This Scope of Work document outlines professional services for the Iowa Department of Public Defense to replace seven existing Lennox rooftop units (RTUs) at the Spencer Readiness Center located at 11 East 23rd Street, Spencer, Iowa. The project requires replacement of the seven RTUs with Lennox Enlight RTUs equipped with factory-installed options including a High Performance Economizer with single enthalpy, multi-speed ECM direct drive supply fan, built-in BACnet IP and MS/TP protocols, R-454B refrigerant, barometric relief damper, low NOx system, combination coil/hail guards, hinged access doors, environ evaporator and condenser coil system, and 2-inch MERV8 PLE filter with condensate switch. The scope additionally requires replacement of existing thermostats with Honeywell TH8321WF VisionPRO 8000 Smart Thermostats, modification of low and high voltage wiring as needed, comprehensive gas line work including replacement of existing unions and ball valves, and roofing work encompassing roof curb adapters, high wind hold-down brackets, and sealing or repairs to penetrations resulting from installation. A mandatory site visit is scheduled for June 30 at 10:00 a.m., with bids due July 8, 2026. All questions regarding the scope must be addressed during the mandatory site visit, and an RSVP is required to philip.payton@dpd.iowa.gov and koby.w.higgins.nfg@army.mil.
Bids will be submitted as a lump sum total via the IMPACS system, and there will not be a public bid opening. All roofing materials must be compatible with DuroLast Inc. roofing systems, and the contractor should contact CenMark Roofing (Zac Franke at 402-650-0633) regarding roofing requirements. The RTUs should be equipped without an additional fused disconnect if possible; if necessary, RTUs must be ordered without the non-fused disconnect to accommodate installation requirements. The issuing officer is Philip Payton, who can be reached at 515-975-6211 or philip.payton@dpd.iowa.gov.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Site Plan.png | PNG image | |
| SOW.pdf | ||
| 1396341-event.pdf | ||
| Spencer_RC_RTU_replacement_site_plan (1).png | PNG image |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Replace 7 exis�ng Lennox RTU's with Lennox Enlight RTU's with the following factory installed op�ons:
High Performance Economizer Factory Installed Single Enthalpy High Performance Economizer Direct Drive Supply Fan: Mul�-Speed ECM Direct Drive Built-in BACnet IP and MS/TP (standard) Refrigerant R-454B Barometric Relief Damper Factory Installed Low Nox Factory Installed Combina�on Coil/Hail Guards Factory Installed Hinged Access Doors Factory Installed Environ Evaporator and Condenser Coil System Factory Installed 2" MERV8 - PLE Filter Factory Installed and condensate switch
Exis�ng low and high voltage:
- replace exis�ng tstats with Honeywell TH8321WF VisionPRO 8000 Smart Thermostats
- low voltage wiring to be replaced from RTU to T-stat if insufficient for opera�on
- if line voltage wiring is sufficient, use otherwise include replacement breakers and wiring as needed
The Lennox Enlight is equipped with a non-fused disconnect, if possible, I do not want to have an addi�onal fused disconnect atached to the RTU. If there is no way around not having the fused disconnect on the RTU, the RTU needs to be ordered without the non-fused disconnect.
Gas:
- provide all materials needed to connect gas to replacement RTU to include replacing exis�ng union and ball valve.
Roofing:
- include roof curb adapters
- include high wind hold down brackets
- penetra�ons needing sealed or repairs needing made from installa�on should be compa�ble with Duro Last Inc. roofing systems.
- I have u�lized Cen�Mark Roofing in the past. Contact informa�on Zac Franke (402)-650-0633