2019_01_03_Kville_West_Elem_Media_Center_Bid_Doc_Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- RFP KEL 190000000773 3
- Issued by
- Kent County, Grand Rapids City, Michigan
About this file
This is a construction bid document and architectural drawing set for the West Elementary Media Center Renovation project in Grand Rapids, Michigan, prepared by Kelloggsville Public Schools in collaboration with Tower Pinkster Titus Associates Inc. (architect/engineer) and a construction manager located at 300 Ionia NW, Grand Rapids. The project encompasses a comprehensive renovation of the media center and associated storage areas on the first floor, totaling 2,039 square feet for the media center renovation and 588 square feet for the storage room renovation within the existing 30,070 square foot first floor. The bid documents were issued on January 3, 2019, and include detailed construction specifications, architectural plans, structural requirements, mechanical systems, electrical systems, plumbing specifications, and technology infrastructure. The documents reference compliance with the 2015 Michigan Building Code and 2012 NFPA 101 Life Safety Code, with the building classified as Use Group E (educational facility), Construction Type IIB, and non-sprinkled.
The project specifications detail extensive renovation requirements including demolition of existing structures, new partition construction with fire-rating designations ranging from smoke-resistant to 2-hour fire ratings, CMU (concrete masonry unit) walls, metal stud framing, gypsum board installation, mechanical systems, electrical power and communications infrastructure, and technology installations. Material specifications include 28-day compressive strength of 1500 PSI for masonry and 4000 PSI for concrete, with detailed requirements for reinforcement, anchoring systems using Hilti products, and adherence to ASTM standards. The documents establish seismic design parameters, roof dead loads of 5.0 PSF, ground snow load of 35 PSF, wind load of 125 PSF, and ground floor live loads of 100 PSF. All shop drawings and submittals require contractor preparation and engineer approval prior to fabrication, with the contractor bearing responsibility for dimensional accuracy and compliance with specifications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
SHEET TITLE
SHEET NUMBER
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
DESIGN TEAM
ARCHITECT/ENGINEER
REFERENCED CODES
SITE ADDRESS
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
COVER SHEET
12-194.45
G 001
WEST ELEMENTARY MEDIA CENTER RENOVATION
KELLOGGSVILLE PUBLIC SCHOOLS
Grand Rapids, Michigan
CONSTRUCTION BID DOCUMENTS
KELLOGGSVILLE
PUBLIC
SCHOOLS
DRAWING INDEX
KELLOGGSVILLE PUBLIC SCHOOLS
WEST KELLOGGSVILLE ELEMENTARY
4555 MAGNOLIA SW
GRAND RAPIDS, MI 49548
TITLE
G 001 COVER SHEET
GENERAL
G 002 TYPICAL SYMBOLS, GENERAL NOTES, INTERIOR PARTITION TYPES AND FIRE-RATING KEY
G 101 OVERALL CODE COMPLIANCE PLAN
STRUCTURAL
S001 STRUCTURAL GENERAL NOTES
S102 ROOF FRAMING PLAN
S301 FRAMING SECTIONS
ARCHITECTURAL
A 101 DEMOLITION & FLOOR PLANS
A 201 REFLECTED CEILING, ROOF PLAN, DOOR SCHEDULE, DOOR AND FRAME TYPES
A 601 FIRST FLOOR FINISH PLAN, MATERIAL SELECTIONS, & TYPICAL FINISH DETAILS
MECHANICAL
M 101 FIRST FLOOR MECHANICAL PLAN
M 150 MECHANICAL ROOF PLAN
M 501 MECHANICAL SCHEDULES AND DETAILS
M 601 TEMPERATURE CONTROLS
ELECTRICAL DEMOLITION
ED 101 FIRST FLOOR ELECTRICAL DEMOLITION PLAN
ELECTRICAL
E 101 FIRST FLOOR POWER AND COMMUNICATIONS PLAN
E 201 FIRST FLOOR LIGHTING PLAN
E 401 ELECTRICAL SYMBOLS AND DETAILS
E 402 ELECTRICAL ONE-LINE DIAGRAM AND DETAILS
E 501 ELECTRICAL PANEL LOAD SHEETS
TECHNOLOGY
T 101 FIRST FLOOR TECHNOLOGY PLAN
T 601 TECHNOLOGY DETAILS
BUILDING:
PLUMBING:
MECHANICAL:
ELECTRICAL:
BARRIER-FREE:
USE GROUP:
CONSTRUCTION TYPE:
AUTOMATIC SPRINKLERS:
FUEL GAS:
2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE
2015 MICHIGAN MECHANICAL CODE
2015 MICHIGAN PLUMBING CODE
2015 MICHIGAN BUILDING CODE AND 2014 ICC & C A117.1
2014 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS
(IFGC) 2015 INTERNATIONAL FUEL GAS CODE
E
2B, II(0,0,0)
NOT PROVIDED
PROJECT AREA
FIRST FLOOR RENOVATION: 2,039 SQ.FT.
FIRST FLOOR EXISTING: 30,070 SQ.FT.
FIRST FLOOR STORAGE ROOM RENOVATION: 588 SQ.FT.
4 EAST FULTON STREET
SUITE 200
GRAND RAPIDS, MICHIGAN 49503
PHONE: 616.456.9944
FAX: 616.456.5936
CONSTRUCTION MANAGER
300 IONIA NW
GRAND RAPIDS, MICHIGAN 49503
PHONE: 616.456.1521
FAX: 616.458.0770
ISSUED FOR DATE
B1
A 451
A 301
A
A 311
A 351
A 321
ROOM NUMBER
SHEET NUMBER
DETAIL NUMBER
ROOM NAME
100'-0" : 100'-0"
DISTANCE IN THE "X" DIRECTION FROM THE "Y" BASE LINE
DISTANCE IN THE "Y" DIRECTION FROM THE "X" BASE LINE
TYPICAL SYMBOLS AND REFERENCES
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
ELEVATION LETTER
SHEET NUMBER
ELEVATION NUMBER
BARRIER-FREE
REVISION IDENTIFIER (ADDENDUM AND BULLETIN)
COLUMN BUBBLE AND LINE
ELEVATION TAG FOR FLOOR PLANS AND
ELEVATION TAG FOR EXTERIOR
ELEVATIONS AND BUILDING SECTIONS
REFLECTED CEILING PLANS
ELEVATION TAG FOR FLOOR PLANS AND
ELEVATION TAG FOR EXTERIOR
ELEVATIONS AND BUILDING SECTIONS
REFLECTED CEILING PLANS
SHEET NUMBER
ELEVATION NUMBER
DOOR NUMBER - CORRESPONDS
TO THE ROOM NUMBER
LETTER DESIGNATES MORE THAN ONE IN ROOM
FINISH FLOOR
ELEVATION 100'-0"
FINISH FLOOR
ELEVATION 100'-0"
100'-0"
100'-0"
NOTE: ROOM NAMES AND NUMBERS ON PLANS
ARE FOR CONSTRUCTION PURPOSES ONLY.
COORDINATE WITH OWNER REGARDING
PROPOSED NUMBERS FOR ALL SIGNAGE,
SCHEDULE AND PANEL DESIGNATIONS.
DETAIL REFERENCE BUBBLE
DETAIL REFERENCE BUBBLE
BUILDING SECTION REFERENCE BUBBLE
EXTERIOR ELEVATION REFERENCE BUBBLE
INTERIOR ELEVATION REFERENCE BUBBLE
ELEVATION TAG - EXISTING
ELEVATION TAG - NEW
U N
IT
A
U N
IT
B
ROOM NAME
A101A
A 502
ROOM IDENTIFICATION TAG
UNIT MATCHLINES
DETAIL TITLE
TYPICAL NOTATION SYMBOLS
ELEVATION AND SECTION REFERENCE SYMBOLS
WORKING POINT LAYOUT TAG
BORROWED LIGHT AND DOOR IDENTIFICATION
SYMBOLS
METAL STUD/FURRING AND CH STUD KEY
METAL STUD/FURRING
DESIGNATION SIZE
A GYPSUM BOARD DIRECT APPLIED TO CMU
B 7/8"
C 1 1/2"
D 1 5/8"
E 2 1/2"
F 3 1/2"
G 3 5/8"
H 4"
J 5 1/2"
K 6"
L 8"
M 10"
N 12"
P (OPEN)
Q (OPEN)
CH STUD
DESIGNATION SIZE
R 2 1/2"
S 4"
T 6"
1X
1X
PARTITION TYPE TAG (REFER TO FLOOR PLANS)
PARTITION TYPE
NUMBER
METAL STUD, FURRING OR
CH STUD FRAMING LETTER
FIRE-RATING, IF REQUIRED
FIRE-RATING KEY
DESIGNATION PARTITION RATING PRIORITY
3 HOUR 1
2 HOUR FIRE/SMOKE 2
2 HOUR 3
1 HOUR FIRE/SMOKE 4
1HOUR 5
SMOKE RESISTANT 6
1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE
SEALED WITH AN APPROVED U.L. RATED PRODUCT.
2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.
3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE
TREATED WOOD.
4. REFER TO SPECIFICATION U.L. RATING INFORMATION.
5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES
FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS
SHEET
FOR MASONRY WALLS THE MASON SHALL FILL VOIDS WITH MORTAR OR GROUT.
FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BOTH SIDES
METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN ALL
WALLS - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD ON ROOM SIDE - BRACE
WALL @ 4'-0" O.C. MAXIMUM.
METAL STUD CHASE WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
BOND BEAM
SEALANT
FLOOR CONSTRUCTION
4" CONCRETE MASONRY UNITS
CMU WALL
U.L. ASSEMBLY - U905 (1 HOUR AND 2 HOUR)
C H A S E
S
ID
E
R O
O M
S
ID
E
6" CONCRETE MASONRY UNITS
8" CONCRETE MASONRY UNITS
10" CONCRETE MASONRY UNITS
12" CONCRETE MASONRY UNITS
1X 3X
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
SHEET TITLE
SHEET NUMBER
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
TYPICAL
SYMBOLS,
GENERAL
NOTES,
INTERIOR
PARTITION
TYPES AND
FIRE-RATING
KEY
12-194.45
G 002
KELLOGGSVILLE
PUBLIC
SCHOOLS
1" = 0'-1"G 002
1 DETAIL TITLE
GENERAL DEMOLITION NOTES GENERAL NOTES - ARCHITECTURAL
12 FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES
AND CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
13 FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH
FIRE AND/OR SMOKE RATED ASSEMBLIES.
14 FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR
FLOOR PLANS.
15 ALL OUTSIDE CORNERS OF COUNTERTOPS ARE TO HAVE A 1" RADIUS, UNLESS
NOTED OTHERWISE.
16 VERIFY ALL CASEWORK DIMENSIONS IN FIELD.
17 PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
18 PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT
OR ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY
MANUFACTURER.
19 PROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL
ROOF TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE
FILLED WITH INSULATION AS SPECIFIED FOR NOISE CONTROL.
20 ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF
PATCHING TO MATCH EXISTING ADJACENT.
1 THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT
PRIOR TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2 ALL EXISTING CONDITIONS SHALL BE FIELD VERIFIED BEFORE WORK BEGINS.
3 DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR
TO THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4 DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS.
FOR CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN
QUESTION.
5 EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/ DECK
ABOVE UNLESS NOTED OR DETAILED OTHERWISE.
6 WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES
AT ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS,
UNLESS NOTED OTHERWISE.
7 TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.
8 TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE
BLOCK LOCATIONS.
9 STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20ga.
10 STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20ga.
11 DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR
DIMENSIONED OTHERWISE.
1 CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO RELATED DEMOLITION
WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL, FLOOR OR CEILING INCLUDES ALL GENERAL
MECHANICAL AND ELECTRICAL ITEMS WHICH ARE A PART OF, OR ATTACHED TO IT
2 CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS AND BE RESPONSIBLE
FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY AND ALL DISCREPANCIES.
3 PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND DEMOLITION AS REQUIRED.
FINISH TO MATCH EXISTING.
4 ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5 PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6 REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL INFORMATION.
7 REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR ADDITIONAL DEMOLITION
NOTES.
8 SALVAGE ALL UNI-STRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF REQUIRED.
9 REFER TO STRUCTURAL FOR SHORING.
10 AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL ARE TO BE REMOVED.
SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS, TACKBOARDS, TACK STRIPS, ETC.
GENERAL PARTITION NOTES
1 NOT ALL WALL TYPES MAY BE USED ON PROJECT.
2 REFER TO LIFE SAFETY PLANS FOR LOCATIONS OF SMOKE AND FIRE-RATED
PARTITIONS.
3 ALL PARTITIONS EXTEND TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
4 LINE OF STRUCTURE/DECK AS SHOWN AT THE HEAD CONDITION OF EACH PARTITION
TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION
CONDITIONS. TERMINATE RATED PARTITIONS AT UNDERSIDE OF STRUCTURAL DECK
TO MAINTAIN RATING. PROVIDE APPROPRIATE FRAMING AND GYPSUM BOARD TO
OFFSET AROUND STRUCTURE OR OTHER OBSTRUCTIONS, SUCH AS PIPING OR
DUCTWORK.
5 PARTITIONS MAY TERMINATE AT STRUCTURAL MEMBERS WITH A RATING GREATER
THAN OR EQUAL THE PARTITION, PROVIDED THAT RATING IS CONTINUOUS TO
STRUCTURAL DECK ABOVE.
6 NON-RATED PARTITIONS THAT EXTEND TO STRUCTURE SHALL TERMINATE AT
UNDERSIDE OF STRUCTURAL DECK TO MAINTAIN A CONTINUOUS PLANE OF GYPSUM
BOARD AS A NOISE, SMOKE OR OTHER TYPE OF BARRIER.
7 ALL PARTITIONS EXTENDING TO STRUCTURE ABOVE SHALL TERMINATE WITH
DEFLECTION TRACK - SEE TYPICAL DETAILS ON THIS SHEET.
8 ALL GYPSUM BOARD PARTITIONS NOT EXTENDING TO THE STRUCTURE MUST BE
BRACED.
9 UL DESIGN NUMBERS REFER TO THE FIRE RESISTANCE DIRECTORY. UNDERWRITERS
LABORATORY, LATEST EDITION.
10 MISCELLANEOUS NON-RATED CHASES TO BE 5/8" GYPSUM BOARD ON 3 5/8" METAL
STUD FRAMING @ 16" O.C., UNLESS NOTED OTHERWISE.
11 MISCELLANEOUS FURRING AROUND COLUMNS TO BE 5/8" GYPSUM BOARD ON
11/2" STUDS, UNLESS NOTED OTHERWISE.
12 FIRE-RATED PARTITIONS TO HAVE FIRE-STOPPING SEALANTS AT HEAD, SILL JUNCTURE
WITH DISSIMILAR MATERIALS, ETC. AND AROUND ALL PENETRATIONS AND OPENINGS.
13 CONSTRUCT ALL PARTITIONS WITH SOUND ATTENUATION BATTS WITH THE FOLLOWING
SOUND BATT THICKESS: 2 1/2" OR LESS METAL STUD - 1 1/2" THICKNESS, 3 5/8"
OR LARGER METAL STUD - 3" THICKNESS. UNLESS NOTED OTHERWISE.
DN
1 HR
HR
1 HR
OFFICE
MEDIA CENTER
CORRIDOR
STORAGE
OFFICE
E G
R E
S S
C L A
S S
R O
O M
E
G R
E S
S
S T
O R
A G
E
116A
115A
TRAVEL D
IS
TANCE 5
4 F
EET
75 F
EET P
ERM
IT
TED
TRAVEL DISTANCE 142 FEET
200 FEET PERMITTED
TRAVEL DISTANCE 39 FEET
75 FEET PERMITTED
E G
R E
S S
M E
D
IA
C E
N T
E R
CLASSROOM
TRAVEL DISTANCE 39 FEET
75 FEET PERMITTED
116B
115B
FIRE-RATING KEY & SYMBOLS
DESIGNATION PARTITION RATING
2 HOUR FIREWALL PROVIDE FROM FLOOR TO UNDERSIDE OF ROOF DECK ABOVE.
CONSTRUCTION SHALL BE CONTINUOUS THROUGH CEILING CAVITIES.
WALL SHALL ALLOW STRUCTURAL COLLAPSE ON EITHER SIDE OF WALL
UNDER FIRE CONDITIONS WITHOUT DAMAGE TO WALL. PROVIDE WITH
90-MINUTE LABELED DOORS W/ CLOSER
1HOUR PROVIDE FROM FLOOR TO UNDERSIDE OF FLOOR OR ROOF DECK
ABOVE. CONSTRUCTION SHALL BE CONTINUOUS THROUGH CEILING
CAVITIES. AT PENETRATIONS THROUGH PARTITION, SEAL OPENINGS
AROUND HVAC, FIRE PROTECTION, PLUMBING, & ELECTRICAL
PENETRATIONS WITH FIRESTOPPING. PROVIDE WITH 45-MINUTE LABELED
DOORS W/ CLOSER EXCEPT PROVIDE 60-MINUTE LABEL FOR STAIR
DOORS.
EGRESS
ROOM
OCCUPANTS
EXIT NUMBER FROM ROOM OR SPACE
MAXIMUM NUMBER OF OCCUPANTS THE EGRESS WIDTH WILL ALLOW
ROOM OR SPACE EGRESS IS FROM
FIRE EXTINGUISHER CABINET: PROVIDE WITH TOP OF OPENING INSTALLED AT 60” AFFFEC
FIRE EXTINGUISHER: PROVIDE MULTIPURPOSE 10LBS. CLASS 4.A:60BC ON HANGER AT 48” AFF
FIRE CODE SYMBOLS
FE
FW
2015 Michigan Building Code:
2015 Michigan Building Code
Section 305 E Group, Type IIB Construction
Table 504.3 Allowable Building Height in Feet Above Gade Plane
E Group, Type IIB Construction, Non-Sprinkled = 55ft.
Table 506.2 Allowable Area Factor in Square Feet
E Group, Type IIB Construction, Non-Sprinkled = 14,500 sq. ft.
Total Building Area: 32,622 Square Feet
1,964 Square Feet - First Floor Renovation
588 Square Feet - First Floor Storage Room Renovation
30,070 Square Feet - First Floor Existing
Table 601
Construction Type: IIB
Structural Framing Members = 0 Hr fire rating
Bearing Walls (Ext.) = 0 Hr fire rating
Bearing Walls (Int.) = 0 Hr fire rating
Nonbearing walls and partitions (Ext. and Int.) = 0 Hr fire rating
Floor Construction = 0 Hr fire rating
Roof Construction = 0 Hr fire rating
Table 602.1
Type IIB - Construction that is that type of construction in which the building elements listed in table 601 are of noncombustible materials, except as permitted in section 603 and elsewhere in this code.
Section 706.4 - Fire walls are not required for this project as the building floor area does not exceed the maximum allowed.
Section 707.3.10 Fire Areas. The fire barriers or horizontal assemblies, or both, separating a single occupancy into different fire areas shall have a fire-resistance rating of not less than that indicated in Table 707.3.10. The fire barriers or horizontal assemblies, or both, separating fire areas of mixed occupancies shall have a fire-resistance rating of not less than the highest value indicated in Table 707.3.10 for the occupancies under construction.
Section 708.3 Fire-resistance ratings. Fire partitions shall have a fire-resistance rating of not less than 1 hour.
Section 803 – Interior Finishes
Table 803.9
Use Group E, (not sprinkled)
Exit Enclosures and Exit Passageways = A
Corridors = B
Rooms and Enclosed Spaces = C
Section 906 – Portable Fire Extinguishers. Portable fire extinguishers shall be installed in the following locations: Table 906.3 Maximum Travel Distance to Fire Extinguisher 75 feet.
1. In existing R-2 occupancy
2. Within 30 feet of commercial cooking equipment
3. In areas with flammable or combustible liquids
4. On each floor of structures under construction
5. Where required by the International Fire Code Sections indicated in Table 906.1
6. Special-Hazard areas
Section 1004.1 Occupant Load. In determining the means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 1004.1.1 through
1004.1.3.
Table 1004.1.2 Maximum Floor Area Allowances per Occupant
Accessory Storage / Mechanical Equip. Rooms 300 gross
Educational - Shops and other vocational room areas 50 net
Business Areas 100 gross
Section 1005 Minimum Required Egress Width. The means of egress width shall not be less than required by this section.
An Occupancy with Sprinkler System Stairway means of egress = 0.2
An Occupancy with Sprinkler System all other means of egress = 0.2
Table 1006.2.1 Spaces With One Exit or Exit Access Doorway
Group E, Without Sprinkler System = 75 Feet
Section 1015.2.1 Where two exits or exit access doorways are required from any portions of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half the diagonal distance of the space.
Table 1017.2 Exit Access Travel Distance: Group E Without Sprinkler = 200 Feet
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
SHEET TITLE
SHEET NUMBER
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
OVERALL CODE
COMPLIANCE
PLAN
12-194.45
G 101
KELLOGGSVILLE
PUBLIC
SCHOOLS
3/32" = 1'-0"
OVERALL FIRST FLOOR CODE COMPLIANCE PLAN
ISSUED FOR DATE
WEST ELEMENTARY
KEY PLAN
SCALE: NO SCALE
0'
5'
10'
15' 25'
1/8" = 1'-0" GRAPHIC SCALE
RENOVATION
AREAS
STRUCTURAL GENERAL NOTES:
1.
TOB
CJ
CMU
EF
EW
OC
UNO
TOS
TOJ TOJ
TOWTOW
FFEFFE
TP
WWF
EL
BL
SEISMIC DESIGN CATEGORY
DESIGN ROOF DEAD LOADS:
DESIGN LIVE LOADS:
LOAD TYPE
ROOF DECK
MEMBRANE/INSULATION
FRAMING
CEILING
LIGHTS
MISC. MECH.
TOTAL
LOAD
LOCATION
STORAGE ROOMS
MECHANICAL ROOMS
STAIRS
WIND
LOAD
125 PSF
125 PSF
100 PSF
2.0 PSF
SEISMIC SITE CLASS
ABBREVIATIONS:7.
= TOP OF FOOTING ELEVATION
= TOP OF PIER ELEVATION
= FINISHED FLOOR ELEVATION
= TOP OF WALL ELEVATION
= TOP OF JOIST ELEVATION
= TOP OF STEEL ELEVATION
= TOP OF BEAM ELEVATION
= CONTROL OR CONSTRUCTION JOINT
= CONCRETE MASONRY UNIT
= EACH FACE
= EACH WAY
= ON CENTER
= UNLESS NOTED OTHERWISE
= WELDED WIRE FABRIC
= ELEVATION
= BRICK LEDGE ELEVATION
2.
3.
4.
5.
4.0 PSF
5.0 PSF
GROUND SNOW LOAD 35 PSF
GROUND FLOOR 100 PSF
MAPPED Ss
MAPPED S1
SDS
SD1
ANCHORS:
1.
2.
3.
4.
5.
6.
1.
SUBMITTALS:
2.
3.
4.
STRUCTURAL GENERAL NOTES
ALL SHOP DRAWINGS AND SUBMITTALS MUST BE REVIEWED AND APPROVED BY THE
CONTRACTOR PRIOR TO SUBMITTAL. ENGINEER'S REVIEW OF SHOP DRAWINGS IS LIMITED
TO CHECKING FOR GENERAL CONFORMANCE WITH DESIGN DRAWINGS AND STRENGTH OF
COMPONENTS AND MATERIALS. CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES FROM
DESIGN DRAWINGS, QUANTITIES, DIMENSIONAL ERRORS OR OMISSIONS IN THE SHOP
DRAWINGS.
ALL SHOP DRAWINGS MUST BE CONTRACTOR CREATED DOCUMENTS AND SHALL NOT BE
REPRODUCTIONS OF THE A/E CONTRACT DOCUMENTS.
SUBMIT SHOP DRAWINGS DETAILING FABRICATION OF EACH MEMBER AND ITS
CONNECTIONS. SHOP DRAWINGS ARE TO BE PREPARED UNDER THE SUPERVISION OF A
LICENSED PROFESSIONAL ENGINEER.
CONTRACTOR SHALL SUBMIT TECHNICAL INFORMATION, CALCULATIONS AND/OR SHOP
DRAWINGS ACCORDING TO THE SPECIFICATIONS FOR THE FOLLOWING:
EXPANSION ANCHORS SHALL BE HILTI KWIK BOLT II ANCHORS UNLESS NOTED OTHERWISE.
MINIMUM EMBEDMENT UNLESS NOTED OTHERWISE SHALL BE:
3•" FOR •" DIAMETER ANCHORS
4" FOR †" DIAMETER ANCHORS
4ƒ" FOR ƒ" DIAMETER ANCHORS
EPOXY ANCHORS SHALL USE HILTI HIT HY 20 ADHESIVE WITH SCREEN TUBES IN HOLLOW
MASONRY & HILTI HIT HY 150 ADHESIVE IN CONCRETE OR SOLID GROUTED MASONRY
UNLESS NOTED OTHERWISE ON THE DRAWINGS.
MINIMUM EMBEDMENT FOR EPOXY ANCHORS IN NORMAL WEIGHT CONCRETE UNLESS NOTED
OTHERWISE SHALL BE:
4‚" FOR •" DIAMETER ANCHORS
5" FOR †" DIAMETER ANCHORS
6†" FOR ƒ" DIAMETER ANCHORS
8‚" FOR 1" DIAMETER ANCHORS
EMBEDMENT DEPTH SHALL BE DEFINED AS THE DISTANCE FROM THE SURFACE OF THE
LOAD-BEARING BASE MATERIAL TO THE DEEPEST PART OF THE ANCHOR AFTER THE
ANCHOR HAS BEEN DRIVEN INTO THE HOLE BUT NOT YET EXPANDED.
EQUIVALENT ANCHORS MAY BE SUBMITTED FOR THE ENGINEERS APPROVAL. SUBMITTALS
ARE THE CONTRACTOR'S RESPONSIBILITY AND MUST INCLUDE EVALUATION REPORTS FROM
THE INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS.
STAINLESS STEEL ANCHORS ARE REQUIRED AT ALL EXPOSED WEATHER CONDITIONS.
MASONRY (CMU)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
MATERIAL PROPERTIES:
MASONRY 28 DAY COMPRESSIVE STRENGTH f'm=1500 PSI
MORTAR (TYPE N) ASTM C270
GROUT FOR BOND BEAMS AND VERTICAL REINFORCING ASTM C476
GROUT 28 DAY COMPRESSIVE STRENGTH 2000 PSI
REFER TO ARCHITECTURAL DRAWINGS FOR MASONRY CONTROL OR EXPANSION JOINT
LOCATIONS.
ALL MASONRY WALLS SHALL BE REINFORCED WITH LADDER TYPE HORIZONTAL JOINT
REINFORCEMENT PLACED EVERY OTHER COURSE FOR RUNNING BOND AND EVERY COURSE
FOR STACK BOND. PROVIDE GALVANIZED WIRE REINFORCEMENT WITH #9 GAGE SIDE RODS
AND #9 GAGE CROSS RODS SPACED 16" O.C.. FOR TWO WYTHE WALLS, PROVIDE THREE
SIDE RODS AND A CAVITY DRIP.
OPENING STEEL LINTEL PER
SIZE 4" OF WALL THICKNESS
> 2'-0" TO 4'-0" INCL É5x3•xŠ
PROVIDE A MINIMUM OF 8" BEARING AT EACH END OF ALL LINTELS UNLESS OTHERWISE
NOTED.
VERTICAL REINFORCING SHALL BE LAPPED AND HELD IN POSITION WITH BAR POSITIONERS.
MINIMUM BAR LAPS AS FOLLOWS:
#3 - 18"
#4 - 24"
#5 - 30"
#6 - 36"
#7 - 42"
#8 - 48"
NO CHASES, RISERS, CONDUITS OR TOOTHING OF MASONRY SHALL OCCUR IN MASONRY
WALLS WITHIN 18" OF CENTERLINE OF BEAM BEARING.
GROUT SOLID ALL REINFORCED CELLS, CELLS BELOW GRADE, AND ALL CELLS BELOW
FINISH FLOOR.
MAXIMUM HEIGHT OF GROUT POUR SHALL NOT EXCEED 5'-0".
VERTICAL CELLS TO BE GROUTED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO
MAINTAIN A TOTAL MINIMUM CLEAR AREA OF 3"x3". ALL OVERHANGING MORTAR, OBSTRUCTIONS AND DEBRIS SHALL BE CLEANED FROM THE INSIDE OF CELLS PRIOR TO
GROUTING.
REINFORCEMENT SHALL BE PLACED PRIOR TO GROUTING.
UNITS SHALL BE PLACED TO THE FULL HEIGHT OF THE GROUT POUR AND GROUT SHALL
BE PLACED IN A CONTINUOUS LIFT. BETWEEN GROUT POURS, A HORIZONTAL
CONSTRUCTION JOINT SHALL BE FORMED BY STOPPING GROUT 1•" BELOW MORTAR
JOINT EXCEPT AT THE TOP OF THE WALL.
ALL CMU WALLS SHALL BE REINFORCED VERTICALLY AS SPECIFIED ON DRAWINGS WITH
THE SPECIFIED BAR FOR THAT WALL AT THE ENDS OF WALLS, AT EACH SIDE OF
CONTROL OR EXPANSION JOINTS, AND AT EACH SIDE OF OPENING, ALL IN FULLY GROUTED
CELLS. IF REINFORCING IS NOT SHOWN ON DRAWINGS, REINFORCE w/ #5 BARS @ 4'-0" ON
CENTER.
PROVIDE BOND BEAMS AT THE TOP OF EACH WALL, ABOVE AND BELOW OPENINGS, AND
WHERE SHOWN. BOND BEAMS SHALL HAVE TWO #5 CONTINUOUS HORIZONTAL BARS AND
SHALL BE FULLY GROUTED. VERTICAL REINFORCING BARS SHALL EXTEND INTO THE BOND
BEAM.
PROVIDE DOWELS INTO FLOOR OR FOUNDATION AT BOTTOM OF WALL TO MATCH SIZE
AND SPACING OF VERTICAL WALL REINFORCING (UNLESS NOTED OTHERWISE ON
DRAWINGS).
PROVIDE WALL STABILITY CONNECTIONS AT TOP OF ALL WALLS UNLESS NOTED
OTHERWISE.
MBC=MICHIGAN BUILDING CODE
ASCE=AMERICAN SOCIETY OF CIVIL ENGINEERS
SER=STRUCTURAL ENGINEER OF RECORD
ASD=ALLOWABLE STRESS DESIGN
ASTM=AMERICAN SOCIETY FOR TESTING OF MATERIALS
ACI=AMERICAN CONCRETE INSTITUTE
AISC=AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI-AMERICAN IRON AND STEEL INSTITUTE
SJI=STEEL JOIST INSTITUTE
SDI=STEEL DECK INSTITUTE
AWS=AMERICAN WELDING SOCIETY
MSJC=MASONRY STANDARDS JOINT COUNCIL
RCSC=RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS
5.0 PSF
THERMAL FACTOR
SNOW EXPOSURE FACTOR 1.0
SNOW LOAD IMPORTANCE 1.1
BUILDING CATEGORY
INT. PRESSURE COEFF.
COMPONENTS/ CLADDING
± 0.18
0' TO 2'-0" INCL É5x3•x‚
CONCRETE:
28 DAYS
60,000
FY, PSI
60,000
65,000
AIR
CONTENT
ASTM
A-615
A-615
A-185
4" MAX
MAX SLUMP
(PER ASTM C-143)
4000(w/c<.50)
4000(w/c<.44)
60,000 A-706
6% ± 1.5%
LOCATION
REINFORCING STEEL
COLUMN TIES
ALL OTHER BARS
WELDED WIRE FABRIC
WELDED REINFORCEMENT
ALL MATERIAL AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE PROJECT
SPECIFICATIONS, THE AMERICAN CONCRETE INSTITUTE (ACI) MANUAL OF CONCRETE
PRACTICE, AND ACI SPECIFICATIONS 301, 305, 306, 315, 318 AND 347.
MATERIAL PROPERTIES: F'C PSI @
4" MAX
3" MAX AT
RAMPS AND
SLOPING
SURFACES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
20.
21.
22.
23.
24.
THE CONCRETE MIX DESIGN SHALL BE PROPORTIONED TO LIMIT PLASTIC SHRINKAGE BY
MINIMIZING THE WATER CONTENT.
NO WATER MAY BE ADDED TO THE CONCRETE MIX ON SITE, UNLESS WATER IS WITHHELD
AT THE BATCHING FACILITY. IF WATER IS WITHHELD AT THE BATCHING FACILITY IT
SHOULD BE REFLECTED ON THE LOAD TICKET. THE TOTAL AMOUNT OF THE WATER IN
THE MIX SHALL NOT EXCEED WHAT IS NOTED ON THE APPROVED MIX. THE SPECIAL
INSPECTOR SHALL RECORD THE TOTAL WATER CONTENT OF EACH INSPECTED LOAD IN
HIS DAILY REPORTS.
SEE SPECIFICATIONS FOR ALL TESTING AND OTHER ADDITIONAL REQUIREMENTS. SUBMIT
CONCRETE MIX DESIGNS TO STRUCTURAL ENGINEER FOR APPROVAL PER SPECIFICATIONS
ALL ACCESSORIES FOR SUPPORTING REINFORCING SHALL BE GALVANIZED OR HAVE
PLASTIC-COATED FEET OR BE STAINLESS STEEL PROTECTED.
REINFORCING SHALL BE DETAILED, FABRICATED, PLACED, AND SUPPORTED IN ACCORDANCE
WITH ACI 315, LATEST EDITION.
WITH A MINIMUM 2" OF CONCRETE COVER FOR PROTECTION AND STEEL SHALL BE
COATED WITH A BITUMINOUS COATING.
ALL CONCRETE SHALL BE CURED FOR A MINIMUM TIME PERIOD PER SPECIFICATIONS
BEFORE REMOVAL OF FORMS.ON FORMS WHERE VERTICAL SURFACES ARE REMOVED
BEFORE THE END OF THE CURING PERIOD, COAT SURFACES WITH LIQUID CURING
COMPOUND.
PROVIDE CONTINUITY OF WALL AND FOOTING REINFORCING AT CORNERS WITH BENT BARS
THE SAME SIZE AND SPACING AS HORIZONTAL WALL REINFORCING.
PROVIDE CORNER BARS AT THE EXTERIOR FACE OF WALL AND FOOTING CORNERS EQUAL
TO HORIZONTAL BARS.
AT ALL STEPS IN FOUNDATION WALLS, PROVIDE AT LEAST TWO VERTICAL #5 DOWELS
INTO FOOTINGS AND GRADE BEAMS.
ALL OPENINGS IN SLABS AND WALLS SHALL HAVE REINFORCING ON EACH SIDE EQUAL TO
THE AMOUNT OF REINFORCING DISPLACED.
SEE ARCHITECTURAL DRAWINGS FOR SIZE, DEPTH, AND LOCATION OF DEPRESSED FLOOR
SLABS TO RECEIVE SPECIAL FINISHES.
PROVIDE CLASS B TENSION LAP SPLICES FOR ALL BARS UNLESS OTHERWISE NOTED.
TENSION LAP SPLICES SHALL MEET THE REQUIREMENTS OF ACI AND CRSI FOR EACH
CONDITION. LAP LENGTHS MUST BE INCREASED PER ACI 318 FOR THE FOLLOWING
CONDITIONS:
A. TOP BARS
B. BARS WITH LESS THAN 2db COVER.
C. BARS WITH LESS THAN 3db CLEAR SPACING.
USE NON-SHRINK, NON-METALLIC GROUT UNDER ALL BASE PLATES, BEARING PLATES, AND
SETTING PLATES.
PRIOR TO PLACING CONCRETE IN ANY LOCATION, VERIFY AND COORDINATE ALL
DIMENSIONS, ELEVATIONS, OPENINGS, RECESSES AND BLOCKOUTS SHOWN ON THE
ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS. IN THE EVENT ERRORS,
CONFICTS, OR OMISSIONS EXIST, CONTACT THE ARCHITECT OR ENGINEER FOR NECESSARY
CORRECTIVE ACTION.
EMBEDDED ITEMS ARE TO BE FURNISHED AND INSTALLED PRIOR TO PLACING CONCRETE.
ANCHOR RODS SHALL BE HELD IN PLACE WITH A RIGID TEMPLATE.
WELDED WIRE FABRIC LOCATED 1" CLEAR FROM TOP OF SLAB.
ALL EXPOSED EDGES OF CONCRETE PIERS, BEAMS AND WALLS SHALL BE CHAMFEREDƒ" x 45 DEGREES.
WHEN PLACING FLOOR CONCRETE OVER COMPOSITE METAL DECK, THE POUR SHALL
START AT THE MIDSPAN OF THE FLOOR BEAMS AND PROCEED TOWARD THE ENDS (TO
MINIMIZE VARIATIONS IN FLOOR SLAB THICKNESS).
FTGS/FOUNDATION WALLS
0.07g
0.05g
6.
ALL EXTERIOR COLUMNS, BASE PLATES, AND ANCHOR BOLTS BELOW GRADE SHALL BE COVERED
FLAT ROOF SNOW (WARM)
GGBS = GROUND GRANULATED BLAST-FURNACE SLAG
EXTERIOR SLAB ON GRADE AND
ALL NON-STRUCTURAL CONCRETE
EXPOSED TO WEATHER.
SPECIAL INSPECTIONS (PER 2015 MICHIGAN BUILDING CODE)
SPECIAL INSPECTIONS REQUIRED (CONTINUOUS OR PERIODIC AS REQUIRED BY THE CODE):
WHERE APPLICATION IS MADE FOR CONSTRUCTION, THE OWNER OR THE CONSTRUCTION
MANAGER ACTING AS THE OWNERS AGENT SHALL EMPLOY ONE OR MORE SPECIAL
INSPECTORS TO PROVIDE INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK
LISTED UNDER SECTION 1704. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO
SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL, FOR
INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL
INSPECTION.THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS BY THE RESIDENT
BUILDING INSPECTOR SPECIFIED IN SECTION 109.
SECTION 1704.2:
FABRICATOR SHOP INSPECTION UNLESS THE FABRICATOR IS REGISTERED AND APPROVED TO
PERFORM WORK WITHOUT INSPECTION BY AN APPROVED SPECIAL INSPECTION AGENCY.
SECTION 1704.3:
STEEL CONSTRUCTION INCLUDING WELDING, BOLTING, REINFORCING STEEL, MATERIAL
VERIFICATION, AND STEEL FRAME JOINT DETAILS PER TABLE 1704.3.
SECTION 1704.4:
CONCRETE CONSTRUCTION INCLUDING FOOTINGS, REINFORCING PLACEMENT, EMBEDDED ITEMS
PLACEMENT, CURING TECHNIQUES, ERECTION OF PRECAST MEMBERS, AND MATERIAL TESTING
PER TABLE 1704.4.
SECTION 1704.5:
MASONRY CONSTRUCTION INCLUDING PROPORTIONS OF MORTAR AND GROUT, GROUT SPACE
AND REINFORCEMENT PLACEMENT , GROUTING OPERATIONS, ANCHORAGE TO STRUCTURAL
MEMBERS, COLD AND HOT WEATHER MASONRY PROTECTION, AND MATERIAL TESTING PER
TABLE 1704.5.1 (REQUIRED FOR CATEGORY I OR II FACILITIES) OR 1704.5.3 (REQUIRED FOR
CATEGORY III FACILITIES). REFER TO THE GENERAL NOTE SECTION ON THIS SHEET FOR
CATEGORY DESIGNATION.
SECTION 1704.7:
SOIL INSPECTION INCLUDING SITE PREPARATION, FILL PLACEMENT, AND EVALUATION OF
IN-PLACE DENSITY.
THESE NOTES SUPPLEMENT THE PROJECT SPECIFICATIONS. SEE PROJECT
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS INDICATED ON DRAWINGS. IN THE
EVENT OF A CONFLICT IN DIMENSIONS BETWEEN ARCHITECTURAL AND STRUCTURAL
DRAWINGS, NOTIFY ARCHITECT OR ENGINEER IMMEDIATELY.
SEE THE PROJECT SPECIFICATIONS FOR ALL TESTING REQUIREMENTS.
CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE LOCAL, STATE, AND FEDERAL CODE
REQUIREMENTS.
NOTES
GENERAL
STRUCTURAL
FLAT ROOF SNOW (COLD)
4000 (w/c<.48) 6% ± 1.5% 4" MAXRETAINING WALLS
19. PROVIDE CONCRETE COVER OVER REINFORCING BARS AS FOLLOWS UNLESS NOTED
OTHERWISE:
A. CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH = 3"
B. PERMANENTLY EXPOSED TO EARTH OR WEATHER= 2"
C. NOT EXPOSED TO EARTH OR WEATHER
WALLS, SLABS= ƒ"
BEAMS, COLUMNS= 1 •"
4000 (w/c<.44) 4" MAX
2.0 PSF
20 PSF
1.0(WARM), 1.1 (COLD)
III
SEISMIC OCCUPANCY CATEGORY III
SEISMIC IMPORTANCE FACTOR 1.25
SEISMIC RESPONSE COEFF (Cs)
RESPONSE MOD. FACTOR (R) 2
INTERIOR SLAB ON GRADE
TOF
PROVIDE DOWELS IN WALL FOOTINGS WITH EQUAL SIZE AND SPACING AS VERTICAL REINFORCING.
ALL CONCRETE SLABS ON METAL DECK SHALL BE REINFORCED WITH 6"X6"-W2.1XW2.1
50,000
46,000
E70XX
92,000
36,000
36,000
42,000
A36
STRUCTURAL BOLTS
ANGLES AND CHANNELS
HSS ROUND
STRUCTURAL STEEL WF SHAPES
STRUCTURAL PLATES,
HSS RECTANGULAR (AND SQUARE)
WELDING ELECTRODES
ANCHOR BOLTS
ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE
WITH THE LATEST EDITIONS OF: THE AISC MANUAL OF STEEL CONSTRUCTION -
ALLOWABLE STRESS DESIGN, THE AISC CODE OF STANDARD PRACTICE FOR STEEL
BUILDINGS, AND AWS D1.1 STRUCTURAL WELDING CODE.
MATERIAL PROPERTIES: Fy, PSI ASTM SPECIFICATION
A992 OR A572 GR 50
A500 GRADE B
A500 GRADE B
AWS D1.1
A325
F1554 GRADE 36
STRUCTURAL STEEL/STEEL JOISTS/METAL DECK:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
A. FLOOR DECK
1.)
2.)
1.)
2.)
B. ROOF DECK
WELD DECK PANELS TO SUPPORTING MEMBERS INCLUDING PERIMETER
STEEL AND/OR BEARING WALLS WITH †" DIA PUDDLE WELDS SPACED
12"OC OR LESS.
OR 36" INTERVALS, WHICHEVER DISTANCE IS SMALLER
WELD DECK PANELS TO SUPPORTING MEMBERS INCLUDING PERIMETER
STEEL AND/OR BEARING WALLS WITH †" DIA PUDDLE WELDS SPACED
12"OC OR LESS (36/4 PATTERN).
SCREW (MIN SCREW SIZE = No.10 TEK) SIDE LAPS AT 3 LOCATIONS PER
SPAN OR 36" INTERVALS, WHICHEVER DISTANCE IS SMALLER.
FIELD CUT ALL METAL ROOF DECK OPENINGS SHOWN ON THE ARCHITECTURAL,
STRUCTURAL, ELECTRICAL AND MECHANICAL DRAWINGS AND REINFORCE ALL OPENINGS
WHERE ANY DIMENSION IS 12" OR LARGER.
DO NOT ATTACH OR HANG EQUIPMENT, CONDUIT, PIPING OR ANY OTHER MATERIALS FROM
THE METAL FLOOR OR ROOF DECK UNLESS APPROVED BY THE ARCHITECT. ANY
SUPPLEMENTAL FRAMING REQUIRED TO HANG FROM THE BEAM, GIRDERS, OR JOISTS SHALL
BE THE RESPONSIBILITY OF THE APPROPRIATE SUBCONTRACTOR.
ANY PIPING, CONDUIT, OR EQUIPMENT TO BE HUNG FROM STEEL JOISTS SHALL BE
ATTACHED WITHIN 3" OF JOIST PANEL POINTS OR AUXILIARY FRAMING TO THE PANEL
POINTS SHALL BE PROVIDED.
THE CONTRACTOR SHALL PROVIDE SHELF ANGLES, GLASS SUPPORTS, LINTELS AND OTHER
MISCELLANEOUS STEEL, AS SHOWN ON THE DRAWINGS AND WHERE REQUIRED TO PROVIDE
LOAD BEARING SUPPORT THROUGHOUT THE BUILDING. NOT EVERY DETAIL IS SHOWN.
STEEL CONTRACTOR SHALL REVIEW ARCHITECTURAL, MECHANICAL, AND OTHER DRAWINGS
FOR ADDITIONAL MISCELLANEOUS STEEL DETAILS AND REQUIREMENTS.
IMMEDIATELY AFTER WELDING DECK AND OTHER METAL
COMPONENTS IN POSITION, COAT WELDS, BURNED AREAS,
AND DAMAGED SURFACE COATING, WITH ZINC RICH PRIME
PAINT.
UNLESS NOTED OTHERWISE, FABRICATOR SHALL DESIGN BEAM CONNECTIONS FOR
REACTION VALUES GIVEN IN THE ALLOWABLE UNIFORM LOAD TABLES IN CHAPTER 2 OF
THE MANUAL OF STEEL CONSTRUCTION. CONNECTIONS SHOULD BE SHOP WELDED AND
FIELD BOLTED. TYPICAL CONNECTIONS SHOULD ASSUME BEARING TYPE "N" SNUG
TIGHTENTED BOLTS. PROVIDE AT LEAST TWO BOLTS PER CONNECTION.
ALL SHOP AND FIELD WELDING SHALL BE PERFORMED BY A QUALIFIED WELDER AND
SHALL CONFORM TO THE CURRENT REQUIREMENTS OF A.W.S. D1.1
STEEL JOISTS AND JOIST GIRDERS SHALL BE FABRICATED AND ERECTED (INCLUDING
BRIDGING) IN ACCORDANCE WITH THE LATEST SPECIFICATIONS OF THE STEEL JOIST
INSTITUTE AND OSHA REQUIREMENTS. JOIST BEARING SEATS SHALL BE 2•" DEEP FOR K
SERIES JOISTS AND 5" DEEP FOR LH SERIES JOISTS. DESIGN ROOF JOISTS AND
CONNECTIONS FOR 30 PSF NET UPLIFT AND 45 PSF NET UPLIFT WITHIN 10 FEET OF
ROOF EDGES. ENDS OF BRIDGING LINES TERMINATING AT A MASONRY WALL OR STEEL
BEAM SHALL BE ANCHORED THERETO. ENDS OF BRIDGING TERMINATING AT OTHER
LOCATIONS SHALL HAVE DIAGONAL CROSS BRACING BETWEEN THE LAST TWO JOISTS IN
ADDITION TO HORIZONTAL BRIDGING.
"LH" SERIES JOISTS SHALL BEAR 6" MIN. ON MASONRY AND 4" MIN. ON STEEL, AND
SHALL BE FASTENED WITH TWO ‚" FILLET WELDS 2" LONG (MINIMUM.) "K" SERIES
JOISTS SHALL BEAR 4" MIN. ON MASONRY WALLS AND 2•" MIN. ON STEEL, AND SHALL
SEE PLANS FOR METAL FLOOR AND ROOF DECK. PROVIDE CONTINUOUS DECK ANGLE
SUPPORTS OR BENT PLATES AROUND PERIMETER OF DECK AREAS, AND AROUND FLOOR
OPENINGS WHERE CONCRETE BULKHEADS ARE REQUIRED. SEE DETAILS FOR TYPICAL SIZE
AND LOCATIONS.
ALL COLUMNS SHALL EXTEND TO TOP OF BEAMS UNLESS NOTED OTHERWISE.
FIELD CUTTING OR ALTERING STRUCTURAL STEEL MEMBERS AND CONNECTIONS IS NOT
PERMITTED WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
GUYS, BRACING, AND FALSEWORK AS REQUIRED TO MAINTAIN STABILITY AND STRENGTH
DURING ERECTION. THESE TEMPORARY SUPPORTS SHALL BE SUFFICIENT TO MAINTAIN
STABILITY OF THE FRAME AGAINST WIND AND ERECTION INDUCED LOADS; AND SHALL
REMAIN IN PLACE UNTIL ALL CONNECTIONS OF THE STEEL FRAME, METAL DECK, SHEAR
WALLS, AND BRACING HAVE BEEN COMPLETED.
COMPOSITE STEEL FLOOR BEAMS AND METAL FLOOR DECK HAVE BEEN DESIGNED
WITHOUT SHORING DURING CONCRETE PLACEMENT.
ALL HORIZONTAL BRACING SHALL BE PLACED TIGHT TO UNDERSIDE OF STEEL FRAME AND
CONNECTED TO PREVENT SAG. ALL VERTICAL BRACING SHALL BE CONCEALED BEHIND
OR WITHIN WALLS.
METAL DECK SHALL BE FASTENED IN ACCORDANCE WITH THE STEEL DECK INSTITUTE
CODE OF STANDARD PRACTICE AND DIAPHRAGM DESIGN MANUAL. UNLESS NOTED
OTHERWISE ON PLANS OR DETAILS; PROVIDE THE FOLLOWING CONNECTIONS:
PROVIDE LINTELS FOR MISC MECHANICAL OPENINGS PER THE FOLLOWING TABLE UNLESS OTHERWISE
NOTED ON THE DRAWINGS:
S001
2.0 PSF
CONCRETE MIX DESIGN AND MATERIALS
CONCRETE AND MASONRY REINFORCING STEEL
MASONRY MATERIALS
ANCHOR BOLT PLANS AND DETAILS
STRUCTURAL STEEL, JOISTS AND STEEL DECK
FOUNDATIONS:
1.
WORK, UNLESS SPECIFIED OR DETAILED OTHERWISE.
DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL FLOOR SLABS ARE IN PLACE AT
CORE DRILLING WILL BE ALLOWED WITHOUT PRIOR APPROVAL BY THE STRUCTURAL
ENGINEER. COORDINATE LOCATION AND SIZE OF OPENINGS WITH APPLICABLE
CONTRACTORS.
ALL FOUNDATION WALL FOOTINGS SHALL PROJECT A MINIMUM OF 4" BEYOND THE FACE
OF WALLS UNLESS NOTED OTHERWISE.
DO NOT REPAIR MISPLACED OR DAMAGED COLUMN ANCHOR BOLTS WITHOUT PRIOR
APPROVAL BY THE STRUCTURAL ENGINEER.
WHERE FOUNDATION WALLS ARE TO HAVE EARTH PLACED ON EACH SIDE, PLACE FILL ON
ALTERNATING SIDES OF WALL IN 12" LIFTS.
VARIANCE WITH THE GEOTECHNICAL REPORT OR WHEN DIFFERENT BEARING MATERIAL IS
EVIDENT AND THERE IS A QUESTION OF BEARING CAPACITY.
CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND DISPOSAL OF UNSUITABLE
SOILS AND ORGANIC MATERIAL.
3.
4.
5.
6.
7.
8.
9.
10.
TOP AND BOTTOM OF WALL AND CONCRETE HAS REACHED DESIGN STRENGTH
(UNLESS NOTED OTHERWISE).
FOUNDATIONS SHALL BEAR ON SOILS HAVING A MINIMUM ALLOWABLE BEARING PRESSURE 2.
PERMANENT CORRUGATED SLAB FORMS SHALL BE FABRICATED FROM ASTM A653
FORM DECK SHALL COMPLY WITH SDI PROVISIONS.
STEEL ROOF DECK SHALL BE PER PLAN. ROOF DECK SHALL COMPLY WITH SDI PROVISIONS.
ALL STEEL JOISTS SHALL BE PRIMED WITH SHOP STANDARD PRIMER COMPLYING WITH
SSPC-PAINT 15. ALL OTHER STEEL SHALL BE PRIMED WITH SHOP STANDARD LEAD AND CHROMATE
FREE NON-ASPHALTIC RUST INHIBITING PRIMER.
D
LOAD BEARING METAL STUDS
SCREW (MIN SCREW SIZE = No.10 TEK) SIDE LAPS AT EACH SUPPORTING MEMBER
PER PLAN.
GALVANIZED STEEL WITH A MINIMUM YIELD STRENGTH OF 33 KSI AND A MINIMUM THICKNESS
B
0.049
SEISMIC BASE SHEAR
CONTRACTORS SHALL NOTIFY ENGINEER OF ANY UNUSUAL SOIL CONDITIONS THAT ARE IN
CONTRACTORS SHALL PROVIDE SLEEVES FOR ALL OPENINGS REQUIRED IN WALLS. NO
THE CONTRACTOR SHALL UNDERSTAND THE SURVEY AND GEOTECHNICAL
REPORT BEFORE BIDDING THE WORK. RECOMMENDATIONS CONTAINED IN THE
GEOTECHNICAL REPORT SHALL BE INCLUDED IN THE CONTRACTOR'S
DIVISION 5 CONTRACTORS SHALL BE RESPONSIBLE FOR THE MEANS, METHODS, AND SAFETY OF ERECTION
OF THE STRUCTURAL STEEL. DIVISION 5 CONTRACTORS SHALL PROVIDE ALL TEMPORARY SUPPORTS, 30 PSF
27 PSF
.079g
WALL: 19 PSF, ROOF: 26 PSF
OF 2500 PSF FOR COLUMN AND WALL FOOTINGS.
MIN CEMENT= 540 LBS/CYD
6% ± 1.5%
BE FASTENED WITH TWO FILLET WELDS 2" LONG (MINIMUM.)
11.
PLANNED FOR BEFORE THE START OF CONSTRUCTION.
SUITABLE CONTROL OF GROUNDWATER SHOULD BE ANTICIPATED AND
GROUNDWATER MAY BE ENCOUNTERED DURING CONSTRUCTION AND
12.
OF OVEREXCAVATION AND COMPACTION REQUIREMENTS.
FILL. SEE REPORT FOR SPECIFIC DIRECTIONS ON THE ZONE
OVEREXCAVATION AND REPLACEMENT WITH COMPACTED ENGINEERED
AREAS NOTED ON THE GEOTECHNICAL REPORT MAY REQUIRE
BUILDING CODE - 2015 MICHIGAN BUILDING CODE
115 MPH (ULTIMATE) EXPOSURE B, IMPORTANCE= 1.15
FOUNDATION DESIGN IS BASED ON THE SOILS INVESTIGATION REPORT NUMBER 1650993.3A BY
DRIESENGA & ASSOC, INC. DATED DEC 5, 2016.
.072g
WALLS
V=.049 Wx WITH ORDINARY CMU SHEAR
SHEET TITLE
SHEET NUMBER
ISSUED FOR DATE
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
KELLOGGSVILLE
PUBLIC
SCHOOLS
12-194.45
G 002
SCALE: „"= 1'-0"
ROOF FRAMING PLAN- UNIT A
FRAMING PLAN NOTES:
1.
2.
3.
4.
6.
FASTEN STEEL DECK TO SUPPORTING MEMBERS WITH PUDDLE WELDS
BETWEEN SDI REQUIREMENTS AND PROJECT REQUIREMENTS, THE MOST
STRINGENT FASTENING REQUIREMENT SHALL GOVERN. DECK SIDELAPS
SHALL BE FASTENED WITH SCREWS, (BUTTON PUNCHING IS NOT
ALLOWED.)
7.UNLESS NOTED OTHERWISE ON PLANS OR DETAILS, ALL MASONRY WALL
INTERSECTIONS SHALL BE CONSTRUCTED AS FOLLOWS:
A.
B.
ALL INTERSECTING 90° CORNERS SHALL BE BONDED AND SHALL
BE REINFORCED W/ PREFABRICATED L-SHAPED HORIZONTAL JOINT
REINFORCEMENT @ 16" OC. WHERE WALLS INTERSECT AT AN
ANGLE OTHER THAN 90°, CORNERS SHALL BE REINFORCED W/
‚"x2"x24" STEEL STRAPS W/ 2" HOOK ON EACH END (28" TOTAL
LENGTH) @ 2'-8" OC. GROUT CELLS SOLID FULL HEIGHT AT EACH
END OF STRAPS.
ALL TEE INTERSECTIONS SHALL BE REINFORCED W/
PREFABRICATED TEE-SHAPED HORIZONTAL JOINT REINFORCEMENT @
8" OC OR W/ ‚"x2"x24" STEEL STRAPS W/ 2" HOOK ON EACH
END (28" TOTAL LENGTH) @ 2'-8" OC. WHERE WALLS INTERSECT
AT AN ANGLE OTHER THAN 90°, INTERSECTIONS SHALL BE
REINFORCED W/ ‚"x2"x24" STEEL STRAPS W/ 2" HOOK ON EACH
END (28" TOTAL LENGTH) @ 2'-8" OC. GROUT CELLS SOLID FULL
HEIGHT AT EACH END OF STRAPS.
5.
PLACED IN GROUTED CMU BOND BEAM.
DP DENOTES ‚"x4" DECK PLATE W/ •"x5" HAS @ 24"OC
(xxx'-x") INDICATES TOP OF STEEL ELEVATION
PER REQUIREMENTS ON S001 AND SDI. IN THE EVENT OF CONFLICT
8.
SEE SHEET S001 FOR GENERAL NOTES AND REQUIREMENTS.
BOTTOM OF DECK ELEVATION (BOD) PER PLANS
9.
10.
DRAINS. PROVIDE FRAME AND SUMP PAN FOR EACH.
RD DENOTES ROOF DRAINS AND OD DENOTES OVERFLOW
PROVIDE L5x3•x‚ (LLV) UNLESS NOTED OTHERWISE.
SEE ARCHITECTURAL SECTIONS FOR EDGE ANGLE SIZES AND LOCATIONS.
DA DENOTES DECK ANGLE- SEE SECTION 4/S301.
10.
11.
12.
EXTEND INTO BOND BEAM.
AREA SOLID UP TO BEARING PLATE. ANCHORS ON BEARING PLATE SHALL
PROVIDE A BOND BEAM AT THE NEXT COURSE DOWN AND GROUT A 16" WIDE
FOR JOIST BEARING ELEVATIONS THAT ARE ABOVE MASONRY COURSING,
BEAMS FOR JOIST BEARING ELEVATIONS THAT ARE AT MASONRY COURSING.
BEARING PLATES SHALL BE SET DIRECTLY ON AND ANCHORED INTO BOND
BEARING PLATES PER DETAILS ON S301 FOR ALL JOISTS BEARING ON CMU WALLS.
UNLESS NOTED OTHERWISE ON THE PLANS OR DETAILS, PROVIDE
PLATES AND ANCHOR BEAMS TO PLATES PER DETAILS ON S301.
BEARING PLATES FOR BEAMS BEARING ON CMU WALLS. GROUT BELOW
UNLESS NOTED OTHERWISE ON THE PLANS OR DETAILS, PROVIDE BP1
OPENING STEEL LINTEL PER
SIZE 4" OF WALL THICKNESS
0' TO 2'-0" INCL É5x3•x‚
PROVIDE LINTELS FOR MISC MECHANICAL OPENINGS PER THE FOLLOWING TABLE
UNLESS OTHERWISE NOTED ON THE DRAWINGS:
13.
MECHANICAL LINTELS COST SHALL BE BID AS AN ALLOWANCE.
> 2'-0" TO 6'-0" INCL É5x3•xŠ
14.
16/S301 AND 17/S301.
ROOF FRAMES AND JOIST STRUTS PER
AT NEW RTU'S, PROVIDE CHANNEL STEEL,
ROOF DECK(RD) SHALL BE PER 1•", 20GA WIDE RIB ROOF DECK UNO.
LOCATIONS PER THE GENERAL NOTES ON S001 (UNO).
8" CMU SHALL BE REINFORCED PER PLAN. SEE ADDITIONAL
S102
PLAN
FRAMING
ROOF
SHEET TITLE
SHEET NUMBER
ISSUED FOR DATE
"-0"'-
THRU EXISTING WALL
@ 16"OC. BOLT CONNECTIONS
ON LT GA STEEL TRUSSES
1•", 20GA ROOF DECK
12-194.45
G 002
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
KELLOGGSVILLE
PUBLIC
SCHOOLS
WEST ELEMENTARY
KEY PLAN
SCALE: NO SCALE
0'
5'
10'
15' 25'
1/8" = 1'-0" GRAPHIC SCALE
V A
R
IE
S
SEE PLAN
T
T H
R E
A D
E D
N O
N S
H R
IN
K
E
M B
D
EQEQ
Q
Q
16"
EQEQ
E Q
Q
7"
C
U R
S E
S
6" 8"
8"
3•"
EQ EQ
3•"
8"
EQEQ
E Q
E Q
14"
SEE ARCH PLANS
U R
S E
S
8"6"
‚" MAX
1" MAX
TYP PIPING , CONDUIT &
PIPING 4" Ì OR GREATER
TO EXCEED 12'-0"
MECH SPECS BUT NOT
HANGER SPACING PER
EXCEED 100# AT ANY HANGER.
COMPLY WITH NFPA. DO NOT
POINTS USING "C-CLAMPS";
BE SUSPENDED AT PANEL
PIPING LESS THAN 4" Ì MAY
1.
2.
DECK FLUTES
JOIST PANEL POINTS. PLACE IN
INCHES OF TOP OR BOTTOM CHORD
REQ'D LOAD; LOCATE WITHIN 2
STEEL SUFFICIENT TO SUPPORT
UNISTRUT OR EQUAL STRUCTURAL
NOTES:
(MAX WT= 500 LBS)
MECH UNIT
OR BEAM
STEEL JOIST (SHOWN)
CORNER BARS
L
L
LARGER AREA
WHERE SIZE & SPACING DIFFER MATCH
MATCH SIZE & SPACING OF HORIZ BARS,
(L=48db )
"TEE" INTERSECTIONCORNERS
SUPPORTED OFF FLOOR OR ROOF DECK.
FOR ANY HANGING EQUIPMENT. ANY HANGING LOADS SHALL NOT BE
THIS DETAIL IS SCHEMATIC SHOWING PIPING SUPPORTS BUT IS APPLICABLE
PANEL POINTS
PROVIDE JOIST STRUTS FOR LOADS THAT DO NOT OCCUR AT JOIST
S301
EQUIPMENT SUPPORT
NOT TO SCALE
A-A
C-C
B-B
TOW EL
VARIES
PER PLAN
VERT WALL REINF
VERT WALL REINF (TYP)
REINF (CONTINUOUS)
HORIZ BOND BEAM
VERT WALL REINF (TYP)
ROD AND SEALANT
ROD AND SEALANT
BUILDING FELT
CONTROL JOINT
INTERRUPTED AT
HORIZ JOINT REINF
IN GROUTED CELLS
VERT WALL REINF
(WHERE APPLICABLE)
INTEGRAL BRICK TIES
CMU CONTROL JOINT
REINF AT JOINT
SECTIONS-INTERRUPT
PER PLAN AND TYP
HORIZ JOINT REINF
OF BOND BEAM
JOINT AT BOTTOM
STOP CONTROL
TYP SECTIONS
BEAM PER PLAN AND
INTERMEDIATE BOND
ABOVE BOND BEAM
REINF EA COURSE
PROVIDE HORIZ JOINT
AT CONTROL JOINT
REINF, INTERRUPT
HORIZ BOND BEAM
MORTAR JOINT
WALL ELEVATION W/ CONTROL JOINT
SECTION C-C: PLAN OF INTERMEDIATE BOND BEAM
SECTION B-B: PLAN OF TYPICAL JOINT REINFORCING
SECTION A-A: PLAN OF TOP OF WALL BOND BEAMSECTIONS
PER PLAN AND TYP
BEAM AND REINF
TOP OF WALL BOND
FILL CAVITY W/ GROUT
MARK
BEARING PLATE SCHEDULE
ANCHORSPLATE SIZE
BP1 (2)-†" DIA
BP2 •x6"x8" (2)-†" DIA
REMARKS
•x7"x7"
SEE TYPICAL BEAM/LINTEL BEARING DETAIL FOR GROUTING REQUIREMENTS
GROUT SOLID
JOIST PER PLAN
TOS VARIES
W/ 4‚" EMBEDMENT
ROD @ 24" OC AND HILTI HY150
GROUTED CMU W/•"Ì THRD
É5x3•x‚, ANCHOR TO SOLID
S301
CONN @ EXT WALL
NOT TO SCALE
S301
PLAN-TYP MASONRY BOND BEAM
NOT TO SCALE
S301
TYP CMU CONTROL JOINT DETAILS
NOT TO SCALE
S301
BRG PLATE SCHEDULE/DETAILS
NOT TO SCALE
JOIST
METAL DECK
AROUND CHANNEL
LEAVE CMU 2" CLRTYP
É4x3x‚, 8" LONG
SEE PLAN
VERT REINF,
S301
WALL BRACING DETAIL
ƒ" = 1'-0"
VERT REINF, SEE PLAN
(TYP)
WELD DECK TO ANGLE
É5x3x‚ LLH CONT, TYP
W/ 4‚" EMBEDMENT (TYP)
INSTALL W/ HILTI HIT HY150
•"Ì THD ROD @ 2'-0" OC,
BRG Ê, SEE PLAN (TYP)
BETWEEN JOIST BEARINGS
GROUT SOLID ALL COURSES
TOJ VARIES
S301
SECTION-JOIST BEARING
NOT TO SCALE
MAX
@ 6'-8"OC
C4x5.4
W/ (2) #5 CONT
8" CMU BOND BEAM
BASE PLATE
LEVELING NUTS
ANCHOR BOLT SIZES
COLUMN, BASE PLATE AND
SEE COLUMN SCHEDULE FOR
BOTT OF BASE PLATE EL
P R
O J E
C T
IO
N
G R
O U
T
TOP OF PIER OR FOOTING
EL - SEE FDN PLANS
& OVERSIZE WASHER
HEAVY HEX NUT
WELD TO ROD
HEAVY HEX NUT
SEE COLUMN SCHEDULE
Ë
Ë
T Y
P
P1
S301
COLUMN BASE PLATE (TYPE P1)
NOT TO SCALE
S301
COLUMN SETTING (TYPE S1)
NOT TO SCALE
ASTM F1554, GRADE 36
1" ANCHOR ROD
1 ‚" BASE Ê
W COL
Ë
Ë
T Y
P
P2
HSS COL
1" BASE Ê
BP3 †"x10"x10" (3)-†" DIA
(STEEL JOISTS ONLY)
GROUT SOLID
W/ (2) #4 CONT
8" CMU BOND BEAM
VERT REINF, SEE PLAN
WELD DECK TO ANGLE
É4x3x‚ LLH CONT, SECTION-TYP JOIST
W/ 4‚" EMBEDMENT
INSTALL W/ HILTI HIT HY150
•"Ì THD ROD @ 24" OC,
S301
BRG @ EXT WALL
NOT TO SCALE
BP2 BRG Ê
SECTIONS
FRAMING
L1
L2
BEAM AND LINTEL SCHEDULE
NOTES:
1.
2.
LOCATED IN EXTERIOR WALLS
GALVANIZE ALL LOOSE ANGLE LINTELS AND BOTTOM PLATE ON BEAM & Ê LINTELS
SIZE
PLATE
BOTTOM
MARK SIZE TYPE
END SUPPORTS
1 2
REMARKS
3.
‰ 3-12
TYPE 1
TYP
TYPE 2
S301
STEEL BEAMS AND LINTELS
NOT TO SCALE
SEE NOTE 3
L3 2
PROVIDE BEARING FOR LINTELS PER TYPICAL BEAM/LINTEL BEARING DETAIL 9/S301
WHEN MASONRY PIERS ARE NOT SPECIFICALLY INDICATED ON PLANS AND/OR DETAILS,
BP1C
HSS16x4x‚ BP1C
†"Ì HAS 6" LONG @ 24" OC, GROUT SOLID IN CMU
L4 1 BP1A
4.
ARE TO BE INSTALLED (WHERE LINTELS ARE DEEPER THAN 8")
PROVIDE CORRUGATED BUCK ANCHORS @ 16"OC ON SIDES OF LINTEL WHERE FACE SHELLS
TYPE 3
(2) L5x3•xŠ
5.
6" BEARING. ALL OTHERS SHALL HAVE 8" BEARING.
BEAMS BEARING PERPENDICULAR TO 8" CMU WALLS SHALL HAVE
TYPE 4
SEE NOTE 3
BP1C
BP1C
GROUT SOLID AS SHOWNGROUT SOLID AS SHOWN
SOLID BELOW
SEE PLANS, GROUT
BEARING PLATE-
MINMIN
PERPENDICULAR TO WALL
BEAMS/LINTELS
PARALLEL TO WALL
BEAMS/LINTELS
S301
TYP BEAM/LINTEL BEARING
NOT TO SCALE
TUBE AT 60 DEG
CUT END OF
TOP OF WALL
CONTINUE TO
ALLOW BAR TO
AND LINTEL TO
IN BRG PLATE
2" DIA HOLE
BAR IN JAMB
(1) #5 CONT
COURSE W/
BOND BEAM
COLUMN PER PLAN
TYPE 5
TIGHTEN NUTS.
W/ BEAM. FINGER
SLOT TO BE PARARELL
IN BEAM FLANGE. 2"
ƒ"x2" SLOTTED HOLES
OR JOIST
BEAM (SHOWN)
WELD TO ANCH (TYP)
HEAVY HEX NUT-TACK
SEE SCHEDULE
BEARING PLATE-
FOR SIZE & QTY
HAS-SEE SCHEDULE
‰ 2"
(2)-†"Ì ANCH
SEE NOTE
TYPE A
TYPE B
EA SIDE OF WEB.
SLOTTED HOLES IN BOTTOM FLANGE
TO ALLOW FOR WELDING, PROVIDE
NOTE: IF BEAM FLANGE IS TOO WIDE
SEE SCHEDULE
BEARING PLATE-
Ê (TYP)
ANCH TO
SEE SCHEDULE
BEARING PLATE-
FOR SIZE & QTY
HAS-SEE SCHEDULE
4"
TYPE C
HSS BEAM
‚ 3"
HSS BEAM
SEE SCHEDULE
BEARING PLATE-
SEE SCHEDULE
BEARING PLATE-
4"
TYPE D
HSS BEAM
‚ 3"
HSS BEAM
SEE SCHEDULE
BEARING PLATE-
TIGHTEN NUTS.
W/ BEAM. FINGER
SLOT TO BE PARARELL
IN BEAM FLANGE. 2"
ƒ"x2" SLOTTED HOLES
WELD TO ANCH (TYP)
HEAVY HEX NUT-TACK
(2)-†"Ì ANCH
TIGHTEN NUTS.
W/ BEAM. FINGER
SLOT TO BE PARARELL
IN BRG PLATE. 2"
ƒ"x2" SLOTTED HOLES
PLAN OF BOTT PLATE
LINTEL BOTT PLATE
BRICK
JAMB CMU
OPENING
•" FROM EDGE OF
BEARING PLATE BACK
SUPPORT, HOLD
JAMB FOR BRICK
CONTINUE 8" BEYOND
PLATE SHALL
BEARING PLATES BUT
LINTELS REQUIRING
FOR BEAM & Ê
‚" SHORT OF CMU
HOLD BOTTOM PLATE
Ë
Ë
T Y
P
P3
HSS COL
1•" BASE Ê
‚"x15"
VERTICAL REINFORCING IN JAMBS
JAMB CELLS AND LAP W/
PROVIDE 16" HOOK INTO CMU
W/ (2) #5 TOP AND BOTT-
16" DEEP CMU LINTEL
OF THE WALL
FIRST 8" AND THE REMAINDER
PROVIDE SOFT JOINT BTWN
CMU BEYOND THE FIRST 8"-
16" TALL LINTEL BEARS ON
TO THE OPENING
ON JAMB CMU ADJACENT
BEARS 8" EACH END
(2) #5 TOP AND BOTT-
16" DEEP CMU LINTEL W/
‚"x1" BENT STRAP @ 24"OC
GROUT SOLID
IN PLACE
USED FOR INSTALLATION-LEFT
(2) OR (3) L3 •x3 •x‚ ANGLES
CAULK JOINT
S301
PORTAL FRAME
NOT TO SCALE
OF OPENING
BACK •" FROM EDGE
HOLD BEARING PLATE
BEARING PLATES,
LINTELS REQUIRING
FOR BEAM & Ê
‚" SHORT OF WALL
HOLD BOTTOM PLATE
MINMIN
SOLID BELOW
SEE PLANS, GROUT
BEARING PLATE-
GROUT SOLID BELOW
FULLY ON PLATE -
BEAM TO BEAR
GROUT SOLID SOLID UNITS GROUT SOLID SOLID UNITS
TYP BEAM/LINTEL BEARING @
S301
EXISTING CONSTRUCTION
NOT TO SCALE
S301 w/ BOT PLATE
CMU
SECTION-TYP JOIST
W/ (2) #4 CONT
8" CMU BOND BEAM
U N
O
SOLID W/ BOND BEAM
(IF REQ'D) AND GROUT
CUT COURSE FOR BRG
(CENTER IN WALL)
BRG Ê, SEE PLAN
S301
BRG @ INT WALL
RTU CURB
BLOCKING REQUIRMENTS
SEE ARCH FOR FLASHING AND
OPENING FRAME"
SEE "TYP ROOF
DECK SUPPORT-
DECK
METAL ROOF
‰ 2-12
TYP
TYP
POINT
TOP CHORD PANEL
IF LOAD IS NOT AT
L2x2x ‚JOIST STRUT
S301
TYP RTU SUPPORT
ELEC DRAWINGS
OPENINGS w/ ARCH, MECH AND
METAL ROOF DECK. COORDINATE
1'-0" WIDER THAN OPENING TO
WELDING 16 GAGE SHEET METAL
OPENINGS LESS THAN 12" BY
LARGER. REINFORCE ROOF
WHERE ANY DIMENSION IS 12" OR
APPLIES TO ALL OPENINGS
TYP OPENING DETAIL SHOWN
NOTE:
É4X4x…,6" LONG
‰ 2
3 SIDES
TYP
STRUT DETAIL.
REQ'D. SEE TYP JOIST
PROVIDE JOIST STRUT AS
TO FRAME OPENING,
PROVIDE ANGLES AS REQ'D
É3x3x‚ AT ROOF(TYP)
S301
OPENING FRAME
NOT TO SCALE
TYP ROOF
JOIST
LOCATIONS
PLATE AT EXISTING ROOF
DECK TO Ê. OMIT
EXACT CURB LAYOUT. WELD
COORDINATE PLACEMENT W/
MINIMUM OF TWO JOISTS)
END OF RTU (SPAN TO A
SPAN TO NEXT JOIST BEYOND
PLACE UNDER RTU CURB.
C6x8.2 w/ ‚x12 CONT Ê, EXTERIOR WALL LINTELS w/ CAVITY
CMU+4" VENEER
w/ CAVITY
CMU+4" VENEER
W/ (2) #5 CONT (TYP)
CMU BOND BEAM
BP4 †"x7"x11" (3)-†" DIA
‚"x15"
‚"x7" BP1A
S301
SECTION
NOT TO SCALE
JOIST PER PLAN
JOIST PER PLAN
(2) #5 CONT
8" BOND BEAM W/
OF WALL
GROUT SOLID TO TOP
JOIST ENDS
PER PLAN BTWN
DECK PLATE
W8x10
TYPE 6
HSS8x4x‚
PER PLAN
BRG PLATE
SHEET TITLE
SHEET NUMBER
ISSUED FOR DATE
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
KELLOGGSVILLE
PUBLIC
SCHOOLS
12-194.45
DN
DN
CORRIDOR
MEDIA CENTER
1 HR
HR
OFFICE
STORAGE
A 201
20' - 0" V.I.F.
116A
A 601
6' - 0"
3K
3K
A 201
3K
KNOX BOX LOCATION
OFFICE
NEW BORROWED LITES -
TOOTH-IN DOUBLE BULLNOSE
CMU AT ALL WINDOW JAMBS.
CENTER BORROWED LITE IN WALL
2' - 8" 8' - 0" 2' - 0" 8' - 0"
115A
1G
A 201
A 201
A 201 4
A 201 4
2' - 8"
CLASSROOM
116B
1G 1G2B
" 2' - 8"
COMPUTER
LAB
WORK ROOM
OFFICE
OPEN OFFICE
TOILET
TLT
SECURE
VESTIBULE
CONFERENCE
TEACHERS
GYMNASIUM
TOILET
CLOSET
CLOSET
NEW ENTRY CANOPY
40' - 0 1/4"
115B
ALIGN WALL WITH EDGE
OF WINDOW OPENING
V .I .F
1G
37' - 8 1/4" V.I.F.
/8
OFFICE
OPEN OFFICE
WORK ROOM
CLASSROOM
TLT
TLT
TLTSTO
SECURE
VESTIBULE
CORRIDOR
MEDIA CENTER
VEST.
OFFICE
OFFICE
COMPUTER LAB
STAGE
STORAGE
14 13
GYMNASIUM
CONFERENCE
TEACHERS LOUNGE
WORK ROOM
WOMEN
J.C.
MEN
/8
V .I .F
/8
/8
/4
2' - 8" 8' - 0" 2' - 0" 8' - 0"
Tower Pinkster Titus Associates Inc.
242 East Kalamazoo Avenue, Suite 200
Kalamazoo, Michigan 49007-5828
269.343.6133 PHONE 269.343.6633 FAX
TOWERPINKSTER.COM
ALL RIGHTS RESERVED2019©
DATE
PROJECT TITLE
SHEET TITLE
SHEET NUMBER
4 East Fulton Street, Suite 200
Grand Rapids, Michigan 49503
616.456.9944 PHONE 616.456.5936 FAX
JANUARY 03, 2019
WEST
ELEMENTARY
MEDIA CENTER
RENOVATION
Grand Rapids, Michigan
DEMOLITION &
FLOOR PLANS
12-194.45
A 101
KELLOGGSVILLE
PUBLIC
SCHOOLS
1/8" = 1'-0"
FLOOR PLAN
1/8" = 1'-0"
DEMOLITION PLAN
WEST ELEMENTARY
KEY PLAN
SCALE: NO SCALE
0'
5'
10'
15' 25'
1/8" = 1'-0" GRAPHIC SCALE
RENOVATION
AREAS
NOTES:
1. SEE A600 SERIES SHEETS FOR INTERIOR ELEVATION…