The contractor is responsible for providing all equipment and labor necessary to offload the compressor from the delivery truck, lower it into the basement well, transport it through the mechanical room, and position it on the installation pad. No forklift is available for use due to space constraints in the mechanical room. The contractor must supply all electrical wiring and equipment to connect the compressor to the existing electrical disconnect switch on the wall, with the government providing prior installation of equipment up to the disconnect switch. Additionally, the contractor must provide all necessary piping, fittings, and connections to integrate the compressor with the building's air system and cooling water supply, which are located adjacent to the pad. The cooling water temperature specification is 48 ± 2 degrees Fahrenheit. Picture requests from potential bidders include images of the crane area, measurements along the path to the pad area, and photographs of the electrical box's exterior and interior to determine wire size requirements. All installation requirements are detailed in section 3.2 of the Statement of Work.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C26-015 High Pressure Air Compressor Questions:
1. Is there a forklift that can be used to install the air compressors?
No. The contractor must provide all equipment necessary to offload the compressor from the truck, lower the compressor into the well at basement level, and move compressor through mechanical room and onto the pad where it will be installed. There is not enough room in the mechanical room for a forklift.
See section 3.2 of the Statement of Work.
2. Is additional wiring or piping needed?
Yes. See section 3.2 of Statement of Work.
Contractor must provide all necessary electrical equipment to connect compressor to electrical disconnect switch on the wall. Government will ensure the proper electrical equipment is installed up to the electrical disconnect switch prior to contractor installation work. See photo.
Contractor must provide all necessary piping, fittings, etc. to connect compressor to building air system and cooling water. These connections are next to the pad, see photo.
3. What is the water temperature for the air compressor?
Cooling water is 48 ± 2 degrees F
4. Does wiring from the disconnect switch require electrical?
See answer to question 2.
Picture Request Questions:
1. Need pictures of crane area
2. Need measurements from the path to pad area
3. Need pictures of the outside and inside of the electrical box, needing wire size