A-3 SOW - Battery Replacement.pdf
PDF 149 KB Posted
- Attached to
- DDWG Batteries
- Solicitation number
- SP330026Q0105
- Issued by
-
Defense Logistics Agency Distribution
About this file
This is a Statement of Work (SOW) issued by Defense Logistics Agency (DLA) Distribution Warner Robins for UPS battery replacement services at their facility located at 455 Byron Street, Building 385, Robins Air Force Base, Georgia.
The requirement calls for labor and replacement batteries to support an Eaton UPS system. The vendor must supply 40 CSB HRL1234WF2FR batteries or equivalent (12V Quick Connect Lead Acid Batteries with 9Ah capacity, 130A maximum discharge current at 5 seconds, 6 cells per unit, and UL94-HB and UL94V-0 flammability ratings) and perform installation services. The vendor is responsible for removing the existing old batteries and installing the new batteries, with all removed batteries to be placed on a commercial pallet in Building 385 for pickup. Services must be performed during standard business hours between 8:30 a.m. and 4:00 p.m. The SOW does not specify contract vehicle type, response deadlines, pricing terms, or award dates.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A-3 SOW - Battery Replacement.pdf | ||
| SP330026Q0105 002.pdf | ||
| Pictures.pdf | ||
| SP330026Q0105 0003.pdf | ||
| SP330026Q0105 002.pdf | ||
| SP330026Q0105 001 .pdf | ||
| SP330026Q0105.pdf | ||
| SP330026Q0105.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEFENSE LOGISTICS AGENCY
DLA DISTRIBUTION Warner Robins
455 Byron Street BLDG 385
ROBINS A F B GA 31098-1887
May 6, 2026
MEMORANDUM FOR RECORD
SUBJECT: STATEMENT OF WORK
REFERENCES: DDWG – UPS Battery Replacement
1. Name of site where work is to be performed:
Site 1: Defense Logistics Agency 455 Byron Street Bldg. 385
2. Description of Requirement
DDWG is requesting labor and replacement batteries to support the Eaton UPS system. CSB
HRL1234WF2FR batteries or equivalent shall be provided to install in the UPS System.
Vendor will need to remove old batteries and install new batteries. All removed batteries shall be placed to the side in building 385 on a commercial pallet for pick up.
The service will be performed during standard business hours between 830 am – 4:00 pm.
3. Description of Quantity of item needed
Quantity: 40
Description: Battery, 12v Quick Connect12V Quick Connect, Lead Acid Battery; 9Ah Capacity;
98.3 mm H x 64mm D x151mm W; UL94-HB and UL94V-0 Flammability rating; 130A at 5sec
Maximum discharge current; 6 Cells per unit; 4W at 15 Minutes rate to 1.67V percell at 25°C
(77°F) capacity; 3.4A Recommended maximum charging current limit; HRL Series; Similar or equal to CSB Battery of America Part Number HRL1234WF2FR