This document outlines quality assurance provisions for a solicitation seeking contractor-owned contractor-operated fuel storage services in Hachinohe, Japan. The Defense Logistics Agency Energy will issue a request for proposal to provide fuel storage and management services, including receiving, storing, protecting and shipping two grades of aviation turbine fuel—Jet A-1 and JP8—from a location in Hachinohe, Japan with a storage capacity of 59,000 barrels across minimum two interconnected and isolated tanks. Services will include receipt via tanker/barge and shipment via pipeline to the U.S. Fleet Logistics Center in Hachinohe. The contract will have a four-year base period from August 15, 2019 to August 14, 2023 with a five-year option. The solicitation is anticipated to publish on or after February 28, 2019 and close approximately 45 days later.
SPE603-19-R-0508 Attachment III, DLA Energy Quality Assurance Provisions (EQAP's) for Storage Services in Hachinohe, Japan
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SPE603-19-R-0508_Amd_0001_w-Attachment_A.pdf | ||
| SPE603-19-R-0508_RFP.pdf | ||
| 19F0508_Attachment_II_OSP.pdf | ||
| 19F0508_Attachment_IV_-_Past_Performance_Info_Disclosure_Consent_Form_(1).pdf | ||
| 19F0508_Attachment_V_-Past_Performance_Questionnaire.pdf | ||
| 19F0508_Attachment_I_PWS.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment III: QUALITY ASSURANCE PROVISIONS
SPE60 -1 -R-05 8
HACHINOHE, JAPAN
COCO STORAGE SERVICES
HACHINOHE, JAPAN
SPE60 -19-R-0508
Quality Assurance Provisions (QAP)
SUPPLEMENTAL QUALITY ASSURANCE PROVISION (SQAP)
REVISIONS
REV DESCRIPTION DATE APPROVED
ENERGY QAP E28 December 2011
E28 CONTRACTOR INSPECTION RESPONSIBILITIES (STORAGE)
(a) Inspection and tests by the Government of services, facilities, and equipment specified within this contract does not relieve the Contractor from responsibility to meet all requirements of the contract
(b) The Contractor shall furnish personnel, facilities, and equipment on-site to accomplish the following routine tests and procedures. These on site resources may be provided by Contractor personnel or by a commercial source action on behalfofthe Contractor. The Quality Representative will not be responsible for performing any of these services for the Contractor.
(1) Sampling of storage tanks, shipments and receipts in accordance with ASTM D 4057, Standard Practice for Manual Sampling of Petroleum and Petroleum Products (API Manual of Petroleum Measurement Standards (MPMS), Chapter 8.1);
(2) Retaining of product composite samples from shipments and receipts as follows:
MINIMUM
METHOD OF SHIPMENT MINIMUM QUANTITY RETENTION PERIOD
Pipeline 20 liters 60days
Tanker/Barge
· Parcel Composite 20 liters 90 days
Each compartment 0.5 liters 90 days
Navy Fleet OilersNessels IO liters 60 days
Tank Truck/Car I liter 15 days
NOTE: After the minimum retention period, samples shall be tested for Appearance, Color (Visual), API Gravity/Density and Flash
Point and, if found to be on-specification, shall be returned to like Government stock on-site. Sample containers may be reused if properly cleaned.
(3) Determining the presence of water in storage tanks, shipments and receipts. Ensure that accurate water cuts are obtained by means ofa water indicating paste conforming to MIL-W-83779B. Two suggested sources are Stewart Hall Chemical Testmaster Water Indicating Paste or Sartomer
Sar Gel Water Indicating Paste (see Note 2 below);
(4) Determining Density at 15 degrees Celsius or API gravity of products by ASTM D 1298 or ASTM D 4052 (see Note 2 below);
(5) Determining the temperature of products by the API MPMS, Chapter 7 (see Note 2 below);
(6) Determining the Appearance of applicable products using ASTM D 4176, I>rocedure I (see Note 2 below);
(7) Determining the visual color of products.
(8) Determining the Flash Point of applicable products using test methods cited in the appropriate product specification (see Note 2 below);
(9) Conversion of gross to net gallonage (liters);
(10) Determining the percentage (volume) of fuel system icing inhibitor (FSII) by means of a portable refractometer in accordance with ASTM D
5006. One suggested source is H.B. Industries, Inc., Glenview, IL 60025 (B/2 Anti-Icing Additive test kit) (see Note 2 below); and
(11) Determining the range of fuel electrical conductivity using ASTM D 2624. One suggested source for a conductivity meter is Emcee
Electronics, Inc., Sarasota, FL 33581 (Model 1152) (see Note 2 below)
SUPPLEMENTAL QUALITY ASSURANCE PROVISION (SOAP)
DEFENSEENERGYSUPPORTCENTER
8725 JOHN J. KINGMAN RD
DISTRIBUTION
STATEMENT-A
APPROVED FOR
PUBLIC RELEASE
DISTRIBUTION IS
"UNLIMITED"
REVIEWED BY
DLA FORM 1889, OCT 2011
FORT BEL VOIR, VIRGINIA 22060-6222
ITEM DATE
11/12/2013 ENERGY QAP E28
DATE NSN
MULTIPLE
DATE SIZE
09/22/2016
SCALE
CODEID NO.
52838
DRAWING NUMBER
PREVIOUS EDITION IS USABLE Add Continuation Page SHEET 1 OF 2 PDF(DLA)
SUPPLEMENTAL QUALITY ASSURANCE PROVISION (SQAP)
REVISIONS
REV DESCRIPTION DATE APPROVED
ENERGY QAP E28 December 20 l l
Note 1: All costs for providing the above tests and procedures shall be included in the monthly service charge. The only exception to the
Contractor 1s obligation to 1,rovide these services as part of the monthly service charge is when the tests described above arc part of the higher order analysis (defined as the following categories: Composite Samples, Storage Tanks After Receipt, Interface Mixtures, Dormant
Stocks and Individual Tests (including particulate contamination) found in the attachment to the solicitations entitled l\HNIMUM
REQUIREMENTS FOR STORAGE SAMPLING AND TESTING. Provisions for providing higher order analyses are covered in the
SAMPLING AND TESTING OF PETROLEUM PRODUCTS (STORAGE) contract provision.
Note 2: Upon request, the Contractor shall permit the Quality Representative unrestricted use of the equipment and aneilla1-y supplies needed to perform this test/procedure on behalf of the Government.
(c) During the contract, the Contractor shall furnish representative samples of the product in each storage tank, shipment or receipt at the request of, and in the manner and to the place designated by, the Quality Representative. Sample size will be 2 gallons for gasoline-type fuels and one gallon or 10 gallons for jet diesel-type fuels. The number of samples to be furnished during any 12-month period shall not exceed eight times the number of tanks specified in the contract. Such samples shall be packed, marked, and shipped by the Contractor, shipping expense prepaid, in containers and shipping boxes furnished by the Contractor. Sample containers shall b e epoxy coated on the interior. This requirement is in addition to sampling required elsewhere in this contract provision and the contract. All reasonable direct shipping costs associated with samples required by this paragraph shall be reimbursed upon request from the Contractor and such costs shall not be included in the monthly service charge.
However, all other costs related to this requirement shall be included as part of the monthly service charge, SUPPLEMENTAL QUALITY ASSURANCE PROVISION DEFENSE ENERGY SUPPORT CENTER
(SOAP) 8725 JOHN J. KINGMAN RD
FORT BELVOIR, VIRGINIA 22060-6222
DISTRIBUTION STATEMENT - A
APPROVED FOR PUBLIC RELEASE SIZE SCALE CODE ID NO. DRAWING NUMBER
DISTRIBUTION IS "UNLIMITED"
52838
DLA FORM 1889, OCT 2011 PREVIOUS EDITION IS USABLE Add Continuation Page SHEET2 OF2 PDF (DLA)
Attachment II- DLA Energy QAPs SPE603-19-R-0508 the start of the performance period the beginning of the performance period.
File details come from the government source that posted it. Updated .