This file contains a Statement of Work and related federal contract opportunity. The Statement of Work outlines requirements for expanding and renovating a residential recovery program center in Honolulu, Hawaii. The Department of Veterans Affairs is soliciting design services for this project through solicitation number 36C77624R0017. Responses are due by April 15, 2023 and the period of performance is expected to be from June 2023 through May 2024. The solicitation will result in a single-award indefinite delivery/indefinite quantity contract with a maximum value of $2.5 million. The opportunity is unrestricted and open to small businesses.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAPIHCS, Facilities Management and Engineering Services/ Building 110 CFA PRRP Addition Honolulu, HI
VCI / FARNSWORTH GROUP
6.1 PROGRAM FOR DESIGN – 28 JAN 2022
PROGRAM FOR DESIGN
PRRP PROGRAM 01272022 REVISION
HONOLULU VAMC PRRP PROGRAM
HONOLULU
Projected Year: 2020 Midpoint Year: 2021
VISN: 21 State: HI Station ID: 459 Station: Honolulu
Installation: VA Pacific Island Health Care System
Project Created: 07 Aug 2020 10:14AM ET by Linda Chan Space Plan Last Edited: 28 Jan 2022 10:41AM ET by Linda Chan
Contents List Created: 07 Aug 2020 02:31PM ET by Linda Chan Contents List Last Edited: 28 Jan 2022 10:41AM ET by Linda Chan
Report Generated: 28 Jan 2022 10:43AM
Project POC: Linda Chan fei.chan@va.gov 425 I Street, NW
Washington, DC 20001
Department: 1 - PRRP PROGRAM
Functional Area: 1 - PATIENT CARE UNIT CALCULATION
Qty Room Code Room Name Unit Area
Net Area
Const Phase
Const Type
1 CALC1 Number of Patient Care Units 0 0 1 0
FA Totals: Room Qty: 1 Net Area: 0 Gross Area: 0
Department: 1 - PRRP PROGRAM
Functional Area: 3 - PATIENT CARE UNIT: PATIENT AREA
Qty Room Code Room Name Unit Area
Net Area
Const Phase
Const Type
16 BRUN1 Bedroom, One-Bed 185 2,960 1 0
1 CMP01 Computer Room 120 120 1 0
1 JANC1 Housekeeping Aides Closet (HAC) 60 60 1 0
1 NULR1 Laundry Room 150 150 1 0
1 IPK01 Multipurpose Room/Lounge / Kitchenette 400 400 1 0
1 RAMR1 Quiet Room/Multipurpose/Consult Room/Family Visiting 180 180 1 0
1 NSTA1 Staff Station 120 120 1 0
1 WRTM1 Team Room 180 180 1 0
16 TSPG1 Toilet / Shower, Patient 60 960 1 0
1 TLTU1 TOILET, staff 60 60 1 0
FA Totals: Room Qty: 40 Net Area: 5,190 Gross Area: 8,045
Privacy Act - FOR OFFICIAL USE ONLY
Program For Design (28 Jan 2022 10:43AM)
PRRP PROGRAM 01272022 REVISION
HONOLULU VAMC PRRP PROGRAM
HONOLULU
Functional Area: 5 - STAFF AND ADMINISTRATIVE AREA
Qty Room Code Room Name Unit Area
Net Area
Const Phase
Const Type
1 SL001 Lounge, Staff 210 210 1 0
1 OFD03 Office, Nurse Manager 100 100 1 0
1 OFA09 Office, Program Director 100 100 1 0
1 TNPG1 Toilet, Staff 60 60 1 0
FA Totals: Room Qty: 4 Net Area: 470 Gross Area: 729
Privacy Act - FOR OFFICIAL USE ONLY
Program For Design (28 Jan 2022 10:43AM)
PRRP PROGRAM 01272022 REVISION
Functional Area: 6 - PATIENT SERVICES
Qty Room Code Room Name Unit Area
Net Area
Const Phase
Const Type
8 TRGM1 Exam /Consult Room 120 960 1 0
1 LAC01 Lactation Room 75 75 1 0
1 LAUN1 Laundry Room, Resident Admission 120 120 1 0
1 OTDL1 Multipurpose Room 400 400 1 0
1 RECP3 Reception, Information Desk 60 60 1 0
1 SRE01 Storage, Multipurpose 100 100 1 0
1 WRTM1 Team Room 240 240 1 0
1 TLTS2 Toilet/ Shower, Resident Admission 60 60 1 0
1 BX001 Vending Area 50 50 1 0
1 BGSV1 Vestibule/lobby 140 140 1 0
1 WTG03 Waiting, General 80 80 1 0
FA Totals: Room Qty: 18 Net Area: 2,285 Gross Area: 3,542
Privacy Act - FOR OFFICIAL USE ONLY
Program For Design (28 Jan 2022 10:43AM)
PRRP PROGRAM 01272022 REVISION
Functional Area: 8 - SUPPORT
Qty Room Code Room Name Unit Area
Net Area
Const Phase
Const Type
1 COMC1 Data and Telecommunications Room 170 170 1 0
1 SRS01 Storage, General 200 200 1 0
1 CSUC3 Utility Room, Clean 100 100 1 0
1 USCL1 Utility Room, Soiled 80 80 1 0
FA Totals: Room Qty: 4 Net Area: 550 Gross Area: 853
Dept Totals: Room Qty: 67 Net Area: 8,495 Gross Area: 13,167
Bldg Totals: Room Qty: 67 Net Area: 8,495 Sum of Dept Gross Area: Gross Area: 16,72213,167
Privacy Act - FOR OFFICIAL USE ONLY
Program For Design (28 Jan 2022 10:43AM)
PRRP PROGRAM 01272022 REVISION
Building Area Summary And Net to Gross Factor Breakdown
Current Building Factor applied to this Project: 1.27
Building GSF
Current 16,722
Privacy Act - FOR OFFICIAL USE ONLY
Program For Design (28 Jan 2022 10:43AM)
PRRP PROGRAM 01272022 REVISION
Report Parameters
Sorted By: Compressed to Dept position, FA position, Room Name
(END OF REPORT)
Privacy Act - FOR OFFICIAL USE ONLY
Program For Design (28 Jan 2022 10:43AM)
PRRP PROGRAM 01272022 REVISION
6.2 FACILITY CONDITION ASSESSMENT
FCA_ID Building No Function Title GSF System Subsystem Useful Lifespan Remaining Life Correction Cost Condition Description Project List Pending Risk
Level
Pending Useful
Lifespan
Pending
Remaining Life Pending Correction Cost
Pending
Condition Pending Description
VA Comments ATEI Response
107474 110 Center for Aging 43305 Plumbing Fire Sprinkler /
Pump 50 38 $ - B In very good condition. 50 35 B * Fire Protection system is in good condition.
107475 110 Center for Aging 43305 Plumbing Fixtures / Piping 50 38 $ - B Majority in very good condition. 50 35 B * Plumbing fixtures and piping, 1998, is in good condition.
107476 110 Center for Aging 43305 Mechanical Ventil (O.A. & Exh) 30 19 $ - B Deteriorating ductwork at OA source intake. 30 15 B * Ductwork is in good condition.
107477 110 Center for Aging 43305 Electrical Nurse Call/Int/TV 15 10 $ - A
[ Field Engineer Review Completed on 06/20/2019 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 06/20/2019 for Project Number 459-19-
CFAFCA created by VHAHONFURUKT.] Old analog
CATV system is in poor condition. Some rooms are experiencing inadequate signal on certain cable TV channels due to problems with interior wiring.
15 12 B
* Old analog CATV system has been repaired in B and C wings. System is working in good condition. Plenum rated cabling is not properly supported above accessible ceilings.
107478 110 Center for Aging 43305 Hazmat Asbestos * * $ - N/A
New bldg. built in 1997, standard VA construction specs used prohibiting use of asbestos in numerous specs.
* * N/A
* Bldg built 1997, standard VA construction specs used prohibiting use of asbestos in numerous specs. No known ACM present.
107479 110 Center for Aging 43305 Electrical Lightning Protect 20 * $ - N/A None. Perform risk assessment per NFPA 780.
5 20 * $281,098 D
* None. Provide lightning protection system per NFPA 780 for a 43,305 sf patient care structure.
107480 110 Center for Aging 43305 Transport Elevators 20 * $ - N/A none * * N/A
* None present.
107481 110 Center for Aging 43305 Mechanical Heating System 30 0 $ 266,174.13 F
Terminal vav units are old and not currently installed, reheats have failed and often not able to fully control units.
3 30 10 $319,236 D
* VAV terminal units were meeting cooling requirements. Reheat controls need to be investigated.
107482 110 Center for Aging 43305 Transport Material Handling * * $ - N/A none * * N/A
* None present.
107561 110 Center for Aging 43305 Plumbing Medical Gases 30 18 $ - B Recommend conducting a med gas study and following their recommendations.
30 15 B
* Med gas systems receive regular maintenance and are in good operating condition.
107562 110 Center for Aging 43305 Architectural Accessibility * * $ - A Fully accessible. * * A * Complies. Remains fully accessible
107563 110 Center for Aging 43305 Architectural Life Safety * * $ - A Fully sprinklered and alarmed * * A Fully sprinklered and alarmed
107564 110 Center for Aging 43305 Electrical Transformer 30 10 $ - C
ABB 500kVA, 11.5kVA:480/277V main pad mounted transformer "T-CFA" located outside is owned and maintained by DPW. Serves main distribution board inside building 110A.
30 5 C
* 500kVA ABB, 11.5kV-480Y277V, 3Ph pad mounted transformer serving the CFA and Generator Building in fair condition and is maintained by Tripler Army DPW.
107566 110 Center for Aging 43305 Structural Floor Systems 100 80 $ - B Concrete slab on grade with no apparent problems. 100 76 B Concrete slab on grade with no apparent problems.
107567 110 Center for Aging 43305 Structural Foundations 100 80 $ - B
Spread footings in generally good condition. Some minor cracking observed at the exposed concrete base at the exterior perimeter (approximately 4 feet o.c.) .
100 75 B
Spread footings in generally good condition. Some minor cracking observed at the exposed concrete base at the exterior perimeter
(approximately 4 feet o.c.) . * Item remains unchanged from previous assessment.
107568 110 Center for Aging 43305 Structural Vertical Members 100 80 $ - B Steel columns with no apparent problems. * * B Steel columns with no apparent problems.
107569 110 Center for Aging 43305 Architectural Signage /
Wayfinding 10 4 $ - C
Interior signs in average condition. Replace sign at C-
120.
10 1 C * Interior signs in average condition unless otherwise noted.
107570 110 Center for Aging 43305 Architectural Fixed Equipment 15 6 $ - C Most equipment is in average condition. 15 1 C Most equipment remain in average condition.
107571 110 Center for Aging 43305 Plumbing Hot Water Heater 25 16 $ - C 2(two) Lochinvar water heaters recently replaced, upgraded last year.
25 10 C * Water heaters, circa 2016, are in good operating condition.
107572 110 Center for Aging 43305 Mechanical Refrigeration Equip 20 0 $ 564,587.88 F
ACCU-6 12 tons, ACCU 5-1 15 tons, ACCU-5 A-1 15 tons, ACCU-3 15 tons, ACCU-1 15 tons, ACCU-2, 10 tons, ACCU-7 15 tons, ACCU-8 10 tons, ACCU-4 15 tons. Compressors are failing regularly, annual replacement typically in the summer months, 9 condensing units with 2 compressors each. ACCU-4 disconnect is unable to be utilized on maintenance shutdowns due to local piping. All ACCU's are directly exposed to landscaping irrigation which is greatly deteriorating the efficiency of their coils through rusting and calcification. ACCU 5-A1 site glass exhibits low refrigerant levels or failure and should be replaced if damaged or the unit charge should be checked to confirm operation. A central cooling system might be a better option to limit maintenance impact
5 20 2 $628,576 D
* ACCU-6 12 tons, ACCU 5-1 15 tons, ACCU-5 A-1 15 tons, ACCU-3 15 tons, ACCU-1 15 tons, ACCU-2, 10 tons, ACCU-7 15 tons, ACCU-8 10 tons, ACCU-4 15 tons. Condensing units are functioning but showing deterioration. Units use refrigerant is discontinued R-22, and are nearing the end of their useful life.
107573 110 Center for Aging 43305 Electrical Secondary Dist. 30 10 $ - C
Majority of electrical system installed in 1996 is in good condition. Siemens Distribution Panel 600A
MCB, 480/277V, 3Ph, 4W installed in 1996 is in good condition. Serves 400A panel NH1, 350A panel NH2, and 225A panel NH3. See building 110A for description of main distribution equipment.
30 5 B
* Majority of building Electrical System is original to Building in 1996 and in good condition. Room A102A: Siemens 600A MCB, 480/277V, 3Ph, 4W fed from generator building; serves other Siemens, GE and
Square D panels and gear.
107574 110 Center for Aging 43305 Architectural Windows 30 10 $ - C
Aluminum double glazed windows in average condition. Mix of fixed units & operable units (at beds).
30 6 C Aluminum double glazed windows in average condition. Mix of fixed units & operable units (at beds).
107575 110 Center for Aging 43305 Architectural Exterior Walls 100 80 $ - B Exterior walls in good condition 100 76 B Exterior walls remain in good condition
107576 110 Center for Aging 43305 Information
Technology
Inside Cable Plant
(ICP)
15 3 $ - C
The ICP consists primarily of plenum CAT 5, installed in 1999, with limited Cat 5e and CAT 6. It is generally in good condition and is supported by J hooks between spaces.
15 exceeds C
* The ICP consists primarily of plenum CAT 5, installed in 1999, with some Cat 5e and CAT 6 upgrades. It is in fair condition.
107577 110 Center for Aging 43305 Mechanical Room Air Dist./Term 30 19 $ - B Supply and Return registers are in good condition. 30 15 B Diffusers and grilles are in good condition.
107578 110 Center for Aging 43305 Electrical Emerg Elec Sys. 25 5 $ - C
Majority of electrical system installed in 1996 is in fair condition. Exit signs are LED-type. See building
110A for description of emergency generator and transfer switches.
25 exceeds C
* Emergency Systems distribution is in average condition, installed in
1996. Exit signs are LED type. Emergency Systems source is in Bldg.
110A. Refer to FCA ID #366671
107579 110 Center for Aging 43305 Electrical Fire Alarm 15 1 $ - C
System in fair condition; including: Addressable
Notifier AM2020 located in lobby with paging and
King Fisher radio transmitter. There are smoke detectors in hold open doors only, manual pull stations, speaker/strobes, duct smoke detectors, and tamper/flow switches.
15 exceeds C
* System installed in 1998 in fair condition; Addressable Notifier
AM2020 with voice evac. located in lobby with paging and King Fisher radio transmitter. Parts are not available. System is functioning properly.
107580 110 Center for Aging 43305 Electrical Elec/Tele Closets * * $ - C
There are separate air conditioned electrical and ventilated telecomm rooms. Generally, all electrical rooms are well ventilated.
* * B
* All Electrical and Telecom Rooms are served by Cooling only, HVAC
System with supply and exhaust in good condition.
107581 110 Center for Aging 43305 Mechanical Ducts & Water Dist. 30 19 $ 254,526.86 D
A majority of the ductwork and water distribution is in okay to good shape, but portions of the ductwork have failed due to humidity and water infiltration. Specifically witnessed at outdoor air intake ductwork on AHU-5, and observed on exterior exposed piping and ductwork. Once these sections are repaired/ replaced this item can be returned to a "B" rating.
30 15 C
* Ductwork and water distribution is in good condition. No water infiltration was visible at the time of inspection, but there were devices present to indicate where past leaks have occurred.
107583 110 Center for Aging 43305 Architectural Interior Finish/Door 10 4 $ - C Most interior finishes are in average condition. 10 exceeds C Most interior finishes remain in average condition.
107584 110 Center for Aging 43305 Architectural Roof 100 80 $ - B Barrel clay tile roof in good condition. 100 76 B Barrel clay tile roof remain in good condition.
107585 110 Center for Aging 43305 Mechanical Air Handling Equip 20 0 $ 972,755.50 F
AHU's 1-6 do have chilled water coils, operating refrigerant is R-22 and some units are only accessible from rooms. Unit casings largely in good condition, internal components are nearing the end of their useful life, and units have met the end of their useful life expectancy.
5 20 2 $1,104,556 D
* AHUs 1-6 are DX-Type, using discontinued refrigerant R-22. Most units are only accessible from inside patient rooms with significantly limited maintenance space. Unit casings largely in decent condition with internal components nearing the end of their useful life.
115157 110 Center for Aging 43305 Architectural Fixed Equipment 15 5 $ - C Pharmacy equipment is in average condition. 15 exceeds C-
* Fixed equipment is in serviceable condition though useful life exceeded. No active pharmacy in this bldg..
115158 110 Center for Aging 43305 Architectural Interior Finish/Door 10 exceeds $ 1,125,279.11 D
Most areas have vinyl composition floor tile that is blistering due to water infiltration from slab on grade. Recommend fluid applied vapor barrier to concrete surface below & replace tile and vinyl base.
2 10 exceeds $1,140,736 D
Most areas have vinyl composition floor tile that is blistering due to water infiltration from slab on grade. Recommend fluid applied vapor barrier to concrete surface below & replace tile and vinyl base. Approx.
40,000 s.f.
115160 110 Center for Aging 43305 Architectural Signage /
Wayfinding 10 10 $ - A Exterior building signage is new 2016. 10 5 B * Exterior building signage, 2016, is in good condition.
115161 110 Center for Aging 43305 Electrical Lighting & Power 25 exceeds $ 589,862.06 D
Approximately (122 - HPS, 45 - Metal Halide, and 75
- Compact Fluorescent) exterior walkway lights need to be replaced due to deterioration from rust.
Water also leaks to fixture thru cracks in each fixture location.
3 25 2 $666,139 D
* Approximately (122 - HPS, 45 - Metal Halide, and 75 - CFL) all exterior walkway lights in poor condition and need to be replaced. Several damaged, deteriorating, or missing. Provide for 60 20W LED, 36in tall, 6in dia. light bollards and 50 10W LED step lights.
115162 110 Center for Aging 43305 Mechanical Air Handling Equip 20 20 $ - A
VFDs have been installed and are new and in good condition. However, the location for access to them is difficult due to being accessed from within the patient area.
15 5 C * VFDs, circa 2010, are in good operating condition .
115163 110 Center for Aging 43305 Mechanical Ducts & Water Dist. 10 4 $ - B Duct cleaning under contract for services every 3-5 years.
10 8 B
Duct cleaning under contract for services every 3-5 years.
115164 110 Center for Aging 43305 Mechanical Ventil (O.A. & Exh) 30 20 $ - C
Duct coming down from the outside air intakes is deteriorating, intake hoods have been maintained and need to be replaced but water intake could be experienced due to proximity to the clay tile roofing. AHU-5 OA intake has caved and has leaked through it's ceiling tile causing short cycling and reducing the ability of the building to control discharge temperature at the unit. Previous replacement and current condition is indicative of a systemic problem that should be addressed prior to replacement or replacement within a similar period of time should be planned for.
30 29 B+
* Some exhaust fans and air intake hoods have been replaced, circa
2020, and are in very good condition. Maintenance access to these is difficult due to roof slope.
115165 110 Center for Aging 43305 Plumbing Fire Sprinkler /
Pump 40 33 $ - B
Fire Sprinkler drops recently replaced and in good condition. Update unit tagging on sprinkler riser.
40 25 B * Sprinkler drops, circa 2014, are in good condition.
115166 110 Center for Aging 43305 Plumbing Fixtures / Piping 50 0 $ 23,138.56 F
Provide 300 Lft 1" insulation to cover piping under the lavatories per handicap requirement. VAMC input suggests most plumbing systems are in good condition.
3 50 35 $25,539 D Piping under lavatories is not insulated per handicap requirements.
171298 110 Center for Aging 43305 Architectural Exterior Walls 100 1 $ 1,565.36 D Reset 2 drain blocks to slope out. Reseal slab to slab expansion joints at South side A wing & at dock.
3 100 76 $2,735 D
Reset 2 drain blocks to slope out. Reseal slab to slab expansion joints at South side A wing & at dock * approx. 100 l.f.
234806 110 Center for Aging 43305 Electrical Secondary Dist. 30 2 $ 17,862.17 D
Correct deficiencies as indicated in the March 2011
AES Design Group and April 2010 Leo A Daly reports. Replace and adjust equipment and devices that do not comply with the requirements as indicated by the Short Circuit and Coordination
Studies.
* * N/A
* DELETE THIS RECORD: Not an FCA item
265042 110 Center for Aging 43305 Information
Technology
Telecommunication s Rooms 20 5 $ - C
The telecommunications rooms are functional however each room has several deficiencies see entries below.
20 exceeds C
* The telecom rooms are functional in fair condition.
265043 110 Center for Aging 43305 Information
Technology
Telecommunication s Rooms 20 5 $ 13,589.59 D
The Telecommunications room A102 the following deficiencies exist: 1) It has a UPS unit and it is working however it does not appear to be monitored. Install an UPS with remote monitoring that is sized to support twenty minutes of continuous power in the event of a power outage and will allow for the smooth transfer between commercial and generator power. 2) There is no grounding from IT equipment to building ground;
install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 3) It has no or inadequate grounding infrastructure;
install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 4)
The wall and/or floor sleeves are full; install larger or additional sleeves to provide for future growth.
459-20-700 3 20 exceeds $15,962 D
* TR A102 should have the equipment racks grounded, Maintenance personnel will address that issue. The room size, lighting and ventilation is adequate to perform duties. Cable management is inadequate and should be upgraded. Provide one 10 foot section of cable tray and two 84 inch vertical cable racks.
265044 110 Center for Aging 43305 Information
Technology
Telecommunication s Rooms 20 5 $ 4,781.82 D
The Telecommunications room B139C the following deficiencies exist: 1) There is no grounding from IT equipment to building ground; install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 2) It has no or inadequate grounding infrastructure; install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 3)
The wall and/or floor sleeves are full; install larger or additional sleeves to provide for future growth.
459-20-700 3 20 exceeds $15,962 D
* The T/R B139C should have the equipment racks grounded, Maintenance personnel will address that issue. The room size, lighting and ventilation is adequate to perform duties. Cable management is inadequate and should be upgraded. Provide for one 10 foot section of cable tray and two 84 inch vertical cable racks.
265045 110 Center for Aging 43305 Information
Technology
Telecommunication s Rooms 20 5 $ 7,605.32 D
The Telecommunications room C114A the following deficiencies exist: 1) There are no convenience outlets; install convenience outlets that are on a separate circuit from circuits supplying power to IT equipment. 2) Verify that IT equipment is powered by a dedicated circuit; install a dedicated circuit to support the IT equipment in the room. 3) There is no grounding from IT equipment to building ground; install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 4) It has no or inadequate grounding infrastructure; install bonding straps on
IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground.
459-20-700 20 exceeds C
* The T/R C114A contains only Nurse Call and TV Systems support in fair condition. Provide convenience outlets and additional grounding on a maintenance level.
269325 110 Center for Aging 43305 Architectural Life Safety * * $ 3,510.05 D Replace concrete entry walk at South gazebo.
Tripping hazard 2 * * $3,964 D
Replace concrete entry walk at South gazebo. Tripping hazard. *
Approx. 50 s.f.
269326 110 Center for Aging 43305 Architectural Life Safety * * $ 3,788.66 D Replace irregular handrail outside room C-119 & C-
120, approx. 20 l.f.
3 * * $4,895 D Replace irregular handrail outside room C-119 & C-120, approx. 20 l.f.
365441 110 Center for Aging 43305 Architectural Accessibility * * $ - C Sinks appear to be at 36" in lieu of the standard 34" for wheelchair access.
* * B * Sinks appear to be compliant.
365442 110 Center for Aging 43305 Architectural Accessibility * $ - C
The exterior door near B135A is a right side approach door. Exiting to the courtyard would be easier with an automatic door operator.
* * C The exterior door near B135A is a right side approach door. Exiting to the courtyard would be easier with an automatic door operator.
365443 110 Center for Aging 43305 Architectural Fixed Equipment 15 3 $ - C
Nurses station is in average condition. Laminate corners are chipped, corner guards should be provided.
* * N/A
* DELETE THIS RECORD: moved to proper subsystem Interior
Finish/Door
365444 110 Center for Aging 43305 Architectural Interior Finish/Door 10 8 $ - B Main entry door was replaced in 2014. 10 3 B Main entry door replaced in 2014 remain in good condition
365445 110 Center for Aging 43305 Architectural Interior Finish/Door 10 exceeds $ 10,815.42 D
Ceramic tile showers do not have a flexible joint installed. Recommend cleaning corner joints of hard grout and installing a flexible silicone joint.
2 10 exceeds $11,248 D
Ceramic tile showers do not have a flexible joint installed. Recommend cleaning corner joints of hard grout and installing a flexible silicone joint. * Approx. 700 l.f.
365446 110 Center for Aging 43305 Architectural Interior Finish/Door 10 exceeds $ - C Corridor wall finishes are dated but in acceptable condition.
10 exceeds C Corridor wall finishes remain dated but in acceptable condition.
365447 110 Center for Aging 43305 Architectural Interior Finish/Door 10 exceeds $ 2,198.28 D
Wall covering in multipurpose room is stained and peeling. Recommend removal and refinishing walls with paint.
1 10 exceeds $28,731 D
Wall covering in multipurpose room is stained and peeling.
Recommend removal and refinishing walls with paint. * Approx. 2000 s.f.
365448 110 Center for Aging 43305 Architectural Interior Finish/Door 10 exceeds $ 69,417.02 D Interior door frames are in need of new paint. 1 10 exceeds $127,694 D
* Most Interior door frames are in need of new paint. Approx. 400 doors at 3ftx7ft
365449 110 Center for Aging 43305 Architectural Interior Finish/Door 10 3 $ 810.52 D 50% of blanket insulation is failing within mechanical room off of loading dock.
10 1 B * Blanket insulation appears to be intact in Mechanical room.
365450 110 Center for Aging 43305 Architectural Interior Finish/Door 10 n/a $ 32,143.63 D
Building expansion joints were not provided at the separate wings causing building finishes to fail.
Recommend installing joints to allow movement.
3 10 exceeds $44,693 D
Building expansion joints were not provided at the separate wings causing building finishes to fail. Recommend installing joints to allow movement. * Approx 200 l.f.
365451 110 Center for Aging 43305 Architectural Life Safety * * $ 47,195.08 D
[ Field Engineer Review Completed on 01/06/2020 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 01/06/2020 for Project Number 459-20-
CFA Lump created by VHAHONFURUKT.] [ Field
Engineer Review Completed on 09/17/2019 by
VHAHONFURUKT.] [ Auto Generated Project
Pending on 09/17/2019 for Project Number 459-19-
CFALump created by VHAHONFURUKT.] Slip coefficient is not adequate on the bathroom ceramic tile. Maintenance is adding abrasive strips to prevent falls. Consider replacement.
3 * * $137,804 D
Slip coefficient is not adequate on the bathroom ceramic tile.
Maintenance is adding abrasive strips to prevent falls. Consider replacement. * Approx. 5000 s.f.
365452 110 Center for Aging 43305 Architectural Life Safety * * $ - A
[ Field Engineer Review Completed on 01/06/2020 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 01/06/2020 for Project Number 459-20-
CFA Lump created by VHAHONFURUKT.] [ Field
Engineer Review Completed on 09/17/2019 by
VHAHONFURUKT.] [ Auto Generated Project
Pending on 09/17/2019 for Project Number 459-19-
CFALump created by VHAHONFURUKT.] All fire rated doors have lost their fire rating from hardware revisions. Recommend replacement with the proper hardware kit.
4 * * $159,618 D
All fire rated doors have lost their fire rating from hardware revisions.
Recommend replacement with the proper hardware kit. * Approx. 100 doors
365453 110 Center for Aging 43305 Architectural Life Safety * * $ - A
[ Field Engineer Review Completed on 01/06/2020 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 01/06/2020 for Project Number 459-20-
CFA Lump created by VHAHONFURUKT.] There was an incomplete remediation project in room B139.
Complete remediation and clean space for patient use.
* * N/A
* DELETE THIS RECORD: Room has been converted into a Storage space.
365454 110 Center for Aging 43305 Architectural Windows 30 5 $ 32,316.94 D Reseal windows on the exterior. 30 6 C * Windows exterior sealants appears to be in average condition.
365455 110 Center for Aging 43305 Electrical Lighting & Power 25 10 $ - C Interior lighting (sconces and recessed down lights) are compact fluorescent and are in fair condition.
25 exceeds C
* Interior Lighting T8 recessed troffers, CFL downlights and CFL sconces installed in 1998 in average condition.
365456 110 Center for Aging 43305 Electrical Lighting & Power 25 20 $ - B Porte Cochere retrofitted with LED lamps (approx.
12 units).
25 17 B
* Porte Corchere LED lighting in good condition
365457 110 Center for Aging 43305 Electrical Lighting & Power 25 exceeds $ 46,277.13 D Approximately 20 recessed in-grade lights are cracked and rusted.
* * N/A
* DELETE THIS RECORD: combined with Rec 115161
365458 110 Center for Aging 43305 Electrical Nurse Call/Int/TV 15 15 $ - A
[ Field Engineer Review Completed on 06/20/2019 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 06/20/2019 for Project Number 459-19-
CFAFCA created by VHAHONFURUKT.] Hill-Rom nurse call system is obsolete and several system failures have occurred.
15 12 B
* System was updated in 2020, devices were replaced in B and C wing.
Hill-Rom System is in good condition
365459 110 Center for Aging 43305 Electrical Nurse Call/Int/TV 15 15 $ - A
[ Field Engineer Review Completed on 06/20/2019 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 06/20/2019 for Project Number 459-19-
CFAFCA created by VHAHONFURUKT.]
WanderGuard system is obsolete.
15 12 B
* System was updated in 2019, devices were replaced in B and C wing.
System is in good condition
365460 110 Center for Aging 43305 Electrical Secondary Dist. 30 29 $ - A 17 pole-mounted LED solar-powered lights were installed in 2015.
30 24 B
* Solar powered LED Parking lot lights installed in 2015 are in good condition.
365461 110 Center for Aging 43305 Electrical Secondary Dist. 30 29 $ - A
Three (3) duplex electric vehicle charging stations were installed in 2015 in the adjacent to building
110A.
30 24 B+
* Three dual output Electric Vehicle Charging Stations installed in 2015 outside Bldg. 110A are in very good condition.
365462 110 Center for Aging 43305 Electrical Secondary Dist. 30 n/a $ - N/A 77kW solar photovoltaic system is being installed in late 2016/early 2017.
* * N/A
* DELETE THIS RECORD: moved to proper system/subsystem.
365463 110 Center for Aging 43305 Electrical Secondary Dist. 30 10 $ 27,303.16 D
Room B122 - 112.5kVA dry-type transformer is warm and loud. Suggest replacement and analysis of connected load to determine if increase in transformer capacity is required.
30 29 B+
* Transformer was replaced in 2020 and is in very good condition
365464 110 Center for Aging 43305 Information
Technology
Telecommunication s Rooms 20 5 $ 2,314.26 D
The Telecommunications room B103A contains the
Hill-Rom Nurse Call headend and the music headend. The following deficiencies exist: 1) There is no grounding from IT equipment to building ground; install bonding straps on IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 2) It has no or inadequate grounding infrastructure; install bonding straps on
IT racks, telephone cabling housings and cable trays such that they are grounded appropriately to the building ground. 3) Room does not have adequate space per VA OIT requirements.
459-20-700 20 exceeds C
* The T/R B103A contains the Hill-Rom Nurse Call headend and the music headend. All equipment is in fair condition. The room is limited for size.
365465 110 Center for Aging 43305 Mechanical Air Handling Equip 20 0 $ 972,755.50 F
Units in the CFA are in difficult to access locations due to being above frequently used room locations.
For this reason they are difficult to maintain, and when the units fail or the drain pans overflow the staff cannot shut down the unit or stop leakage until they come in through the patient space which isn't sanitary or safe.
* * N/A
* DELETE THIS RECORD: Unnecessary record. Not an FCA item.
365466 110 Center for Aging 43305 Mechanical Ducts & Water Dist. 30 1 $ 107,980.85 D Rebalancing hasn't occurred following construction. 3 30 3 $138,245 D Rebalancing hasn't occurred following construction.
365467 110 Center for Aging 43305 Mechanical Ventil (O.A. & Exh) 30 exceeds $ 31,994.33 D
Outside air intakes and associated ductwork have experienced reduced life due to the marine environment. Recommend repair, replacement and in some cases increasing distance from surrounding surfaces to intakes.
30 25 B
* Some exhaust fans and air intake hoods have been replaced, and are in good condition. Maintenance access to these is difficult due to roof slope.
365468 110 Center for Aging 43305 Plumbing Fixtures / Piping 50 exceeds $ - A
[ Field Engineer Review Completed on 09/17/2019 by VHAHONFURUKT.] [ Auto Generated Project
Pending on 09/17/2019 for Project Number 459-19-
CFALump created by VHAHONFURUKT.] Hot water currently around 170 degrees to combat legionella bacteria - but should be closer to 120 for patient safety. Need to address Legionella bacteria, so that temperature can be lowered back to a safe range.
50 35 B
* Temperature sensors showed the hot water to be operating closer to the appropriate temperatures.
365469 110 Center for Aging 43305 Structural Building Frame
Seismic
* * $ - B
The structure was commissioned in 1997. The structure must have been designed for seismic forces per VA Seismic Design Requirements (H-18-
8). Accordingly, the structure should resist seismic forces dictated by present standards.
100 76 B
The structure was commissioned in 1997. The structure was designed for seismic forces per VA Seismic Design Requirements *(H-08-8) with
'86 revisions. Accordingly, the structure should resist seismic forces dictated by present standards.
365470 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 66,801.49 F Life Safety Systems are non-compliant. 5 * * $66,242 F Life Safety Systems are non-compliant. * Need seismic bracing. Item remains deficient from previous assessment
365471 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 46,277.13 F Hazardous Materials are non-compliant. Shut off valves need to installed.
5 * * $52,994 F
Hazardous Materials are non-compliant. * Shut off valves need to be installed. Need seismic bracing. Item remains deficient from previous assessment
365472 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 70,187.55 F Partitions are non-compliant. 5 * * $79,491 F Partitions are non-compliant. * Need seismic bracing. Item remains deficient from previous assessment
365473 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 31,206.47 F Ceilings are non-compliant. 5 * * $33,121 F Ceilings are non-compliant. * Need seismic bracing. Item remains deficient from previous assessment
365474 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 31,206.47 F Ceilings are non-compliant. 5 * * $33,121 F Ceilings are non-compliant. * Need seismic bracing Item remains.
deficient from previous assessment
365475 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ - B Parapets, Cornices, Appendages are compliant. * * B Parapets, Cornices, Appendages are compliant.
365476 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ - N/A Stairs are non-applicable. * * N/A
Stairs are non-applicable.
365477 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 106,882.38 F Contents and Furnishings are non-compliant. 5 * * $99,364 F Contents and Furnishings are non-compliant. * Need seismic bracing
Item remains. Deficient from previous assessment
365478 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 167,005.05 F Mechanical and Electrical Equipment are non-compliant.
5 * * $165,606 F
Mechanical and Electrical Equipment are non-compliant. * Need seismic bracing Item remains. deficient from previous assessment
365479 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 233,806.54 F Piping is non-compliant. 5 * * $264,970 F Piping is non-compliant. * Need seismic bracing Item remains. deficient from previous assessment
365480 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 133,602.97 F Ducts are non-compliant. 5 * * $158,982 F Ducts are non-compliant. * Need seismic bracing Item remains.
deficient from previous assessment
365481 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* $ - N/A Elevators are non-applicable. * * N/A
Elevators are non-applicable.
365482 110 Center for Aging 43305 Structural
Non Structural
Components &
Equipments-Seismic
* * $ 61,819.70 F Light Fixtures are non-compliant 5 * * $66,242 F Light Fixtures are non-compliant. * Need seismic bracing Item remains.
deficient from previous assessment
365638 110 Center for Aging 43305 Structural Building Frame-
Wind
* * $ - B Steel frame - no apparent problems. 100 76 B Steel frame - no apparent problems.
365639 110 Center for Aging 43305 Structural Floor Systems 100 80 $ - B Metal roof deck on steel roof trusses with no apparent issues.
100 76 B Metal roof deck on steel roof trusses with no apparent issues.
365640 110 Center for Aging 43305 Structural Foundations 100 30 $ 463,828.41 D
On the ocean side of the building, the foundation at the corner is settling and bowing out. Recommend investigation to find cause of problem & remediation.
5 100 25 $25,220 D
On the ocean side of the building, the foundation at the corner is settling and bowing out. Recommend investigation to find cause of problem & remediation. *Item remains deficient from previous assessment
365641 110 Center for Aging 43305 Structural Floor Systems 100 15 $ 66,801.49 D
The exterior wood framed gazebo is showing signs of rusting at the steel connections. Recommend attention to prevent further damage.
5 100 10 $44,693 D
The exterior wood framed gazebo is showing signs of rusting at the steel connections. *Recommend repaint with rust resistant coating to prevent further damage. Item remains deficient from previous assessment and as deteriorated further. Approx. 20sf for connections only or 3-12ftx12ft structures to be painted to maintain architectural consistency
366664 110A Center for Aging
Generator 440 Architectural Exterior Walls 100 80 $ - C Exterior walls are in average condition. 100 76 C Exterior walls remain in average condition.
366665 110A Center for Aging
Generator 440 Architectural Exterior Walls 100 2 $ 2,735.51 D
Replace caulk at base of exterior wall to sidewalk / stoop.
2 100 exceeds $2,820 D
Replace caulk at base of exterior wall to sidewalk / stoop. * Approx. 50 l.f.
366666 110A Center for Aging
Generator 440 Architectural Roof 20 10 $ - C
Clay tile roof is in good condition, the roof vent added at the ridge allows water infiltration during driving rains.
20 6 C Clay tile roof is in good condition, the roof vent added at the ridge allows water infiltration during driving rains.
366667 110A Center for Aging
Generator 440 Architectural Interior Finish/Door 10 exceeds $ 21,182.91 F
The doors are rusty and corroded. There are holes in the doors.
3 10 exceeds $24,879 D
The doors are rusty and corroded. There are holes in the doors. *
Replace 5ftx7ft double doors
366668 110A Center for Aging
Generator 440 Architectural Interior Finish/Door 10 10 $ - C Floor slab is cracked but sufficient for use. 10 exceeds C * Floor slab has very minor cracks and in average condition.
366669 110A Center for Aging
Generator 440 Architectural Life Safety * * $ - B Exits are sufficient for a maintenance space. * * B Exits are sufficient for a maintenance space.
366670 110A Center for Aging
Generator 440 Electrical Elec/Tele Closets * * $ - N/A
None.
* * N/A
* None present or required.
366671 110A Center for Aging
Generator 440 Electrical Emerg Elec Sys. 25 5 $ 61,703.72 D
Indoor Caterpillar 200kW/250kVA, 480/277V, 3Ph, 4W diesel engine generator. Generator overheats and goes into shutdown when loaded to greater than 85-90%. Issues with generator control cabinet gauges not operating properly.
25 2 C-
* Indoor Caterpillar 200kW/250kVA, 480/277V, 3Ph, 4W diesel engine generator with 50 gallon day tank, fed from exterior mounted 1000 gallon double walled tank. Generator is in workable condition due to poor maintenance.
366672 110A Center for Aging
Generator 440 Electrical Emerg Elec Sys. 25 5 $ - C
Interior 50G day tank for generator system connected to exterior above grade 1000G double-walled fuel tank.
* * N/A
* DELETE THIS RECORD: combined with Rec 366671
366673 110A Center for Aging
Generator 440 Electrical Emerg Elec Sys. 25 5 $ 26,840.57 D
Caterpillar 100A, 3-pole Life Safety transfer switch
(ATS-2) and 175A, 3-pole Critical transfer switch
(ATS-1) are in fair-to poor condition and are nearing the end of their useful life. Project is currently in design to replace the switches.
25 2 C
* ASCO 100A, 480V, 4-pole ATS-1 and 175A, 480V, 4-pole ATS-2 with bypass isolation are in fair condition and nearing end of useful life.
Controls parts are no longer available.
366674 110A Center for Aging
Generator 440 Electrical Fire Alarm 15 3 $ - C System is in fair condition and is served by the fire alarm system within building 110.
15 exceeds C
* Fire alarm devices are in fair condition, served from Building 110 Fire
Alarm System.
366675 110A Center for Aging
Generator 440 Electrical Lighting & Power 25 10 $ - C T8 fluorescent strip lights, LED exit signs, and battery light (bug-eyes) are in fair condition.
25 2 C
* Fluorescent T8 industrial lights, emergency battery unit equipment, and LED Exits are in fair condition.
366676 110A Center for Aging
Generator 440 Electrical Lightning Protect 20 * $ - N/A
None. Perform risk assessment per NFPA 780.
5 20 * $5,321 D
*There is currently no lightning protection system in place for this building. Provide a lightning protection system for this 440sf building.
366677 110A Center for Aging
Generator 440 Electrical Nurse Call/Int/TV 15 * $ - N/A
None.
15 * N/A
* None present or required
366678 110A Center for Aging
Generator 440 Electrical Secondary Dist. 30 10 $ - C
Siemens 800A, 480/277V, 3Ph, 4W main switchboard MSB installed in 1996 is in fair condition; however space is not mechanically conditioned and slight signs of corrosion are showing on gear. Suggest conditioning space to remove humidity.
30 5 C
* 800A, 480Y277V, 3Ph, 4W, Siemens Switchboard MSB installed in
1996 is in fair condition. Gear serves Bldgs. 110 and 110A for normal and emergency service. Electrical Equipment Room has no cooling or humidity control.
366679 110A Center for Aging
Generator 440 Electrical Secondary Dist. 30 28 $ - A Square D PowerLogic metering system installed in
2014 is in good condition.
30 23 B+
* Square D PowerLogic metering equipment, 2014, is in very good condition
366680 110A Center for Aging
Generator 440 Electrical Transformer 30 10 $ - C
ABB 500kVA, 11.5kVA:480/277V main pad mounted transformer T-CFA located outside is owned and maintained by DPW. Serves main distribution board inside building 110A.
30 5 B
* 500kVA ABB 11.5kV-480Y277V, 3Ph Pad Mounted transformer adjacent to the building is in good condition and is owned and maintained by DPW. Transformer serves 800A MSB.
366681 110A Center for Aging
Generator 440 Structural Vertical Members 100 80 $ - B Cmu bearing walls in good condition. 100 76 B * CMU bearing walls in good condition.
366682 110A Center for Aging
Generator 440 Structural Floor Systems 100 80 $ - B
Exposed metal roof deck on miscellaneous structural steel roof trusses in good condition.
100 76 B
Exposed metal roof deck on miscellaneous structural steel roof trusses in good condition.
366683 110A Center for Aging
Generator 440 Structural Floor Systems 100 80 $ - B
Concrete slab on grade in average condition. Minor cracking observed & paint needed.
100 76 B
Concrete slab on grade in average condition. Minor cracking observed
& paint needed.
366684 110A Center for Aging
Generator 440 Structural
Building Frame-
Wind
* * $ - B CMU shear walls in good condition. 100 76 B CMU shear walls in good condition.
366737 110A Center for Aging
Generator 440 Structural
Building Frame
Seismic
* * $ - B CMU shear walls in good condition. 100 76 B CMU shear walls in good condition.
366738 110A Center for Aging
Generator 440 Plumbing Fixtures / Piping 50 38 $ 3,856.65 D
Anti siphon valve on suction side of generator is present, but not on discharge side of fuel tank.
4 50 35 $5,321 D
Anti siphon valve on suction side of generator is present, but not on discharge side of fuel tank.
014NEW 110 Center for Aging 43305 Architectural Accessibility 1 * * $27,561 D B-wing: Staff women's lockers -29 small lockers are non-compliant.
Staff men's lockers - 18 small lockers are non-compliant.
015NEW 110 Center for Aging 43305 Architectural Accessibility 1 * * $19,154 D Room C-121 and adjacent room - 10 medium lockers in total are non compliant. Kitchen area- 8 medium lockers are non compliant.
016NEW 110 Center for Aging 43305 Architectural Accessibility 1 * * $31,924 D
* Police Check-In desk /counter is too high, modify One counter to comply.
017NEW 110 Center for Aging 43305 Architectural Assessibility 1 * * $31,924 D Missing pipe insulation under sinks throughout facility , provide approx. 100 pipe insulations.
018NEW 110 Center for Aging 43305 Architectural Interior Finish Door 10 exceeds C Nurses station is in average condition. Laminate corners are chipped, corner guards should be provided.
019NEW 110 Center for Aging 43305 Energy Renwable Energy 30 26 A
* SMA 78kW solar photovoltaic System installed at parking canopy in
2017 is in excellent condition.
020NEW 110 Center for Aging 43305 Architectural Signage/Wayfinding 1 10 exceeds $3,192 D Kitchen sign is broken, repair/replace one sign
6.3 CONCEPTUAL PRRP EXPANSION FLOOR PLANS
54'-0"
UP
OCCUPANCY LEGEND
CIRCULATION
PRRP - PATIENT CARE
PRRP - PATIENT SERVICES
PRRP - STAFF AND ADMIN
PRRP - SUPPORT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONCEPTUAL
DEVELOPMENT
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10 engineering discipline <EDIT TEXT>:
# 110
VISN 21 - CFA Expansion
A u to d e s k D o c s /V
IS
N
C
F A
E x p a n s io n /A
V
IS
N
-C
F A
E x p a n s io n
.0
R V
T
.r v t
/1
/2
:3
:4
P
M
A1.2a
OPTION 1 - OVERALL 2ND LEVEL
SPACE PROGRAM
SCALE: 1/16" = 1'-0"
OPTION 1 - OVERALL SPACE PROGRAM - 12,000 GSF TOTAL NEW PROGRAM SPACE
Revisions: Date:
0 8 16 32
NORTH
PLAN
VARIANCES IN PROGRAMMED SQUARE FOOTAGE
05/20/2022 JMS CMW
0211758.01
Overall Option 1 feedback (PRRP, CLC, Rehab user group):
Least favorable, and not likely to pursue. Option 1 was not further refined as part of this study. Included for record only.
P L A N T
IN
G
MAIN ENTRY
DN.
P L A N T
IN
G
UP
BB
F
BBF
BBF
BBF
BBFBBF
BBF
BBF
BBF
BB
F
BB
F
BB
F
BB
F
BBF
BB
F
BB
F
BBF
BBFBBF
BBFBBF
BBF
BB
F
BBF
BBF
BB
F
69 SF
OXYGEN
STOR.
136 SF
VENDING
ROOM
143 SF
STORAGE
1311 SF
DINING /
REC.
ROOM
729 SF
CORRIDOR
685 SF
TRAY
MAKE-UP
73 SF
NON-
FOOD
STOR.
120 SF
OFFICE
41 SF
W.
RR
41 SF
M.
RR120 SF
OFFICE
86 SF
COOLER
79 SF
COOLER
40 SF
HAC.
33 SF
TRASH
37 SF
COM.
70 SF
STORAGE
196 SF
ELEC.
132 SF
MECH.
48 SF
TELE.
146 SF
DIET
37 SF
RR
190 SF
CORRIDOR
63 SF
ELEVATOR
2132 SF
SECY.
120 SF
OFFICE
121 SF
OFFICE
95 SF
RR
119 SF
STORAGE119 SF
SHOWER
49 SF
STAFF
RR
41 SF
HAC.
302 SF
CLASSROOM
CONFERENCE
572 SF
OFFICE
119 SF
HBPC
COORD.
101 SF
OFFICE
101 SF
OFFICE
203 SF
MEDITA.
101 SF
CHAPLAIN
814 SF
CORRIDOR
152 SF
RMS
WAITING
AREA
149 SF
OFFICE
120 SF
OFFICE
249 SF
OFFICE
119 SF
OFFICE117 SF
BATH
180 SF
ACTIVITIES
STORAGE
257 SF
KITCHEN
111 SF
STORAGE
89 SF
REHAB.
1034 SF
OCCUPATIONAL
THERAPY
99 SF
TREATMENT
RM
99 SF
REHAB.
OFFICE
114 SF
OFFICE
101 SF
THERAPY
OFFICE
283 SF
SATELITE
PHARMACY
96 SF
MECH.
86 SF
MECH.
188 SF
MECH.
167 SF
STAIRS
OCCUPANCY LEGEND
CIRCULATION
CLC - PATIENT CARE
CLC - PATIENT SERVICES
CLC - STAFF AND ADMIN
CLC - SUPPORT
OTHER
PRRP - SUPPORT
REHABILITATION - PATIENT SERVICES
REHABILITATION - STAFF AND ADMIN
SUPPORT
37 SF
ELEV.
EQUIP.
RM
FIRE WALL
FIRE WALL
NEW
CIRCULATION,
SUPPORT
SPACE,
(3) EXISTING
OFFICES
REMOVED
257 SF
KITCHEN
1140 SF
MULTIPURPOSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONCEPTUAL
DEVELOPMENT
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10 engineering discipline <EDIT TEXT>:
# 110
VISN 21 - CFA Expansion
A u to d e s k D o c s /V
IS
N
C
F A
E x p a n s io n /A
V
IS
N
-C
F A
E x p a n s io n
.0
R V
T
.r v t
/1
/2
:3
:4
P
M
A1.2b
OPTION 1 - MAIN LEVEL SPACE
PROGRAM
SCALE: 1/8" = 1'-0"
OPTION 1 - MAIN LEVEL SPACE PROGRAM - RENOVATION OF EXISTING = 15,910 GSF
Revisions: Date: 05/20/2022
0 4 8 16
NORTH
PLAN
JMS CMW
0211758.01
Overall Option 1 feedback (PRRP, CLC, Rehab user group):
92 SF
LACTATION
RM
120 SF
STAFF
STATION
170 SF
DATA /
TELECOM.
RM
170 SF
ELECTRICAL
RM
210 SF
STAFF
LOUNGE
433 SF
MULTIPUR.
RM/
LOUNGE/
KITCHENETTE
400 SF
MULTIPURPOSE
ROOM
139 SF
LAUNDRY
ROOM
120 SF
EXAM/
CONSULT
120 SF
EXAM/
CONSULT
120 SF
EXAM/
CONSULT
120 SF
EXAM/
CONSULT
98 SF
STORAGE,
MULTIPURPOSE
120 SF
COMPUTER
ROOM
95 SF
UTILITY
ROOM,
CLEAN
190 SF
TEAM
ROOM
237 SF
LOBBY
60 SF
RECEPTION
90 SF
WAITING,
GENERAL
135 SF
TOILET/SH.,
RESIDENT
ADMISSION
120 SF
LAUNDRY
ROOM,
RESIDENT
ADMISSION
80 SF
UTILITY
ROOM,
SOILED
64 SF
HAC
120 SF
EXAM/
CONSULT
80 SF
TOILET,
STAFF
180 SF
QUIET/
MULTIPURPOSE/
CONSULT/
VISITING 120 SF
EXAM/
CONSULT
120 SF
EXAM/
CONSULT
240 SF
TEAM
ROOM
50 SF
VENDING
200 SF
STORAGE,
GENERAL
120 SF
OFFICE,
PROGRAM
DIRECTOR
138 SF
OFFICE,
NURSE
MANAGER
PATIENT CARE UNIT: PATIENT AREA
STAFF AND ADMIN AREA
SUPPORT
PRRP PROGRAM
PRRP PROGRAM
PRRP PROGRAM
190 SF
1 BDRM
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
187 SF
1 BDRM
187 SF
1 BDRM
60 SF
STAFF
RR
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
187 SF
1 BDRM
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
59 SF
TOILET/
SHWR
1886 SF
CORRIDOR
170 SF
CORRIDOR
187 SF
1 BDRM
168 SF
STAIRS
OCCUPANCY LEGEND
CIRCULATION
PRRP - PATIENT CARE
PRRP - PATIENT SERVICES
PRRP - STAFF AND ADMIN
PRRP - SUPPORT
69 SF
ELEVATOR
DN
8'-0"
120 SF
EXAM/
CONSULT
6'-0"
8'-0"
170 SF
MECHANICAL
RM
652 SF
CORRIDOR
187 SF
1 BDRM
59 SF
TOILET/ SHWR
59 SF
TOILET/ SHWR
12 SF
ELEC.
CLST.
PATIENT SERVICES
PRRP PROGRAM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONCEPTUAL
DEVELOPMENT
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10 engineering discipline…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .