SJPSB Cooler-Freezer Combined Bid Set 06-17-25.pdf
PDF 10 MB Posted
- Solicitation number
- 24-286
- Issued by
- St. Martin Parish, Louisiana
About this file
This document is a comprehensive construction bid set prepared by Thompson Luke & Associates for the St. James Parish School Board's Walk-In Cooler/Freezer Replacement Project located at the School Board Warehouse at 1876 W Main Street in Lutcher, Louisiana. The project involves a complete demolition and replacement of existing walk-in cooler and freezer facilities, including removing current refrigeration units, electrical connections, sprinkler systems, and associated infrastructure. The construction documents are dated June 17, 2025, and include detailed architectural, structural, mechanical, electrical, and fire protection plans for a new walk-in cooler measuring approximately 446 square feet and a walk-in freezer measuring approximately 906 square feet.
The project scope includes installing new refrigeration systems with multiple evaporator coils, electrical connections, sprinkler heads, lighting, temperature alarm systems, and associated infrastructure. The new refrigeration system will feature two separate compressor systems, one for the cooler and one for the freezer, with network switches and on-demand defrost controllers. Electrical requirements include a new 100A panel (Panel "CF") fed from the existing Panel "B", with specific circuits for lighting, evaporator coils, drain line heaters, and emergency lighting. The project also involves modifying existing electrical, mechanical, and fire protection systems to accommodate the new walk-in cooler and freezer units, with careful coordination required to maintain existing building systems and meet all current building and safety codes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SJPSC Cooler-Freezer Replacement Bid Specs.pdf | ||
| Request for Bids- Freezer Cooler Project Advertisement.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THOMPSON LUKE & ASSOCIATES
Project Number:
Date:
Reviewed by:
THOMPSON LUKE &
ASSOCIATES
10705 Rieger Road, Suite 101 Baton Rouge, LA 70809
TEL. 225-293-9474
www.tlaeng.com
Drawn by:
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated used or disclosed without written consent of engineer. Do not scale drawings. Use given dimensions only. If not shown, verify correct dimensions with the engineer. Contractor shall check and verify all dimensions and conditions at job site. Any and all quantities which are included within this material are approximate and for estimating purposes only. Contractor shall be responsible for verifying actual quantities when constructing project.
NO
T F
O R C
O
NSTRUCTIO
N
/1
/2
:4
:4
A M
C U s e rs
\jo h n w
\D o c u m e n ts
\2
-2
S J P
S B
C o o le r- F re e z e r
(R jo h n C
D M
T .r v t
W a lk
-I n
C o o le r/ F re e z e r R e p la c e m e n t
S t.
J a m e s P a ri s h
S c h o o l B o a rd
W a re h o u s e
W M ai n
S tr ee t
Lu tc he r, L A
24-286
06.17.2025
GENERAL COVER SHEET
G0.0
Design Development
NO. DESCRIPTION DATE
GENERAL NOTES
RENOVATION NOTES
PROJECT INFORMATION VICINITY MAP
1. CONTRACTORS MUST VISIT THE SITE TO VERIFY ALL EXISTING CONDITIONS, BUILDING TYPES AND CONSTRUCTION AND ALL DIMENSIONS. THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO SUBMITTING A PROPOSAL OR BID. THE CONTRACTOR SHALL BECOME GENERALLY FAMILIAR WITH THE PROJECT, AND WITH THE IMPACT OF THE NEW WORK ON THE EXISTING CONDITIONS. ANY AREAS OF CONCERN SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO SUBMITTING A PROPOSAL OR BID. NO ADDITIONAL CHARGE TO THE OWNER WILL BE APPROVED WHICH IS ATTRIBUTABLE TO THE CONTRACTOR'S FAILURE TO COMPLETE THIS RESPONSIBILITY.
2. PROTECT EXISTING WORK WHICH IS TO REMAIN IN PLACE, BE REUSED, OR REMAIN THE PROPERTY OF THE OWNER.
3. PROTECT ELECTRICAL AND MECHANICAL SERVICES AND UTILITIES WHERE REMOVAL OF EXISTING UTILITIES AND PAVEMENTS IS SPECIFIED. PROVIDE BARRICADES, TEMPORARY COVERING OF EXPOSED AREAS, AND TEMPORARY SERVICES OR CONNECTIONS FOR ELECTRICAL AND MECHANICAL UTILITIES.
4. REMOVE EXISTING UTILITIES AS INDICATED AND UNCOVERED BY WORK AND TERMINATE IN A MANNER CONFORMING TO THE NATIONALLY RECOGNIZED CODE OR STANDARD COVERING THE SPECIFIC UTILITY AND APPROVED BY THE OWNER. IF UTILITY LINES ARE ENCOUNTERED THAT ARE NOT SHOWN ON THE DRAWINGS, DO NOT PROCEED. CONTACT THE ENGINEER FOR
FURTHER INSTRUCTIONS.
5. THE INFORMATION CONTAINED ON THESE DRAWINGS WITH REGARD TO THE EXISTING CONDITIONS OF CONSTRUCTION IN NO WAY RELEASES THE CONTRACTOR FROM THE RESPONSIBILITY FOR VERIFYING COMPLETELY ALL FIELD CONDITIONS RELATING TO AND AFFECTING THE EXECUTION OF THE WORK, AS DESCRIBED IN THESE CONTRACT DOCUMENTS.
6. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY AND DOCUMENT ALL EXISTING DIMENSIONS, ELEVATIONS AND BENCHMARKS, MATERIALS AND METHODS OF CONSTRUCTION THAT MAY AFFECT OR BE AFFECTED BY NEW WORK, AND TO COORDINATE SUCH FIELD VERIFICATION WITH THE CONTRACT DOCUMENTS AND THE EXECUTION OF THE WORK. DISCREPANCIES AND/OR CONFLICTS INVOLVING ANTICIPATED EXISTING CONDITIONS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION IMMEDIATELY.
7. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ASSIST THE ENGINEER IN MAKING THEIR EVALUATIONS AND RECOMMENDATIONS BY PROVIDING IN A TIMELY MANNER, AT NO ADDITIONAL COST TO THE OWNER, ACCURATE AND COMPLETE DRAWINGS, SKETCHES, AND PHOTOGRAPHS SUFFICIENT TO CLEARLY DESCRIBE DISCREPANCIES, CONFLICTS, AND CONCEALED OR
OTHERWISE UNANTICIPATED EXISTING CONDITIONS AFFECTING NEW CONSTRUCTION.
8. THE ENGINEER HAS ENDEAVORED TO IDENTIFY AS COMPLETELY AS POSSIBLE IN THE DRAWINGS AND SPECIFICATIONS EXISTING ITEMS OR EQUIPMENT AND CONSTRUCTION THAT ARE REQUIRED TO BE REMOVED OR OTHERWISE DEMOLISHED SO AS TO ALLOW THE EXECUTION OF NEW WORK TO BE PERFORMED. THE INFORMATION IS PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR, AND IS IN NO WAY INTENDED TO MEAN THAT DEMOLITION IS LIMITED ONLY TO THOSE ITEMS SPECIFICALLY IDENTIFIED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
EXECUTE DEMOLITION WORK AS REQUIRED TO ALLOW THE EXECUTION OF NEW WORK.
9. ALL AREAS ABOVE OR ON THE EXIST. CEILING THAT ARE AFFECTED BY INSTALLATION OF NEW WORK SHALL BE REPAIRED COMPLETELY WITH MATERIALS AND PRODUCTS TO MATCH EXIST.
INSTALLATION AND FIRE-RATED ASSEMBLIES.
10. ANY DEMOLITION SCOPE WHICH MAY POTENTIALLY COMPROMISE THE STRUCTURAL INTEGRITY OF THE EXIST. BUILDING OR NEW CONSTRUCTION, SHALL BE IMMEDIATELY CALLED TO THE
ATTENTION OF THE ENGINEER, PRIOR TO PERFORMING, OR PROCEEDING WITH ANY WORK.
11. AT ANY WALL THAT IS AFFECTED BY DEMOLITION OR CONSTRUCTION, PAINT THE ENTIRE WALL FROM INTERIOR CORNER TO INTERIOR CORNER, AND TOP TO BOTTOM FOR THE ENTIRE
LENGTH OF THE WALL.
12. ALL EMERGENCY EXITS SHOULD REMAIN CLEAR AND USABLE THROUGHOUT ENTIRE CONSTRUCTION PROCESS UNLESS SPECIFICALLY COORDINATED FOR LIFE SAFETY MEASURE. PROVIDE ANY TEMPORARY PROTECTIONS, WALKWAYS OR ALTERNATE EGRESS MEANS AS REQUIRED TO ACCOMMODATE THIS. ANY WORK THAT WOULD REQUIRE THE TEMPORARY CLOSURE OF EXITS SHOULD BE CONDUCTED AFTER HOURS, AND COORDINATED WITH THE OWNER'S REPRESENTATIVE.
13. ALL LIFE SAFETY SYSTEMS, FIRE ALARMS, STROBE DEVICES, ANNUNCIATORS, SMOKE DETECTORS, AND PULL STATIONS ARE TO REMAIN COMPLETELY OPERATIONAL THROUGHOUT THE DEMOLITION AND CONSTRUCTION PROCESS FOR OCCUPIED SPACES. THE CONTRACTOR SHALL PROVIDE ADDITIONAL MEASURES FOR AREAS WHERE LIFE SAFETY SYSTEMS ARE TO BE RENDERED INACTIVE AND SHALL COORDINATE ALL SYSTEM INTERRUPTIONS WITH THE STATE FIRE MARSHAL INSPECTOR, PRIOR TO PERFORMING ANY WORK.
14. ALL PORTIONS OF THE EXISTING BUILDING SHALL REMAIN WEATHERTIGHT AND SECURED AT ALL TIMES. IF CONSTRUCTION IS POSTPONED, THE CONTRACTOR SHALL SECURE THE BUILDING
FROM THE ELEMENTS, INCLEMENT WEATHER, AND VANDALISM.
15. REMOVE AND TRANSPORT DEBRIS AND RUBBISH IN A MANNER THAT WILL PREVENT SPILLAGE ON PAVEMENTS, STREETS, OR ADJACENT AREAS. CLEAN UP SPILLAGE FROM PAVEMENTS, STREETS, AND ADJACENT AREAS, IN COMPLIANCE WITH ALL LOCAL AND STATE REQUIREMENTS. DESIGNATE ON SITE VEHICLE WASH STATION.
1. PRIOR TO BIDDING, THE CONTRACTOR (AND SUBCONTRACTING BIDDERS) SHALL VISIT THE EXISTING BUILDING, SITE, AND SURROUNDING AREA AND THOROUGHLY ACQUAINT THEMSELVES WITH ALL ASPECTS OF THE PROJECT DEMOLITION AND CONSTRUCTION, AS INDICATED AND/OR IMPLIED WITHIN THIS DOCUMENT. ANY DISCREPANCIES, OMISSIONS OR CONFLICTS RELATIVE TO THE INFORMATION CONTAINED WITHIN THE DOCUMENTS, THE FIELD VERIFIED CONDITIONS, OR ITEMS WHICH MAY INTERFERE WITH THE SATISFACTORY COMPLETION OF THE WORK, SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY. FAILURE BY THE CONTRACTOR TO PROVIDE THESE MEASURES SHALL NOT BE JUSTIFICATION FOR ADJUSTMENT IN THE CONTRACT SUM.
2. ALL WORK IS TO HAVE A ONE YEAR WARRANTY, MINIMUM.
3. THE DRAWINGS, AND ANY SUBSEQUENTLY ISSUED ADDENDA, AMENDMENTS, FIELD ORDERS, OR CHANGE ORDERS ARE PART OF THESE CONTRACT DOCUMENTS.
4. NAMING A CERTAIN BRAND OR MANUFACTURER IS TO DESIGNATE THE GENERAL STYLE, TYPE, CHARACTER, AND QUALITY STANDARD OF THE PRODUCT DESIRED. SUBSTITUTION REQUESTS MUST BE
SUBMITTED PRIOR TO BIDDING.
5. CONSTRUCTION GENERATING EXCESSIVE NOISE SHALL BE PERFORMED AFTER HOURS AND/OR COORDINATED WITH OWNER/PROJECT REPRESENTATIVE.
6. IN NO WAY DO THE DIMENSIONS SHOWN ON THE PLANS REPRESENT AN EXACT QUANTITY OF MATERIALS. THE BIDDER IS SOLELY RESPONSIBLE FOR THE QUANTITIES IN HIS BID.
7. THE DRAWINGS REPRESENT GENERAL LOCATIONS OF IMPROVEMENTS. IT SHALL BE THE GENERAL CONTRACTORS RESPONSIBILITY TO LOCATE ALL IMPROVEMENTS ON SITE PRIOR TO ALTERATION, ADDITION, OR TIE-IN. ALL DAMAGE SHALL BE PROPERLY REPAIRED BY THE CONTRACTOR, AT THE CONTRACTOR'S EXPENSE.
8. THE CONTRACTOR SHALL PROTECT THE SITE AND PROPERTY AT ALL TIMES. ALL AREAS SHALL BE MAINTAINED FREE OF TRASH AND CONSTRUCTION DEBRIS AND ALL WASTE SHALL BE REMOVED FROM THE SITE ON A WEEKLY BASIS, AT A MINIMUM, OR AS DIRECTED BY THE OWNER/FACILITY MANAGER. COORDINATE THE EXACT LOCATION FOR THE TRASH DUMPSTER AND STAGING AREAS WITH THE OWNER/FACILITY MANAGER. REMOVAL AND DISPOSAL OF ALL DEBRIS, SUBSTANCES AND MATERIALS IS BE ACCOMPLISHED ACCORDING TO SPECIFICATIONS IN ADDITION TO FEDERAL, STATE, AND
LOCAL REGULATIONS.
9. THE STORAGE OF MATERIALS ON SITE SHALL BE ALLOWED IN DESIGNATED AREAS. THESE AREAS WILL BE DETERMINED AT THE PRE-BID MEETING. ANY DAMAGE TO EXISTING AREAS / SURFACES DUE TO STORAGE & STAGING SHALL BE RESTORED TO THE ORIGINAL CONDITION BY GENERAL CONTRACTOR AT THE CONTRACTOR'S EXPENSE.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PERMITS AND ANY CHARGES FOR TIE-IN TO EXISTING STREETS AND UTILITIES. ALL IMPACT FEES, IF ANY, SHALL BE THE CONTRACTOR'S RESPONSIBILITY. THE CONTRACTOR SHALL OBTAIN AND PAY ALL NECESSARY PERMITS, AND AFTER COMPLETION, FURNISH OWNER CERTIFICATIONS OF FINAL INSPECTIONS AND APPROVAL AS ISSUED BY THE INSPECTION DEPARTMENT OF THE PARISH. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL NECESSARY CERTIFICATES OF INSPECTION, FROM FEDERAL AND STATE
AUTHORITIES BOTH AT ROUGH-IN AND COMPLETION.
11. ALL MATERIALS AND WORK SHALL CONFORM TO ALL GOVERNING CODES, REGULATIONS, AND AGENCIES.
12. ELECTRICAL WORK SHALL COMPLY WITH NFPA AND NATIONAL ELECTRICAL CODE AND BE PERFORMED BY A LICENSED ELECTRICIAN.
13. PENETRATIONS THROUGH RATED CONSTRUCTION SHALL BE SEALED BY APPROVED FIRESTOP SYSTEMS OR DEVICES TESTED IN ACCORDANCE WITH ASTM E-814 OR ANSI/UL 1479.
14. REMOVAL AND DISPOSAL OF ALL SUBSTANCES AND MATERIAL IS TO BE ACCOMPLISHED ACCORDING TO FEDERAL, STATE AND LOCAL REGULATIONS.
15. ALL MATERIALS SHALL BE NEW EXCEPT WHERE OTHERWISE NOTED AND SHALL CONFORM WITH THE STANDARDS OF UNDERWRITER'S LABORATORY IN EVERY CASE WHERE SUCH A STANDARD HAS BEEN ESTABLISHED FOR THE PARTICULAR TYPE OF MATERIAL IN QUESTION. INSTALL ALL MATERIALS AND SYSTEMS IN PROPER RELATION WITH ADJACENT CONSTRUCTION AND WITH UNIFORM
APPEARANCE.
16. CONTRACTOR SHALL ANTICIPATE AND MAKE ANY AND ALL ARRANGEMENTS WITH LOCAL GOVERNMENT AGENCIES, SHOULD ENTRY ONTO, OR OBSTRUCTION OF, A PUBLIC WAY BE NECESSARY IN
CONNECTION WITH THE WORK.
17. THE CONTRACTOR SHALL PROVIDE ANY SITE DEMOLITION / UTILITY RELOCATION NECESSARY FOR COMPLETION OF WORK.
18. THE CONTRACTOR SHALL PROVIDE ANY SITE DEMOLITION/UTILITY RELOCATION AS NECESSARY FOR COMPLETION OF THE OVERALL SCOPE OF WORK. VERIFY ALL EXISTING UTILITIES AND EXACT LOCATIONS, PRIOR TO PERFORMING ANY WORK. CONTRACTOR SHALL NOTIFY ENGINEER IMMEDIATELY REGARDING ANY CONFLICTS WHICH MAY EXIST AT THE SITE AND THAT WHICH IS REPRESENTED IN THE DOCUMENTS. THE REPAIR AND/OR REPLACEMENT OF ANY SYSTEM COMPONENTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, SHOULD THEY BE DAMAGED DURING THE COURSE OF
DEMOLITION OR CONSTRUCTION.
19. PRIOR TO ALTERATION, ADDITION OR TIE-IN TO EXISTING FACILITIES/ UTILITIES, ANY DAMAGE BY CONTRACTOR SHALL BE PROPERLY REPAIRED BY THE CONTRACTOR, AT THE CONTRACTOR'S EXPENSE.
20. CONTRACTOR SHALL EXERCISE CARE TO AVOID DAMAGE TO EXISTING WORK, ADJACENT SURFACES, AND ADJOINING AREAS INCLUDING BUT NOT LIMITED TO THE PORTION OF THE WORK THAT IS TO REMAIN AS A PART OF THE COMPLETED CONSTRUCTION. CONTRACTOR SHALL BE REQUIRED TO REPAIR OR OTHERWISE RESTORE ANY SUCH AREAS OR SURFACES THAT BECOME DAMAGED OR
REMOVED ON ACCOUNT OF THE DEMOLITION AND/OR CONSTRUCTION WORK.
21. CONTRACTOR SHALL INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH PRODUCT AND MATERIAL MANUFACTURER'S INSTRUCTIONS AND REVIEWED SUBMITTALS.
22. ALL ITEMS NOT SPECIFICALLY NOTED AS OWNER PROVIDED OR OWNER INSTALLED SHALL BE PROVIDED AND INSTALLED BY CONTRACTOR.
23. WORK INDICATED AS "NOT IN CONTRACT", "N.I.C.", OR "BY OTHERS" SHALL BE PERFORMED BY OWNER'S SEPARATE CONTRACTORS. CONTRACTOR SHALL ASSIST IN COORDINATING THE WORK BY
SEPARATE CONTRACTORS WITH THE WORK OF THIS CONTRACT.
24. DEMOLITION SHALL BE PERFORMED IN AN ORDERLY SEQUENCE, SCHEDULED BY THE CONTRACTOR AND COORDINATED WITH THE OWNER. SHOULD HAZARDOUS MATERIALS, OR MATERIALS SUSPECTED TO BE HAZARDOUS BE ENCOUNTERED, THE CONTRACTOR SHALL NOT PROCEED AND IMMEDIATELY CALL TO THE ATTENTION OF THE OWNER. ALL HAZARDOUS WASTE SHALL BE CONTAINED, ABATED, REMOVED, AND DISPOSED OF IN ACCORDANCE WITH FEDERAL REGULATIONS, LA.D.E.Q. AND THE OWNER'S ASBESTOS MANAGEMENT PLAN.
25. IN ORDER TO ACHIEVE SUBSTANTIAL COMPLETION, THE CONTRACTOR SHALL PROVIDE ELEVATION CERTIFICATES SHOWING THAT ALL EQUIPMENT, ELECTRICAL PANELS, & DEVICES HAVE BEEN
LOCATED ABOVE THE DESIGN FLOOD ELEVATION.
26. PRIOR TO START OF DEMOLITION/CONSTRUCTION, CONTRACTOR IS TO COORDINATE WITH OWNER/PROJECT REPRESENTATIVE ANY REMAINING ITEMS LOCATED IN BUILDING INTENDED FOR
CONTRACTOR REMOVAL/DISPOSAL.
BASE BID: (AS PER CONSTRUCTION DOCUMENTS):
• MECHANICAL:
1. REMOVE EXISTING SPRINKLER HEADS IN COOLER AND FREEZER, REPLACE WITH NEW. ADJUST SPRINKLER PIPING AS NECESSARY TO ACCOMMODATE NEW HEAD LAYOUT.
2. ROUTE NEW COPPER CONDENSATE DRAIN PIPING FOR COOLER AND FREEZER.
• ELECTRICAL:
1. DEMOLISH EXISTING LIGHTING, RECEPTACLES, AND EXISTING COOLER/FREEZER CONNECTIONS IN PREPARATION FOR NEW COOLER/FREEZER INSTALLATION. REFEED NEW COOLER/FREEZER AS
SHOWN ON POWER PLANS.
2. PROVIDE NEW 120/208V 1Ø PANEL TO ACCOMODATE NEW CIRCUITRY.
3. REMOVE AND REPLACE SPECIFIED EMERGENCY LIGHTING PER LIGHTING PLANS.
CONSTRUCTION DOCUMENTS FOR
Walk-In Cooler/Freezer Replacement St. James Parish School Board Warehouse
1876 W Main Street Lutcher, LA 70071
June 17, 2025
PROFESSIONAL OF RECORD
THOMPSON LUKE & ASSOCIATES, LLC
GENERAL
G0.0 GENERAL COVER SHEET
STRUCTURAL
DS1.01 DEMOLITION/SHORING PLAN
S1.01 FOUNDATION PLAN
S2.01 STRUCTURAL SECTIONS & DETAILS
S2.02 STRUCTURAL SECTIONS
S2.03 STRUCTURAL SECTIONS
S2.04 STRUCTURAL SECTIONS
FOOD SERVICE
FS1.0 EXISTING WALK-IN COOLER & FREEZER DEMOLITION PLAN
FS1.1 FOOD SERVICE EQUIPMENT FLOOR PLAN
FS2.1 WALK-IN COOLER/FREEZER DETAILS
FS2.2 WALK-IN COOLER/FREEZER DETAILS
FS3.1 WALK-IN COOLER/FREEZER SLAB DEPRESSION PLAN
FS4.1 WALK-IN PLUMBING/ELECTRICAL ROUGH-IN PLAN
FS4.2 WALK-IN PLUMBING/ELECTRICAL ROUGH-IN PLAN
MECHANICAL
DFP1.0 FIRE PROTECTION DEMOLITION PLAN
FP1.0 FIRE PROTECTION PLAN
M0.0 MECHANICAL COVER SHEET
M1.0 MECHANICAL/PLUMBING PLAN
ELECTRICAL
E0.0 ELECTRICAL COVER SHEET
E1.0 ELECTRICAL - DEMO PLAN
E1.1 ELECTRICAL - NEW PLAN
E2.0 ELECTRICAL - PANEL SCHEDULES & DETAILS
SHEET INDEX
St. James Parish School Board Members:
Chris M. Kimball, Superintendent
Nicole Florent, President Marty Poche, Vice President
Diana Cantillo, Board Member Tim Detillier, Board Member Sue Beier, Board Member
Angela Washington, Board Member Raymond Gros, Board Member
/1
7/
A B C
G
H 1'
4"
/4
1'
4"
2' - 11 5/8" 25' - 0" 6' - 0 3/8"
34' - 0"
HATCHED AREA INDICATED EXTENT OF SAWCUTING/DEMOLITION SCOPE
ALL GRADE BEAMS, SLAB, REINFORCING STEEL, AND ANY ELEMENTS
DEFINED IN THE ARCH. DOCUMENTS SHOULD BE DEMO'D IN THIS AREA.
DEMO TO CMU WALL.
(CMU WALL TO REMAIN)
EXISTING GRADEBEAMS
C
G
H
4"
/8
/8
EXISTING PEMB
COL.
EXISTING PEMB
COL.
PRIOR TO ANY DEMOLITION
PEMB. COLS. TO BE TIED TOGETHER WITH 1 1/8" WIRE ROPE,
CAPABLE OF SAFELY RESISTING 20,000 LBS. OF TENSION.
WIRE ROPE TO REMAIN IN PLACE
UNTIL COMPLETION OF NEW GRADE BEAMS.
THIS INCLUDES FULL CURING OF CONCRETE AND EPOXY.
WIRE ROPE TO BE ATTACHED TO EXISTING COLUMNS WITH
HARDWARE CAPABLE OF SAFELY RESISTING 20,000 LBS. OF
TENSION.
25' - 0" 6' - 8"
WIRE ℄ 1' 6" A.F.F.
1/
8" W
IR
E
R O
PE
1/
8" W
IR
E
R O
PE
TYP.
LIVI
C GNIREENIGNE
License No. 39038 JAMES R. LeBOUEF
ENGINEER
IN
TA
EOFLOUISIANAS
T
PROFESSIONAL
Jmcstamp.dwg 12297 44936
DATE:
SHEET NO:
DRAWN:
TH
O
M
PS
O N
L U
KE
A
SS
O C
IA
TE
S, L
.L .C
PH
O
N E
5-
3-
BA
TO
N R
O U
G E, L A
R
IE
G
ER
R O
AD
, S
U
IT
E
CHECKED:
TLA PROJECT NO:
DS-101
W al k- In
C oo le r/F re ez er R ep la ce m en t
W M ai n
St re et Lu tc he r, LA
FD
JL
06/17/2025 24-286
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
1/4" = 1'-0"
FOUNDATION PLAN - DEMOLITION
1/4" = 1'-0"
SHORING PLAN
Revision Date
A B C 25' - 0" 6' - 8"
11' - 5 3/8"
/4
5/
8"
5/ 8"
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
EXISTING FOUNDATION WALL
1'
4"
/4
EXISTING 4" SLAB SAWCUT
LINE
EXISTING 4" SLAB SAWCUT
LINE
EXISTING 4" SLAB SAWCUT
LINE
NEW 4" SLAB
14' - 5"
N
EW
" S
LA
B
1'
5/
8"
N
EW
" S
LA
B
0"
2'
4"
1'
8"
31' - 0" 1' - 1 5/8"
2' - 11 5/8"
18' - 7" 1' - 1 5/8"
NEW 4" SLAB
2' - 0"
EXISTING PEMB BENT
EXISTING PEMB BENT
EXISTING PEMB BENT
EXISTING PEMB BENT
EXISTING CMU BUMPOUT
NEW GRADE BEAMS,
SEE SECTIONS FOR SIZING AND REINFORCEMENT (TYP.)
EXISTING 8" CMU WALL
NEW 4" FREEZER SLAB
NEW 4" FREEZER SLAB
EXISTING FOUNDATION WALL
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
S-201
S-201
2' - 0"
S-201
S-201
S-202
S-202
S-202
S-202
S-203
S-203
1'
4"
G
H
S-203
S-203
S-204
S-204
S-204
S-204
LIVI
C GNIREENIGNE
License No. 39038 JAMES R. LeBOUEF
ENGINEER
IN
TA
EOFLOUISIANAS
T
PROFESSIONAL
Jmcstamp.dwg 12297 44936
DATE:
SHEET NO:
DRAWN:
TH
O
M
PS
O N
L U
KE
A
SS
O C
IA
TE
S, L
.L .C
PH
O
N E
5-
3-
BA
TO
N R
O U
G E, L A
R
IE
G
ER
R O
AD
, S
U
IT
E
CHECKED:
TLA PROJECT NO:
S-101
W al k- In
C oo le r/F re ez er R ep la ce m en t
W M ai n
St re et Lu tc he r, LA
FD
JL.
06/17/2025 24-286
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
1/4" = 1'-0"
FOUNDATION PLAN - TOC. EL. 3'-4"
1.
2.
3.
4.
5.
6.
7.
8.
ALL CONCRETE AND REINFORCING STEEL SHALL CONFORM TO THE LATEST ACI CODE.
UNLESS SPECIFICALLY NOTED OTHERWISE ON THESE PLANS, ALL CONCRETE SHALL DEVELOP A
MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3,000 PSI FOR SLABS AND 4,000 PSI FOR ALL
CONCRETE BELOW SLABS/PAVING.
UNLESS SPECIFICALLY NOTED OTHERWISE ON THESE PLANS, ALL REINFORCING STEEL SHALL
CONFORM TO ASTM A615, GRADE 60.
WHERE REINFORCING STEEL IS CALLED TO BE WELDED, WELDABLE REINFORCING STEEL SHALL
BE USED.
PROVIDE ALL NECESSARY REINFORCING STEEL ACCESSORIES REQUIRED TO SECURELY HOLD
THE REINFORCING STEEL IN THE POSITION SHOWN ON THESE PLANS.
ALL REINFORCING IN MEMBERS IN CONTACT WITH THE EARTH BUT NOT FORMED AGAINST EARTH
SHALL HAVE A MINIMUM OF TWO (2) INCHES OF CONCRETE COVER.
ALL REINFORCING IN FACES OF MEMBERS FORMED AGAINST THE EARTH SHALL HAVE A MINIMUM
OF THREE (3) INCHES OF CONCRETE COVER.
ALL REINFORCING BAR LAPS SHALL BE 44 BAR DIAMETERS FOR #6 OR SMALLER AND 55 BAR
DIAMETERS FOR #7 OR LARGER. GRADE BEAM TOP BARS SHALL BE SPLICED WITHIN THE MIDDLE
THIRD OF BEAM SPAN. GRADE BEAM BOTTOM BARS SHALL BE SPLICED AT BEAM SUPPORTS.
CONCRETE AND REINFORCING STEEL NOTES:
SPECIAL FOUNDATION NOTES:
1.
2.
3.
NO GEOTECHNICAL INFORMATION WAS FURNISHED FOR THIS
PROJECT. THIS ENGINEER HAS ASSUMED THAT THE SOIL
CONDITIONS FOR THIS DESIGN ARE FIRM, STABLE, AND NON-
EXPANSIVE AND ARE CAPABLE OF SAFELY SUPPORTING 1000 PSF
FOR CONTINUOUS FOOTINGS. BY USING THESE PLANS, THE
OWNER HOLDS HARMLESS THE ENGINEER FROM ALL LIABILITY AND
DAMAGES ARISING FROM UNSTABLE SOIL CONDITIONS OR FROM
CONDITIONS WHERE FACTORS CAUSE THE SOIL CONDITIONS TO
BECOME UNSTABLE AND ALLOW MOVEMENT WITHIN THE
FOUNDATION AND STRUCTURAL SYSTEM. IF CONDITIONS ARE
FOUND TO BE OTHER THAN HEREIN STATED, STOP OPERATIONS
AND NOTIFY ARCHITECT SO HE CAN HAVE THE NECESSARY
INVESTIGATION AND CORRECTIONS TO PLANS DONE.
ALL FILL AND BACKFILL MATERIAL SHALL HAVE A "CL"
CLASSIFICATION WITH A LIQUID LIMIT LESS THAN 45 AND A
PLASTICITY INDEX BETWEEN 8 AND 22.
EARTH FORMS ARE ACCEPTABLE PROVIDED THE SOIL IS FIRM
ENOUGH TO MAINTAIN STABILITY OF THE EXCAVATIONS BEFORE
AND DURING THE INSTALLATION OF CONCRETE.
1.
2.
3.
4.
5.
6.
7.
ALL POST-INSTALLED ANCHORS SHALL HAVE A CODE REPORT RECOGNIZING THE
PRODUCT FOR THE APPROPRIATE APPLICATION. THE CONTRACTOR SHALL INCLUDE
THE CODE REPORT WITH THE POST-INSTALLED ANCHOR SUBMITTAL.
THE CONTRACTOR SHALL SUBMIT ANCHOR PRODUCT DATA IN ACCORDANCE WITH THE
SUBMITTAL REQUIREMENTS CALLED FOR IN THE CONSTRUCTION DOCUMENTS.
ANCHOR PRODUCT DATA SHALL INCLUDE ALLOWABLE ANCHOR SHEAR AND TENSILE
FORCES FOR THE APPROPRIATE APPLICATION.
FOR ANCHORING INTO CONCRETE:
A. ADHESIVE ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN
ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308.
ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING AISC SPECIFICATIONS:
WIDE FLANGE SHAPES: ASTM A992 GRADE 50
CHANNEL, ANGLE, TEE & MISC. PLATES: ASTM A36
TUBE STEEL: ASTM A500 GRADE B (46 KSI)
PIPE: ASTM A53 GRADE B
THE CONTRACTOR SHALL CONTACT THE MANUFACTURER'S REPRESENTATIVE FOR
PRODUCT INSTALLATION TRAINING AND A LETTER SHALL BE SUBMITTED TO THE
ARCHITECT AND/OR ENGINEER OF RECORD INDICATING TRAINING HAS TAKEN PLACE.
FOR ADHESIVE ANCHORS, ALL HOLES MUST BE CLEANED WITH A HOLE CLEANING
BRUSH PRIOR TO THE INSTALLATION OF ADHESIVE. CLEAN HOLES PER
MANUFACTURER'S RECOMMENDATIONS. CLEANING HOLES WITH AN AIR COMPRESSOR
IS NOT ALLOWED.
POST-INSTALLED ANCHORS SHALL NOT BE PLACED IN CONCRETE THAT IS LESS THAN
7 DAYS OLD.
POST- INSTALLED ANCHOR NOTES:
1 2
1' - 4"
(3) #5 BOTTOM LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
1'
8"
(3) #4 MID LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
(2) #4 TOP LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
TYP. @ 8 PLCS. THIS SIDE
12" GRAVEL BED
COMPACTED SUBGRADE
EXISTING 8" CMU WALL
EXISTING PEMB BENT
EXISTING FOUNDATION WALL
5 5/8" 1' - 4"2"
EMBED REINFORCEMENT
TO EXISTING FOUNDATION
WALL W/ EPOXY
(MIN. 4" EMBED,
TYP. @ 8 PLCS. THIS SIDE)
EXISTING FOUNDATION WALL
EXISTING 8" CMU WALL
(2) #3 @ 12" OC.
TOC EL. 3' - 4" TOC EL. 3' - 4"
CONT. #3
9"
S-201
VAPOR BARRIER
G H
1 2
SEE TYPICAL 4" SLAB DETAIL
FOR REINFORCEMENT
S-201
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
12" GRAVEL BED
COMPACTED SUBGRADE
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
VAPOR BARRIER
1' - 0"
#4 @ 18" OC.
(2) CONT. #4 @ 6" OC.
T&B
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
11" 1' - 1"
S-201
6"
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO EXISTING WALL)
(2) CONT. #4 BARS @ 12" O.C.
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIER
S-201
1'
2"
TOC EL. 3' - 4" TOC EL. 3' - 4"
1' - 4"
EXISTING 8" CMU WALL
TOC EL. 3' - 4"
CONT. #3
CONT. #4
9"
2" 5 5/8" 1' - 4"
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
EXISTING FOUNDATION WALL
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
#3 @ 18" OC.
6" 6"
10"
G H
#4 @ 12" O.C.
4" SLAB ON GRADE
6.6 W2.9XW2.9 WIREMESH
FOR REINFORCEMENT
TYPICAL 4" & 5" SLAB ON GRADE DETAIL
4" COOLER/FREEZER SLAB NOTE:
SLAB DEFINED AS "COOLER" OR
"FREEZER SLAB" MUST BE
PERFECTLY LEVEL.
4" SLAB
12" GRAVEL BED
COMPACTED SUBGRADE
VAPOR BARRIER
FREEZER/COOLER SLAB
6.6 W2.9XW2.9 WIREMESH
FOR REINFORCEMENT4" SLAB
1" SELF LEVELING
GROUT
COMPACTED SUBGRADE
VAPOR BARRIER
INSULATED FLOOR
5" SLAB
12" GRAVEL BED
(REUSE EXISTING GRAVEL
WHERE POSSIBLE)
#4 @ 48" OC. EA. WAY.
CONCRETE BRICK @
INTERSECTIONS OF #4'S
1'
0" 5"1"
4" 4"
FOR REINFORCEMENT
SEE SECTIONS.
SEE SLAB DETAIL FOR REINFORCEMENT INFO.
4" 4"
1" 5"
1'
2"
5" SLAB ON GRADE
4" FREEZER SLAB
NOTE:
SEE FREEZER/COOLER
MFG FOR FLATNESS AND
LEVEL REQUIREMENTS.
CONC. CURB
6"
6"
4" 2"
2" CAULKING OR
OTHER WATERPROOF EXPANSION
MATERIAL
4" INSULATED WALL
CONT. #3
#3 DOWEL @ 24" OC.
1" SELF LEVELING GROUT
VAPOR BARRIER
4" INSULATED FLOOR
TOC EL. 3' - 4"
LIVI
C GNIREENIGNE
License No. 39038 JAMES R. LeBOUEF
ENGINEER
IN
TA
EOFLOUISIANAS
T
PROFESSIONAL
Jmcstamp.dwg 12297 44936
DATE:
SHEET NO:
DRAWN:
TH
O
M
PS
O N
L U
KE
A
SS
O C
IA
TE
S, L
.L .C
PH
O
N E
5-
3-
BA
TO
N R
O U
G E, L A
R
IE
G
ER
R O
AD
, S
U
IT
E
CHECKED:
TLA PROJECT NO:
S-201
W al k- In
C oo le r/F re ez er R ep la ce m en t
W M ai n
St re et Lu tc he r, LA
FD
Checker
06/17/2025 24-286
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
SECTION
1" = 1'-0"2
SECTION
1" = 1'-0"3DETAIL
1 1/2" = 1'-0"1
1 2
1' - 4"
1'
8"
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
TYP. @ 8 PLCS. THIS SIDE
COMPACTED SUBGRADE
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
EXISTING 8" CMU WALL
TOC EL. 3' - 4"
CONT. #3
CONT. #4
9"
2" 5 5/8" 1' - 4"
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
EXISTING FOUNDATION WALL
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
#3 @ 18" OC.
6" 5"
6" 6 1/4"
S-201
S-201
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
12" GRAVEL BED
VAPOR BARRIER
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO EXISTING WALL)
4" 2" 4"
1'
8"
TOC EL. 3' - 4"
(2) CONT. #4 @ 6" OC.
T&B
1' - 1 5/8" 2"
(3) #4 MID LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
(3) #5 BOTTOM LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
12" GRAVEL BED
VAPOR BARRIER
(2) #4 @ 18" OC.
S-201
G H
S-204
1 2
EXISTING 8" CMU WALL
TOC EL. 3' - 4"
CONT. #3
CONT. #4
9"
2" 5 5/8" 1' - 4"
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
EXISTING FOUNDATION WALL
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
#3 @ 18" OC.
5"
S-201
6" 6"
S-201
1' - 1"
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
12" GRAVEL BED
VAPOR BARRIER
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO EXISTING WALL)
4" 2" 4"
1'
8"
TOC EL. 3' - 4"
6"
1' - 4"
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
COMPACTED SUBGRADE
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
(2) CONT. #4 @ 6" OC.
T&B
1' - 1 5/8" 2"
12" GRAVEL BED
VAPOR BARRIER
(2) #4 @ 18" OC.
S-201
5" SLAB REINFORCING
9"
TOC EL. 3' - 4"
6"1' - 0"
6"
11"
G H
S-204
LIVI
C GNIREENIGNE
License No. 39038 JAMES R. LeBOUEF
ENGINEER
IN
TA
EOFLOUISIANAS
T
PROFESSIONAL
Jmcstamp.dwg 12297 44936
DATE:
SHEET NO:
DRAWN:
TH
O
M
PS
O N
L U
KE
A
SS
O C
IA
TE
S, L
.L .C
PH
O
N E
5-
3-
BA
TO
N R
O U
G E, L A
R
IE
G
ER
R O
AD
, S
U
IT
E
CHECKED:
TLA PROJECT NO:
S-202
W al k- In
C oo le r/F re ez er R ep la ce m en t
W M ai n
St re et Lu tc he r, LA
FD
Checker
06/17/2025 24-286
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
SECTION
1" = 1'-0"1
SECTION
1" = 1'-0"2
1 2G H
1' - 4"
1'
8"
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
TYP. @ 8 PLCS. THIS SIDE
COMPACTED SUBGRADE
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
EXISTING 8" CMU WALL
TOC EL. 3' - 4"
CONT. #3
CONT. #4
9"
2" 5 5/8" 1' - 4"
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
EXISTING FOUNDATION WALL
#3 @ 18" OC.
6" 5"
S-201
S-201
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
12" GRAVEL BED
VAPOR BARRIER
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO EXISTING WALL)
4" 2" 4"
1'
8"
TOC EL. 3' - 4"
1' - 1 5/8" 2"
(3) #4 MID LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
(3) #5 BOTTOM LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
12" GRAVEL BED
VAPOR BARRIER
(2) #4 @ 18" OC.
S-201
(3) #5 BOTTOM LAYER
GRADE BEAM REINFORCEMENT
SEE 2/S-203
EMBED REINFORCEMENT
TO EXISTING FOUNDATION
WALL W/ EPOXY
(MIN. 4" EMBED,
TYP. @ 8 PLCS. THIS SIDE)
(2) CONT. #4 @ 6" OC.
T&B
CONT. #4 BAR
EXISTING PEMB. COLUMN EXISTING PEMB. COLUMN
S-204
(3) #4 MID LAYER
GRADE BEAM
REINFORCEMENT
SEE 2/S-203
A B C
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
S-201
6"
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO
EXISTING WALL)
(2) CONT. #4 BARS @ 12" O.C.
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIER
EXISTING 4" SLAB
2' - 11 5/8"
3/4" EXPANSION JOINT
1'
8"
6"
1' - 8 5/8"
3/8" (3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO EXISTING WALL)
(2) CONT. #4 BARS
TOP LAYER
(EMBEDED AT END
TO EXISTING WALL)
CONT. #4 BAR
#4 @ 18" OC.
W/ 8" EMBED
SEE TYPICAL 4" SLAB DETAIL
FOR REINFORCEMENT
S-201
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
1' - 4" 9" 1' - 0" 6"
4" 1'
4"
TOC EL. 3' - 4"
1' - 4"
11' - 5 3/8"
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END
TO EXISTING WALL)
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO
EXISTING WALL)
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIER
1'
2" 6"
6" 1' - 0" 1' - 0" 6"
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
#4 @ 18" OC.
(2) CONT. #4 @ 6" OC.
T&B
8"
7 5/8"2"
2 3/8" 1 5/8"
1' - 0"6"
6"
1'
0"
S-201
SIM.
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIERTOC EL. 3' - 4" TOC EL. 3' - 4"
#4 @ 12" O.C.
LIVI
C GNIREENIGNE
License No. 39038 JAMES R. LeBOUEF
ENGINEER
IN
TA
EOFLOUISIANAS
T
PROFESSIONAL
Jmcstamp.dwg 12297 44936
DATE:
SHEET NO:
DRAWN:
TH
O
M
PS
O N
L U
KE
A
SS
O C
IA
TE
S, L
.L .C
PH
O
N E
5-
3-
BA
TO
N R
O U
G E, L A
R
IE
G
ER
R O
AD
, S
U
IT
E
CHECKED:
TLA PROJECT NO:
S-203
W al k- In
C oo le r/F re ez er R ep la ce m en t
W M ai n
St re et Lu tc he r, LA
FD
Checker
06/17/2025 24-286
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
SECTION
1" = 1'-0"1
SECTION
A B C
2' - 0"
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO
EXISTING WALL)
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIER
EXISTING 4" SLAB
3/4" EXPANSION JOINT
1'
8"
6"
1' - 8 5/8"
3/8"
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END TO EXISTING WALL)
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO EXISTING WALL)
(2) CONT. #4 BARS
TOP LAYER
(EMBEDED AT END
TO EXISTING WALL)
CONT. #4 BAR
#4 @ 18" OC.
W/ 8" EMBED
SEE TYPICAL 4" SLAB DETAIL
FOR REINFORCEMENT
S-201
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
TOC EL. 3' - 4"
6"
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
(3) CONT. #5 BARS
BOTTOM LAYER
(EMBEDED AT END
TO EXISTING WALL)
(3) CONT. #4 BARS
MID LAYER
(EMBEDED AT END TO
EXISTING WALL)
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIER
6"
6" 1' - 0" 1' - 0" 6"
SEE TYPICAL 5" SLAB DETAIL
FOR REINFORCEMENT
S-201
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
#4 @ 18" OC.
(2) CONT. #4 @ 6" OC.
T&B
8"
7 5/8"2"
2 3/8" 1 5/8"
1' - 0"6"
6"
1'
0"
S-201
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
COMPACTED SUBGRADE
12" GRAVEL BED
VAPOR BARRIERTOC EL. 3' - 4"
11 5/8"
6"
6"6"
TOC EL. 3' - 4"
1' - 9"
6"
SIM.
S-201
A C
2' - 0"
EXISTING 4" SLAB
3/4" EXPANSION JOINT
1'
8"
6"
1' - 8 5/8"
3/8"
CONT. #4 BAR
#4 @ 18" OC.
W/ 8" EMBED
12" GRAVEL BED
VAPOR BARRIER
COMPACTED SUBGRADE
TOC EL. 3' - 4"
(2) CONT. #4 @ 6" OC.
T&B
8"
7 5/8"2"
2 3/8" 1 5/8"
1'
0"
S-201
EXISTING 8" CMU WALL
EXISTING FOUNDATION WALL
COMPACTED SUBGRADE
12" GRAVEL BEDVAPOR BARRIER
11 5/8"
SIM.
S-201
(3) #5 BOTTOM LAYER
GRADE BEAM REINFORCEMENT
SEE 3/S-201
(3) #4 MID LAYER
GRADE BEAM REINFORCEMENT
SEE 3/S-201
EMBED REINFORCEMENT
TO EXISTING FOUNDATION WALL
W/ EPOXY (MIN. 4" EMBED)
TYP. @ 8 PLCS. THIS SIDE
LIVI
C GNIREENIGNE
License No. 39038 JAMES R. LeBOUEF
ENGINEER
IN
TA
EOFLOUISIANAS
T
PROFESSIONAL
Jmcstamp.dwg 12297 44936
DATE:
SHEET NO:
DRAWN:
TH
O
M
PS
O N
L U
KE
A
SS
O C
IA
TE
S, L
.L .C
PH
O
N E
5-
3-
BA
TO
N R
O U
G E, L A
R
IE
G
ER
R O
AD
, S
U
IT
E
CHECKED:
TLA PROJECT NO:
S-204
W al k- In
C oo le r/F re ez er R ep la ce m en t
W M ai n
St re et Lu tc he r, LA
FD
Checker
06/17/2025 24-286
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
SECTION
1" = 1'-0"1
SECTION
(-10°F)
EXISTING FREEZER
(906 SF)
(+35°F)
EXISTING COOLER
(274 SF)
WAREHOUSE
FOOD
SERVICE
OFFICE
OFFICE
4"x12"
TROUGH DRAIN
FLOOR DRAIN
4" DIA.
SLAB VENT
4" DIA.
SLAB VENT
4"x12"
TROUGH DRAIN
3" DIA.
BALLARD (TYP.)
SPRINKLER
SYS. ABOVE
THERMAL BREAK
THERMAL BREAK
** NOTE **
GENERAL CONTRACTOR RESPONSIBLE FOR DISCONNECTION,
DEMOLITION, AND REMOVAL OF ALL UTILITIES
ASSOCIATED WITH THE DEMOLITION WORK INDICATED ON
THIS DRAWING - REFER TO APPLICABLE ENGINEERING
DRAWINGS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS
ROOF OVERHANG/CANOPY ABOVE
2 2
EXISTING OVERHEAD
STRUCTURAL BEAM (TYP.)
RE: EL1/FS2.1
RAMP UP
RAISED
DOCK
RAISED CURB
1. DEMOLISH AND REMOVE EXISTING CHAIN LINK FENCE ENCLOSURE.
2. DEMOLISH AND REMOVE EXISTING REFRIGERATION UNITS AND ASSOCIATED COMPONENTS (REFRIGERANT
PIPING, EVAPORATOR COILS AT COOLER/FREEZER ROOMS, ETC.).
3. DEMOLISH AND REMOVE EXISTING WALK-IN COOLER/FREEZER ROOMS AND ASSOCIATED COMPONENTS (DOORS, LIGHT FIXTURES, SUSPENDED CEILING HARDWARE, ETC.).
4. DEMOLISH AND REMOVE FLOOR SYSTEM OF EXISTING WALK-IN COOLER/FREEZER ROOMS. RE: DETAIL
D1/THIS SHEET FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
5. DEMOLISH AND REMOVE EXISTING OFFICE (AND ASSOCIATED COMPONENTS) IN ITS ENTIRETY.
SHEET DEMOLITION KEYNOTES
NOTE: WORK LISTED BELOW IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR UNLESS NOTED OTHERWISE.
REMOVE EXISTING CONCRETE
FLOOR
SCALE: 3/4"=1'-0"
EXISTING CONDITIONS AND DEMOLITION REQUIREMENTS - EXISTING WALK-IN COOLER & FREEZERD1 REF:
REMOVE EXISTING FOAM SLAB
INSULATION, IF INSTALLED
REMOVE EXISTING THERMAL
BREAK(S)
EXISTING
RECESS
REMOVE EXISTING WALK-IN COOLER
AND FREEZER INSULATED PANELS
VERIFY
VERIFY
VERIFY
EXISTING CONCRETE SUB-FLOOR SHALL
BE MODIFIED TO MEET INDICATED
REQUIREMENTS OF NEW WALK-IN COOLER
& FREEZER (AS NEEDED) - BY GC
RE: DETAIL A/FS1.1
EXISTING GRAVEL
BED TO REMAIN
EXISTING PVC VENT/DRAIN
PIPE TO REMAIN
CENTERLINE
OF EXISTING
VENT PIPE
(VERIFY)
EXISTING BUILDING
FLOOR/CONCRETE SLAB
EXISTING WALK-IN COOLER & FREEZER DEMOLITION FLOOR PLAN1
SCALE: 1/4"=1'-0"
THOMPSON LUKE & ASSOCIATES
W al k- In
C oo le r/F re ez er R ep la ce m en t
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
W M ai n
St re et Lu tc he r, LA
Project Number:
Date:
Reviewed by:
24-286
June 17, 2025
GKF
THOMPSON LUKE &
ASSOCIATES
10705 Rieger Road, Suite 101 Baton Rouge, LA 70809
TEL. 225-293-9474
www.tlaeng.com
NO. DESCRIPTION DATE
Drawn by: CJT
Contract Documents
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated used or disclosed without written consent of engineer. Do not scale drawings. Use given dimensions only. If not shown, verify correct dimensions with the engineer. Contractor shall check and verify all dimensions and conditions at job site. Any and all quantities which are included within this material are approximate and for estimating purposes only. Contractor shall be responsible for verifying actual quantities when constructing project.
6/
/2
4:
:5
PM
G :\P
R O
JE
C
TS
\1
0\
St
J am es S ch oo l B oa rd W ar eh ou se
\D ra w in gs \1
3-
SJ
PS
B C
D
BI
D
S
ET
5.
dw g
EXISTING WALK-IN COOLER &
FREEZER DEMOLITION PLAN
FS1.0
FREEZER
(906 SF)
(+35°F)
COOLER
(446 SF)
WAREHOUSE
FOOD
SERVICE
OFFICE
RAMP UP
RAISED
DOCK
RAISED CURB
31'-8"
29'-11"
24'-8"
19'-3"
60"W x 78"H
HINGED
DOOR
60"W x 78"H
HINGED
DOOR
B
FS2.1
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHT
B
FS2.1
A
B
B
A
B
B
C
C
G (TYPICAL)
G (TYPICAL)
H
H
H
H
D
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHT
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHT
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHT
(REAR)
AIR FLOWAIR FLOW
AIR FLOWAIR FLOW
NEW CHAIN LINK FENCE
ENCLOSURE WITH 13'-0" LONG
MINIMUM GATED SECTION - BY GC2
EXISTING OVERHEAD
STRUCTURAL BEAM (TYP.)
RE: EL1/FS2.1
EL1
FS2.1
E
E
FREEZER SYSTEM "A"
FREEZER SYSTEM "B"
FREEZER SYSTEM "A"
FREEZER SYSTEM "B"
F
2"
2"
2"
D
FS1.1
A
FS1.1
D
FS2.1
C
FS2.1
LEGEND:
A. DIVISION 11 (FOOD SERVICE EQUIPMENT) - CONTRACTOR FURNISHED AND INSTALLED
B. BY OTHER DIVISIONS (AS INDICATED)
C. NOT IN CONTRACT (BY OTHERS, VENDOR, ETC.)
FOOD SERVICE EQUIPMENT SCHEDULE
DESCRIPTIONQTY.
1. 1 WALK-IN COOLER/FREEZER A
2. 1 REMOTE REFRIGERATION SYSTEM A
3. 38 STORAGE PALLETS (BY OWNER/VENDOR) C
ITEM
NO.
EQUIP.
CLASS.
A. EXISTING 4" DIAMETER PVC SLAB VENT TO REMAIN FOR REUSE.
B. EXISTING 3" DIAMETER CONCRETE BOLLARDS TO REMAIN FOR REUSE.
C. EXISTING 4" X 12" FLOOR DRAIN TROUGH TO REMAIN FOR REUSE.
D. STAINLESS STEEL TRIM (PART OF ITEM NO. 1).
E. HEATED PRESSURE RELIEF PORT (PART OF ITEM NO. 1) WITHIN INSULATED WALL PANELS.
EXACT QUANTITY AND LOCATIONS SHALL BE DETERMINED BY WALK-IN UNIT MANUFACTURER.
F. SPECIFIED REMOTE REFRIGERATION SYSTEM INCLUDES TWO (2) COMPRESSORS (SYSTEM "A" & SYSTEM "B") FOR THE FREEZER ROOM, EACH SUPPORTING TWO (2) EVAPORATOR COILS. INSTALL
EVAPORATOR COILS FOR EACH SYSTEM AS INDICATED ON FLOOR PLAN.
G. 6" X 6" CONCRETE CURBS - BY GENERAL CONTRACTOR (GC).
H. NEW 6" DIAMETER CONCRETE FILLED BOLLARD - BY GENERAL CONTRACTOR (GC).
SHEET KEYNOTES.
NOTE: ITEMS LISTED BELOW ARE THE RESPONSIBILITY OF DIVISION 11 UNLESS NOTED OTHERWISE.
4"
4"
1"
10'-0"
FINISHED
FLOOR TO TOP
OF WALK-IN
PANELS
10'-8" O.A.
CLR/FZR
PANELS
9'-8"
INTERIOR
HEIGHT
9"
RECESS
12" MINIMUM
(VERIFY)
18" ℄
MINIMUM
(VERIFY)
5" MIN.
(VERIFY)
EXISTING GRAVEL
BED TO REMAIN
EXISTING
VENT/DRAIN PIPE
TO REMAIN (AT
FREEZER ONLY)
EXISTING BUILDING
FLOOR/CONCRETE
SLAB
INSULATED WALL AND
CEILING PANELS
SEALED REINFORCED CONCRETE
FLOOR (4,000 PSI) - BY GC
6"
6"
SEALED CONCRETE CURB
W/SLOPED TOP AND REBAR
ANCHORS - BY GC
CAULKING OR CONCRETE
FILL - BY GC
EXISTING/MODIFIED CONCRETE
SLAB/SUB-FLOOR TO MEET INDICATED
REQUIREMENTS - BY GC
6 MIL THICK POLYETHYLENE SHEETS
AND SEALED JOINTS (DIVISION 11)
SELF-LEVELING GROUT FILL
(DIVISION 11)
INSULATED FLOOR PANEL
(DIVISION 11)
NEW WALK-IN COOLER & FREEZER FLOOR PLAN1
SCALE: 1/4"=1'-0"
THOMPSON LUKE & ASSOCIATES
W al k- In
C oo le r/F re ez er R ep la ce m en t
St . J am es
P ar is h
Sc ho ol B oa rd
W ar eh ou se
W M ai n
St re et Lu tc he r, LA
Project Number:
Date:
Reviewed by:
24-286
June 17, 2025
GKF
THOMPSON LUKE &
ASSOCIATES
10705 Rieger Road, Suite 101 Baton Rouge, LA 70809
TEL. 225-293-9474
www.tlaeng.com
NO. DESCRIPTION DATE
Drawn by: CJT
Contract Documents
All drawings and written material appearing herein constitute original and unpublished work of the engineer and may not be duplicated used or disclosed without written consent of engineer. Do not scale drawings. Use given dimensions only. If not shown, verify correct dimensions with the engineer. Contractor shall check and verify all dimensions and conditions at job site. Any and all quantities which are included within this material are approximate and for estimating purposes only. Contractor shall be responsible for verifying actual quantities when constructing project.
6/
/2
4:
:5
PM
G :\P
R O
JE
C
TS
\1
0\
St
J am es S ch oo l B oa rd W ar eh ou se
\D ra w in gs \1
3-
SJ
PS
B C
D
BI
D
S
ET
5.
dw g
FOOD SERVICE EQUIPMENT
FLOOR PLAN
FS1.1
(906 SF)
(+35°F)
COOLER
(446 SF)
WAREHOUSE
FOOD
SERVICE
OFFICE
RAMP UP
RAISED
DOCK
RAISED CURB
31'-8"
29'-11"
24'-8"
19'-3"
10 GA. HEATED S/S THRESHOLD
W/INSULATED SILL BELOW
(FOR THERMAL BREAK)
4"
4"
WALL-MOUNTED
LED LIGHT
FIXTURE
EXISTING/MODIFIED CONCRETE
SLAB/SUB-FLOOR - BY GC
RE: DETAIL A/FS1.1
CAULKING OR CONCRETE
FILL - BY GC
POSITIVE-
ACTION
HYDRAULIC
DOOR CLOSER
LOCKING LATCH
W/INSIDE
SAFETY RELEASE
36" HIGH 1/8" ALUMINUM
DIAMOND TREADPLATE ON
INTERIOR/EXTERIOR OF
DOOR AND DOOR SECTION
EXISTING BUILDING
CONCRETE FLOOR
6 MIL THICK POLYETHYLENE SHEETS
AND SEALED JOINTS (DIVISION 11)
SELF-LEVELING GROUT FILL
(DIVISION 11)
INSULATED FLOOR PANEL
(DIVISION 11)
INSULATED WALL AND
CEILING PANELS
SCALE: 3/4"=1'-0"
WALK-IN COOLER & FREEZER - AT DOOR SECTIONSB REF: FS1.1
1"
10'-0"
TOP OF
CLR/FZR
PANELS
60"W x 78"H
HINGED
DOOR
60"W x 78"H
HINGED
DOOR
9'-8"
INTERIOR
HEIGHT
B
FS2.1
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHT
B
FS2.1
LEGEND:
A. DIVISION 11 (FOOD SERVICE EQUIPMENT) - CONTRACTOR FURNISHED AND INSTALLED
B. BY OTHER DIVISIONS (AS INDICATED)
C. NOT IN CONTRACT (BY OTHERS, VENDOR, ETC.)
FOOD SERVICE EQUIPMENT SCHEDULE
DESCRIPTIONQTY.
1. 1 WALK-IN COOLER/FREEZER A
2. 1 REMOTE REFRIGERATION SYSTEM A
3. 38 STORAGE PALLETS (BY OWNER/VENDOR) C
ITEM
NO.
EQUIP.
CLASS.
A. EXISTING 4" DIAMETER PVC SLAB VENT TO REMAIN FOR REUSE.
B. EXISTING 3" DIAMETER CONCRETE BOLLARDS TO REMAIN FOR REUSE.
C. EXISTING 4" X 12" FLOOR DRAIN TROUGH TO REMAIN FOR REUSE.
D. STAINLESS STEEL TRIM (PART OF ITEM NO. 1).
E. HEATED PRESSURE RELIEF PORT (PART OF ITEM NO. 1) WITHIN INSULATED WALL PANELS.
EXACT QUANTITY AND LOCATIONS SHALL BE DETERMINED BY WALK-IN UNIT MANUFACTURER.
F. SPECIFIED REMOTE REFRIGERATION SYSTEM INCLUDES TWO (2) COMPRESSORS (SYSTEM "A" & SYSTEM "B") FOR THE FREEZER ROOM, EACH SUPPORTING TWO (2) EVAPORATOR COILS. INSTALL
EVAPORATOR COILS FOR EACH SYSTEM AS INDICATED ON FLOOR PLAN.
G. 6" X 6" CONCRETE CURBS - BY GENERAL CONTRACTOR (GC).
H. NEW 6" DIAMETER CONCRETE FILLED BOLLARD - BY GENERAL CONTRACTOR (GC).
SHEET KEYNOTES.
NOTE: ITEMS LISTED BELOW ARE THE RESPONSIBILITY OF DIVISION 11 UNLESS NOTED OTHERWISE.
J
J
J
J
J
J
J
J
J
J
E-3
E-1
E-5
E-4
E-2
E-2
J E-6
1'-10"
55'-1"
1'-2"
32'-0"
30'-3"
24'-10"
19'-7"12'-5"
P-1 1 3/4" TYPE "L" COPPER CONDENSATE DRAIN LINE FROM COOLER ROOM EVAPORATOR
COILS TO FLOOR DRAIN 2,3
P-2 1 3/4" TYPE "L" COPPER CONDENSATE DRAIN LINE FROM FREEZER ROOM EVAPORATOR
COILS TO FLOOR DRAIN 2,3
P-3 1 FLOOR DRAIN FOR NEW CONDENSATE DRAIN LINE OF COOLER/FREEZER
EVAPORATOR COILS
P-4 -- FLOOR DRAIN TROUGH
PLUMBING ROUGH-IN DATA SCHEDULE
CONN.
NO.
ITEM
NO. DESCRIPTION OF UTILITY REQUIREMENTS NOTES
A
B
B
A
B
B
C
C
G (TYPICAL)
G (TYPICAL)
H
H
H
H
D
SCALE: NONE
COOLER/FREEZER LIGHT FIXTURE INSTALLATIOND7
FILL CONDUIT WITH FOAM URETHANE SEALANT
TO PREVENT CONDENSATION WITHIN LIGHT
FIXTURES (TYP.)
SEAL ALL PENETRATIONS WITH
USDA APPROVED SEALANT (TYP.)
WALL AND CEILING MOUNTED LIGHT FIXTURES
ABOVE WALK-IN CEILING PANEL
TMP MD B W DOORR
TEMPERATURE
PROBE
MOTION
SENSOR
(MD-1)
Y
B W R Y
MAGNETIC
DOOR
CONTACT
(MC-1)
TEMPERATURE
ALARM SYSTEM
PANEL (75LC)
LIGHTED
PANIC
BUTTON
(IP-1)
DOOR WITHIN EACH ROOM
BUILDING
POWER SUPPLY
120 VAC
A B C ABOVE CEILING PANEL
SCALE: NONE
WALK-IN COOLER/FREEZER TEMPERATURE ALARM & LIGHT CONTROL SYSTEM WIRING DIAGRAMD8
FIELD WIRING (BY CONTRACTOR)
PRE-WIRED (BY MANUFACTURER)
A. 120-VOLT CONTROL WIRING FOR TEMPERATURE
ALARM SYSTEM PANEL (75LC). LIGHTING RELAY
RATED FOR 8.3A @120V.
B. 22 AWG LOW VOLTAGE CONTROL WIRING FOR
MOTION SENSOR(S) (MD-1).
C. 22 AWG LOW VOLTAGE CONTROL WIRING FOR
LIGHTED PANIC BUTTON(S) (IP-1).
D. 22 AWG LOW VOLTAGE CONTROL WIRING FOR
MAGNETIC DOOR CONTACT(S) (MC-1).
E. 25' LONG MANUFACTURER FURNISHED
TEMPERATURE PROBE/WIRE ASSEMBLY.
WIRING DIAGRAM KEYNOTES
LEGEND
A
E
B D
C
NOTE:
REFER TO
MANUFACTURER
AS-BUILT WIRING
DIAGRAMS FOR
ADDITIONAL
INFORMATION
SCALE: NONE
REFRIGERANT LINE INSULATION & JACKETINGD4 REF:
LIQUID LINE
SUCTION LINE
SEALED INSULATION JOINT
(AS APPLICABLE)
0.016" THICK TYPE 3003-H14 ALUMINUM
ALLOY SELF-FASTENING JACKETING FOR
PROTECTION OF ALL EXTERIOR (OUTDOOR)
REFRIGERANT LINES
SEALED ALUMINUM
JACKETING JOINT
(AS APPLICABLE)
AP/ARMAFLEX INSULATION
A
A
B
C
D
E
DETAIL KEYNOTES
A. ALL REFRIGERANT LINES SHALL BE RIGID REFRIGERANT GRADE TYPE "L" COPPER.
B. ALL REFRIGERANT LINES SUBJECT TO SWEATING SHALL BE FULLY INSULATED WITH
AP/ARMAFLEX AS FOLLOWS:
- 3/4" (MINIMUM) FOR COOLER LINES; 1-1/2" FOR POORLY-VENTILATED AREAS.
- 1" (MINIMUM) FOR FREEZER LINES; 2" FOR POORLY-VENTILATED AREAS.
C. ALL JOINTS SHALL BE SEALED WITH GLUE IN ACCORDANCE WITH INSULATION MANUFACTURER'S
RECOMMENDATIONS. DUCT TAPE AT JOINTS IS NOT ACCEPTABLE.
D. FURNISH AND INSTALL MATCHING ALUMINUM JACKETING ELBOW COVERS AT ALL EXTERIOR
(OUTDOOR) REFRIGERANT PIPING ANGLES AND BENDS.
E. FURNISH AND INSTALL MATCHING ALUMINUM JACKETING STRAPPING AND SEALS AT ALL JOINTS
IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
BUILDING WALL/ROOF, CONCRETE SLAB, OR
INSULATED WALL/CEILING PANEL OF WALK-IN
COOLER AND/OR FREEZER (AS APPLICABLE)
INSULATED REFRIGERANT LINE
RE: DETAIL D2/FS1.01
THREADED ROD,
UNI-STRUT/HARDWARE
UNI-STRUT/HARDWARE
C
A
. DETAIL KEYNOTES
A. MOUNTING TO INSULATED CEILING PANELS NOT ALLOWED FOR OUTDOOR COOLER/FREEZER INSTALLATIONS AND SHALL BE AVOIDED WHENEVER POSSIBLE FOR INDOOR INSTALLATIONS. WHEN MOUNTING TO INSULATED WALL OR CEILING PANELS, HARDWARE SHALL NOT PENETRATE MORE THAN HALFWAY THROUGH PANEL DEPTH -- PENETRATIONS SHALL BE FILLED AND SEALED WITH USDA GRADE SILICONE TO PREVENT
MOISTURE INTRUSION.
B. BUILDING ROOF PENETRATIONS SHALL BE FILLED AND SEALED UTILIZING BEST INDUSTRY PRACTICES AND
IN ACCORDANCE WITH LOCAL BUILDING CODES.
C. STANDARD PIPE CLAMPS MAY BE UTILIZED ON OUTDOOR ALUMINUM-JACKETED AND INSULATED REFRIGERANT
LINES.
D. HARDWARE (NUTS, BOLTS) SHOWN FOR REFERENCE ONLY. FURNISH AND INSTALL NECESSARY STAINLESS STEEL HARDWARE IN A WORKMANLIKE MANNER AND IN COMPLIANCE WITH LOCAL BUILDING CODES TO MEET
PROJECT REQUIREMENTS.
D
SCALE: NONE
REFRIGERANT LINE SUPPORTD5 REF:
B
SURFACE-MOUNTED INSTALLATION
SUSPENDED INSTALLATION
PIPE CLAMP W/INTEGRAL
THERMOPLASTIC ELASTOMER CUSHION
INSTALLED OVER INSULATION
OVERHEAD
STRUCTURAL
CEILING
AND/OR
SUPPORT
D
P-3
P-2
P-2
P-1
P-1
J E-5
J E-5
J E-5
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHTJ
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHTJ
48" CEILING LIGHT48" CEILING LIGHT48" CEILING LIGHT 48" CEILING LIGHT48" CEILING LIGHTJ
4"
4"
CAULKING OR CONCRETE
FILL - BY GC
SCALE: 3/4"=1'-0"
WALK-IN COOLER & FREEZER - AT ADJACENT WALLSC REF: FS1.1
1"
COOLER
(+35°F)
FREEZER
(-10°F)
4"
4"
1"
SCALE: 3/4"=1'-0"
WALK-IN COOLER & FREEZER - AT BUILDING WALLSD REF: FS1.1
4"
4"
1"
WALL
PANEL
CEILING
PANEL
HANGER PLATE W/ 3/8" X 1 1/2"
BOLT W/ NUT & LOCK WASHER
1/4" x 2 1/2" x 2 1/2"
ALUM. SUPPORT ANGLE
NOTE:
FURNISH AND INSTALL ALL HARDWARE (SUPPORT ANGLE(S)/UNISTRUT,
TURNBUCKLES, THREADED HANGER RODS, AND NUTS/WASHERS) - DIVISION 11.
TO
STRUCTURE
SUPPORT
ABOVE
BRIDGING UNISTRUT OR ANGLE
(IF BUILDING STRUCTURAL SUPPORT
IS NOT LOCATED DIRECTLY ABOVE)
**ALL SUPPORTS AND THREADED
HANGERS MUST BE INSTALLED LEVEL**
TO
STRUCTURE
SUPPORT
ABOVE
SCALE: NONE
WALK-IN COOLER/FREEZER SUSPENDED CEILING INSTALLATION DETAILD2 REF: FS101
HANGER
PLATE
3/8" ALL-
THREAD ROD
EYE
TURNBUCKLE
SUPPORT
ANGLE
THE LOCKED
CAMLOCK HOLDS
THE HANGER
PLATE IN PLACE
@ THE PANEL
JOINT
FROM TOP OF CEILING
PANEL TO TOP OF
TURNBUCKLE
3/8" ALL-
THREAD ROD
VER
IFY
W/M
ANF
VER
IFY
W/M
ANF
VER
IFY
W/M
ANF
BOTTOM OF RECESS
9" BELOW FINISHED FLOOR
EXISTING FINISHED FLOOR
10'-0" A.F.F.
T.O.COOLER/FREEZER
14'-0" A.F.F.
BOTTOM OF BEAM (MAX.)
11'-8" A.F.F.
BOTTOM OF BEAM (MIN.)
20 GA. STAINLESS
STEEL DOOR AND DOOR
FRAME WALL PANELS
(EXTERIOR/INTERIOR)
BOTTOM OF RECESS
9" BELOW FINISHED FLOOR
EXISTING FINISHED FLOOR
10'-0" A.F.F.
T.O.COOLER/FREEZER
14'-0" A.F.F.
BOTTOM OF BEAM (MAX.)
11'-8" A.F.F.
BOTTOM OF BEAM (MIN.)
SCALE: 3/4"=1'-0"
ELEVATION DETAIL - WALK-IN COOLER & FREEZEREL1 REF:
EXISTING STRUCTURAL
BEAM AND COLUMN
NEW COOLER
(+35°F)
NEW FREEZER
(-10°F)
EXISTING ROOF AND
SUPPORT BEAMS
EXISTING GUTTER
(TYPICAL)
(REAR)
AIR FLOWAIR FLOW
AIR FLOWAIR FLOW
67"
120" HOUSING
(120 1/4" W/FEET)
42"
12"
40" HOUSING
(43 1/4" W/FEET)
VER"
36"
SCALE: NONE
REMOTE COOLER & FREEZER REFRIGERATION SYSTEM - INSTALLATION AND CLEARANCES DETAILD3 REF: FS101
GENERAL DETAIL NOTES
1. REFRIGERATION RACK WEIGHT = 3,250 LBS.. NOTE: UNIT WILL BE TOP HEAVY.
2. REFRIGERATION SYSTEM SPECIFIED INCLUDES:
* CRANKCASE HEATERS * (2) 5-PORT NETWORK SWITCH (RE: FS4.1 AND FS4.2)
* FAN CYCLING SWITCHES * BOTTOM RIGHT (2) COMPARTMENTS WILL BE EMPTY
* PHASE LOSS MONITOR
3. EXACT SIZE AND QUANTITY OF REFRIGERANT LINES (NOT SHOWN) REQUIRED ARE PROJECT SPECIFIC AND SHALL BE VERIFIED. ROUTING OF NEW REFRIGERANT LINES SHALL FOLLOW EXISTING LINES WHERE POSSIBLE. REFER TO DETAILS D4 & D5 ON THIS SHEET FOR ADDITIONAL REQUIREMENTS.
4. NEW AND/OR MODIFIED EXISTING BUILDING PENETRATIONS FOR THE INSTALLTION OF THE NEW REFRIGERANT LINES (DIVISION 11) SHALL BE PROVIDED AND SEALED BY THE GENERAL
CONTRACTOR.
5. EXISTING CHAIN LINK FENCE ENCLOSURE (NOT SHOWN) TO BE MODIFIED OR REPLACED BY GENERAL CONTRACTOR TO ACCOMMODATE NEW REFRIGERATION UNIT AND INDICATED CLEARANCE
REQUIREMENTS.
EXISTING RAMP,
DOCK, AND
RAILING
EXTERIOR
BUILDING WALL
EXISTING RAISED
CURB/WALKWAY
EXISTING PARKING
LOT
MAIN, NON-FUSED
DISCONNECT
ELECTRICAL CONTROL
PANEL ACCESS
ALL STAINLESS
STEEL HOUSING
STAINLESS STEEL
LIFT-OUT LOUVERS
NEW CHAIN LINK FENCE
ENCLOSURE WITH 13'-0" LONG
MINIMUM GATED SECTION - BY GC2
EXISTING OVERHEAD
STRUCTURAL BEAM (TYP.)
RE: EL1/FS2.1
EL1
FS2.1
E
E
FREEZER SYSTEM "A"
FREEZER SYSTEM "B"
FREEZER SYSTEM "A"
FREEZER SYSTEM "B"
F
NETWORK SWITCH
PROVIDED BY
MANUFACTURER
NOTE: EACH EVAPORATOR EQUIPPED WITH A CONTROLLER PROVIDED
PRE-MOUNTED TO HOUSING OF EVAPORATOR ASSEMBLY.
WIRING SCHEDULE FOR ELECTRICAL CONTRACTOR REQUIREMENTS:
· EACH COIL REQUIRES (3) 115V 12AWG MIN. TO PROVIDE HOUSE
POWER TO THE COIL (HOT, NEUTRAL, GROUND).
· ALL COILS IN THE SAME ROOM MUST BE BONDED TO EACH OTHER
AND CONNECTED TO DATA SWITCH.
CAT5/6e CABLE (ETHERNET)
PROVIDED BY G.C. FOR
INTERCONNECTIVITY FROM
CONTROLLER TO SWITCH
GROUNDDISCONNECT SWITCH
(LOCATED ON COIL)
120V/1PH/60HZ
SUPPLIED BY HOUSE
H N G
VOLTAGEDESCRIPTIONSYS
*REFERENCE ROUGH-IN SCHEDULE FOR COIL AMP DRAW.
FOR OPTIONAL MONITORING
CONNECTIVITY
CAT5/6e CABLE (ETHERNET)
PROVIDED BY G.C. FOR
INTERCONNECTIVITY TO
BUILDING NETWORK SYSTEM
CAT5/6e CABLE (ETHERNET)
PROVIDED BY G.C. FOR
INTERCONNECTIVITY FROM
CONTROLLER TO SWITCH
ITEM COIL #DESCRIPTIONPORT #
5 - -LAN IF REQUIRED
ITEM COIL #DESCRIPTIONPORT #
5 - -LAN IF REQUIRED
VOLTAGEDESCRIPTIONSYS
2 POLE
DISCONNECT SWITCH
(LOCATED ON COIL)
GROUND
L1 L2 G
115/1WALK-IN COOLERA
115/1WALK-IN COOLERA
B1 WALK-IN FREEZER 208/1
B1 WALK-IN FREEZER 208/1
B2 WALK-IN FREEZER 208/1
B2 WALK-IN FREEZER 208/1
PORTS FOR VISUAL ONLY.
SEE REFRIGERATION
NETWORK SWITCH TABLE(S)
FOR PORT/COIL
ASSIGNMENT.
A WALK-IN COOLER 1
A WALK-IN COOLER 2
B1 WALK-IN FREEZER 1
B1 WALK-IN FREEZER 2
B2 WALK-IN FREEZER 3
B2 WALK-IN FREEZER 4
FIELD WIRING (BY ELECTRICAL CONTRACTOR)
PRE-WIRED (BY MANUFACTURER)
SCALE: NONE
REMOTE REFRIGERATION SYSTEM EVAPORATOR COILS ELECTRICAL AND DATA WIRING DIAGRAMSD9
WIRING DIAGRAM - ECO-SMART DEMAND DEFROST
CONTROLLERS FOR WALK-IN COOLER WITH MULTIPLE COILS
EVAPORATOR COIL
SUPPLIED BY HOUSE
120V POWER OUTLET
NEMA 5-15R
REFRIGERATION NETWORK SWITCH TABLE
SWITCH 1
REFRIGERATION NETWORK SWITCH TABLE
SWITCH 2
WIRING DIAGRAM - EVAPORATOR COILS NETWORK
DATA AND COMPONENTS
WIRING DIAGRAM - ECO-SMART DEMAND DEFROST
CONTROLLER FOR WALK-IN FREEZER WITH MULTIPLE COILS
NOTE: EACH EVAPORATOR EQUIPPED WITH A CONTROLLER PROVIDED
PRE-MOUNTED TO HOUSING OF EVAPORATOR ASSEMBLY.
WIRING SCHEDULE FOR ELECTRICAL CONTRACTOR REQUIREMENTS:
· EACH COIL REQUIRES (3) 208V (AWG SIZE ACCORDING TO
HEATER LOAD AND LOCAL CODE) TO PROVIDE HOUSE POWER TO
THE COIL (L1, L2 AND GROUND).
· ALL COILS IN THE SAME ROOM MUST BE BONDED TO EACH OTHER
AND CONNECTED TO DATA SWITCH.
FIELD WIRING (BY ELECTRICAL CONTRACTOR)
PRE-WIRED (BY MANUFACTURER)
EVAPORATOR COIL
*REFERENCE ROUGH-IN SCHEDULE FOR COIL AMP DRAW.
208-230V/1PH/60HZ
SUPPLIED BY HOUSE
1. ROUGH-IN PLAN SHOWS APPROXIMATE LOCATIONS FOR UTILITY REQUIREMENTS OF FOOD SERVICE EQUIPMENT SPECIFIED (INCLUDING EXISTING AND FUTURE EQUIPMENT) PLUS ELECTRICAL CONVENIENCE OUTLETS.
CONTRACTOR SHALL FURNISH DIMENSIONED LOCATIONS FROM FINISHED WALLS AND/OR CENTER-LINE OF
COLUMNS FOR ALL UTILITIES SHOWN ON CONTRACT DOCUMENT ROUGH-IN DRAWINGS.
2. WHERE POSSIBLE, ALL ELECTRICAL CONDUIT/WIRING SHALL BE EXTENDED UP THROUGH AND OUT OF
BUILDING WALLS.
3. EXTEND AND CONNECT WIRING FROM JUNCTION BOXES TO CONNECTION POINTS ON FOOD SERVICE EQUIPMENT -
DIVISION 26.
4. WALL-MOUNTED JUNCTION BOXES SHALL BE RECESSED IN BUILDING WALL SO THAT EQUIPMENT CAN BE
INSTALLED AGAINST WALLS.
5. FURNISH AND INSTALL ALL NECESSARY LINE DISCONNECT SWITCHES, UNLESS SPECIFIED OTHERWISE -
DIVISION 26.
6. FURNISH AND INSTALL CONDUIT, JUNCTION BOXES, AND FIELD WIRING FOR COILS, CEILING-MOUNTED LIGHT FIXTURES, PRESSURE RELIEF PORTS, AND FREEZER DRAIN LINE HEATERS (FURNISHED BY DIVISION
11) OF WALK-IN COOLERS/AND FREEZERS - DIVISION 26.
7. HORIZONTAL RUNS OF CONDUIT FOR CEILING-MOUNTED LIGHT FIXTURES SHALL BE MOUNTED ON TOP OF
WALK-IN CEILING PANELS - DIVISION 26.
8. ELECTRICAL CONDUIT WITHIN WALK-IN SHALL BE FILLED (INSIDE CONDUIT) WITH FOAM URETHANE TO
PREVENT CONDENSATION - DIVISION 26.
9. PENETRATIONS OF WALK-IN CEILING/WALL PANELS SHALL BE SEALED WITH USDA-APPROVED SEALANT.
10. FURNISH AND INSTALL JUNCTION BOX ON TOP OF WALK-IN COOLER/FREEZER FOR POWER SOURCE OF TEMPERATURE ALARM SYSTEM…