SOW Attachment (2) Existing Conditions.pdf

PDF 4 MB Posted

Attached to
NSWCPD | B542 Design Build Fire Alarm Repairs (Mass Notification Systems)
Solicitation number
N64498-25-R-4034
Issued by

About this file

This document is a Statement of Work (SOW) Attachment detailing the existing fire alarm control panel (FACP) system for Building 542 at the Philadelphia Naval Business Center. The attachment includes a comprehensive floor plan layout, module details, and multiple photographs documenting the current fire alarm and mass notification system infrastructure.

The documentation provides a detailed inventory of the existing NFS2-640 fire alarm system, including 28 device modules with specific addresses, types (such as monitors, relays, pull stations), and locations. The floor plan shows the positioning of various fire alarm components like pull stations, risers, and equipment rooms. Accompanying photographs capture the physical layout of the fire alarm control panel, pump room, risers, waterflow switches, and tamper switches across different areas of the building. This technical documentation appears to support the naval contract opportunity for a design-build fire alarm and mass notification system replacement project.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

neal.j.moran Text Box SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

BLDG 542 FIRE ALARM & MASS NOTIFICATION SYSTEM (FA&MNS) REPAIR

Sheet 1 of 8 neal.j.moran Stamp neal.j.moran

Fire Alarm Control Panel (FACP) Floor Plan -- Existing Layout

All Current Modules

Device

Address/

Point

Type

Code Label

Walk Test

Participation

Control-By-Event

Switch

Inhibit

SilenceableCustom Label Extended Label

Flash

Scan Type

SLC

Loop/

Panel

Site ID: 0

Date: 5/27/2014

NFS2-640

Port ID: 0 Node Address: 0

Waterflow Delay

(Sec)

Modules

Monitor N/A N/A PULL STATION EAST N/A 1 1 Z11MINI/DUAL MONITOR N/A

Monitor N/A N/A PULL STATION WEST N/A 2 1 Z12MINI/DUAL MONITOR N/A

Monitor N/A N/A PULL STATION SOUTH N/A 3 1 Z13MINI/DUAL MONITOR N/A

Monitor N/A N/A RISER 1 COL C9 FLOW/TAMPER N/A 4 1 Z14MINI/DUAL MONITOR N/A

Monitor N/A N/A RISER 2 PUMP RM ROOF WATERFLOW N/A 5 1 Z15MINI/DUAL MONITOR N/A

Monitor N/A N/A RISER 3 COL C32 FLOW/TAMPER N/A 6 1 Z16MINI/DUAL MONITOR N/A

Monitor N/A N/A RISER 4 COL C38 FLOW/TAMPER N/A 7 1 Z17MINI/DUAL MONITOR N/A

Non Fire N/A N/A SPARE N/A 8 1 Z70MINI/DUAL MONITOR N/A

Non Fire N/A N/A SPARE N/A 9 1 Z70MINI/DUAL MONITOR N/A

Non Fire N/A N/A SPARE N/A 10 1 Z70MINI/DUAL MONITOR N/A

Relay No No FIRE PUMP CONTROLLER TROUBLE No 11 1 Z20RELAY N/A

Relay No No FIRE PUMP RUN No 12 1 Z21RELAY N/A

Relay No No FIRE PUMP ENGINE TROUBLE No 13 1 Z22RELAY N/A

Relay No No PUMP ROOM AC FAIL AND TAMPERS No 14 1 Z23RELAY N/A

Monitor N/A N/A CEILING HEATS N/A 15 1 Z17ZONE MONITOR N/A

Pull Station N/A N/A FIRE PUMP ROOM N/A 16 1 Z9MANUAL STATION N/A mcamarote Typewritten Text mcamarote Typewritten Text mcamarote Typewritten Text Building 542 mcamarote Typewritten Text mcamarote Typewritten Text neal.j.moran Text Box SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

BLDG 542 FIRE ALARM & MASS NOTIFICATION SYSTEM (FA&MNS) REPAIR

Sheet 2 of 8

Device

Address/

Point

Type

Code Label

Walk Test

Participation

Control-By-Event

Switch

Inhibit

SilenceableCustom Label Extended Label

Flash

Scan Type

SLC

Loop/

Panel

Site ID: 0

Date: 5/27/2014

NFS2-640

Port ID: 0 Node Address: 0

Waterflow Delay

(Sec)

Track Superv N/A N/A FIRE PUMP ENGINE TROUBLE N/A 17 1 Z22MINI/DUAL MONITOR N/A

Monitor N/A N/A FIRE PUMP RUNNING N/A 18 1 Z21MINI/DUAL MONITOR N/A

Track Superv N/A N/A PUMP ROOM TROUBLE N/A 19 1 Z23MINI/DUAL MONITOR N/A

Track Superv N/A N/A FIRE PUMP C0NTROLLER TROUBLE N/A 20 1 Z20MINI/DUAL MONITOR N/A

Tamper N/A N/A PUMP ROOM MAIN VALVE N/A 21 1 Z23MONITOR N/A

Tamper N/A N/A PUMP ROOM BYPASS VALVES N/A 22 1 Z23MONITOR N/A

Tamper N/A N/A PUMP RM MAIN CONTROL VAVLE N/A 23 1 Z13MONITOR N/A

Waterflow N/A N/A PUMP ROOM MAIN FLOW SWITCH N/A 24 1 Z9MINI/DUAL MONITOR

Waterflow N/A N/A PUMP ROOMS SPRINKLER FLOW SWITCH N/A 25 1 Z9MINI/DUAL MONITOR

Tamper N/A N/A PUMP ROOM TEST HEADER N/A 26 1 Z23MINI/DUAL MONITOR N/A

Tamper N/A N/A PUMP ROOM SUPPLY N/A 27 1 Z23MINI/DUAL MONITOR N/A

Tamper N/A N/A PUMP ROOM SPRINKLER VAVLE N/A 28 1 Z23MONITOR N/A

Bell Circuits

Bell Circuit Yes No BUILDING BELL Yes - Fire 1 Z88,Z0N/A N/A

Horn Circuit Yes No FIRE PUMP ROOM Yes - Fire 2 Z88,Z0N/A N/A

Control Yes No PANEL CIRCUIT NO. 3 Yes - Fire 3 Z0N/A N/A

Control Yes No PANEL CIRCUIT NO. 4 Yes - Fire 4 Z0N/A N/A neal.j.moran Text Box SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

Sheet 3 of 8

SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

Sheet 4 of 8

Photo 1: Roof Deck – Inside Building Photo 2: Fire Alarm Control panel (FACP)

Photo 3: Fire Alarm Control panel (FACP) Photo 4: Riser No. 1.

Text Box SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

Sheet 5 of 8

Photo 5: Pump Room Photo 6: Pump Room Fire Alarm

Photo 7: Pump Room Main Piping Photo 8: Riser No. 2

Text Box SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

Sheet 6 of 8

Photo 9: Riser No. 3 Photo 10: Fire Alarm Pull Station (TYP.)

Photo 11: Waterflow Switch (TYP.) Photo 12: Waterflow Switch Info. (TYP.)

Text Box SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

Sheet 7 of 8

Photo 13: Tamper Switch (TYP.) Photo 14: Tamper Switch Nameplate (TYP.)

SOW Attachment 2 Fire Alarm Control Panel (FACP) Floor Plan Layout/Module Pts./Pictures

Sheet 8 of 8

SOW Attachment (2) Existing Conditions
FACP Floor Plan Layout_Rough
Building 542 Module Report
Fire Pump Controller Functions

Pictures12