This document is the project manual for the West Elementary Media Center renovation project undertaken by Kelloggsville Public Schools in Grand Rapids, Michigan. The project, identified as Project Number 12-194.45 and dated January 3, 2019, was designed by Tower Pinkster Titus Associates, Inc. The specifications cover Division 21 through 33 and include comprehensive requirements for HVAC systems, electrical systems, plumbing, fire protection, and building specialties. The project manual details mechanical, electrical, and structural specifications necessary for the renovation of the elementary school's media center, encompassing work related to heating, ventilating, air conditioning, insulation, control systems, and related building infrastructure. The specifications require adherence to Michigan Mechanical Code and applicable state and local codes, with all equipment to be UL or FM listed and labeled for their intended applications.
The specifications establish detailed requirements for HVAC insulation materials, control systems utilizing direct digital controls (DDC) and Building Management System (BMS) technology, and comprehensive testing and balancing procedures. The BMS contractor must have a local office within 75 miles of the job site and provide factory-trained engineers capable of 24-hour emergency service. All components are guaranteed against defects in materials and workmanship for one year from acceptance, with the contractor responsible for repair or replacement at no charge during the warranty period. The specifications require open, interoperable system architecture supporting LonWorks, BACnet, Modbus, and SNMP protocols, with unlimited point capacity and NAC expansion capability. Installation must comply with all applicable codes including NFPA 90A and 90B, with FCC Part 15 compliance required for all electronic equipment. The project specifications do not identify specific pricing, set-asides, or contract award dates within this manual section.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Tower Pinkster Titus Associates, Inc.
242 East Kalamazoo Avenue, Suite 200, Kalamazoo, MI 49007-5828
4 East Fulton Street, Suite 200, Grand Rapids, MI 49503
West Elementary Media Center
PROJECT MANUAL
January 3, 2019*
OWNER
KELLOGGSVILLE PUBLIC SCHOOLS
242 52nd Street Grand Rapids, Michigan 49548
PROJECT NUMBER
SET NUMBER
VOLUME NUMBER 2
Divisions 21 through 33
Architect’s Project No. 12-194.45
PROJECT NO. 12-194.45 0 - 1
KELLOGSVILLE PUBLIC SCHOOLS 01/03/2019
WEST ELEMENTARY MEDIA CENTER RENO.
© 2019 Tower Pinkster Titus Associates - All Rights Reserved
TABLE OF CONTENTS
Refer to Construction Manager’s Project Manual issued by Owen-Ames-Kimball Company for additional procurement, contracting, and general requirements.
VOLUME 1
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
CONTRACTING REQUIREMENTS
00 6323 CADD File Transfer Waiver 00 6324 BIM Transfer Waiver 00 6325 Substitution during Construction Request Form 00 7200 General Conditions 00 7300 Supplementary Conditions 00 7343 Wage Rate Requirements
DIVISION 01 - GENERAL REQUIREMENTS
01 2200 Unit Prices 01 2300 Alternates 01 2500 Substitution Procedures 01 2600 Contract Modification Procedures 01 2900 Payment Procedures 01 3100 Project Management and Coordination 01 3300 Submittal Procedures 01 4000 Quality Requirements 01 4200 References 01 6000 Product Requirements 01 7300 Execution 01 7700 Closeout Procedures 01 7823 Operation and Maintenance Data 01 7839 Project Record Documents 01 7900 Demonstration and Training
DIVISION 02 - EXISTING CONDITIONS
02 4119 Selective Demolition
DIVISION 03 – CONCRETE (Not Applicable)
DIVISION 04 - MASONRY
04 2000 Unit Masonry
DIVISION 05 - METALS
05 1200 Structural Steel Framing 05 2100 Steel Joist Framing
PROJECT NO. 12-194.45 0 - 2
05 3100 Steel Decking 05 4000 Cold-Formed Metal Framing 05 4400 Cold-Formed Metal Trusses 05 5000 Metal Fabrications
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 1000 Rough Carpentry 06 1600 Sheathing
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 2413 Polymer-Based Exterior Insulation and Finish System (EIFS) 07 4113.16 Standing-Seam Metal Roof Panels 07 7100 Roof Specialties 07 7253 Snow Guards 07 9200 Joint Sealants 07 9219 Acoustical Joint Sealants
DIVISION 08 - OPENINGS
08 1113 Hollow Metal Doors and Frames 08 1416 Flush Wood Doors 08 3113 Access Doors and Frames 08 7100 Door Hardware 08 8000 Glazing 08 8813 Fire-Resistant Glazing
DIVISION 09 - FINISHES
09 2216 Non-Structural Metal Framing 09 2900 Gypsum Board 09 5113 Acoustical Panel Ceilings 09 6513 Resilient Base and Accessories 09 6813 Tile Carpeting 09 9123 Interior Painting
DIVISION 10 - SPECIALTIES
10 4413 Fire Protection Cabinets 10 4416 Fire Extinguishers
DIVISION 11 – EQUIPMENT (Not Applicable)
DIVISION 12 - FURNISHINGS (Not Applicable)
DIVISION 13 - SPECIAL CONSTRUCTION (Not Applicable)
DIVISION 14 - CONVEYING EQUIPMENT (Not Applicable)
PROJECT NO. 12-194.45 0 - 3
VOLUME 2
DIVISION 21 - FIRE SUPPRESSION (Not Applicable)
DIVISION 22 – PLUMBING (Not Applicable)
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 0500 Common Work Results for HVAC 23 0513 Common Motor Requirements for HVAC Equipment 23 0519 Meters and Gages for HVAC Piping 23 0529 Hangers and Supports for HVAC Piping and Equipment 23 0553 Identification for HVAC Piping and Equipment 23 0593 Testing, Adjusting, and Balancing for HVAC 23 0700 HVAC Insulation 23 0900 Instrumentation and Control for HVAC 23 1123 Facility Natural Gas Piping 23 3113 Metal Ducts 23 3300 Air Duct Accessories 23 3600 Air Terminal Units 23 3713 Diffusers, Registers, and Grilles 23 7413 Packaged Outdoor Central-Station Air Handling Units
DIVISION 26 - ELECTRICAL
26 0500 Common Work Results for Electrical 26 0519 Low-Voltage Electrical Power Conductors and Cables 26 0526 Grounding and Bonding for Electrical Systems 26 0529 Hangers and Supports for Electrical Systems 26 0533 Raceways and Boxes for Electrical Systems 26 0553 Identification for Electrical Systems 26 0923 Lighting Control Devices 26 2200 Low Voltage Transformers 26 2416 Panelboards 26 2726 Wiring Devices 26 5100 Interior Lighting
DIVISION 27 - COMMUNICATIONS (Not Applicable)
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 3100 Fire Detection and Alarm
PROJECT NO. 12-194.45 0 - 4
DIVISION 31 – EARTHWORK (Not Applicable)
DIVISION 32 - EXTERIOR IMPROVEMENTS (Not Applicable)
DIVISION 33 – UTILITIES (Not Applicable)
END OF TABLE OF CONTENTS
TOILET, BATH, AND LAUNDRY ACCESSORIES
PROJECT NO. 12-194.45 10 2800 - 1
SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Public-use washroom accessories.
2. Warm-air dryers.
3. Underlavatory guards.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Product Schedule: Indicating types, quantities, sizes, and installation locations by room of each accessory required.
1. Identify locations using room designations indicated.
2. Identify accessories using designations indicated.
1.3 INFORMATIONAL SUBMITTALS
A. Sample warranty.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.5 WARRANTY
A. Manufacturer's Special Warranty for Mirrors: Manufacturer agrees to repair or replace mirrors that fail in materials or workmanship within specified warranty period.
1. Warranty Period: 15 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 OWNER-FURNISHED MATERIALS
A. Owner-Furnished Materials: Toilet paper dispensers and soap dispensers.
PROJECT NO. 12-194.45 10 2800 - 2
2.2 PERFORMANCE REQUIREMENTS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.3 PUBLIC-USE WASHROOM ACCESSORIES
A. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated or comparable product by one of the following:
1. A & J Washroom Accessories, Inc.
2. American Specialties, Inc.
3. Bobrick Washroom Equipment, Inc.
4. Bradley Corporation.
5. GAMCO Specialty Accessories; a division of Bobrick.
B. Toilet Tissue (Roll) Dispenser (4): Surface mounted, Owner furnished and Contractor installed.
C. Liquid-Soap Dispenser (6): Surface mounted, Owner furnished and Contractor installed.
D. Grab Bar (1, 2, and 3):
1. Mounting: Flanges with concealed fasteners.
2. Material: Stainless steel, 0.05 inch (1.3 mm) thick.
a. Finish: Smooth, No. 4 finish (satin) on ends and slip-resistant texture in grip area.
3. Outside Diameter: 1-1/2 inches (38 mm).
4. Configuration and Length: As indicated on Drawings.
E. Mirror Unit (5):
1. Frame: Stainless-steel angle, 0.05 inch (1.3 mm) thick.
a. Corners: Welded and ground smooth.
2. Hangers: Produce rigid, tamper- and theft-resistant installation, using method indicated below.
a. Wall bracket of galvanized steel, equipped with concealed locking devices requiring a special tool to remove.
3. Size: 18 by 34 inches(457 by 864 mm) unless indicated otherwise.
2.4 WARM-AIR DRYERS
A. High-Speed Warm-Air Dryer (7):
1. Products: Subject to compliance with requirements, provide one of the following:
PROJECT NO. 12-194.45 10 2800 - 3
a. AJW Architectural Products; U1512EA-120V.
b. American Dryer, Inc; EXTREMEAIR GXT Series High Speed Hand Dryer.
c. American Specialties, Inc; TURBO-Dri HIGH SPEED HAND DYRER.
d. Bradley Corporation; Aerix + High Speed, High-Efficiency Hand Dryer, 2922-287300.
e. Extreme Air; GTX9-M.
f. GAMCO Specialty Accessories; a division of Bobrick; Surface-Mounted High Speed Hand
Dryer, DR-570.
g. Saniflow Hand Dryer Corporation; Machflow, M09A.
h. World Dryer Corporation; Smartdri Plus.
2. Description: High-speed, warm-air hand dryer for rapid hand drying.
3. Mounting: Surface mounted.
4. Operation: Electronic-sensor activated with operation time of 10 to 15 seconds.
5. Cover Material and Finish: Steel or aluminum, with white enamel finish.
6. Electrical Requirements: Match building electrical service.
2.5 UNDERLAVATORY GUARDS
A. Underlavatory Shield-Type Guard: Provide one for each wall-mounted lavatory.
1. Products: One of the following:
a. Truebro by IPS Corporation; Lav-Shield.
b. Zurn Industries, Inc.; Rigid Lavatory Enclosure – Vandal Guard.
2. Description: One piece shield for covering supply and drain piping assemblies and other underlav mounted accessories to prevent direct contact with and to provide vandal resistance. Field trim to fit tightly to lavatory and adjacent surfaces.
3. Material and Finish: Rigid, high impact, stain resistant, molded PVC plastic, white.
2.6 FABRICATION
A. Keys: Provide universal keys for internal access to accessories for servicing and resupplying. Provide minimum of six keys to Owner's representative.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install accessories according to manufacturers' written instructions, using fasteners appropriate to substrate indicated and recommended by unit manufacturer. Install units level, plumb, and firmly anchored in locations and at heights indicated.
1. Grab Bars: Install to withstand a downward load of at least 250 lbf (1112 N), when tested according to ASTM F 446.
PROJECT NO. 12-194.45 10 2800 - 4
B. Adjusting and Cleaning: Adjust accessories for unencumbered, smooth operation. Replace damaged or defective items.
1. Remove temporary labels and protective coatings.
2. Clean and polish exposed surfaces according to manufacturer's written recommendations.
END OF SECTION 10 2800
FIRE PROTECTION CABINETS
PROJECT NO. 12-194.45 10 4413 - 1
SECTION 10 4413 - FIRE PROTECTION CABINETS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes fire-protection cabinets for the following:
1. Portable fire extinguishers.
B. Related Requirements:
1. Section 10 4416 "Fire Extinguishers."
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: For fire-protection cabinets.
C. Product Schedule: For fire-protection cabinets. Indicate whether recessed, semirecessed, or surface mounted. Coordinate final fire-protection cabinet schedule with fire-extinguisher schedule to ensure proper fit and function. Use same designations indicated on Drawings.
1.3 CLOSEOUT SUBMITTALS
A. Maintenance data.
1.4 COORDINATION
A. Coordinate size of fire-protection cabinets to ensure that type and capacity of fire extinguishers indicated are accommodated.
B. Coordinate sizes and locations of fire-protection cabinets with wall depths.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Rated Fire-Protection Cabinets: Listed and labeled to comply with requirements in ASTM E 814 for fire-resistance rating of walls where they are installed.
PROJECT NO. 12-194.45 10 4413 - 2
2.2 FIRE-PROTECTION CABINET
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. JL Industries, Inc.; a division of the Activar Construction Products Group.
2. Larsens Manufacturing Company.
3. Nystrom, Inc.
4. Potter Roemer LLC.
B. Cabinet Type (FEC): Suitable for fire extinguisher.
1. Cabinet Construction: Fire rating matching rating of wall installed in.
a. Fire-Rated Cabinets: Construct fire-rated cabinets with double walls fabricated from 0.043-inch- (1.09-mm-) thick cold-rolled steel sheet lined with minimum 5/8-inch- (16-mm-) thick fire-barrier material. Provide factory-drilled mounting holes.
2. Cabinet Material: Cold-rolled steel sheet.
3. Semirecessed Cabinet: One-piece combination trim and perimeter door frame overlapping surrounding wall surface with exposed trim face and wall return at outer edge (backbend).
a. Rolled-Edge Trim: 2-1/2-inch (64-mm) backbend depth.
4. Cabinet Trim Material: Same material and finish as door.
5. Door Material: Aluminum sheet.
6. Door Style: Vertical duo panel with frame.
7. Door Glazing: Tempered float glass (clear).
8. Door Hardware: Manufacturer's standard door-operating hardware of proper type for cabinet type, trim style, and door material and style indicated.
a. Provide projecting door pull and friction latch.
b. Provide concealed hinge permitting door to open 180 degrees.
C. Materials:
1. Cold-Rolled Steel: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B.
a. Finish: Baked enamel or powder coat.
b. Color: White.
2. Aluminum: ASTM B 221 (ASTM B 221M), with strength and durability characteristics of not less than Alloy 6063-T5 for aluminum sheet. ASTM B 221 (ASTM B 221M) for extruded shapes.
a. Finish: Clear anodic.
3. Tempered Float Glass: ASTM C 1048, Kind FT, Condition A, Type I, Quality q3, 3 mm thick, Class 1 (clear).
PROJECT NO. 12-194.45 10 4413 - 3
2.3 FABRICATION
A. Fire-Protection Cabinets: Provide manufacturer's standard box (tub) with trim, frame, door, and hardware to suit cabinet type, trim style, and door style indicated.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Prepare recesses for semirecessed fire-protection cabinets as required by type and size of cabinet and trim style.
B. Install fire-protection cabinets in locations and at mounting heights indicated or, if not indicated, at heights acceptable to authorities having jurisdiction.
1. Fire-Protection Cabinets: 54 inches (1372 mm) above finished floor to top of cabinet.
C. Fire-Protection Cabinets: Fasten cabinets to structure, square and plumb.
D. Adjust fire-protection cabinet doors to operate easily without binding. Verify that integral locking devices operate properly.
END OF SECTION 10 4413
FIRE EXTINGUISHERS
PROJECT NO. 12-194.45 10 4416 - 1
SECTION 10 4416 - FIRE EXTINGUISHERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes portable, hand-carried fire extinguishers and mounting brackets for fire extinguishers.
B. Related Requirements:
1. Section 10 4413 "Fire Protection Cabinets."
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.3 INFORMATIONAL SUBMITTALS
A. Warranty: Sample of special warranty.
1.4 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.5 COORDINATION
A. Coordinate type and capacity of fire extinguishers with fire-protection cabinets to ensure fit and function.
1.6 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace fire extinguishers that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Failure of hydrostatic test according to NFPA 10.
b. Faulty operation of valves or release levers.
2. Warranty Period: Six years from date of Substantial Completion.
PROJECT NO. 12-194.45 10 4416 - 2
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10, "Portable Fire Extinguishers."
B. Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent testing agency acceptable to authorities having jurisdiction.
2.2 PORTABLE, HAND-CARRIED FIRE EXTINGUISHERS
A. Fire Extinguishers: Type, size, and capacity for each fire-protection cabinet and mounting bracket indicated.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Ansul Incorporated.
b. Buckeye Fire Equipment Company.
c. JL Industries, Inc.; a division of the Activar Construction Products Group.
d. Kidde Residential and Commercial Division; Subsidiary of Kidde plc.
e. Larsens Manufacturing Company.
f. Nystrom Building Products.
g. Potter Roemer LLC.
2. Instruction Labels: Include pictorial marking system complying with NFPA 10, Appendix B.
B. Multipurpose Dry-Chemical Type in Steel Container (FE): UL-rated 4-A:60-B:C, 10-lb (4.5-kg) nominal capacity, with monoammonium phosphate-based dry chemical in enameled-steel container.
2.3 MOUNTING BRACKETS
A. Mounting Brackets: Manufacturer's standard galvanized steel, designed to secure fire extinguisher to wall or structure, of sizes required for types and capacities of fire extinguishers indicated, with plated or black baked-enamel finish.
1. Manufacturer: Provide product by same manufacture as fire extinguisher.
2. Provide mounting bracket for each hand-carried fire extinguisher not installed in a fire protection cabinet unless indicated otherwise.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Examine fire extinguishers for proper charging and tagging.
PROJECT NO. 12-194.45 10 4416 - 3
1. Remove and replace damaged, defective, or undercharged fire extinguishers.
B. Install fire extinguishers and mounting brackets in locations indicated and in compliance with requirements of authorities having jurisdiction.
1. Mounting Brackets: 54 inches (1372 mm) above finished floor to top of fire extinguisher.
C. Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, at locations indicated.
END OF SECTION 10 4416
COMMON WORK RESULTS FOR HVAC
PROJECT NO. 12-194.45 23 0500 - 1
SECTION 23 0500 - COMMON WORK RESULTS FOR HVAC
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Piping materials and installation instructions common to most piping systems.
2. Dielectric fittings.
3. Sleeve-seal systems.
4. Sleeves.
5. Stack-sleeve fittings.
6. Escutcheons.
7. Grout.
8. HVAC demolition.
9. Equipment installation requirements common to equipment sections.
10. Painting and finishing.
11. Concrete bases.
12. Supports and anchorages.
B. Related Sections:
1. Division 01 Section "Alternates" for requirements of alternates that relate to this Division.
1.2 ACTION SUBMITTALS
A. Product Data: For dielectric fittings.
1.3 QUALITY ASSURANCE
A. Provide HVAC systems, equipment, and materials in accordance with Michigan Mechanical Code and other applicable codes and regulations, and with authorities having jurisdiction.
B. Steel Support Welding: Qualify processes and operators according to AWS D1.1, "Structural Welding Code--Steel."
C. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."
1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
2. Certify that each welder has passed AWS qualification tests for welding processes involved and that certification is current.
D. Electrical Characteristics for HVAC Equipment: Equipment of higher electrical characteristics may be furnished provided such proposed equipment is approved in writing and connecting electrical services, PROJECT NO. 12-194.45 23 0500 - 2 circuit breakers, and conduit sizes are appropriately modified. If minimum energy ratings or efficiencies are specified, equipment shall comply with requirements.
1.4 DELIVERY, STORAGE, AND HANDLING
A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture.
B. Deliver products to project properly identified with names, model numbers, types, grades, compliance labels, and similar information needed for distinct identifications; adequately packaged and protected to prevent damage during shipment, storage, handling, and up to substantial completion. Coordinate deliveries of mechanical materials and equipment to minimize construction site congestion.
1.5 COORDINATION
A. Arrange for pipe spaces, chases, slots, and openings in building structure during progress of construction, to allow for HVAC installations.
B. Coordinate installation of required supporting devices and sleeves in structural components.
C. Coordinate requirements for access panels and doors for HVAC items requiring access that are concealed behind finished surfaces. Access panels and doors are specified in Division 08 Section "Access Doors and Frames."
PART 2 - PRODUCTS
2.1 PIPE, TUBE, AND FITTINGS
A. Refer to individual Division 23 piping Sections for pipe, tube, and fitting materials and joining methods.
B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.
C. All grooved joint couplings, fittings, valves, and specialties shall be the products of a single manufacturer.
Grooving tools shall be of the same manufacturer as the grooved components.
1. All castings used for coupling housings, fittings, valve bodies, etc., shall include listing/approval stamp, label, or other markings made to specified standards.
2.2 JOINING MATERIALS
A. Refer to individual Division 23 piping Sections for special joining materials not listed below.
B. Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system contents.
1. ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch(3.2-mm) maximum thickness unless thickness or specific material is indicated.
PROJECT NO. 12-194.45 23 0500 - 3
a. Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze flanges.
b. Narrow-Face Type: For raised-face, Class 250, cast-iron and steel flanges.
C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated.
D. Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux according to ASTM B 813.
E. Brazing Filler Metals: AWS A5.8, BCuP Series, copper-phosphorus alloys for general-duty brazing, unless otherwise indicated; and AWS A5.8, BAg1, silver alloy for refrigerant piping, unless otherwise indicated.
F. Welding Filler Metals: Comply with AWS D10.12 for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.
2.3 DIELECTRIC FITTINGS
A. Description: Combination fitting of copper alloy and ferrous materials with threaded end connections that match piping system materials.
1. Insulating Material: Suitable for system fluid, pressure, and temperature.
B. Dielectric Unions: Factory-fabricated, union assembly, for 250-psig(1725-kPa) minimum working pressure at 180 deg F(82 deg C) with threaded end connections.
C. Dielectric Couplings: Galvanized-steel coupling with inert and noncorrosive, thermoplastic lining; threaded ends; and 300-psig(2070-kPa) minimum working pressure at 225 deg F(107 deg C).
D. Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic lining; threaded ends; and 300-psig(2070-kPa) minimum working pressure at 225 deg F(107 deg C).
2.4 SLEEVE-SEAL SYSTEMS
A. Description: Modular sealing-element unit, designed for field assembly, for filling annular space between piping and sleeve.
1. Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.
2. Pressure Plates: Plastic.
3. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length required to secure pressure plates to sealing elements.
2.5 SLEEVES
A. Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated.
B. Galvanized-Steel Wall Pipes: ASTM A 53/A 53M, Schedule 40, with plain ends and welded steel collar;
zinc coated.
PROJECT NO. 12-194.45 23 0500 - 4
C. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc coated, with plain ends.
D. Galvanized-Steel-Sheet Sleeves: 0.0239-inch (0.6-mm) minimum thickness; round tube closed with welded longitudinal joint.
2.6 STACK-SLEEVE FITTINGS
A. Description: Manufactured, cast-iron sleeve with integral clamping flange. Include clamping ring, bolts, and nuts for membrane flashing.
1. Underdeck Clamp: Clamping ring with setscrews.
2.7 ESCUTCHEONS
A. Description: Manufactured wall and ceiling escutcheons with an ID to closely fit around pipe, tube, and insulation of insulated piping and an OD that completely covers opening.
B. One-Piece, Cast-Brass Type: With polished, chrome-plated or rough-brass finish and setscrew fastener.
C. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with chrome-plated finish and spring-clip fasteners.
D. One-Piece, Stamped-Steel Type: With chrome-plated finish and spring-clip fasteners.
E. Split-Casting Brass Type: With polished, chrome-plated or rough-brass finish and with concealed hinge and setscrew.
F. Split-Plate, Stamped-Steel Type: With chrome-plated finish, concealed or exposed-rivet hinge, and spring-clip fasteners.
2.8 GROUT
A. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
B. Characteristics: Nonshrink; recommended for interior and exterior applications.
C. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.
D. Packaging: Premixed and factory packaged.
2.9 MECHANICAL ROOF PENETRATIONS
A. Roof Curbs for Duct Penetrations: Prefabricated heavy-gage galvanized steel or aluminum curb with mitered and welded corners, minimum 1 1/2 inch thick rigid fiberglass insulation adhered to inside walls, built-in cant and mounting flange for roof decks, and wood nailer. Size as required to suit roof opening
PROJECT NO. 12-194.45 23 0500 - 5
and ductwork. Overall minimum height shall be 12 inches above roof insulation. Provide curbs with level tops and bottoms to match roof slope. Provide galvanized steel flashing and seal water tight. Provide insulation on interior flashing surfaces exposed to building air. Pate or equivalent.
B. Pipe Curbs for Single or Multiple Pipe Penetrations: Prefabricated heavy-gage galvanized steel or aluminum curb with mitered and welded corners, minimum 1 1/2 inch thick rigid fiberglass insulation adhered to inside walls, built-in cant and mounting flange for roof decks, wood nailer, and acrylic clad ABS plastic cover(s), PVC boot(s), and stainless steel clamps.. Size as required to suit roof opening and piping. Overall minimum height shall be 12 inches above roof insulation. Provide curbs with level tops and bottoms to match roof slope. Pate or equivalent.
C. Pipe Curbs for Single Pipe Penetrations: All roof pipe penetrations up to 10" O.D. shall be flashed and sealed using a Pate or equivalent pipe seal, consisting of a spun aluminum base having a minimum five inch roof surface flange, a stepped polyvinyl chloride boot to be secured to the base and the pipe with adjustable stainless steel clamps as furnished.
PART 3 - EXECUTION
3.1 HVAC DEMOLITION
A. Refer to Division 01 Section "Execution" and Division 02 Section "Selective Demolition" for general demolition requirements and procedures.
B. Disconnect, demolish, and remove HVAC systems, equipment, and components indicated to be removed.
1. Piping to Be Removed: Remove portion of piping indicated to be removed and cap or plug remaining piping with same or compatible piping material within 6 inches of main.
2. Piping to Be Abandoned in Place: Drain piping and cap or plug piping with same or compatible piping material.
3. Ducts to Be Removed: Remove portion of ducts indicated to be removed and plug remaining ducts with same or compatible ductwork material.
4. Ducts to Be Abandoned in Place: Cap or plug ducts with same or compatible ductwork material.
5. Equipment to Be Removed: Disconnect and cap services and remove equipment.
6. Equipment to Be Removed and Reinstalled: Disconnect and cap services and remove, clean, and store equipment; when appropriate, reinstall, reconnect, and make equipment operational.
7. Equipment to Be Removed and Salvaged: Disconnect and cap services and remove equipment and deliver to Owner.
C. If pipe, insulation, or equipment to remain is damaged in appearance or is unserviceable, remove damaged or unserviceable portions and replace with new products of equal capacity and quality.
3.2 PIPING SYSTEMS - COMMON REQUIREMENTS
A. Install piping according to the following requirements and Division 23 Sections specifying piping systems.
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems.
Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump
PROJECT NO. 12-194.45 23 0500 - 6
sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved.
1. Drawings are diagrammatic with no attempt made to show every ell, tee, transition, fitting, or appurtenance. Provide installations that are complete in every detail, compliant with all applicable codes, and as required to provide a fully functional and operational system even though every item is not specifically indicated.
C. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas.
D. Install piping at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.
E. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
F. Install piping to permit valve servicing.
G. Install piping at indicated slopes.
H. Install piping free of sags and bends.
I. Install fittings for changes in direction and branch connections.
J. Install piping to allow application of insulation.
K. Select system components with pressure rating equal to or greater than system operating pressure.
3.3 ESCUTCHEON INSTALLATION
A. Install escutcheons for penetrations of walls, ceilings, and finished floors according to the following:
1. Escutcheons for New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type.
b. Chrome-Plated Piping: One-piece, cast-brass or split-casting brass type with polished, chrome-plated finish.
c. Insulated Piping: One-piece, stamped-steel type or split-plate, stamped-steel type with concealed hinge.
d. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, cast-brass or split-casting brass type with polished, chrome-plated finish.
e. Bare Piping at Ceiling Penetrations in Finished Spaces: One-piece, cast-brass or split-casting brass type with polished, chrome-plated finish.
f. Bare Piping in Unfinished Service Spaces: One-piece, cast-brass or split-casting brass type with polished, chrome-plated or rough-brass finish.
g. Bare Piping in Equipment Rooms: One-piece, cast-brass or split-casting brass type with polished, chrome-plated or rough-brass finish.
2. Escutcheons for Existing Piping:
PROJECT NO. 12-194.45 23 0500 - 7
a. Chrome-Plated Piping: Split-casting brass type with polished, chrome-plated finish.
b. Insulated Piping: Split-plate, stamped-steel type with concealed or exposed-rivet hinge.
c. Bare Piping at Wall and Floor Penetrations in Finished Spaces: Split-casting brass type with polished, chrome-plated finish.
d. Bare Piping at Ceiling Penetrations in Finished Spaces: Split-casting brass type with polished, chrome-plated finish.
e. Bare Piping in Unfinished Service Spaces: Split-casting brass type with polished, chrome-plated or rough-brass finish.
f. Bare Piping in Equipment Rooms: Split-casting brass type with polished, chrome-plated or rough-brass finish.
3.4 SLEEVE INSTALLATION
A. Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.
1. Sleeves are not required for core-drilled holes.
B. For sleeves that will have sleeve-seal system installed, select sleeves of size large enough to provide 1-inch (25-mm) annular clear space between piping and concrete slabs and walls.
C. Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and walls are constructed.
1. Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment areas or other wet areas 2 inches (50 mm) above finished floor level.
2. Using grout, seal the space outside of sleeves in slabs and walls without sleeve-seal system.
D. Install sleeves for pipes passing through interior partitions.
1. Cut sleeves to length for mounting flush with both surfaces.
2. Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular clear space between sleeve and pipe or pipe insulation.
3. Seal annular space between sleeve and piping or piping insulation; use joint sealants appropriate for size, depth, and location of joint. Comply with requirements for sealants specified in Section 07 9200 "Joint Sealants."
E. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping specified in Section 07 8413 "Penetration Firestopping."
3.5 STACK-SLEEVE-FITTING INSTALLATION
A. Install stack-sleeve fittings in new slabs as slabs are constructed.
1. Install fittings that are large enough to provide 1/4-inch (6.4-mm) annular clear space between sleeve and pipe or pipe insulation.
PROJECT NO. 12-194.45 23 0500 - 8
2. Secure flashing between clamping flanges for pipes penetrating floors with membrane waterproofing. Comply with requirements for flashing specified in Section 07 6200 "Sheet Metal Flashing and Trim."
3. Install section of cast-iron soil pipe to extend sleeve to 2 inches (50 mm) above finished floor level.
4. Extend cast-iron sleeve fittings below floor slab as required to secure clamping ring if ring is specified.
5. Using grout, seal the space around outside of stack-sleeve fittings.
B. Fire-Barrier Penetrations: Maintain indicated fire rating of floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for firestopping specified in Section 07 8413 "Penetration Firestopping."
3.6 SLEEVE-SEAL-SYSTEM INSTALLATION
A. Install sleeve-seal systems in sleeves in exterior concrete walls and slabs-on-grade at service piping entries into building.
B. Select type, size, and number of sealing elements required for piping material and size and for sleeve ID or hole size. Position piping in center of sleeve. Center piping in penetration, assemble sleeve-seal system components, and install in annular space between piping and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make a watertight seal.
3.7 SLEEVE AND SLEEVE-SEAL SCHEDULE
A. Use sleeves and sleeve seals for the following piping-penetration applications:
1. Exterior Concrete Walls Above Grade:
a. Piping Smaller Than NPS 6 (DN 150): Cast-iron wall sleeves, galvanized-steel wall sleeves, or galvanized-steel-pipe sleeves.
b. Piping NPS 6 (DN 150) and Larger: Cast-iron wall sleeves, galvanized-steel wall sleeve, or galvanized-steel-pipe sleeves.
2. Exterior Concrete Walls below Grade:
a. Piping Smaller Than NPS 6 (DN 150): Cast-iron wall sleeves with sleeve-seal system.
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space between piping and sleeve for installing sleeve-seal system.
b. Piping NPS 6 (DN 150) and Larger: Cast-iron wall sleeves with sleeve-seal system.
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space between piping and sleeve for installing sleeve-seal system.
3. Concrete Slabs-on-Grade:
a. Piping Smaller Than NPS 6 (DN 150): Cast-iron wall sleeves with sleeve-seal system.
PROJECT NO. 12-194.45 23 0500 - 9
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space between piping and sleeve for installing sleeve-seal system.
b. Piping NPS 6 (DN 150) and Larger: Cast-iron wall sleeves with sleeve-seal system.
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space between piping and sleeve for installing sleeve-seal system.
4. Concrete Slabs above Grade:
a. Piping Smaller Than NPS 6 (DN 150): Stack-sleeve fittings.
b. Piping NPS 6 (DN 150) and Larger: Stack-sleeve fittings.
5. Interior Partitions:
a. Piping Smaller Than NPS 6 (DN 150): Galvanized-steel-pipe sleeves.
b. Piping NPS 6 (DN 150) and Larger: Galvanized-steel-sheet sleeves.
3.8 PIPING JOINT CONSTRUCTION
A. Join pipe and fittings according to the following requirements and Division 23 Sections specifying piping systems.
B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.
D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube end.
Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead-free solder alloy complying with ASTM B 32.
E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and Tube" Chapter, using copper-phosphorus brazing filler metal complying with AWS A5.8.
F. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:
1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified.
2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged.
Do not use pipe sections that have cracked or open welds.
G. Welded Joints: Construct joints according to AWS D10.12, using qualified processes and welding operators according to Part 1 "Quality Assurance" Article.
H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application.
Install gasket concentrically positioned. Use suitable lubricants on bolt threads.
PROJECT NO. 12-194.45 23 0500 - 10
3.9 PIPING CONNECTIONS
A. Make connections according to the following, unless otherwise indicated:
1. Install unions, in piping NPS 2(DN 50) and smaller, adjacent to each valve and at final connection to each piece of equipment.
2. Install flanges, in piping NPS 2-1/2(DN 65) and larger, adjacent to flanged valves and at final connection to each piece of equipment.
3. Wet Piping Systems: Install dielectric unions, dielectric couplings, or dielectric nipple fittings to connect piping materials of dissimilar metals.
3.10 EQUIPMENT INSTALLATION - COMMON REQUIREMENTS
A. Sequence, coordinate, and integrate installations of mechanical equipment, giving particular attention to large equipment requiring positioning prior to closing in the building.
B. Install equipment to allow maximum possible headroom unless specific mounting heights are not indicated.
C. Install equipment level and plumb, parallel and perpendicular to other building systems and components in exposed interior spaces, unless otherwise indicated.
D. Install HVAC equipment to facilitate service, maintenance, and repair or replacement of components.
Connect equipment for ease of disconnecting, with minimum interference to other installations.
1. Extend grease fittings to accessible locations.
E. Install equipment to allow right of way for piping installed at required slope.
F. Installing contractor shall bear all additional costs, including that of Architect/Engineer redesign and that of other trades, incurred as a result of installation of other than scheduled equipment.
G. Verify final equipment locations for roughing-in.
H. Refer to equipment specifications in other Sections of these Specifications for roughing-in requirements.
3.11 PAINTING
A. Damage and Touchup: Repair marred and damaged factory-painted finishes with materials and procedures to match original factory finish.
3.12 CONCRETE BASES
A. Concrete Bases: Anchor equipment to concrete base according to equipment manufacturer's written instructions and according to seismic codes at Project.
1. Construct concrete bases of dimensions indicated, but not less than 4 inches(100 mm) larger in both directions than supported unit.
PROJECT NO. 12-194.45 23 0500 - 11
2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch(450-mm) centers around the full perimeter of the base.
3. Install epoxy-coated anchor bolts for supported equipment that extend through concrete base, and anchor into structural concrete floor.
4. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
5. Install anchor bolts to elevations required for proper attachment to supported equipment.
6. Install anchor bolts according to anchor-bolt manufacturer's written instructions.
7. Use 3000-psi(20.7-MPa), 28-day compressive-strength concrete and reinforcement as specified in
Division 03 section for cast-in-place concrete.
3.13 ERECTION OF METAL SUPPORTS AND ANCHORAGES
A. Refer to Division 05 Section "Metal Fabrications" for structural steel.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor HVAC materials and equipment.
C. Field Welding: Comply with AWS D1.1.
3.14 GROUTING
A. Mix and install grout for HVAC equipment base bearing surfaces, pump and other equipment base plates, and anchors.
1. Clean surfaces that will come into contact with grout.
2. Provide forms as required for placement of grout.
3. Avoid air entrapment during placement of grout.
4. Place grout, completely filling equipment bases.
5. Place grout on concrete bases and provide smooth bearing surface for equipment.
6. Place grout around anchors.
7. Cure placed grout.
3.15 MECHANICAL ROOF PENETRATIONS
A. Install mechanical roof penetrations in accordance with roof curb manufacturer’s recommendations and in strict compliance with roofing manufacturer’s requirements.
1. Roofs with Warranty: Roof penetrations and curbs shall be installed in such a manner to maintain roofing warranty.
B. Roof Curbs for Duct Penetrations: Provide galvanized steel flashing and seal water tight. Provide insulation on interior flashing surfaces exposed to building air.
C. Pipe Curbs for Pipe Penetrations: Secure boot to curb base and secure boot to pipe with adjustable stainless steel clamps.
PROJECT NO. 12-194.45 23 0500 - 12
3.16 INSTALLATION OF ACCESS DOORS
A. Where lay-in ceilings are used, the access to ceiling space is provided through the removable ceiling panels. Where access is required to valves, pipes, dampers or other devices in spaces above non-removable ceilings or in chases, the Contractor requiring the access doors shall provide access doors.
Access doors required in rated walls and ceiling shall bear the same rating. Access panels and doors are specified in Division 08 Section "Access Doors and Frames."
1. Set frames accurately in position and securely attached to supports, with face panels plumb and level in relation to adjacent finish surfaces.
2. Adjust hardware and panels after installation for proper operation.
3.17 FIELD QUALITY CONTROL
A. Replace broken and damaged escutcheons and floor plates using new materials.
END OF SECTION 23 0500
COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
PROJECT NO. 12-194.45 23 0513 - 1
SECTION 23 0513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes general requirements for single-phase and polyphase, general-purpose, horizontal, small and medium, squirrel-cage induction motors for use on ac power systems up to 600 V and installed at equipment manufacturer's factory.
1.2 COORDINATION
A. Coordinate features of motors, installed units, and accessory devices to be compatible with the following:
1. Motor controllers.
2. Torque, speed, and horsepower requirements of the load.
3. Ratings and characteristics of supply circuit and required control sequence.
4. Ambient and environmental conditions of installation location.
B. For motors using variable frequency controller, motors to be designed for such application and suitable for use throughout speed range without overheating.
PART 2 - PRODUCTS
2.1 GENERAL MOTOR REQUIREMENTS
A. Comply with requirements in this Section except when stricter requirements are specified in HVAC equipment schedules or Sections.
B. Comply with NEMA MG 1 unless otherwise indicated.
2.2 MOTOR CHARACTERISTICS
A. Duty: Continuous duty at ambient temperature of 40 deg C and at altitude of 3300 feet(1000 m) above sea level.
B. Capacity and Torque Characteristics: Sufficient to start, accelerate, and operate connected loads at designated speeds, at installed altitude and environment, with indicated operating sequence, and without exceeding nameplate ratings or considering service factor.
2.3 POLYPHASE MOTORS
A. Description: NEMA MG 1, Design B, medium induction motor.
PROJECT NO. 12-194.45 23 0513 - 2
B. Efficiency: Energy efficient, as defined in NEMA MG 1.
1. Provide premium efficient motors where scheduled or when used with a variable frequency controller.
C. Service Factor: 1.15.
D. Multispeed Motors: Variable torque.
1. For motors with 2:1 speed ratio, consequent pole, single winding.
2. For motors with other than 2:1 speed ratio, separate winding for each speed.
E. Multispeed Motors: Separate winding for each speed.
F. Rotor: Random-wound, squirrel cage.
G. Bearings: Regreasable, shielded, antifriction ball bearings suitable for radial and thrust loading.
H. Temperature Rise: Class B.
I. Insulation: Class F.
J. Code Letter Designation:
1. Motors 15 HP and Larger: NEMA starting Code F or Code G.
2. Motors Smaller than 15 HP: Manufacturer's standard starting characteristic.
K. Enclosure Material: Manufacturer’s standard material.
2.4 POLYPHASE MOTORS WITH ADDITIONAL REQUIREMENTS
A. Motors Used with Variable Frequency Controllers: Ratings, characteristics, and features coordinated with controller.
1. Windings: Copper magnet wire with moisture-resistant insulation varnish, designed and tested to resist transient spikes, high frequencies, and short time rise pulses produced by pulse-width modulated inverters.
2. Premium-Efficient Motors: Class B temperature rise; Class F insulation.
3. Shaft Grounding Ring: Factory installed shaft grounding ring consisting of maintenance free, circumferential, bearing protection ring with conductive micro fiber shaft contacting material.
2.5 SINGLE-PHASE MOTORS
A. Motors larger than 1/20 hp shall be one of the following, to suit starting torque and requirements of specific motor application:
1. Permanent-split capacitor.
2. Split phase.
3. Capacitor start, inductor run.
PROJECT NO. 12-194.45 23 0513 - 3
4. Capacitor start, capacitor run.
B. Multispeed Motors: Variable-torque, permanent-split-capacitor type.
C. Bearings: Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust loading.
D. Motors 1/20 HP and Smaller: Shaded-pole type.
E. Thermal Protection: Internal protection to automatically open power supply circuit to motor when winding temperature exceeds a safe value calibrated to temperature rating of motor insulation. Thermal-protection device shall automatically reset when motor temperature returns to normal range.
2.6 ELECTRONIC COMMUTATION MOTOR (ECM)
A. Description: Motor to be an electronic commutation motor (ECM) specifically designed for direct drive fan applications. Motors shall be permanently lubricated with heavy-duty ball bearings to match the fan load and prewired to the specific voltage and phase. Internal motor circuitry shall convert AC power supplied to the fan to DC power to operate the motor. Motor shall be speed controllable down to 20% of full speed (80% turndown). Speed shall be controlled by either a potentiometer dial mounted on the motor or by a 0- 10 VDC signal. Motor shall be a minimum of 85% efficient at all speeds.
PART 3 - EXECUTION (Not Applicable)
END OF SECTION 23 0513
METERS AND GAGES FOR HVAC PIPING
PROJECT NO. 12-194.45 23 0519 - 1
SECTION 23 0519 - METERS AND GAGES FOR HVAC PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Thermometers.
2. Gages.
3. Test plugs.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
1.3 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
PART 2 - PRODUCTS
2.1 LIQUID-IN-GLASS THERMOMETERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Ashcroft.
2. Marsh Bellofram.
3. Miljoco Corp.
4. Trerice, H. O. Co.
5. Weiss Instruments, Inc.
6. Weksler Instruments.
B. Case: Metal or plastic, 9 inches(229 mm) long.
C. Tube: Red or blue reading, organic-liquid filled, with magnifying lens.
D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings.
E. Window: Glass or plastic.
F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device.
G. Stem: Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation.
PROJECT NO. 12-194.45 23 0519 - 2
H. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of 1.5 percent of range.
2.2 THERMOWELLS
A. Manufacturers: Same as manufacturer of thermometer being used.
B. Description: Pressure-tight, socket-type metal fitting made for insertion into piping and of type, diameter, and length required to hold thermometer.
C. Heat-Transfer Medium: Mixture of graphite and glycerin.
2.3 PRESSURE GAGES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Ashcroft.
2. Marsh Bellofram.
3. Miljoco Corp.
4. Trerice, H. O. Co.
5. Weiss Instruments, Inc.
6. Weksler Instruments.
B. Direct-Mounting, Dial-Type Pressure Gages: Indicating-dial type complying with ASME B40.100.
1. Case: Liquid-filled type, drawn steel or cast aluminum, 4-1/2-inch(114-mm) diameter.
2. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated.
3. Pressure Connection: Brass, NPS 1/4(DN 8), bottom-outlet type unless back-outlet type is indicated.
4. Movement: Mechanical, with link to pressure element and connection to pointer with front recalibration.
5. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings.
6. Pointer: Red or other dark-color metal.
7. Window: Glass or plastic.
8. Ring: Metal.
9. Accuracy: Grade A, plus or minus 1 percent of middle half scale.
10. Vacuum-Pressure Range: 30-in. Hg of vacuum to 15 psig of pressure(100 kPa of vacuum to 103 kPa of pressure).
11. Range for Fluids under Pressure: Two times operating pressure.
C. Pressure-Gage Fittings:
1. Valves: NPS 1/4(DN 8) brass:
a. Ball valve for water systems.
2. Tubing: NPS 1/4(DN 8) steel or copper.
3. Snubbers: ASME B40.5, NPS 1/4(DN 8) brass bushing with corrosion-resistant, porous-metal disc of material suitable for system fluid and working pressure.
PROJECT NO. 12-194.45 23 0519 - 3
2.4 TEST PLUGS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Flow Design, Inc.
2. MG Piping Products Co.
3. National Meter, Inc.
4. Peterson Equipment Co., Inc.
5. Sisco Manufacturing Co.
6. Trerice, H. O. Co.
7. Watts Industries, Inc.; Water Products Div.
B. Description: Corrosion-resistant brass or stainless-steel body with core inserts and gasketed and threaded cap, with extended stem for units to be installed in insulated piping.
C. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F(3450 kPa…