SOW 662-21-105 Replace Research HVAC Systems v03-21.pdf
PDF 185 KB Posted
- Attached to
- Z1DA--Replace Research HVAC Systems | 662-21-105 Federal contract opportunity
- Solicitation number
- 36C26121R0082
About this file
This statement of work outlines the replacement of a chiller system and repair of two air handling units at the San Francisco Veterans Affairs Medical Center. The scope of work requires a contractor to provide all materials, labor, equipment, and services to directly replace three modular chillers and repair the discharge isolation dampers on two air handling units. Replacement chillers must be modular units or approved equals sized at 20 tons each. Damper repairs include replacement or refurbishment of components and resolution of existing interference issues. The work must be performed outside regular hours to minimize disruption and include provision of temporary facilities.
The related federal contract opportunity is a pre-solicitation announcement for a request for proposal with an estimated value between $100,000 and $250,000 to fulfill the scope of work outlined. The solicitation will be a total service-disabled veteran owned small business set-aside issued by the Department of Veterans Affairs Network Contracting Office 21 for the San Francisco Veterans Affairs Health Care System campus. The NAICS code is 238220 for plumbing, heating, and air conditioning contractors and responses are due on or around July 25, 2021.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ATTACHMENT B - Criteria 2-Contractor Certification Safety and Environmental.docx | DOCX document | |
| SOW Attachment 2 - B41 Mechanical Drawings.pdf | ||
| SOW Attachment 1 - Task Locations and Existing Equipment Photos.pdf | ||
| ATTACHMENT A - Criteria 1-Experience.xlsx | XLSX spreadsheet | |
| 2018 Contractor Preconstruction Safety Handbook.pdf | ||
| SOW Attachment 3 - B41 AHU-1 and AHU-2 MFG Dwgs.pdf | ||
| 36C26121R0082.docx | DOCX document | |
| Wage Decision CA20210018_7-23-2021.pdf | ||
| 662-21-105 Specifications-Combined.pdf | ||
| ATTACHMENT C - Supplemental Price Breakdown.xlsx | XLSX spreadsheet | |
| SF CAMPUS MAP 11.07.19 - B41 Entrance.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work for
Replace Research HVAC Systems
662-21-105
March 2, 2021
Background
1) The San Francisco Veterans Affairs (VA) Medical Center (SFVAMC) requires replacement of a chiller system and repair services for two air handling units (AHU) serving Building 41, located at 4150
Clement St, San Francisco CA 94121.
2) The chiller system, located on the roof of Building 41, consist of three (3) Clima-Cool 20-ton packaged air cooled modular chillers. The chiller system will require complete replacement due to issues resulting from recent heat exchanger failures.
3) Two (2) air handling units located within the penthouse of Building 41 provide the building spaces with 100% outside air. Currently, the supply air dampers on each AHU are not able to fully shut. This issue is the result of physical interference within the dampers assemblies and is attributed to the damper assemblies being poorly fitted into the AHUs. To correct this issue and allow for proper operation of the dampers each AHU requires refurbishment or replacement of the existing damper assemblies, and resolution of the poor fit condition.
Scope
The contractor shall provide services, including material, labor, and equipment, for the following scope, in accordance with all applicable codes, specifications, and directives:
1) Replacement of the Building 41 Chiller (Modules #1, #2, and #3), to include:
a) Direct replacement modular chiller units or approved equals.
i) Units shall be supplied with manufacturer's condenser coil protection, or an approved equivalent coil protection system (e.g. – Heresite P-413, Modine Insitu, etc).
ii) If deviating from direct replacement units, contractor must demonstrate all schedule parameters are met and perform any design work needed to address necessary structural, utilities connections, or roof work.
b) Complete installation, Building Automation System (BAS) control system integration, startup, and testing of the new system.
c) Removal and disposal of existing units.
2) Repair of the discharge isolation dampers on Building 41 AHU #1 and AHU #2. For each AHU, the damper repair services shall include:
a) Replacement or refurbishment of the existing discharge isolation dampers.
i) All replacement components shall be direct replacements or approved equals.
b) Resolution of existing interference and fit issues, to allow for proper operation of the new or refurbished dampers.
c) Installation, adjustment, and testing of the new or refurbished dampers.
Additional Notes
1) All work will be performed at the Medical Center (Building 41) and must minimize disruption to the building’s work spaces and surrounding areas.
a) Electric Outages: Any work that will require a utility outage affecting the building’s regularly occupied workspaces, such as a shutdown or partial shutdown of building’s electric, shall be performed outside of the facilities “regular hours” as defined in the contract.
b) Crane Activity: Any work that will disrupt traffic flow at the facility or requires the building to be unoccupied, such as crane setup and crane operations, shall be performed outside of the facilities “regular hours” as defined in the contract.
c) Restroom and Handwash Facilities: The contractor shall provide a portable restroom and handwash station, designated for use by contractor personnel and any subcontractors, for the duration of on-site activity. Entrance to the interior of SFVAMC buildings shall be limited to the minimum access required to complete the work described in the Statement of Work.
2) Details of existing modular chillers:
Manufacturer: Clima-Cool
Model #: UCA020BFASACE0L
Type: Air Cooled Package
Size: 20-ton
Voltage: 460/3/60
Compressor Type: Scroll
Refrigerant: R-410A
3) Details of existing AHU discharge isolation dampers:
Manufacturer: Nailor Industries
Model #: 1210
Mfg Description: Smoke Damper Steel Airfoil Blade Type, Nominal Size, for Reference Only: 59” x 30” (2 @ 29.5” x 30”)
Enclosure/Mounting Style: Side Mounting Plate, No Sleeve
Leakage Rating: Class I
Max Velocity / Pressure Rating: 3000 fpm @ 6" w.g.
Elevated Temperature: 250°F
Bearings: Stainless Steel
Actuator Mounting: External
Actuator Location: Multi-hand
Actuator Fail Position: Close
Certification and Accreditation
The Certification and Accreditation (C&A) requirements do not apply. A Security Accreditation Package is not required.