SOW.pdf
PDF 1016 KB Posted
- Attached to
- Base Electrical System Study Federal contract opportunity
- Solicitation number
- W50S9320B5004
- Issued by
- Department of the Army National Guard
About this file
This scope of work document outlines requirements for an electrical system study of the Muniz Air National Guard Base in Puerto Rico. The study will include performing an electrical load assessment and power quality analysis across the base distribution system through the use of power recorders and harmonic analyzers. A site visit is scheduled for April 28, 2020. Quotes are due by May 11, 2020 for the following deliverables: as-built drawings of the one-line diagram and site plan utilizing base CADD standards; a comprehensive electrical system study report analyzing the existing conditions, scenarios evaluated, equipment loadings, voltage and current distortions, inspection findings, and recommendations; and submission of the final report in Word and PDF formats on compact disks. The period of performance is 90 days from award. The solicitation is set aside for small businesses with a NAICS code of 238210 and size standard of $16.5M.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Industry Questions and Answers (PDF).pdf | ||
| Electric utility bills.pdf | ||
| Combined Synopsis - Solicitation.pdf | ||
| DD369 - Police Record Check.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNICAL PROVISIONS
FROM:
156th AW/MSG BASE CIVIL ENGINEER
PUERTO RICO AIR NATIONAL GUARD
CAROLINA, PUERTO RICO
SCOPE OF WORK FOR
BASE ELECTRICAL SYSTEM STUDY
TUMR192102
FOR:
156th AW/MSG CONTRACTING OFFICER
PUERTO RICO AIR NATIONAL GUARD
CAROLINA, PUERTO RICO
TECHNICAL PROVISIONS
SCOPE OF WORK FOR
BASE ELECTRICAL SYSTEM STUDY
TUMR192102
GENERAL INDEX
SECTION CONTENTS PAGE NO.
1 General Scope 1
2 Project Description 1
3 Objective and Milestones 1
4 Detailed Description of Submittals 2
5 General Requirements 3
6 Reference Drawings 4
SCOPE OF WORK
FOR
TUMR192102 Base Electrical System Study
1.0 GENERAL SCOPE:
The Architect-Engineer shall provide all materials and services for Base Electrical System
Study
2.0 PROJECT DESCRIPTION:
2.1 Muniz Air National Guard Base Power Electrical Distribution system consist of a main underground three phase 4,160V electrical feeder coming from Puerto Rico Electrical
Power Authority (PREPA) existing switch unit 24 (SU-24).This feeder provide power to a main switch unit located next to building 11. Electrical system metering equipment is located in this switch. From the main switch seven underground 4,160V electrical feeders conform the backbone of the base primary distribution system.
2.2 Perform an electrical system study to the Power distribution system of Muniz Air
National Guard Base, Carolina, Puerto Rico. The evaluation should consider the health of the facility’s electrical power distribution system. With the results of the evaluation, provide documentation of existing electrical system configuration, overall system condition, improvement needs and electrical system availability and reliability.
3.0 OBJECTIVES AND MILESTONES:
3.1 Perform an electrical load study (Voltages, VA, Watts, Power factors currents etc.) and power quality assessment throughout the installation of power recorders and or harmonic analyzer at the main switch unit (4.16kV) and to all the distribution transformers.
3.2 Perform visual inspection as necessary to the Base Main electrical distribution system, including main switch unit, substation A and B, distribution transformers, underground primary feeders, electrical manholes etc.
3.3 Contractor is responsible of provide manpower and materials to open manholes and provide dewatering system if necessary to perform the electrical manholes inspections.
3.4 The contractor shall provide all labor, equipment, supplies, consultant services and all site investigations, surveys, analysis and verification of existing electrical system in order to complete this study.
3.5 Attend a preliminary conference to discuss the requirements and walk through of the area. Gather required information to begin the assessment.
3.6 Contractor Qualifications: The study shall be prepared by a qualified Registered
Professional Electrical Engineer licensed in Puerto Rico working for an Electrical
Testing Company (NETA Full member Company) with a least 10 years of experience performing this type of studies and analysis.
3.7 Develop an Electrical System Study Report. Attend a report review meeting.
TUMR192102 Base Electrical System Study
3.8 .Incorporate report review comments into report. Submit Final report package. Include all requirements from contract.
4.0 DETAILED DESCRIPTION OF SUBMITTALS
4.01 (Provide a minimum of the following) The contractor shall prepare an as built drawings (22" X 34") of the electrical system one line diagram and electrical site plan for the electrical primary distribution system, utilizing Muniz ANG Base
CADD standards at working scale with a Cover Sheet in Standard format depicting the project name and number, half size sets are 11” x 17”.
4.02 A complete Electrical System Study Report which includes as a minimum the following:
1. Basis, description, purpose, and scope of study.
2. Tabulations of the data used to model the system components and a corresponding one line diagram.
3. Descriptions of the scenarios evaluated and the basis of each.
4. Tabulations of power, RMS current, RMS Voltage, Peak Voltage, power factor versus equipment ratings. The tabulation shall identify percentage of rated load and the scenario for the percentage is based. Overloaded equipment shall be clearly noted.
5. Tabulations of calculated voltage distortion factors, current distortion and individual harmonics vs the limits specified by ANSI/IEEE519.
6. Comparison equipment nameplate data with available drawings and specifications.
7. Inspection of physical and mechanical conditions.
8. Inspection of anchorage, alignment, grounding, and required area clearances.
9. Conclusions,recommendations and recommendations estimated cost.
4.03 The 100% Final report specifications shall be submitted using Word for Windows version 6.0. In addition a PDF copy of the final report will be required. The report shall be placed on compact disks. All report shall be typed on 8 1/2" X 11" pages
(maps, drawings, and spreadsheets may be fold out pages).
TUMR192102 Base Electrical System Study
5.0 GENERAL REQUIREMENTS:
5.1 Only the Contracting Officer can change the scope of the work described in this
Statement of Work. The government is under no obligation to compensate the
Contractor for work performed outside of the scope of this task order without prior written approval of the Contracting Officer. The Contractor is therefore cautioned that performing work beyond that described here, without first receiving written direction, will be done at the Contractor’s expense without recourse against the government or its agents.
5.2 Changes to the scope of this task assignment, which the Contractor feels to be in the best interest of the government, may be submitted to the Contracting Officer for consideration. Any such request for changes must be made at or before the preliminary submittal.
Submittal Schedule
Data Gathering 30 Calendar Days
Report Preparation 20 Calendar Days
Government Review 5 Calendar Days
Pre-final Submittal 5 Calendar Days
Government Review 5 Calendar Days
Final Submittal 7 Calendar Days
TOTAL 72 Calendar Days
TRANSFOMERS PLAN
GENERATORS
STOP
STOP
MUÑIZ ANG BASE
156th AIRLIFT WING
MUÑIZ ANG BASE LUIS MUÑOZ MARIN INTERNATIONAL AIRPORT
BASE MASTER PLAN
SCALE
SHEET
DATE
ANG NO.
PRANG
APPROVED
DRAWN BY
TRACED BY
OF
ANG CIVIL ENGINEER
SUBMITTED
156TH BASE MUÑIZ
| Front Cover |
| TUMR192102 Base Electrical System Study |
| Muniz Oneline Diagram 8APR2015 |
| ELEC & POWER |