Tech Specs CIRCUIT BREAKER TESTER.pdf
PDF 66 KB Posted
- Attached to
- Smart High Primary Injection Test System
- Solicitation number
- SP4706-24-Q-0039
- Issued by
-
Defense Logistics Agency
About this file
This document contains the technical specifications for a Smart High Current Primary Injection Test System required by the Defense Logistics Agency (DLA) Product Test Center in Columbus, Ohio. The system must be new, capable of outputting up to 2,000A with multiple adjustable output ranges, include advanced measurement and automation features, and provide the ability to test low-voltage molded-case circuit breakers up to 225A. Required accessories include a Smart Touch View Interface, PowerDB Pro software licenses, and a 24-month extended warranty. Delivery is required within 10 weeks of contract award, with the system to be shipped to the specified DLA location. The document is related to Solicitation SP4706-24-Q-0039 for the Smart High Primary Injection Test System procurement, which is being conducted by the DLA.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AMENDED_SF1449_SP470624Q0039.pdf | ||
| SF_1449SP470624Q0039.pdf | ||
| CIRCUIT BREAKER TechSpecsSOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Rev 06/26/2024
Technical Specifications
Smart High Primary Injection Test System
DLA Product Test Center, VTA
I. The contractor shall provide all labor, materials, tools, transportation, supplies, supervision, etc. (except as noted), necessary to provide all components for a Smart High Current Primary Injection Test System used to test low-voltage molded-case circuit breakers up to a rating of 225A to the Defense Supply Center Columbus
(DSCC), Columbus, Ohio. The salient characteristics of the Smart High Current Primary Injection Test System are as listed below:
A. Smart High Current Primary Injection Test System with support equipment and with the following salient characteristics:
1. Shall be new, not refurbished.
2. Shall be supplied with Operating manual.
3. Shall be powered by standard US 115V, 15A AC power outlet.
4. Shall be able to output up to 2,000A and be expendable to 7478A if running 4 units in parallel.
5. Shall have three continuously adjustable output ranges: 25 to 500A at 3.5 V MAX, 6.25 to 125A at
14V MAX and 1.25 to 25A at 70V MAX.
6. Shall have a 5-digit auto ranging ammeter display ranging from 1.0000A to 99.999 kA with an accuracy of RMS pulse +/- 1.5% of reading or +/- 0.075A.
7. Shall have a 5-digit auto ranging voltameter display ranging from 0.01 to 600.00V with an accuracy of +/- 1%.
8. Shall have a 5-digit auto ranging timer display ranging from 0.001 to 99999 seconds with an accuracy of +/- 1%.
9. Shall have two ethernet and two USB 2.0 communication ports.
10. Shall be a smart high current primary injection test system for all forms of high current testing required in a substation, including testing overcurrent relays, circuit breakers, motor overloads and current transformers.
11. Shall be Designed for switchgear commissioning, circuit breaker, CT commissioning, ground grid and relay testing
12. Shall have the ability to perform high current commissioning tests as well as test low-voltage molded-case circuit breakers up to a rating of 225A.
13. Shall have software that includes thousands of circuit breaker curve TCC curves.
14. Shall have the ability to turn on at the current zero crossing every time for any load by automatically adjusting the output firing angle.
15. Shall be able to execute automated test programs from a laptop or manually controlled from a Smart
Touch View Interface.
16. Shall include a Smart Touch View Interface that has a simplified touch screen input for manual control.
17. Shall include fuse, circuit breaker and overload protective devices to be incorporated in the system.
18. Shall be provided with software that allows for automated testing, report generation and maintenance record keeping of all primary injection and low voltage circuit breaker tests.
19. Shall have software that includes thousands of circuit breaker curve TCC curves.
20. Shall be able to all breaker parameters including: long time pick-up, long time timing, short time pick-up, short time timing, instantons pick-up, ground fault pick-up and ground fault timing.
21. Shall be able to record up to ten trip/ reclose operations with each trip current, trip time and reclose time recorded.
22. Shall have: a Certificate of Calibration and a 24 Month Extended Warranty.
Rev 06/26/2024
Technical Specifications
Smart High Primary Injection Test System
DLA Product Test Center, VTA
B. Required Upgrades and Accessories - Brand Name or Equal:
1. Shall at a minimum have: Included Accessories: All necessary electrical cables, communication cables to install and operate machine.
2. Shall be provided with a Smart Touch View Interface that uses a stand ethernet cable and PoE operation, include non-volatile built-in data storge for saving tests and test results and have two USB ports for transferring test results.
3. Shall include the PowerDB Pro Licenses, SQL Upgrade, and purchases options support and maintenance for a period of one year from the date of delivery of the equipment.
C. Other Requirements:
1. Delivery: 10 Weeks from date of the award.
2. Contractor shall give notification to Jeremiah L. Jones (jeremiah.l.jones@dla.mil /614-692-8955) when the instrument is ready to be delivered.
3. All shipping costs are to be included in the contracted price.
4. The instrument shall be delivered to:
Defense Supply Center Columbus
300 North James Road, Bldg 17-3
Mark for: DLA Product Test Center, Bldg 11-7 (TE Lab)
Attn: Jeremiah L. Jones (jeremiah.l.jones@dla.mil / 614-692-8955)
Columbus, Ohio 43213
5. Invoices shall be submitted through Wide Area Workflow (WAWF), See DFARS Clause 252.232-
7006 Wide Area Workflow Payment Instructions for detailed instructions on how to submit invoices.
mailto:jeremiah.l.jones@dla.mil mailto:jeremiah.l.jones@dla.mil
File details come from the government source that posted it. Updated .