This document outlines the scope of work for a federal contract solicitation to provide unidirectional flushing services for the water distribution system at Aberdeen Proving Ground. The contractor will be required to locate, inspect, and operate distribution valves and fire hydrants; record water flows; and create a GIS database compatible with the base's current system. Additional work may include repairs to valves and hydrants. The contractor must provide weekly reports and a final report within 30 days listing areas flushed, water usage, and other requested details. The contractor will use their own tools and vehicles to perform the work in a safe, efficient, and professional manner according to the minimum specifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL TERMS AND CONDITIONS

Unidirectional Water Main Flushing

1. CONDITIONS – Bidders should become familiar with all conditions, instructions and specifications governing their proposal. Once the award has been made, failure to have read all the conditions, instructions and specifications of their contract is not a reason to alter the original contract or to request additional compensation. The term "APG” in these bid documents means Aberdeen Proving Grounds

2. ADJUSTMENTS TO CONTRACT - APG reserves the right to adjust the quantities of work, either up or down, dependent upon the current budget or until budgeted funds are depleted without prejudice to the Contract. Payment is based on accepted unit prices.

3. MULTI-YEAR CONTRACT - Contracts with duration greater than 12 months require annual renewals to be signed by APG and Contractor.

4. DAMAGES TO PROPERTY

4.1 CONTRACTOR is responsible for property damage caused by their work performed for this contract and shall replace or restore it to its original condition at no cost to the occupant, owner or APG. APG shall be held harmless for all liability under the Scope of Work of this contract.

4.2 If damage exists before work begins (i.e. sidewalk, driveway cracks) it is recommended that the COR be notified prior to starting work.

5. COMPLETION TIME, PENALTY AND LIQUIDATED DAMAGES

5.1 If the CONTRACTOR does not complete the work within the specified Contract time or within allowed extended time, the CONTRACTOR is liable to APG for (specified amount), as liquidated damages, for each calendar overrun day from the contract time or allowed extended time.

5.2 Penalty or liquidated damages owed to APG may be deducted from payments to the CONTRACTOR.

6. MEETING BEFORE WORK BEGINS - Contractor must meet with the COR (contracting officer’s representative) or designee(s) before starting work to review the contract specifications, provide project contacts, and the manner that work will proceed, among other items. If APG deems a Contractor’s employee to be unfit or unsuitable to perform the contracted work due to intoxication, drug use, by virtue of abusive or obnoxious behavior, by poor quality of work, poor demeanor, or other similar reasons, then upon written request by COR, the Contractor shall remove said employee from APG work and furnish a suitable and competent replacement.

7. SAFETY - When working in APG rights-of-way, the contractor shall follow IDOT Standard Specifications for Road and Bridge Construction for work zone safety.

SCOPE OF WORK

Bidding requirements, general terms and conditions, scope of work and other special requirements are all part of the bidding document and contract specifications. Standard specifications of technical or professional societies and federal, state or local agencies referred to shall include all amendments as of the date of advertisement for bids.

CONTRACTOR execute APG’s Unidirectional Flushing program to locate, inspect, assess, and operate distribution system valves and hydrants, record water flowed, and create a deliverable GIS format suitable and compatible with APG’s current GIS/Database system. Fire hydrants requiring additional (requiring backhoe excavation) work to make them fully operational shall be told to the COR or designee. Minor repairs to valves and/or hydrants may be required which will be repaired/replaced by CONTRACTOR at the Government’s discretion and billed accordingly. The final report is due within thirty days after project completion. Weekly reports will be delivered to the COR or designee on Monday mornings listing work performed the previous week: sections flushed, water used and other information requested by the COR. The specifications are the minimum APG requirements and any omission shall not relieve the CONTRACTOR of furnishing quality service in a timely manner. CONTRACTOR shall provide the services in a safe, efficient and professional manner. The CONTRACTOR shall provide their own tools and vehicles to execute this scope.

1. MINIMUM EXPERIENCE REQUIREMENTS OF PROJECT PERSONNEL:

CONTRACTOR must provide courteous, professional, trained and qualified personnel.

2. SAFETY: A minimum Two Man Crew is required to work together at all times. The use of a one man unit is not acceptable and may terminate contract.

3. UNIDIRECTIONAL FLUSHING SCOPE OF SERVICE: CONTRACTOR shall execute APG’s program to unidirectional flush the water distribution system, create a deliverable database in a suitable format that is compatible with APG’s current GIS/Database system platform. This work essentially consists of:

3.1 Mapping of all flushing sequences in a way that allows their positions and processes to be known and readily re-creatable by APG personnel upon demand.

3.2 Inspection of required fire hydrants for appearance, accessibility, leakage and functionality following the AWWA M-17 manual, NFPA 291 and ISO requirements.

3.3 Inspection of required main line valves for, accessibility, and functionality in accordance with the AWWA M-44 manual.

3.4 Operation of each located required main line valve to insure its ability to operate and fully “close” upon demand. Adherence to the AWWA M-44.

3.5 Enter Fire hydrant, main line valve and flushing sequencing information in an Excel Spreadsheet.

4. Backflow Prevention Devices

4.1 The Contractor shall provide all personnel, equipment, supplies, transportation, tools, materials, supervision, and other items and non-personal services necessary to perform inspection and testing of Backflow Prevention Devices as defined in this Performance Work Statement (PWS).

4.2 Inspection and testing of Backflow Prevention Devices (BFPD) for evidence of dripping, leaking in order to protect drinking water supply and quality for human consumption.

4.3 The contractor will coordinate temporary water shutdowns to equipment or buildings with the COR (Contracting Officer’s Representative)

4.4 The contractor will perform annual compliance inspection, testing, and certification of each backflow prevention device into an authorized Cross Connection Control Management Program.

4.5 A copy of the certification shall be posted at all backflow prevention devices

4.6 The contractor shall not interfere with the normal operations of the current property owner to the extent possible. Contractor must leave all work areas clean and free of debris. Restore any site damages to the mechanical room and to the exterior of the building to its original forms.

4.7 Emergency Service & Repair

The contractor will perform annual maintenance and repairs. Backflow device repairs for failing devices shall be repaired and retested at date and time of original scheduled testing event using backflow rebuild kits for appropriate size backflow device, if repair is just flushing backflow device hourly rate will apply. Contractor to respond to any Complaint/Calls regarding a problem/Leaking Backflow Assembly. Repairs and Re-Certification shall be completed the same time as call in.

4.8 Installer’s Qualification: Qualified firms that are approved, authorized, and licensed by the Maryland State Board of Plumbing. Master Plumbers must be used and be allowed to install products devices, issue certifications, and provide a manufacturer’s warranty. The firm must also be able to provide for testing of mechanical and electrical equipment.

4.9 Backflow Device Recertification:

The contractor will recertify backflow devices annually – Any additions or subtractions to current list will be in writing and put in COR file

Edgewood Area Backflow Devices

3956
WasteWaterTreat Basement pump rm
RPZ
1 1/2"
3950
WasteWater TreatmentPlant.Rear wall
RPZ
1 1/2"
3861-1
WasteWaterTreatPlant.Blower rm
RPZ
1 1/2"
3853
WasteWaterTreatment plant.Basement
RPZ
1 1/4"
3950-1
WasteWaterTreatPlant.Next to door
RPZ
2"
3956-1
WasteWater Treatment Plant Boiler rm
RPZ
3/4"
3861-2
WasteWaterTreatPlant.Blower rm
RPZ
1 1/2"
3861-3
Chemical feed room
RPZ
1"
3857
Main in workshop.Right of entrance
RPZ
2 1/2"
3854
WasteWaterTreatPlant.Right of entrance
RPZ
1 1/2"
1946-1
Mechancial room
RPZ
3/4"
3512
Boiler room
RPZ
1 1/4"
3512-1
Boiler room
RPZ
2"
3512-2
Boiler room
RPZ
2"
3512-3
Boiler room
RPZ
2"
3512-4
Boiler room
RPZ
3/4"
3081-2
Boiler room
RPZ
3/4"
3081-3
Boiler room
RPZ
3/4"
3081
Boiler room
RPZ
6"
3081-1
Boiler room-BYPASS
RPZ
6"
3344
Next to Water Heater
RPZ
1 1/2"
4230
Mechanical Room
RPZ
1"
4620-2
Mechanical Room Bypass
RPZ
1"
4620-1
Mechanical Room
RPZ
1"
5425
Mechanical Room
RPZ
1"
5134-2
Mechanical Room
RPZ
1"
5427
Next to Front Door
RPZ
2"
4227-2
Mechanical Room
RPZ
3/4"
5604
Main. End of building.Corridor
RPZ
4"
5265
Mechanical Room
RPZ
4"
4586
Next to mens rm behind box out
RPZ
1 1/2"
5165
Break room. Kitchen pantry
RPZ
1 1/4"
4225-5
Mechanical room
RPZ
1 1/4"
1400
Behind refrigerator
RPZ
1"
5365
Next to front door
RPZ
2 1/2"
4225-3
Mech rm.See bldg 4221 for access
RPZ
2 1/2"
1645
Exterior mechanical roo,
RPZ
2"
4225-4
Mechanical room
RPZ
3/4"
4227
Mechanical room
RPZ
4"
2200
Mechanical rm.Rear of building
RPZ
1 1/2"
4040
Exterior mechanical room
RPZ
1 1/2"
4810
Mens bathroom
RPZ
1 1/2"
4081-5
New Mechanical room
RPZ
1 1/2"
4811
Mens bathroom.Behind access panel
RPZ
1 1/2"
4081-3
Mechanical room
RPZ
1"
4081-4
Rear of old mechanical room
RPZ
1"
1260-2
Mechanical room
RPZ
1/2"
4306
Shop area. Truck area
RPZ
2"
5554
Mens rm.Behind door.See Rich at E5560
RPZ
2"
4081
Mechanical room
RPZ
3"
4081-1
Mechanical room RPZ is on TOP
RPZ
3"
4081-2
Mechanical room.RPZ is on BOTTOM
RPZ
3"
2901
Mechanical room
RPZ
8"
2901-1
Mechanical room
RPZ
8"
3949-1
Mechanical room
RPZ
3/4"
1902-1
Mechanical room
RPZ
1 1/4"
5800-1
Mechanical room. Exterior wall
RPZ
1/2"
5800
Outside mens room
RPZ
2"
5800-2
Lab above sink
RPZ
3/4"
3550
Storage Bay First Bay Door
RPZ
1 1/2"
3554
BAY Door
RPZ
1 1/2"
3607
Conference room Closet
RPZ
1 1/2"
3724-2
Equipment Room
RPZ
1 1/4"
1942-1
Mechanical room
RPZ
1"
5307
Mechanical Room
RPZ
1"
5664
North End Warehouse
RPZ
2"
5103-1
Mechanical room
RPZ
1"
4301-3
Mechanical Room
RPZ
1"
2100-5
Mechanical room
RPZ
1"
2100-6
Mechanical room
RPZ
1"
2100-7
Room 3106
RPZ
1/2"
2100-8
Lab 2302
RPZ
1"
3240
Mech room.Rear of building
RPZ
3/4"
3100-2
Mechanical room
RPZ
1"
3100-2
Mechanical room
RPZ
2"
2101
Basement mechanical room
RPZ
3/4"
3100-3
Mechanical room
RPZ
3/4"
3100-4
Mechanical room
RPZ
3/4"
3100-5
Mechanical room
RPZ
3/4"
3100-6
Mechanical room
RPZ
3/4"
1464
Mechanical room
RPZ
1 1/2"
1464-2
Mechanical room
RPZ
3/4"
4223-2
Mechanical room
RPZ
3/4"
3832-4
Mech rm. Behind boiler.On bottom
RPZ
1"
3832-2
Mech rm.Behind boiler. On top
RPZ
2"
2410
Break room
RPZ
1 1/4"
3832-5
Mech rm. Behind boiler.On bottom
RPZ
1"
3832-3
Mech rm. Behind boiler On top
RPZ
2"
5100-3
Mechanical room
RPZ
2"
5352
Behind bathroom/ac unit
RPZ
2"
5240-1
Mech rm above water heater
RPZ
1/2"
1675
Mechanical Room
RPZ
2 1/2"
4517
Exterior Mechanical Room
RPZ
2"
5183-1
Mechanical Room
RPZ
3/4"
E2900-VB1
Exterior
VB
3/4"
E2900-VB2
Exterior
VB
3/4"
E2900-VB3
Exterior
VB
3/4"
E2900-VB4
Exterior
VB
3/4"
E2900-VB5
Exterior
VB
3/4"
E2900-VB6
Exterior
VB
3/4"
E2900-VB7
Exterior
VB
3/4"
E2900-VB8
Exterior
VB
3/4"
4903
Access panel in lobby
RPZ
1 1/2"
3942
Bathroom
RPZ
1 1/2"
3549-5
Mech room.Left of entrance
RPZ
2"
3549-6
Mech room.Left of entrance
RPZ
2"
3549-7
Back of mechanical room
RPZ
2"
3549-4
Mech room.Left of entrance
RPZ
3/4"
5642
Rear of bldg in boiler hut
RPZ
1"
5660
Under back of trailer
RPZ
3/4"
3949
Hallway closet
RPZ
1 1/2"
3836
Mechanical room
RPZ
1 1/2"
2100-2
Mechanical room
RPZ
1 1/4"
2100-3
Mechanical room
RPZ
1 1/4"
2100-1
Mechanical room
RPZ
1"
3549-9
Back of mechanical room
RPZ
2"
3549-11
Back of mechanical room
RPZ
2"
5232
Office.2nd cubical behing plywood
RPZ
2"
4215-1
Basement mechanical room
RPZ
3"
3549-8
Back of mech room. BYPASS
RPZ
3/4"
3549-10
Back of mechanical room.BYPASS
RPZ
3/4"
3549-12
Back of mechanical room
RPZ
3/4"
4215
Basement mechanical room
RPZ
3/4"
2100
Mechanical room
RPZ
4"
2100-4
Mechanical room
RPZ
4"
3150-3
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-5
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-10
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-13
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-15
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-17
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-20
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-22
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-24
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-26
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-28
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-32
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-33
Interstitial space between 2nd & 3rd floor
RPZ
1 1/2"
3150-36
1st Floor mechanical room BYPASS
RPZ
1 1/2"
3150-40
Mechanical room
RPZ
1 1/4"
3150-19
Interstitial space between 2nd & 3rd floor
RPZ
1"
3150-37
3rd Floor mechanical room
RPZ
1"
3150-1
Interstitial space between 2nd & 3rd floor
RPZ
1/2"
3150-2
Interstitial space between 2nd & 3rd floor
RPZ
1/2"
3150-6
Interstitial space between 2nd & 3rd floor
RPZ
1/2"
3150-16
Interstitial space between 2nd & 3rd floor
RPZ
1/2"
3150-18
Interstitial space between 2nd & 3rd floor
RPZ
1/2"
3150-14
Interstitial space between 2nd & 3rd floor
RPZ
1/2"
3150-34
1st Floor mechanical room BYPASS
RPZ
2"
3150-35
1st Floor mechanical room BYPASS
RPZ
3"
3150-39
1st floor tank room
RPZ
3"
3150-4
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-7
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-8
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-9
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-11
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-12
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-21
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-23
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-25
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-27
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-29
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-30
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-31
Interstitial space between 2nd & 3rd floor
RPZ
3/4"
3150-38
Ist floor crawl space
RPZ
4"
3150-41
1st Floor crawl space BYPASS
RPZ
4"
1570
Mechanical room basement
RPZ
1 1/2"
1570-2
Basement Sprinkler room
RPZ
2 1/2"
3400-21
Penthouse Mechanical room
RPZ
1 1/2"
3400-22
Penthouse Room 310
RPZ
1 1/2"
3400-23
Penthouse Room 310
RPZ
1 1/2"
3401-3
2ND Floor mechanical room
RPZ
1 1/2"
3400-10
1st Floor mech room
RPZ
1 1/4"
3400-9
1st Floor mech room
RPZ
1"
3400-11
1st Floor mech room
RPZ
1"
3400-14
Penthouse Room 310
RPZ
2"
3400-15
Penthouse Mechanical room
RPZ
2"
3400-16
Penthouse Mechanical room
RPZ
2"
3400-17
Penthouse Mechanical room
RPZ
2"
3400-12
Penthouse Room 310
RPZ
3/4"
3400-13
Penthouse Room 310
RPZ
3/4"
3400-18
Penthouse Room 310
RPZ
3/4"
3400-19
Penthouse Room 310
RPZ
3/4"
3400-20
1st Floor mech room
RPZ
3/4"
3401-1
2ND Floor mechanical room
RPZ
3/4"
3401-2
2ND Floor mechanical room
RPZ
3/4"
3401-4
2ND Floor mechanical room
RPZ
1 1/2"
3835-3
Mechanical room next to entrance
RPZ
2 1/2"
3835-4
Basement mechanical room
RPZ
2"
3835-2
Mech room next to entrance
RPZ
3"
3401-5
2ND Floor mechanical room
RPZ
3/4"
3401-6
Exterior mechanical room
RPZ
4"
3401-7
Exterior mechanical roomBYPASS
RPZ
4"
3401-8
Mechanical room
RPZ
2"
3401-9
Mechanical room
RPZ
2"
3401-10
Mechanical room
RPZ
2"
3401-11
Mechanical room
RPZ
2"
3410-2
Meachine room #1
RPZ
3/4"
3510-2
Mechanical room
RPZ
3/4"
5179-3
Warehouse next to shower
RPZ
1 1/2"
5173
Next to steam station.Back of warehouse
RPZ
1 1/4"
3101
Mechanical room
RPZ
2"
1260-1
Mechanical room
RPZ
2"
1902
Mechanical room
RPZ
2"
1901
Mechanical room
RPZ
3"
1901-1
Mechanical room
RPZ
3/4"
4223-1
Mechanical room
RPZ
2"
3007
In closet,left of door
RPZ
1 1/2"
5183
Basement mechanical room
RPZ
2"
3109
Mechanical room
RPZ
2"
4595
Interior sprinkler room
RPZ
2"
5642
Rear of building. In hut
RPZ
1"
3928-1
Mechanical room
RPZ
1 1/2"
5884
Right of Building Entrance
RPZ
1 1/2"
3615
Bathroom stall
RPZ
1 1/2"
3931-1
Mechanical room
RPZ
1 1/4"
1407
Womens bathroom
RPZ
1"
3330-1
Mechanical room
RPZ
1"
3348
Mens bathroom
RPZ
1"
3615
Next to mop sink
RPZ
1"
3330-2
Mechanical room
RPZ
2"
3330-4
Mechanical room. Basement
RPZ
2"
5240
Break room closet
RPZ
2"
3612-1
Front door to the left
RPZ
2"
3831
Mechanical room
RPZ
2"
4475
Mechanical room behind air handler
RPZ
2"
4039
Exterior Mechanical Room
RPZ
2"
5685
Back right corner Roll up Door
RPZ
2"
5840
Mens Room
RPZ
3"
3330-5
Mechanical room
RPZ
3/4"
3330
Under stair case
RPZ
4"
3330-3
Under stair case BYPASS
RPZ
4"
3331
Basement/Across from mensroom
RPZ
4"
3615
Bathroom stall
RPZ
1 1/2"
3928-1
Mechanical rm. Left wall
RPZ
1 1/2"
3931-1
Mechanical room left of door
RPZ
1 1/4"
3348
Mens room
RPZ
1"
3615-1
Behind washing machine
RPZ
1"
3330-1
Mechanical room
RPZ
1"
5240
Water heater room in breakroom
RPZ
2"
3612-1
Southwest corner of building
RPZ
2"
3831
Mechanial room
RPZ
2"
4475
Mech room behind air handler
RPZ
2"
3524
Attic-right side of building
RPZ
2"
3526
Mechanical room.Right of door
RPZ
2"
3330-2
Mechanical room
RPZ
2"
3330-4
Mechanical room
RPZ
2"
3312-1
Boiler room
RPZ
3"
3312-2
Boiler room BYPASS
RPZ
3"
3320
Mechanical room
RPZ
3"
3330-5
Mechanical room
RPZ
3/4"
3630
Warehouse right of door
RPZ
3/4"
3330-3
Under stair case
RPZ
4"
3331
Closet across from mens room
RPZ
4"
3726-1
Mechanical room
RPZ
2 1/2"
4220
Exterior mechanical room
RPZ
2"
4221
Mechanical room
RPZ
2"
4228-1
Mechanical room
RPZ
2"
4140
Mechanical room
RPZ
3"
3516
In work shop office
RPZ
3"
3934-1
Warehouse
RPZ
3/4"
3724-1
Mechanical room
RPZ
4"
3551
Janitor closet
RPZ
1 1/2"
3552
North corner of building
RPZ
1 1/2"
4526
Exterior mechanical room
RPZ
1 1/2"
3947-2
Warehouse closet
RPZ
1"
4525
Utility room
RPZ
1"
5103
Mechanical room
RPZ
2 1/2"
3947-1
Garage bay closet
RPZ
2"
3948
Mechanical room
RPZ
2"
4524
Closet
RPZ
2"
5100
Mens room behind tanks
RPZ
2"
5106
Breakroom
RPZ
2"
3830-1
Main in chase
RPZ
2"
4900
Apt #4 closet
RPZ
3"
5100-2
Mech room BYPASS
RPZ
3"
5106-1
Mens room.Heat exchanger
RPZ
3/4"
5100-1
Mechanical room
RPZ
4"
3100
Mechanical room
RPZ
4"
3100-1
Mechanical room
RPZ
4"
1607
Bathroom
RPZ
1 1/4"
4586
Next to mens rm hallway
RPZ
1 1/2"
4586-1
Mechanical room
RPZ
1 1/2"
1932
Warehouse next to bay door
RPZ
1 1/2"
5828-3
Boiler room
RPZ
1 1/4"
1930-5
Mechanical room
RPZ
1 1/4"
1930-5
Mechanical room
RPZ
1 1/4"
3832-1
Mechanical room
RPZ
2"
5828
Mech rm BYPASS.Right of baydoor
RPZ
2"
5828-1
Mech rm BYPASS.Right of baydoor
RPZ
2"
1930
Mechanical room
RPZ
2"
3510-1
Mechanical room
RPZ
3"
5828-2
Boiler room
RPZ
3/4"
3161-1
Mechanical room
RPZ
3/4"
1930-1
Mechanical room BYPASS
RPZ
3/4"
1930-2
Mechanical room
RPZ
3/4"
1930-3
Mechanical room BYPASS
RPZ
3/4"
1930-4
Mechanical room
RPZ
3/4"
2188
Mechanical room
RPZ
2"
2188-1
Mechanical room
RPZ
2"
4224
Mechanical room
RPZ
2"
4210-3
Boiler room
RPZ
1 1/2"
3103
Outside water heater room
RPZ
1 1/2"
3548
Janitor closet
RPZ
1 1/2"
3156-3
Mechanical room
RPZ
1 1/4"
3156-4
Mechanical room
RPZ
1"
4210-1
Mechanical room
RPZ
2"
3156
Mechanical room
RPZ
2"
3156-1
Mechanical room
RPZ
3/4"
E-1260G-01
Golf Course Green #01
VB
3/4"
E-1260G-02
Golf Course Green #02
VB
3/4"
E-1260G-03
Golf Course Green #03
VB
3/4"
E-1260G-04
Golf Course Green #04
VB
3/4"
E-1260G-05
Golf Course Green #05
VB
3/4"
E-1260G-06
Golf Course Green #06
VB
3/4"
E-1260G-07
Golf Course Green #07
VB
3/4"
E-1260G-08
Golf Course Green #08
VB
3/4"
E-1260G-09
Golf Course Green #09
VB
3/4"
E-1260G-10
Golf Course Green #07
VB
3/4"
E-1260G-11
Golf Course Green #08
VB
3/4"
E-1260G-12
Golf Course Green #09
VB
3/4"
3928
Mechanical room
RPZ
1 1/2"
4620
Mechanical room
RPZ
2"
3831
Mechanical room
RPZ
2"
4475
Mechanical room
RPZ
2"
4230-2
Mechanical room
RPZ
3"
4516-3
Exterior mechanical room
RPZ
3"
1942
Warehouse next to bay door
RPZ
2"
2901-2
3rd Floor. Mechanical room
R
4"
2800
Mechanical room
RPZ
3/4"
2800-1
Mechanical room
RPZ
4"
3566-1
Front of water heater
RPZ
1 1/2"
3566
Next to deco tank
RPZ
2"
5234-1
Janitor closet
RPZ
1 1/2"
2162
Warehouse. Behind furnace
RPZ
1 1/2"
1043
Mechanical/sprinkler room
RPZ
1 1/2"
1042
Janitor closet
RPZ
2"
5560
Mechanical room
RPZ
1 1/2"
5560-2
Mechanical room
RPZ
1"
1457
Mechanical room
RPZ
3/4"
5179-3
Warehouse next to shower
RPZ
1 1/2"
5180
Truck bay
RPZ
1 1/2"
3615
Bathroom Stall
RPZ
1 1/2"
3931-1
Mechanical Room
RPZ
1 1/4"
5141
Ladies room
RPZ
1"
3462-1
Next to sprinkler room
RPZ
1"
2101
Water heater room
RPZ
1"
2101-1
Water heater room
RPZ
1"
3348
Mens Room
RPZ
1"
3615-1
Behind Wash Machine
RPZ
1"
3462
Sprinkler room
RPZ
2 1/2"
5140
Sprinkler room
RPZ
2"
2101-2
Water heater room
RPZ
2"
2390
Mechanical room
RPZ
2"
5240
Water Heater Room
RPZ
2"
3612
Southwest Corner of Building
RPZ
2"
2101-3
Mechanical room
RPZ
3/4"
2101-4
Mechanical room
RPZ
3/4"
2390-1
Mechanical Room
VB
3/4"
3330-5
Mechanical Room
RPZ
3/4"
5014
Mechanical room
RPZ
1 1/2"
4305-4
Mech rm wall.Boiler make up
RPZ
1"
4305-1
Mechanical room
RPZ
2 1/2"
1523
Bathroom. Main water
RPZ
3/4"
3326
Conference room
RPZ
1 1/2"
4465-1
Office
RPZ
2"
1401
Mechanical room closet
RPZ
2"
3400-5
Mechanical room
RPZ
3"
3400-6
Mechanical room
RPZ
3"
3400-7
Mechanical room
RPZ
3"
3400-8
Mechanical room
RPZ
3"
1526
Restroom Main water
RPZ
3/4"
1375
Mens room.May need contact info
RPZ
3/4"
3400-8
Exterior mechanical room
RPZ
4"
3401-7
Ext mechanical roomBYPASS
RPZ
4"
4222
Closet next to laundry room
RPZ
4"
1430
Rear storage room
RPZ
4"
3400-3
Mechanical room
RPZ
6"
3400-4
Mechanical room
RPZ
6"
2330
Mechanical room
RPZ
1 1/2"
5357
On outside wall next to bathrooms
RPZ
1"
3106
Communication closet
RPZ
2"
2187
Oficce next to bathroom
RPZ
1 1/2"
5233
Janitor closet
RPZ
1 1/2"
2900-13
Mechanical room E-3000
DC
1 1/2"
2900-14
Mechanical room E-3000
DC
1 1/4"
2900-15
C-5000 Mechanical room
RPZ
1"
2900-16
B-4000 Mechanical room
RPZ
1"
2900-3
Station E-3B/E-3 Mech rm 2905
DC
1/2"
2900-4
Station 3-C/E-3Mech rm.Lab2907
DC
1/2"
2900-5
Station E-3F/E3Mech rm.Lab2915
DC
1/2"
2900-6
StationE-3K/E3 Mech rm.Lab2301
DC
1/2"
2900-7
StationE3A/E3 Mech rm.Lab2903
DC
1/2"
2900
4th Floor.Mechanical room
RPZ
2 1/2"
2900-8
StationE3N/E-3Mech rm.Lab2311
DC
3/4"
2900-9
StationE30/E-3Mech rm.Lab2315
DC
3/4"
2900-10
StationE3G/E-3Mech rm.Lab2302
DC
3/4"
2900-11
StationE3L/E3Mech rm.Lab2303
DC
3/4"
2900-12
StationE-3M/E3Mech rm.Lab2305
DC
3/4"
2900-1
Mechanical room.E-4000 BYPASS
RPZ
6"
2900-2
Mechanical room.E-4000
RPZ
6"
4655-1
Pool house pump room
RPZ
1 1/2"
4655
Mechanical room
RPZ
2"
5360
Mechanical shop
RPZ
4"
5360-1
West corner next to bathroom
RPZ
4"
4535
Janitor closet
RPZ
3/4"
4536
Janitor closet
RPZ
3/4"
4060
Sprinkler room
RPZ
3/4"
5236
Basment mech rm.Next to pump
RPZ
2"
5236-1
Mechanical room
RPZ
2"
1901
Mechanical room.Main water
RPZ
3"
1901-1
Mechanical room
RPZ
3/4"
5057
Bathroom
RPZ
1"
1574
Boiler room
RPZ
2"
4405
South wall
RPZ
2"
3244-1
Mechanical room BYPASS
RPZ
2"
3244-2
Mechanical room
RPZ
2"
3244-3
Mechanical room
RPZ
3/4"
4010
Storage area
RPZ
1"
5126-1
Behind 8" backflow
RPZ
2"
4010-1
Storage area
RPZ
2"
3549-2
Mechanical room BYPASS
RPZ
6"
3549-3
Mechanical room
RPZ
6"
5126-3
Boiler room back wall.BYPASS
RPZ
6"
5126-4
Boiler room back wall
RPZ
6"
5126-2
Next to material room
RPZ
8"
1932
Warehouse next to bay door
RPZ
1 1/2"
2194-1
Mechanical room
RPZ
1"
1958
Outside mechanical room
RPZ
2"
2433
Electric room
RPZ
2"
2194
Mechanical room
RPZ
2"
1958-1
Outside mechanical room
RPZ
3/4"
2169
Boiler room
RPZ
1 1/2"
5390
Mechanical room
RPZ
2 1/2"
5002
Next to basement door
RPZ
2"
3580
Mechanical room
RPZ
2"
3580-1
Mechanical room
RPZ
3"
5290-1
Mechanical room
RPZ
3/4"
5180
Truck bay
RPZ
1 1/2"
2172
Ice house at Marina
RPZ
3/4"
4902-1
Mechanical room
RPZ
1/2"
4902
Mechanical room
RPZ
3"
4902-2
Mechanical room
RPZ
3/4"
5146
Mechanical room
RPZ
1 1/4"
5703
Next to utility sink
RPZ
1"
4110-1
Mechanical room BYPASS
RPZ
2 1/2"
4110-2
Mechanical room
RPZ
2 1/2"
5641
Lab office
RPZ
2"
5707
Next to bathroom
RPZ
2"
5866
Next to eyewash
RPZ
2"
4110-4
Mechanical room
RPZ
3/4"
4110-5
Mechanical room
RPZ
3/4"
4110-6
Mechanical room
RPZ
3/4"
4110-7
Mechanical room
RPZ
3/4"
2901-3
2901 Cup Blvd.Mechanical room
RPZ
4"
5803
Mechanical room
RPZ
2 1/2"
5158
Sprinkler room
RPZ
2"
5803-1
Mechanical room
RPZ
3/4"
4160-1
Boiler room
RPZ
3"
4160-2
Boiler room BYPASS
RPZ
3"
5027
Closet near steam pit
RPZ
2"
6814
Shower room
RPZ
1"
6811-1
Mens bathroom
RPZ
2"
6811-2
Mechanical room
RPZ
2"
6810-1
Mens bathroom
RPZ
2"
6810-4
Mens bathroom
RPZ
2"
6812
Mechanical room
RPZ
2"
6810-5
Boiler room
RPZ
3/4"
6810-6
Boiler Mech room
RPZ
3/4"
7010
Bathroom
RPZ
3/4"
6811-3
Boiler room
RPZ
3/4"
5664-1
Next to office ice machine
RPZ
1"
3160-1
Mechanical room
RPZ
3/4"
3160
Mechanical room
RPZ
4"
1356-T
IT room.Trailer on left
RPZ
2"
5354
Next to bay door
RPZ
4"
5430
Next to bay door
RPZ
3"
5185
Tool room
RPZ
6"
1950-2
Womens bathroom
RPZ
1 1/4"
1950-1
Womens bathroom
RPZ
2"
Marina
Marina bulkhead
RPZ
1"
4301-2
Mech rm.Cooling Tower
RPZ
1 1/2"
4301-3
Mechanical room
RPZ
1"
4301-4
Mech rm.Boiler make up
RPZ
1"
4301-1
Mechanical room. BYPASS
RPZ
4"
4301
Mechanical room
RPZ
6"
5830-1
Warehouse
RPZ
2"
5830-2
Warehouse
DC
4"
2174
Mens bathroom
RPZ
1 1/2"
2400-1
Mechanical Room
RPZ
1"
2400
Sprinkler room
RPZ
3"
2174-1
Shower room
RPZ
3/4"
5951-2
Hallway by mens bathroom
RPZ
2 1/2"
1431
Boiler room
RPZ
2"
5951-1
Mens bathroom
RPZ
3"
1431-1
Boiler room
RPZ
3/4"
5951-3
Upstairs mechanical room
RPZ
3/4"
5951-4
Upstairs mechanical room
RPZ
3/4"
3844-4
Mechanical room
RPZ
1"
3844-2
Mechanical room
RPZ
2"
3844
Mechanical room BYPASS
RPZ
3"
3844-1
Mechanical room
RPZ
3"
3844-3
Mechaincal room
RPZ
4"
3844-5
Mechanical room
RPZ
4"
5863
Water heater room
RPZ
1 1/2"
5864
Left end of bldg. Room 8
RPZ
2"
4585
Mens bathroom
RPZ
2"
4585-1
Mechanical room
RPZ
2"
4913
Bathroom
RPZ
2"
4585-2
Mechanical room
RPZ
3/4"

5. The CONTRACTOR will not be held responsible for possible valve or hydrant failures during operation, damage done to the water system during water main flushing (i.e. water leaks, discolored water, turbidity, etc.), or possible damage to the APG’s individual water customer unless unsatisfactory or neglectful operations by CONTRACTOR.

6. SEQUENCING ACTION: Before starting field work, a Standard Operating Procedure of action sequencing for the flushing activity shall be set. Contingencies like mitigation of reduced fire flows in critical areas (i.e. medical facilities, schools, etc.) must be included.

6.1 This work may require flushing to be performed after regular duty hours (0700-1600) to not interrupt missions with low water pressure.

6.2 This may require weekend and or holiday work if an emergency arises.

7. CUSTOMER NOTIFICATION

7.1 CUSTOMER BILLING MAILER: CONTRACTOR will assist develop a letter which briefly explains the Unidirectional Water Main Flushing program which must be approved by COR.

7.2MEDIA NOTIFICATION: CONTRACTOR will develop a press release to explain the Unidirectional Water Main Flushing program and affected areas. APG Public Affairs Office will send the press releases. This type of customer notification greatly reduces the number of customer complaints about discolored water.

8. FLUSHING

8.1 VALVES: To increase the water main velocity without opening additional hydrants (to conserve water), specific valves will be closed prior to flushing as per APG’s Unidirectional Plan. These valves will be recorded to insure that all valves are re-opened at the end of each day. A Standard Operating Procedure for valve operations will be included with the plan.

8.2 PRESSURE READINGS: CONTRACTOR will use accurate pressure gauges to determine that the required velocities are achieved during the flushing process. CONTRACTOR shall provide recently-dated proof that the pressure gauges used have been calibrated.

9. DOCUMENTATION AND COMMUNICATION:

9.1 CONTRACTOR’S field crew will meet as agreed, with COR to go over areas of the Unidirectional Flushing program.

9.2 Atlas Corrections and Notations: CONTRACTOR will document and note needed corrections on GIS maps. These notations will be part of the final report so APG can make corrections to their existing GIS files.

9.3 At the end of each day, or as requested, a written list of broken or inoperable fire hydrants or mainline valves will be given to COR. Critical fire hydrants/valves that may be subject to breakage will be discussed as far as operation PRIOR to exercising to prevent loss of fire protection.

9.4 Information collected by the CONTRACTOR and other information provided by APG shall be marked as Controlled Unclassified Information (CUI) and will not be shared without written permission from the APG.

9.5 Submit a Unidirectional Flushing Log with the final report including:

A. Areas where work was performed B. Type of problems observed C. Location of problems discovered D. Mapping errors

9.6 Submit final report to APG by thirty working days after fieldwork is complete.

9.7 Unidirectional Flushing data must be exportable into Excel spreadsheet.

10. ASSUMPTIONS AND SERVICES PROVIDED BY APG

10.1 Furnish all maps, atlases, (two copies) and records to properly conduct the Unidirectional Flushing program. Digital copies of the map (AutoCAD, ArcView) will be provided if available.

10.2 Make available, on a reasonable but periodic basis, staff with a working knowledge of the water system to help with inoperable or difficult to operate fire hydrants and with general water system information. This APG employee will not assist the CONTRACTOR on a full time basis.