T T
E E
SYMBOL DESCRIPTION
POWER DISTRIBUTION
SURFACE/FLUSH MOUNTED BRANCH
CIRCUIT PANELBOARD. 208Y/120V OR
240/120V. REFER TO PANELBOARD
SCHEDULE
MANUAL MOTOR STARTER OR MOTOR
RATED SWITCH. DESIGNATION REFERS TO
ELECTRIC EQUIPMENT AND CONTROL
SCHEDULE
NON-FUSED DISCONNECT SWITCH.
DESIGNATION REFERS TO ELECTRIC
EQUIPMENT AND CONTROL SCHEDULE
ELECTRICAL
SYMBOL DESCRIPTION
DUPLEX RECEPTACLE,
SUBSCRIPTS AS FOLLOWS:
AFI
CR
EP
GFI
H
IG
SS
WP
TR
WR
USB
ARC FAULT INTERRUPTER
CORROSION RESISTANT
EXPLOSION PROOF
GROUND FAULT INTERRUPTER
HOSPITAL GRADE
ISOLATED GROUND
SURGE SUPPRESSION
WEATHER PROOF
TAMPER RESISTANT
WEATHER RESISTANT
UNIVERSAL SERIAL BUS
SYMBOL LIST
JUNCTION BOX
MOTORM
MS
J
EMERGENCY POWER OFF PUSHBUTTONEPO
120 VOLT CONNECTION TO EQUIPMENT
E-3
SYMBOL DESCRIPTION
MISCELLANEOUS
REFERENCE TO DRAWING NOTE
REFERENCE TO EQUIPMENT OR
FEEDER NUMBER
DETAIL REFERENCE SYMBOL
SYMBOL DESCRIPTION
LINE STYLES
INDICATES NEW DEVICE OR EQUIPMENT
REFERENCE TO DEMOLITION NOTE2
INDICATES EXISTING DEVICE OR EQUIPMENT
TO REMAIN
INDICATES DEVICE OR EQUIPMENT TO BE
REMOVED OR RELOCATED
INDICATES ELECTRIC SERVICE LINE
INDICATES TELEPHONE SERVICE LINE
NUMBER INDICATES CIRCUIT BREAKER NO.1
GENERAL SITE NOTES APPLY TO ALL SITE ELECTRICAL DRAWINGS.
OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY THE CITY OF
CORNELL.
THE ELECTRICAL CONTRACTOR SHALL ENGAGE THE SERVICES OF A
QUALIFIED SUBCONTRACTOR FOR EXCAVATION, BACKFILL AND CONCRETE
WORK.
A MINIMUM OF TWO DAYS PRIOR TO EXCAVATION, CONTACT DIG SAFELY
NEW YORK, INC (1-800-962-7962) AND OBTAIN A STAKEOUT OF ALL PUBLIC
AND PRIVATE UTILITIES LOCATED IN THE AREA OF EXCAVATION.
COORDINATE PRIVATE UTILITIES WITH THE OWNER PRIOR TO EXCAVATION.
HAND EXCAVATE ADJACENT EXISTING UTILITIES INCLUDING STORM AND
SANITARY SYSTEMS TO AVOID DAMAGE. REPORT ANY DAMAGED UTILITIES
TO THE OWNERS REPRESENTATIVE IMMEDIATELY.
PROVIDE BRACING, SHORING, SHEATHING AND OTHER WORK FOR
PROTECTION OF PERSONNEL, THE CONTRACT WORK, EXCAVATIONS,
TREES, SHRUBS, EXISTING STRUCTURES, AND SURROUNDING PROPERTIES.
PROVIDE AND MAINTAIN BARRICADES, WARNING SIGNS, FLAGS, AND
LIGHTS TO PROVIDE PROTECTION FOR WORK, WORKMEN, PUBLIC, AND
PROPERTY. COORDINATE PARKING LOT AND/OR PARKING GARAGE
DISRUPTIONS WITH THE OWNER IN ADVANCE.
PROVIDE PUMPS, HOSES, PIPE, LABOR AND FUEL NECESSARY TO KEEP
EXCAVATIONS FREE OF WATER ACCUMULATION. OPERATE AND MAINTAIN
EQUIPMENT. DISCHARGE WATER IN MANNER NOT TO UNDERMINE OR
DISTURB EXISTING OR ADJACENT STRUCTURES OR LAND. DO NOT
DISCHARGE DIRT, BACKFILL, DEBRIS, INTO SANITARY OR STORM
DRAINAGE SYSTEMS.
INSTALL TELEPHONE, CABLE AND ELECTRIC CONDUITS AS STRAIGHT AS
POSSIBLE. INSTALL CONDUITS BELOW SITE LIGHTING CONDUITS AND GAS
LINES AND ABOVE WATER, STORM, AND SANITARY PIPING.
TRANSITION ALL CONDUITS TO GRS PRIOR TO RISING ABOVE GRADE.
MAINTAIN ROAD ACCESS AT ALL TIMES. PROVIDE STEEL PLATES OVER
TRENCH AS REQUIRED.
PROTECT UTILITIES, SIDEWALKS, STRUCTURES, PAVEMENTS AND OTHER
FACILITIES FROM DAMAGE CAUSED BY SETTLING, LATERAL MOVEMENTS,
UNDERMINING, WASHOUTS AND OTHER HAZARDS CREATED BY EXCAVATION
WORK.
COMPLETELY RESTORE THE AREA TO THE CONDITION PRIOR TO THE
START OF EXCAVATION AND TRENCHING WORK.
GENERAL SITE NOTES:
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
SYMBOL DESCRIPTION
ABBREVIATIONS AND TAGS
LINETYPE LEGEND
SYMBOL DESCRIPTION
AFF ABOVE FINISHED FLOOR
(E) EXISTING
EC ELECTRICAL CONTRACTOR
ERL EXISTING TO RELOCATE
EXISTING TO REMAINETR
GC GENERAL CONTRACTOR
MC MECHANICAL CONTRACTOR
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
PUMPP
POINT OF CONNECTION
POINT OF DISCONNECTION
INSTALLATION KEYNOTE
REMOVAL KEYNOTE
WPCO WALL PLATE CLEANOUT
WH WALL HYDRANT
VTR VENT THROUGH ROOF
RPZ REDUCED PRESSURE ZONE
PD PUMP DISCHARGE
PLUMBING CONTRACTORPC
COLD WATER PIPING (C)
HOT WATER PIPING (H)
HW RECIRCULATION PIPING (HWR)
VENT PIPING (V)
STORM PIPING (ST)
SANITARY OR WASTE PIPING
(SAN or W)
G NATURAL GAS PIPING (G)
IW INDIRECT WASTE PIPING (IW)
W WATER MAIN (EXTERIOR)
DIRECTION OF FLOW
EXISTING PIPING
PIPING TO BE REMOVED
PIPING SYMBOLS
SYMBOL DESCRIPTION
ELBOW UP, ELBOW DOWN
DROP CONNECTION
ROLL DOWN
CLEANOUT (CO)
STRAINER
UNION
CAP OR PLUG
SHUT OFF VALVE
AQUASTAT
CHECK VALVE
PRESSURE REGULATING VALVE
BALANCE VALVE
ANGLE VALVE
REGULATOR
SOLENOID VALVE
3-WAY VALVE
RELIEF VALVE
PLUG VALVE
BUTTERFLY VALVE
NEEDLE VALVE
TS VALVE WITH TAMPER SWITCH
FS FLOW SWITCH
SS
ST
V
HWR
CO
TURNER
E N G I N E E R I N G , P C
One Woodbury Boulevard Rochester, NY 14604
585.381.3360 Tel
Project No.
IT IS A VIOLATION OF LAW FOR ANY PERSONS,
UNLESS ACTING UNDER THE DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, TO ALTER
ANY ITEM ON THIS DOCUMENT IN ANY WAY. ANY
LICENSEE WHO ALTERS THIS DOCUMENT IS
REQUIRED BY LAW TO AFFIX HIS OR HER SEAL
AND THE NOTATION "ALTERED BY", FOLLOWED
BY HIS OR HER SIGNATURE AND A SPECIFIC
DESCRIPTION OF THE ALTERATIONS.
Client
Project
Drawing
Issue Date:
Proj. No.
Sheet
Proj. Status:
EP001
GENERAL NOTES,
SPECIFICATIONS, AND
SYMBOLS
19223
CORNELL USDA
GENERATOR
CORNELL COOPERATIVE
EXTENSION
19223
01/02/2020
ISSUED FOR BID
ELECTRICAL SPECIFICATIONS
1. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES TO PERFORM
ALL OPERATIONS REQUIRED FOR THE COMPLETE INSTALLATION AND
RELATED WORK AS SHOWN ON DRAWINGS AND SPECIFIED HEREIN. ELECTRIC
EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMAN LIKE MANNER.
PROVIDE ALL ELECTRICAL EQUIPMENT CONNECTIONS. PROVIDE ALL
REQUIRED SUPPORTS AND ACCESSORIES. INSTALL ALL WORK IN
COMPLIANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE,
NFPA-70, NEW YORK STATE UNIFORM FIRE PREVENTION AND BUILDING CODE,
NEW YORK STATE ENERGY CONSERVATION CONSTRUCTION CODE, OSHA
REQUIREMENTS, AND LOCAL ORDINANCES.
2. INSTALL ALL WIRING AND EQUIPMENT IN ACCORDANCE WITH THE 2014
NATIONAL ELECTRICAL CODE.
3. OBTAIN AN UNDERWRITERS CERTIFICATE UPON SUBSTANTIAL COMPLETION.
4. COORDINATE ALL WORK WITH OTHER TRADES.
5. WIRE SHALL BE STRANDED COPPER WITH THHN/THWN INSULATION, MINIMUM
#12 AWG.
6. INTERIOR CONDUIT SHALL BE EMT WITH COMPRESSION FITTINGS.
7. EXTERIOR, ABOVE GRADE CONDUIT SHALL BE RIGID STEEL WITH THREADED
FITTINGS.
8. EXTERIOR, BELOW GRADE CONDUIT SHALL BE PVC, SCHEDULE 80, DIRECT
BURIED.
9. TYPE MC CABLE WITH A SEPARATE INSULATED GROUND IS PERMITTED. IN
INTERIOR, CONCEALED LOCATIONS. SUPPORT CABLE ON MINIMUM 4.5'
CENTERS.
10. EMERGENCY GENERATOR SHALL BE AS FOLLOWS:
•25 KW/31.25 KVA
•208Y/120 VOLTS
•NATURAL GAS FIRED
•ALUMINUM, WEATHER RESISTANT HOUSING, BISQUE COLOR
•100A-3P OUTPUT CIRCUIT BREAKER
•GENERATOR ANNUNCIATOR PANEL
•DESIGN MAKE: GENERAC PROTECTOR SERIES, MODEL RG025, OR
APPROVED EQUAL
11. AUTOMATIC TRANSFER SWITCH SHALL BE AS FOLLOWS:
•250 VOLT, 100 AMPERE, THREE POLE
•NEMA 3R
•BREAK BEFORE MAKE
•DESIGN MAKE: GENERAC, OR APPROVED EQUAL
12. ALL HOMERUNS TO PANELBOARDS SHALL BE INSTALLED IN EMT CONDUIT.
TYPE MC CABLE MAY BE USED FROM OUTLET BOXES IN THE CEILING TO
DEVICES AND LUMINAIRES, AND MAY BE RUN HORIZONTALLY IN THE METAL
STUD PARTITIONS.
13. PROVIDE UPDATED TYPE-WRITTEN DIRECTORIES FOR ALL PANELBOARDS
AFFECTED BY THIS PROJECT.
14. ALL EXPOSED WIRING SHALL BE INSTALLED IN CONDUIT OR SURFACE METAL
RACEWAY.
15. WHEREVER POSSIBLE, INSTALL ALL RACEWAYS CONCEALED AND DEVICES
FLUSH MOUNTED. WHERE REQUIRED DUE TO FIELD CONDITIONS, PROVIDE
SURFACE METAL RACEWAY. PAINT TO MATCH EXISTING SURFACES.
16. OUTLET BOXES AND COVERS SHALL BE GALVANIZED STEEL, NOT LESS THAN
1-1/2" DEEP, 4" SQUARE OR OCTAGONAL, WITH KNOCKOUTS. OUTLET BOXES
EXPOSED TO MOISTURE, EXTERIOR, WET OR DAMP LOCATIONS SHALL BE
CADMIUM CAST ALLOY COMPLETE WITH THREADED HUBS AND GASKETED
SCREW FASTENED COVERS. MINIMUM BOX SIZE SHALL BE AS INDICATED IN
ARTICLE 370 OF THE NATIONAL ELECTRIC CODE FOR THE CONDUCTORS AND
DEVICES INSTALLED. MAKE SHALL BE STEEL CITY OR EQUAL.
17. DUPLEX RECEPTACLES SHALL BE CONSTRUCTION GRADE. INTERIOR TYPE
SHALL BE DUPLEX, 20 AMPERE, TWO-POLE, THREE-WIRE, 125 VOLTS AC,
GROUNDING, WITH SIDE AND BACK TERMINAL CONNECTIONS AND SPLITWIRING
LINK, U.L. LISTED, WITH THERMOPLASTIC COVERPLATES. COLOR TO BE LIGHT
ALMOND. MAKE SHALL BE HUBBELL OR EQUAL.
18. PROVIDE LABELS ON ALL RECEPTACLES INDICATING BRANCH CIRCUIT PANEL
AND CIRCUIT NUMBER.
19. WIRING DEVICES SHALL BE CONSTRUCTION GRADE, LIGHT ALMOND IN
COLOR, WITH THERMOPLASTIC COVERPLATES. MAKE SHALL BE HUBBELL OR
EQUAL.
20. WEATHER RESISTANT DEVICE COVERS SHALL BE UL LISTED WITH THE DEVICE
PLUGGED IN. MAKE SHALL BE HUBBELL OR EQUAL.
21. PANELBOARDS SHALL HAVE ALUMINUM BUS WITH PLUG-ON CIRCUIT BREAKERS
AND HINGED TRIM. COORDINATE TRIM TYPE IN THE FIELD. MAKE SHALL BE
SQUARE D OR EQUAL.
22. DISCONNECT SWITCHES SHALL BE HEAVY DUTY WITH COPPER BUS. KNIVES
SHALL BE VISIBLE IN THE OPEN POSITION. MAKE SHALL BE SQUARE D OR
EQUAL.
23. MANUAL MOTOR STARTERS AND MOTOR RATED SWITCHES SHALL BE 277
VOLT, 30 AMPERE RATED, IN A NEMA 1 ENCLOSURE WITH A H-O-A SELECTOR
SWITCH AND A RELAY FOR REMOTE CONTROL OF THE EQUIPMENT IN THE
AUTO MODE. PROVIDE OVERLOADS AS REQUIRED. MAKE SHALL BE SQUARE
D CLASS 2510 OR EQUAL.
24. PROVIDE FIRE STOPPING FOR ALL PENETRATIONS THROUGH FLOORS, WALLS
AND ALL OTHER RELATED ASSEMBLIES. PROVIDE FIRE STOPPING SYSTEMS
IN ACCORDANCE WITH ASTM E814.
ELECTRICAL GENERAL NOTES
A. GENERAL NOTES APPLY TO ALL ELECTRICAL DRAWINGS.
B. PROVIDE UPDATED TYPE WRITTEN PANELBOARD SCHEDULES FOR ALL
PANELS USED IN THIS PROJECT.
C. REFER TO CORNELL STANDARD 260526 GROUNDING AND DETAILS
2.3.1 - 2.3.6.
D. PROVIDE BLANK COVERPLATES ON ALL EXISTING AND NEW UNUSED
OUTLET BOXES.
E. COORDINATE ALL CONDUIT RUNS WITH OTHER TRADES PRIOR TO
ROUGH-IN. RELOCATE ANY CONDUITS AS NECESSARY TO PERMIT
INSTALLATION OF DUCTWORK, PIPING OR ANY SUPPORTS.
F. PROVIDE CUTTING, PATCHING TO MATCH, AND FIRE SEAL AS REQUIRED
WHERE EXISTING COMMUNICATION OR ELECTRICAL WORK HAS BEEN
REMOVED AND WHERE NEW WORK IS INSTALLED. COORDINATE WITH
GENERAL CONTRACTOR.
G. REFER TO ATTACHEMENT 4 - NYSEG PAD MOUNTED TRANSFORMER
FOR TRANSFORMER PAD, METERING, AND TRANSFORMER
LOCATION/SET BACK REQUIREMENTS.
H. NOT USED.
I. COORDINATE MOUNTING HEIGHTS OF DEVICES WITH ARCHITECTURAL
ELEVATIONS AND OWNER PRIOR TO ROUGH-IN.
J. REFER TO ARCHITECTURAL PLANS FOR PHASING.
ALL WORK AND MATERIALS SHALL CONFORM TO AND BE INSTALLED,
INSPECTED AND TESTED IN ACCORDANCE WITH THE GOVERNING RULES AND
ALL REGULATIONS OF FEDERAL, STATE AND LOCAL GOVERNMENTAL
AGENCIES.
EACH CONTRACTOR SHALL HOLD A LICENSE AND/OR CERTIFICATION TO
PERFORM THE WORK REQUIRED WITHIN THE CONTRACT DOCUMENTS. COPIES OF
CURRENT LICENSE AND/OR CERTIFICATION SHALL BE SUBMITTED TO ENGINEER
AND OWNER’S REPRESENTATIVE FOR APPROVAL PRIOR TO START OF WORK.
APPLY AND INSTALL MATERIALS, EQUIPMENT, AND SPECIALTIES IN
ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. CONFLICTS
BETWEEN THE MANUFACTURER'S INSTRUCTIONS AND THE CONTRACT DOCUMENTS
SHALL BE REFERRED TO THE ENGINEER AND OWNER'S REPRESENTATIVE FOR
RESOLUTION.
ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. ALL
METHODS OF CONSTRUCTION, DETAILS OF WORKMANSHIP, THAT ARE NOT
SPECIFICALLY DESCRIBED OR INDICATED IN THE CONTRACT DOCUMENTS,
SHALL BE SUBJECT TO THE CONTROL AND APPROVAL OF THE ENGINEER AND
OWNER'S REPRESENTATIVE. EQUIPMENT AND MATERIALS SHALL BE OF THE
QUALITY AND MANUFACTURE INDICATED. THE EQUIPMENT SPECIFIED IS BASED
UPON THE ACCEPTABLE MANUFACTURERS LISTED. WHERE "APPROVED EQUAL" IS
STATED, EQUIPMENT SHALL BE EQUIVALENT IN EVERY WAY TO THE EQUIPMENT
SPECIFIED AND WILL BE ALLOWED SUBJECT TO APPROVAL.
MATERIALS SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS AND A
SMOKE DEVELOPED RATING OF 50 OR LESS, IN ACCORDANCE WITH NFPA 255.
EQUIPMENT SHALL BEAR THE UNDERWRITER'S LABORATORIES (UL), OR OTHER
APPROVED AGENCY-LISTING/LABEL. THIS LISTING REQUIREMENT APPLIES TO
THE ENTIRE ASSEMBLY. ANY MODIFICATIONS TO EQUIPMENT TO SUIT THE INTENT
OF THE SPECIFICATIONS SHALL BE PERFORMED IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE AND LISTED BY U.L. POTABLE WATER SYSTEMS AND
EQUIPMENT SHALL BE BUILT ACCORDING TO AWWA STANDARDS. GAS-FIRED
EQUIPMENT AND SYSTEM SHALL MEET AGA REGULATIONS AND SHALL HAVE AGA
LABEL. ALL MATERIALS, UNLESS OTHERWISE SPECIFIED, SHALL BE NEW AND BE
THE STANDARD PRODUCTS OF THE MANUFACTURER. USED EQUIPMENT OR
DAMAGED MATERIAL WILL BE REJECTED. CATALOG NUMBERS ARE SOMETIMES
LISTED IN THE SPECIFICATIONS TO AID SELECTION OF THE EQUIPMENT AND ARE
FOR REFERENCE ONLY. ALL EQUIPMENT MUST MEET THE WRITTEN DESCRIPTION
OF THE SPECIFICATION, INCLUDING ALL REQUIRED ACCESSORIES, POWER
SUPPLIES, HARDWARE, ETC., REGARDLESS OF THE LISTED CATALOG NUMBER.
ERRORS IN THE CATALOG NUMBER DO NOT ALLEVIATE THE RESPONSIBILITY OF
PROVIDING THE PROPER EQUIPMENT REQUIRED FOR THE INSTALLATION AND
FIELD CONDITIONS. THE MATERIALS, PRODUCTS AND EQUIPMENT DESCRIBED IN
THE CONTRACT DOCUMENTS ESTABLISH A STANDARD OF QUALITY, FUNCTION,
DIMENSIONS AND APPEARANCE THAT MUST BE MET BY ANY PROPOSED
SUBSTITUTION.
EACH CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR CONSTRUCTION
SAFETY AT ALL TIMES AND PROVIDE, AS PART OF CONTRACT, ALL TRENCH OR
BUILDING SHORING, SCAFFOLDING, SHIELDING, DUST/FUME PROTECTION,
MECHANICAL/ELECTRICAL PROTECTION, SPECIAL GROUNDING, SAFETY
RAILINGS, BARRIERS, AND OTHER SAFETY FEATURE REQUIRED TO PROVIDE
SAFE CONDITIONS FOR ALL WORKMEN AND SITE VISITORS.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO KEEP CLEAN ALL EQUIPMENT AND
PLUMBING FIXTURES PROVIDED UNDER THIS CONTRACT FOR THE DURATION OF
THE PROJECT. EACH TRADE SHALL KEEP THE PREMISES FREE FROM AN
ACCUMULATION OF WASTE MATERIAL OR RUBBISH CAUSED BY THEIR
OPERATIONS. IN FACILITIES REQUIRING AN ENVIRONMENT OF EXTREME
CLEANLINESS, AND IT IS THE CONTRACTOR'S RESPONSIBILITY TO ADHERE TO
THE STRICT REGULATIONS REGARDING PROCEDURES ON THE EXISTING
PREMISES. AFTER ALL TESTS ARE MADE AND INSTALLATIONS COMPLETED
SATISFACTORILY. THOROUGHLY CLEAN ENTIRE INSTALLATION, BOTH EXPOSED
SURFACES AND INTERIORS. REMOVE ALL DEBRIS CAUSED BY WORK. REMOVE
TOOLS, SURPLUS, MATERIALS, WHEN WORK IS FINALLY ACCEPTED.
ALL FINISHED EQUIPMENT SURFACES DAMAGED DURING CONSTRUCTION SHALL
BE BROUGHT TO "AS NEW" CONDITION BY TOUCH UP OR REPAINTING. ANY RUST
SHALL BE REMOVED AND PRIMED PRIOR TO REPAINTING. TAKE ALL
NECESSARY PRECAUTIONS WITH EQUIPMENT, SYSTEMS AND BUILDING TO
PREVENT DAMAGE DUE TO FREEZING AND/OR WATER DAMAGE. REPAIR OR
REPLACE, AT NO CHANGE IN CONTRACT, ANY SUCH DAMAGE TO EQUIPMENT,
SYSTEMS AND BUILDING. PERFORM FIRST SEASONS WINTERIZING IN PRESENCE
OF OWNER'S OPERATING STAFF.
ALL PIPING AND FITTINGS USED ON THIS PROJECT SHALL BE NEW AND MARKED
WITH MANUFACTURER'S NAME AND SHALL COMPLY WITH ALL APPLICABLE ASTM
AND ANSI STANDARDS. ALL PIPING SHALL BE LABELED AND INSULATED AS
NOTED.
NO PLUMBING EQUIPMENT SHALL BE HIDDEN OR COVERED UP PRIOR TO
INSPECTION BY THE ENGINEER AND OWNER'S REPRESENTATIVE. ALL WORK THAT
IS DETERMINED TO BE UNSATISFACTORY SHALL BE CORRECTED IMMEDIATELY
AT NO ADDITIONAL COST. CONCEAL ALL CONTRACT WORK ABOVE CEILINGS
AND IN WALLS, BELOW SLABS, AND ELSEWHERE THROUGHOUT BUILDING. IF
CONCEALMENT IS IMPOSSIBLE OR IMPRACTICAL, NOTIFY ENGINEER AND
OWNER'S REPRESENTATIVE BEFORE STARTING THAT PART OF THE WORK AND
INSTALL ONLY AFTER THEIR APPROVAL. IN AREAS WITH NO CEILINGS, INSTALL
ONLY AFTER ENGINEER AND OWNER'S REPRESENTATIVE REVIEWS AND
COMMENTS ON ARRANGEMENT AND APPEARANCE.
BEFORE ACCEPTANCE OF THE WORK, FURNISH NECESSARY SKILLED LABOR TO
OPERATE ALL SYSTEMS BY SEASONS. INSTRUCT THE OWNER'S DESIGNATED
PERSONNEL ON THE PROPER OPERATION AND MAINTENANCE OF SYSTEMS AND
EQUIPMENT. OBTAIN WRITTEN ACKNOWLEDGMENT FROM PERSON INSTRUCTED
PRIOR TO ACCEPTANCE REPEAT THE INSTRUCTIONS IF ASKED TO DO SO.
CONTRACTOR IS FULLY RESPONSIBLE FOR SYSTEMS UNTIL ACCEPTANCE, EVEN
THOUGH OPERATED BY OWNER'S PERSONNEL, UNLESS OTHERWISE AGREED IN
WRITING. PROVIDE OPERATING, MAINTENANCE AND STARTING PRECAUTIONS
AND PROCEDURES TO BE FOLLOWED BY THE OWNER FOR OPERATING
SYSTEMS AND EQUIPMENT. MOUNT THE INSTRUCTION IN CLEAR PLASTIC HOLDER
ON OR ADJACENT TO THE EQUIPMENT.
FIRE-STOPPING FOR OPENINGS THROUGH FIRE AND SMOKE RATED WALL AND
FLOOR ASSEMBLIES: PROVIDE MATERIALS AND PRODUCTS LISTED OR
CLASSIFIED BY AN APPROVED INDEPENDENT TESTING LABORATORY FOR
"THROUGH-PENETRATION FIRE-STOP SYSTEMS." THE SYSTEM SHALL MEET THE
REQUIREMENTS OF "FIRE TESTS OF "THROUGH-PENETRATION FIRE-STOPS"
DESIGNATED ASTM E814. PROVIDE FIRE-STOP SYSTEM SEALS AT ALL
LOCATIONS WHERE PIPING, TUBING, CONDUIT, ELECTRICAL
BUSWAYS/CABLES/WIRES, DUCTWORK AND SIMILAR UTILITIES PASS THROUGH OR
PENETRATE FIRE RATED WALL OR FLOOR ASSEMBLY. PROVIDE FIRE-STOP
SEAL BETWEEN SLEEVE AND WALL FOR DRYWALL CONSTRUCTION. THE MINIMUM
REQUIRED FIRE RESISTANCE RATINGS OF THE WALL OR FLOOR ASSEMBLY
SHALL BE MAINTAINED BY THE FIRE-STOP SYSTEM. THE INSTALLATION SHALL
PROVIDE AN AIR AND WATERTIGHT SEAL. THE METHODS USED SHALL
INCORPORATE QUALITIES, WHICH PERMIT THE EASY REMOVAL OR ADDITION OF
ELECTRICAL CONDUITS OR CABLES WITHOUT DRILLING OR USE OF SPECIAL
TOOLS. THE PRODUCT SHALL ADHERE TO ITSELF TO ALLOW REPAIRS TO BE
MADE WITH THE SAME MATERIAL AND PERMIT THE VIBRATION, EXPANSION
AND/OR CONTRACTION OF ANY ITEMS PASSING THROUGH THE PENETRATION
WITHOUT CRACKING, CRUMBLING AND RESULTING REDUCTION IN FIRE RATING.
PROVIDE ALL REQUIRED SUPPORTS, BEAMS, ANGLES, HANGERS, RODS,
BASES, BRACES, AND OTHER ITEMS TO PROPERLY SUPPORT CONTRACT
WORK. SUPPORTS SHALL MEET THE APPROVAL OF THE ENGINEER AND
OWNER'S REPRESENTATIVE. MODIFY STUDS, ADD STUDS, ADD FRAMING, OR
OTHERWISE REINFORCE STUDS IN METAL STUD WALLS AND PARTITIONS AS
REQUIRED TO SUIT CONTRACT WORK. IF NECESSARY, IN STUD WALLS, PROVIDE
SPECIAL SUPPORTS FROM FLOOR TO STRUCTURE ABOVE. FOR PRECAST
PANELS/PLANKS AND METAL DECKS, SUPPORT MECHANICAL/ELECTRICAL
WORK AS DETERMINED BY MANUFACTURER, ENGINEER, AND OWNER'S
REPRESENTATIVE. PROVIDE HEAVY GAUGE STEEL MOUNTING PLATES FOR
MOUNTING CONTRACT WORK. MOUNTING PLATES SHALL SPAN TWO OR MORE
STUDS. SIZE, GAUGE, AND STRENGTH OF MOUNTING PLATES SHALL BE
SUFFICIENT FOR EQUIPMENT SIZE, WEIGHT, AND DESIRED RIGIDITY.
PIPING SHALL NOT BE SUPPORTED BY WIRES, BAND IRON, CHAINS, OR FROM
OTHER PIPING OR DUCT WORK, NOR BY VERTICAL EXPANSION BOLTS.
SUPPORT PIPING WITH INDIVIDUAL HANGERS FROM CONCRETE INSERTS,
WELDED SUPPORTS, OR BEAM CLAMPS OF PROPER CONFIGURATION AND
LOADING DESIGN REQUIREMENTS FOR EACH LOCATION; REPLACE IF NOT
SUITABLE. FOLLOW MANUFACTURER'S SAFE LOADING RECOMMENDATIONS.
SUSPEND WITH RODS OF SUFFICIENT LENGTH FOR SWING, USING PROPER
DIAMETER ROD FOR PIPE SIZE. PROVIDE ADDITIONAL STRUCTURAL STEEL
MEMBERS, HAVING ONE COAT RUSTPROOF PAINT, WHERE REQUIRED FOR
PROPER SUPPORT. PROVIDE OVERSIZED HANGERS WHERE
INSULATION/SUPPORTS MUST PASS BETWEEN PIPE AND HANGER. PROVIDE
CONTINUOUS SUPPORT OR EXTRA SUPPORTS FOR PLASTIC PIPE PER
MANUFACTURER'S REQUIREMENTS. HANGERS, WHEN ATTACHED TO JOISTS,
SHALL ONLY BE PLACED AT THE TOP OR BOTTOM CHORD PANEL POINT. ONLY
CONCENTRIC TYPE HANGERS ARE PERMISSIBLE; "C" TYPE NOT PERMITTED ON
JOISTS. PROVIDE RISER CLAMPS FOR EACH RISER AT EACH FLOOR. USE
TRAPEZE HANGERS WHERE A GROUP OF PIPING CAN BE INSTALLED.
PROVIDE COMPLETE PLUMBING CONNECTIONS TO ALL PLUMBING EQUIPMENT.
PROVIDE CONTROL CONNECTIONS TO EQUIPMENT WHERE INDICATED ON THE
DRAWINGS. PROVIDE VALVES ON PIPING AHEAD OF EACH PIECE OF
EQUIPMENT. PROVIDE ALL PIPING, TRIM, ACCESSORIES AND CONNECTIONS AS
REQUIRED FOR PROPER EQUIPMENT OPERATION OF EQUIPMENT PROVIDED BY
THIS CONTRACT, OWNER-FURNISHED EQUIPMENT AND EQUIPMENT FURNISHED BY
OTHER CONTRACTS. REFER TO MANUFACTURER'S DRAWINGS/SPECIFICATIONS
FOR REQUIREMENTS OF SPECIAL EQUIPMENT. VERIFY CONNECTION
REQUIREMENTS BEFORE BIDDING AND CONFIRM PRIOR TO ROUGHING.
PROVIDE ALL EXCAVATION AND BACKFILL, ROCK AND DEBRIS REMOVAL AND
RELATED WORK REQUIRED FOR ALL PLUMBING WORK.
TRENCH EXCAVATION: BY OPEN CUT, TO PROPER DEPTH AND GRADE NO
WIDER THAN REQUIRED FOR PLACEMENT OF WORK AND NOT MORE THAN 50
FT. IN ADVANCE OF UTILITY BEING INSTALLED. SHOULD TRENCH BOTTOM BE
WET, UNSTABLE, AND/OR OTHERWISE INCAPABLE OF SUPPORTING THE
CONTRACT WORK, IMMEDIATELY REPORT SAME TO OWNER'S REPRESENTATIVE.
SHOULD IT BE DEEMED UNSUITABLE, EXCAVATE TO DEPTH AS DIRECTED AND
BACKFILL WITH GRAVEL TO TRENCH DEPTH, OR PROVIDE CONCRETE
CRADLING. IN ADDITION TO GOVERNING CODES, PROTECT SIDES OF
EXCAVATIONS WITH SHEETING AND BRACING WHERE NECESSARY TO PREVENT
SLIDING OR CAVING OF BANKS AND TO PROTECT ADJACENT STRUCTURES.
REMOVE AS BACKFILL IS PLACED. PROVIDE AT LOCATIONS ADJACENT TO
EXISTING MANHOLES, HYDRANTS, AND SIMILAR ITEMS.
CUSHION AND BEDDING SAND: CLEAN, COARSE, FREE OF ORGANIC MATTER,
CONFORMING TO NEW YORK SATE DOT ITEM NO. 703-06. CRUSHED STONE:
CRUSHED STONE, GRADED, FREE OF ORGANIC MATERIALS, NO. 1 TO NO. 4
SIZE. CONFORMING TO NEW YORK STATE DOT ITEM NO. 703-0201. GRAVEL
FILL: WELL-GRADED NATURAL INORGANIC SAND AND GRAVEL CONFORMING
TO NEW YORK STATE DOT ITEM NO. 703-0202.
BEDDING: PROVIDE AROUND ALL PIPING WITH COARSE SAND FROM 6 IN.
BELOW TO 8 IN. ABOVE. APPLY BY HAND AND COMPACT UNDER AND AT
SIDES BY MECHANICAL MEANS. PIPING, JACKETS AND SAND BED MUST BE
INSPECTED AND TESTED PRIOR TO BACKFILL OF ANY NATURE. PROVIDE
NECESSARY ANCHORS, THRUST BLOCKS, FOR TESTING. FILL REMAINDER OF
TRENCH IN 12 IN. LAYERS, USE ORDINARY FILL MATERIAL, EXCEPT AS
OTHERWISE SPECIFIED. DO NOT USE FROZEN MATERIAL. REMOVE BOULDERS,
STONES, BROKEN ROCK, WOOD, BRICKS, BLOCKS, AND DEBRIS FROM FILL
MATERIAL BEFORE BACKFILL OPERATION. PROVIDE FINAL COMPACTION FOR
ALL TRENCHES BY MECHANICAL MEANS. USE MECHANICAL TAMPING
MACHINERY.
ORDINARY FILL: WELL-GRADED, NATURAL SOIL, MEETING THE FOLLOWING
REQUIREMENTS. FREE OF ORGANIC AND OTHER COMPRESSIBLE MATERIALS,
DEBRIS AND FROZEN MATERIALS, AND OF STONES LARGER THAN 4 IN.
MAXIMUM DIMENSION. BE OF SUCH NATURE AND CHARACTER THAT IT CAN BE
COMPACTED TO THE SPECIFIED DENSITIES. FREE OF ANY CLAY, HIGHLY
PLASTIC CLAYS, OF MATERIALS SUBJECT TO DECAY, DECOMPOSITION, OR
DISSOLUTION, AND OF CINDERS, ASH AND OTHER CORROSIVE MATERIALS.
FREE OF WOOD, STUMPS, ROOTS, ETC. MAXIMUM DRY DENSITY OF NOT LESS
THAN 115 LBS. PER CU. FT. MATERIAL FROM EXCAVATION ON THE SITE MAY BE
USED AS ORDINARY FILL IF IT MEETS THE ABOVE REQUIREMENTS.
BUILD LINES TO GRADE AND ELEVATIONS SHOWN. PROVIDE STAKES, GRADE
BOARDS, CLEATS, NAILS, INSTRUMENTS. LOCATE AND STAKE EACH NEW RUN
FOR ITS ENTIRE LENGTH. VERIFY ELEVATIONS GIVEN. START EACH
EXCAVATION AT LOW POINT. NOTIFY ENGINEER OF ELEVATION
DISCREPANCIES. PROTECT MARKS AND STATIONS. BEFORE STARTING
EXCAVATING WORK, COORDINATE WITH OWNER'S SITE REPRESENTATIVE AND
FURNISH SCHEDULE OF OPERATIONS TO OWNER. REMOVE MATERIALS
INCLUDING MASONRY WORK, RUBBLE, EARTH, BRICKWORK, CONCRETE, SAND,
DEBRIS, ABANDONED PIPE LINES, DRAINS AND SEWERS, ROCKS, BOULDERS,
AND CONCRETE, ALL OF WHICH IS CONSIDERED "EARTH EXCAVATION."
PROVIDE FOR LEGAL DISPOSITION OF EXCESS EXCAVATED MATERIALS. MAKE
ALLOWANCE FOR GRAVEL FILL, SAND BASES, THRUST BLOCKS, SHEET PIPING,
DRAINAGE PUMPS, AND WORK SPACE. START EXCAVATION AT ROUGH GRADE
AND PROVIDE FORM WORK AND SHEET PILING WHERE REQUIRED.
NATURAL GAS PIPING SHALL BE SCHEDULE 40 BLACK STEEL, WELDED
CONNECTIONS AND FITTINGS FOR PIPE SIZES LARGER THAN 21/2'', THREADED
AND SCREWED FITTINGS FOR PIPE SIZES 2'' AND SMALLER (USE TEFLON TAPE
FOR ALL THREADED CONNECTIONS). UNDERGROUND NATURAL GAS PIPING
SHALL BE SDR11 POLYETHYLENE TUBING WITH FUSION WELDED JOINTS AND
FITTINGS. TUBING SHALL BE VISIBLY MARKED FOR USE IN BURIED NATURAL
GAS SYSTEMS AND CONTAIN LOCATING WIRING. PROVIDE ALL NATURAL GAS
SYSTEMS IN COMPLIANCE WITH 2015 INTERNATIONAL FUEL GAS CODE AND
NYSEG REQUIREMENTS.
ACCURATELY ESTABLISH GRADE AND ELEVATION OF PIPING BEFORE SETTING
SLEEVES. INSTALL PIPING WITHOUT SPRINGING OR FORCING (EXCEPT WHERE
SPECIFICALLY CALLED FOR), MAKING PROPER ALLOWANCE FOR EXPANSION
AND ANCHORING. ARRANGE PIPING AT EQUIPMENT WITH NECESSARY OFFSETS,
UNIONS, FLANGES, AND VALVES, TO ALLOW FOR EASY PART REMOVAL AND
MAINTENANCE. OFFSET PIPING AND CHANGE ELEVATION AS REQUIRED TO
COORDINATE WITH OTHER WORK. AVOID CONTACT WITH OTHER MECHANICAL
OR ELECTRICAL SYSTEMS. PROVIDE ADEQUATE MEANS OF DRAINING AND
VENTING UNITS, RISERS, CIRCUITS AND SYSTEMS. CONCEAL PIPING UNLESS
OTHERWISE CALLED FOR. REAM PIPES AFTER CUTTING AND CLEAN BEFORE
INSTALLING. CAP OR PLUG EQUIPMENT AND PIPE OPENINGS DURING
CONSTRUCTION. INSTALL PIPING PARALLEL WITH LINES OF BUILDING,
PROPERLY SPACED TO PROVIDE CLEARANCE FOR INSULATION. MAKE
CHANGES IN DIRECTION AND BRANCH CONNECTIONS WITH FITTINGS. DO NOT
INSTALL VALVES, UNIONS AND FLANGES IN INACCESSIBLE LOCATIONS.
MATERIALS WITHIN A SYSTEM AND BETWEEN SYSTEMS SHALL BE CONSISTENT.
IF THIS IS NOT POSSIBLE, INSTALL DIELECTRIC FITTINGS.
PROVIDE ALL HANGERS AND SUPPORTS FOR PIPING IN ACCORDANCE WITH
THE 2015 INTERNATIONAL PLUMBING CODE.
NATURAL GAS VALVES: BRONZE BODY, SCREWED ENDS, AGA APPROVED AND
UL LISTED. MILWAUKEE BB2-100.
LABEL ALL PLUMBING PIPING ON PROJECT WITH ACRYLIC WRAP-AROUND
LABELS WITH FLOW ARROWS. LABEL PIPING EVERY 20'-0'' O.C. AND ON BOTH
SIDES OF WALL AND FLOOR PENETRATIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
PLUMBING SPECIFICATIONS
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
PLUMBING CONTRACTOR SHALL REQUEST A COMPLETE SET OF BID
DOCUMENTS (DRAWINGS AND SPECIFICATIONS) INCLUDING BUT NOT LIMITED
TO, ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, CIVIL, FIRE
PROTECTION, ETC. FOR BIDDING AND COORDINATION PURPOSES.
INCLUDE IN PLUMBING BID ALL LABOR, MATERIALS, TOOLS, PLANT,
TRANSPORTATION, EXCAVATION, EQUIPMENT, INSURANCE, TEMPORARY
PROTECTION, PERMITS, INSPECTIONS, TAXES AND ALL NECESSARY AND
RELATED ITEMS REQUIRED TO PROVIDE COMPLETE AND OPERATIONAL
PLUMBING SYSTEMS SHOWN AND DESCRIBED. PROVIDE ALL SCAFFOLDING,
RIGGING, HOISTING AND SERVICES NECESSARY FOR ERECTION AND
DELIVERY OF EQUIPMENT AND APPARATUS FURNISHED INTO THE PREMISES.
THESE ITEMS SHALL BE REMOVED FROM PREMISES WHEN NO LONGER
REQUIRED.
REFERENCES TO CODES AND STANDARDS CALLED FOR IN THE CONTRACT
DOCUMENTS MEAN THE LATEST EDITION, AMENDMENT AND REVISIONS TO
THE CODES AND STANDARDS IN EFFECT ON THE DATE OF THESE
CONTRACT DOCUMENTS, UNLESS OTHERWISE NOTED.
THE DRAWINGS ARE DIAGRAMMATIC. DRAWINGS SHOW APPROXIMATE
LOCATIONS OF EQUIPMENT, AND FIXTURES. COORDINATE ALL PLUMBING
AND SYSTEMS, EQUIPMENT, AND MATERIALS INSTALLATION WITH ALL OTHER
BUILDING COMPONENTS. THE PLUMBING CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY CHANGES IN OPENINGS AND LOCATIONS
NECESSITATED BY THE EQUIPMENT INSTALLED. THE ARCHITECTURAL
DRAWINGS SHALL INDICATE THE PLACEMENT OF ALL WALL AND CEILING
MOUNTED PLUMBING EQUIPMENT AND DEVICES IN ALL ROOMS WITH THE
EXCEPTION OF MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS. EXACT
LOCATIONS ARE SUBJECT TO THE APPROVAL OF THE ENGINEER AND
OWNER'S REPRESENTATIVE.
DUE TO THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO
INDICATE ALL OFFSETS, FITTINGS, CHANGES IN ELEVATION, ETC. VERIFY
FINAL LOCATIONS FOR ROUGH-INS WITH FIELD MEASUREMENTS AND WITH
THE EQUIPMENT BEING CONNECTED. VERIFY EXACT LOCATION AND
ELEVATIONS AT WORK SITE PRIOR TO ANY ROUGH IN WORK. DO NOT
SCALE PLANS. IF FIELD CONDITIONS, DETAILS, CHANGES IN EQUIPMENT OR
SUBMITTAL INFORMATION REQUIRE A SIGNIFICANT CHANGE TO THE
ORIGINAL DOCUMENTS, CONTACT THE ENGINEER AND OWNER'S
REPRESENTATIVE FOR APPROVAL BEFORE PROCEEDING. COORDINATE
WORK WITH OTHER TRADES AND DETERMINE EXACT ROUTING OF ALL
DUCT, PIPE, CONDUIT, ETC., BEFORE FABRICATION AND INSTALLATION.
ARRANGE FOR ALL CHASES, SLOTS AND OPENINGS IN OTHER BUILDING
COMPONENTS THAT ARE NOT INDICATED ON DRAWINGS, TO ALLOW FOR
PLUMBING INSTALLATIONS. COORDINATE WITH ARCHITECTURAL DRAWINGS.
VERIFY WITH ENGINEER AND OWNER'S REPRESENTATIVE EXACT LOCATION
OF ALL EQUIPMENT IN FINISHED AREAS, SUCH AS THERMOSTATS, FIXTURE
AND SWITCH MOUNTING HEIGHTS, AND EQUIPMENT MOUNTING HEIGHTS.
PROVIDE ALL NECESSARY PIPING, CONNECTIONS, ACCESSORIES,
SUPPORTS, HANGERS, ANCHORS, WIRING AND CONTROLS FOR COMPLETE
AND FUNCTIONAL INSTALLATION OF ALL THE ITEMS PROVIDED UNDER THIS
CONTRACT.
PROVIDE ALL REQUIRED EXCAVATION, BACKFILL AND COMPACTION FOR
UNDERGROUND WORK.
SLEEVE ALL PENETRATIONS THROUGH OUTSIDE OR FOUNDATION WALLS
WATERTIGHT.
FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. REFER
TO ARCHITECTURAL DRAWINGS FOR LOCATIONS AND RATING OF ALL FIRE
RATED ASSEMBLIES.
FIELD VERIFY EXACT LOCATION, COMPOSITION AND CONDITION OF ALL
SITE PIPING, VALVES AND SYSTEMS AS REQUIRED FOR WORK OF THE
CONTRACT.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
PLUMBING GENERAL NOTES
Revision Schedule
NO. DESC. DATE
1 PANEL SCHEDULE 2/4/2020
2 EP1 SCHEDULE 2/6/2020
3 OWNER REQUESTED
CHANGES
2/24/2020
4 UTILITY ADDITIONS 8/20/2020
TOTAL EST. DEMAND: 0 A
TOTAL CONN.: 0 A
TOTAL EST. DEMAND: 0 VA
TOTAL CONN. LOAD: 0 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 112667 A 112667 A 112667 A
TOTAL LOAD: 13520000... 13520000 VA 13520000...
11 SPACE -- -- 0 0 -- -- SPACE 12
9 SPACE -- -- 0 0 -- -- SPACE 10
7 SPACE -- -- 0 0 -- -- SPACE 8
5 0 13520 6
3 0 13520 4
LVP1 200 A 3
0 13520
3 100 A ATS-1
CKT CIRCUIT DESCRIPTION TRIP POLES A (kVA) B (kVA) C (kVA) POLES TRIP CIRCUIT DESCRIPTION CKT
NOTES: PANELBOARD IS EXISTING. PROVIDE (1) NEW 100A/3P CIRCUIT BREAKER TO MATCH PANEL CONSTRUCTION.
MDP EAST GREENHOUSE 1 400 A 3Ø, 4W 120/208 WYE SURFACE 25kA I-LINE TYPE 1
MCB MLO
NAME LOCATION SOURCE
RATING (AMPS)
PHASE/WIRE VOLTAGE MOUNTING KAIC DESIGN MAKE NEMA TYPE
HINGED TRIM 200% NEUTRAL SUB-FEED LUGS SPD SIZE:PANELBOARD SCHEDULE SE RATED SUB-FEED BREAKER FEED-THRU LUGS INTEGRAL SPD
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION LUMENS LAMP VOLTAGE
DESIGN MAKE ACCEPTABLE
MANUFACTURERMANUFACTURER MODEL NO.
EM1 WALL MOUNTED, LED, TWO-HEAD EMERGENCY BATTERY PACK WITH SELF DIAGNOSTICS AND TESTING. SUITABLE
FOR DAMP LOCATIONS.
650 EACH HEAD (2) 6 WATT LED EA 120 ISOLITE LIGHTING BUG6W WH MTB SD APPROVED EQUAL
X1 SINGLE FACED UNIVERSAL MOUNT LED EXIT SIGN WITH WHITE THERMOPLASTIC HOUSING, RED LETTERS, AND
REMOVABLE CHEVRONS
- 2.76 WATT LED 120 ISOLITE LIGHTING RL-AC-R-U-WH-MTEBP APPROVED EQUAL
X2 SINGLE FACED UNIVERSAL MOUNT LED EXIT SIGN AND EMERGENCY BATTERY PACK COMBINATION UNIT WITH WHITE
HOUSING, RED LETTERS, REMOVABLE CHEVRONS, AND NI-CAD BATTERY AND SELF DIAGNOSICS
125 EACH HEAD 2.76 WATT LED 120 ISOLITE LIGHTING RLC-LED-R-U-WH-MTEB APPROVED EQUAL
KM2
Text Box
AS-BUILTS
ChrisM.Wilson Typewritten Text 5 USDA Notes on As-Builts 09/24/2020 (CMW/EPM)