 A GEN BATTERY CHARGER 40

37 SPACE -- -- 0.00 0.50 1 20 A BLOCK HEATER 38

35 SPACE -- -- 0.00 0.00 -- -- SPACE 36

33 SPACE -- -- 0.00 0.00 -- -- SPACE 34

31 SPACE -- -- 0.00 0.00 -- -- SPACE 32

29 SPACE -- -- 0.00 0.00 -- -- SPACE 30

27 SPACE -- -- 0.00 0.00 -- -- SPACE 28

25 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 26

23 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 24

21 ROOF PUMP 20 A 1 0.10 0.10 1 20 A ROOF PUMP 22

19 EAST EM AND EXIT LTG 20 A 1 0.03 0.03 1 20 A WEST EM AND EXIT LTG 20

17 ENVIROSTEP 20 A 1 0.18 0.18 1 20 A ENVIROSTEP 18

15 OVERHEAD CURTAIN 20 A 1 0.30 0.30 1 20 A OVERHEAD CURTAIN 16

13 PAD PUMP AND VENT 20 A 1 0.68 0.68 1 20 A PAD PUMP AND VENT 14

11 EXHAUST FAN 2-SPD 20 A 1 1.51 1.51 1 20 A EXHAUST FAN 2-SPD 12

9 EXHAUST FAN 1-SPD 20 A 1 0.82 0.82 1 20 A EXHAUST FAN 1-SPD 10

7 GABLE SHUTTER AND... 20 A 1 0.11 0.11 1 20 A GABLE SHUTTER AND... 8

5 HAF FANS 20 A 1 0.91 0.91 1 20 A HAF FANS 6

3 JET FAN AND SHUTTER 20 A 1 1.00 1.00 1 20 A JET FAN AND SHUTTER 4

1 UNIT HEATERS - MODINE... 20 A 1 0.96 0.96 1 20 A UNIT HEATERS - MODINE... 2

CKT CIRCUIT DESCRIPTION TRIP POLES A (kVA) B (kVA) C (kVA) POLES TRIP CIRCUIT DESCRIPTION CKT

NOTES:

EP1 EAST GREENHOUSE 1 100 A 3Ø, 4W 120/208 WYE SURFACE 10kA TYPE 1

MCB MLO

NAME LOCATION SOURCE

RATING (AMPS)

PHASE/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE

HINGED TRIM X 200% NEUTRAL SUB-FEED LUGS SPD SIZE:PANELBOARD SCHEDULE SE RATED SUB-FEED BREAKER FEED-THRU LUGS INTEGRAL SPD

KM2

Text Box

AS-BUILTS

ChrisM.Wilson Polygon

ChrisM.Wilson Polygon

ChrisM.Wilson Typewritten Text 5 USDA Notes on As-Builts 09/24/2020 (CMW/EPM)

ChrisM.Wilson Typewritten Text

ChrisM.Wilson Polygonal Line

ChrisM.Wilson Polygonal Line

ChrisM.Wilson Typewritten Text

ChrisM.Wilson Typewritten Text Secondary Pressure Regulator/Governor Installed (11" WC)

ChrisM.Wilson Typewritten Text Site Photo (09/24/2020) - Location of Secondary Pressure Regulator/Governor

ChrisM.Wilson Cross-Out

ChrisM.Wilson Line

ChrisM.Wilson Line

ChrisM.Wilson Polygon

ChrisM.Wilson Typewritten Text

DIGITAL CONTROL PANEL IS CONNECTED DIRECTLY TO ATS AS-BUILT

ChrisM.Wilson Polygonal Line

ChrisM.Wilson Typewritten Text