This Scope of Work document outlines the specifications for an annual elevator maintenance contract with Hurst Euless Bedford Independent School District (HEB ISD) in Texas. The contract requires vendors to provide routine maintenance, corrective repairs, emergency services, and annual inspections for all elevators and chairlifts operated by the district. The successful vendor must employ trained, qualified technicians holding a current State of Texas Elevator License and a Qualified Elevator Inspector (QEI-1) Certification from the American Society of Mechanical Engineers (ASME). Services are to be provided during regular working hours of Monday through Wednesday, 7:00 am to 5:00 pm, and Thursday through Friday, 7:00 am to 10:00 pm, with the vendor required to respond to service calls within two hours of receipt. The contract includes monthly preventive maintenance for geared, gearless, and hydraulic elevator systems with specific task lists; quarterly inspections; semi-annual electrical checks; and annual comprehensive maintenance including brake shoe replacement, oil flushing, full load governor testing, and backup battery replacement every three years. Monthly firefighter Phase I and Phase II recall tests must be performed in compliance with NFPA 101 standards and ASME A17.1/CSA B44 requirements. Annual inspections by Texas Department of Licensing and Regulation-registered inspectors are mandatory, with all work adhering to applicable Texas Administrative Code Chapter 74 standards.
Pricing shall be provided on a per-location basis with separate hourly rates quoted for after-hours emergency services and overtime work. All repair quotes for non-maintenance work discovered during inspections require itemized pricing, and vendors must submit monthly performance reports for each elevator and comprehensive six-month written reports to the district. The vendor is responsible for programming all in-car emergency phones, providing a compatible iPhone application for service request monitoring, and maintaining monthly service logs documenting firefighter checks. The district reserves the right to terminate the agreement for breach of contract, poor performance, maintenance neglect, misconduct, non-appropriation of funds, or for convenience. Vendors must comply with the district's tobacco-free, drug-free, weapon-free, and alcohol-free campus policies and complete security screening procedures. The contract term and renewal options are not specified in this scope document, though the agreement is described as annual with ongoing performance monitoring through field audits and supervisory reviews.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP #26-13
Elevator Maintenance
Scope of Work
The intent of this specification is to establish an annual contract for required elevator maintenance, repair, and annual inspections of Hurst Euless Bedford Independent School District elevators listed herein. The successful vendor shall provide routine maintenance, corrective repair and emergency service, as well as annual inspections to all the listed elevators and lifts.
The awarded vendor shall supply trained, qualified, and technically skilled employees who have a State of Texas license to provide services and /or inspection.
- In addition to a copy of the State of Texas Elevator License(s) submitted, a copy of the Inspector’s current QEI-1 (Qualified Elevator Inspector) Certification issued through the American Society of Mechanical Engineers (ASME) will also be required.
The awarded vendor shall maintain elevator rides with smooth acceleration, retardation, and soft stops. Door operation shall be quiet and positive with smooth checking when traveling.
1. ON SITE RULES
- All campus visitors, including elevator technicians and/or repair persons, must complete a security screening in the campus office. Visitors are required to present a valid driver’s license to receive a RAPTOR visitor badge.
- A representative from Maintenance must be present to escort service -technicians before entering a campus. Primary phone number for Maintenance is 817-399-2403 with a secondary number 817-399-2400.
- The DISTRICT is a tobacco-free, drug-free, weapon-free and alcohol-free environment. It is the responsibility of the VENDOR to ensure that its employees, agents, and subcontractors are not under the influence of drugs or alcohol and/or in possession of drugs, tobacco, alcohol, or weapons. If an employee, agent, or subcontractor of VENDOR is found to be under the influence and/or in possession of drugs/tobacco, alcohol, or weapons at the time of service, the VENDOR will be notified at once by DISTRICT that the individual(s) must be immediately restricted from all DISTRICT campuses/departments. Repeated offenses by VENDOR could result in contract termination for default.
2. APPLICABLE CODES AND COMPLIANCE
Unless noted otherwise, all work and inspections shall strictly adhere to:
- Administrative Rules of the Texas Department of Licensing and Regulation 16 Texas Administrative code, Chapter 74, Elevators, escalators, and related equipment, in accordance with the following standards, terms and conditions.
3. INITIAL ASSESSMENT
- Initial visit will include assessment of all elevators and chairlifts to include a report on the findings.
4. MINIMUM PREVENTIVE MAINTENANCE FREQUENCY AND TASK
The following preventive maintenance frequency and task lists are not inclusive of all required maintenance points for the variety of equipment available throughout the elevator industry. These maintenance frequency and task lists are designed to be examples of the preventive maintenance quality level required by this SPECIFICATION. The Vendor is required to submit specific preventive maintenance frequency and task lists for each type of equipment prior to commencement of contract.
a. Geared & Gearless Each Visit:
o Ride each elevator and observe performance, leveling, floor stops, door opening and closing operation and noise.
o Test safety edges, photo eyes, detectors, door open buttons, and alarm bell.
o Check for proper car and car button operation and all indicator illuminations and lantern operations.
Monthly:
o Clean and inspect machine, controller, selector, motor, motor generator/SCR (Silicon-Controlled Rectifier) and governor.
o Clean and inspect car top, operating switches, door operator and controls, car door hangers, gibs, detectors, and/or photo eyes and safety edges. Lubricate and adjust door operator and door accessory equipment.
o Clean and inspect hoist way door hangers, interlocks, linkage, pickup assembly, door gibs, non-vision wing and hoist way switches.
o Clean and inspect governor tension sheave, car and counterweight buffers and compensating sheave assembly. Clean pit and check safety plank and travel cable loops.
o Clean machine room, check communicators and brushes, clean and adjust controller and selector contracts and relays.
o Check car and hall fixture lamps, leveling and floor stops; alarm bell and emergency stop and inspect travel cable.
o Firefighter Phase I and Phase II recall tests performed to meet NFPA 101 (Section 9.4) requirements aligned with ASME A17.1/CSA B44
Phase I Recall Test: Turn the fireman’s key switch at the designated recall level to the "ON" position (or trigger a corresponding lobby/machine room smoke detector). Confirm the cars return non-stop to the primary or alternate designated floor, park with doors open, and go out of public service.
Phase II In-Car Operation Test: Enter the car, insert the firefighter's key, and verify that manual car operation, continuous pressure door closing, and floor selection controls work properly.
Record Keeping: Log the date, individual tester/mechanic details, specific elevator unit/bank IDs, and a pass/fail status for the recall and in-car functions.
Quarterly:
o Inspect rope and shackles, car and counterweight guides, TM (traction machine) and slow down switches, adjust and lubricate as required and check emergency light.
o Check and adjust brake, inspect and lubricate pivot pins.
o Clean and adjust controller and selector components including contacts relays and timers. Check transformers and rectifiers.
Vacuum or brush all controller and selector switches.
o Check complete safety circuit.
o Check selector cables and /or tapes. Lubricate selector drive worm.
Inspect selector drive.
o Clean, inspect and lubricate governor linkage.
o Inspect, rotate and equalize hoist cables. Inspect cable shackle sand fastenings.
o Check adjustment of roller/slide car and counterweight guides. Check bearings/liners and fastenings.
o Inspect TM (traction machine), Slow down, leveling and/or limit switches.
o Clean and inspect all car and hoist way door contacts and interlocks.
o Check door closing force. Check car and hoist way hanger rollers and adjust up thrust.
o Inspect door operator bearings and cams.
o Clean and inspect governor tail sheave, compensating sheaves, compensation ropes and hitches and/or compensating ropes and hitches and/or compensating, chains, guides, and hitches.
o Clean and inspect car and counterweight buffers. Check buffer oil level and operation.
Semi Annual:
o Check control and main line fuses, voltage readings, motor and motor generator wire connections, overloads, armature clearance and brake cores.
o Check motor overload devices, resistor, and resistance connections.
o Check car safety mechanism and governor rope hitch.
Annual: Every June o Drop Brake shoes, clean lubricate and adjust. Flush and replace worm gear oil.
o Check all controller and selector terminals. Check and clean all fuse holders.
o Check car frame, overhead, car counterweight sheaves, sills and pit.
o Annual lubrication of motor, motor generator, and machine bearings, deflector, compound and compensating sheaves and governor tension sheave bearings. Check All fasteners.
o Annual car safety test. Clean, inspect and lubricate governor and safety mechanisms. Check buffer oil level.
o Adjust motor control and perform logic systems operation check.
o Clean hoist way and hoist way equipment including guide rails, counterweights, hoist way door hangers, interlocks, closers, headers, and related devices. Check all fastenings on guide rails, brackets, and entrances. Check all traveling cables.
o All back-up batteries to be tested annually and changed every three (3) years. This will include the date (month/year) sticker of when the new batteries were installed.
Five Year (Provisional):
o Perform full load governor, and safety and buffer test
b. Hydraulic passenger and service Each Visit:
o Ride each elevator and observe performance, leveling, floor stops, door opening and closing operation, and noise.
o Test safety edges, photo eyes, detectors, Door open buttons, and alarm bell.
o Check for proper car and hail button operation and all indicator illuminations and lantern operations.
o Check for leaks in power unit, hydraulic control valve silencer, sound couplings and oil line.
Monthly:
o Clean and inspect power unit, controller, and motor. Check drive belt tension and condition.
o Check leaks and oil level in power unit. Clean power unit oil drip pan.
o Clean and inspect car top, operating switches, door operator, and controls, car door hangers, gibs, detectors and/or photo eyes and safety edges. Lubricate and adjust door operator and door accessory equipment.
o Clean and inspect hoist way door hangers, interlocks, linkage, pickup assembly, door gibs, detectors and /or photo eyes and safety edges.
Lubricate and adjust door operator and door accessory equipment.
o Clean and inspect hoist way door hangers, interlocks, linkage, pickup assembly, door gibs, non-vision wing and hoist way switches.
o Clean and inspect hydraulic plunger, seals, and packing. Check jack oil drip container o Check guide rail lubrication dip containers in pit.
o Firefighter Phase I and Phase II recall tests performed to meet NFPA
101 (Section 9.4) requirements aligned with ASME A17.1/CSA B44 Phase I Recall Test: Turn the fireman’s key switch at the designated recall level to the "ON" position (or trigger a corresponding lobby/machine room smoke detector). Confirm the cars return non-stop to the primary or alternate designated floor, park with doors open, and go out of public service.
Phase II In-Car Operation Test: Enter the car, insert the firefighter's key, and verify that manual car operation, continuous pressure door closing, and floor selection controls work properly.
Record Keeping: Log the date, individual tester/mechanic details, specific elevator unit/bank IDs, and a pass/fail status for the recall and in-car functions.
Quarterly:
o Check motor and pump sheave alignment. Check motor and pump fastenings.
o Adjust hydraulic control valve. Clean hydraulic control valve strainers.
Check hydraulic control valve locking nuts, adjustment screws and mounting fastenings.
o Clean and adjust controller components including relays and timers.
Check transformers and rectifiers. Vacuum or brush all controller parts.
o Check out complete safety circuit.
o Check adjustment of roller/slide car guides. Check bearings/liners and fastenings.
o Inspect TM (traction machine), slowdown, leveling and/or limit switches.
o Clean and inspect all car and hoist way door contacts and interlocks.
o Check door closing force. Check car and hoist way hanger rollers and adjust up thrusts.
o Inspect the door operator bearings and cams.
Semi-Annual:
o Check control and main line fuses, voltage readings and motor wire connections.
o Check motor overload devices, resistor/resistance connections and starters, contactors and contacts.
Annual: Every June o Check all controller terminals. Check and clean all fuse holders.
o Check car frame sills and pit.
o Annual hydraulic pressure test. Check relief valve seal and tag valve with current test information, date test was performed and performing company name.
o Elevator Communication System checked annually.
o All back-up batteries to be tested annually and changed every three (3) years. This will include the date (month/year) sticker of when the new batteries were installed.
5. REPAIR SERVICES
Examples of these repairs include, but are not limited to, failure of elevators to operate, failure to level properly, failure of door mechanisms to function correctly and other operations that would cause the elevator to be taken out of service.
- The agreement includes service calls, during regular working hours of regular working days of Monday through Wednesday, 7:00 am - 5:00 pm and Thursday through Friday, 7:00 am – 10:00 pm, for repairs to elevator systems that render the elevator inoperable or unsafe for service. All work shall be based on regular working hours on regular working days.
- The proposal shall include emergency call-back maintenance during regular working hours during regular working days. This is not a separate rate during normal working hours.
- Revamping of signal fixtures shall be covered under regular service time only.
- Use of lubricants shall conform to the elevator manufacturer’s specifications.
- All non-maintenance repairs during any inspections require an itemized quote of repairs and pricing.
6. PERFORMANCE REQUIREMENTS
- The vendor shall submit monthly reports for each elevator/lift. The Vendor shall submit to District written performance reports at the end of each 6-month period. The Vendor shall submit, when applicable, any written recommendations related to safety issues, new attachments etc. Vendors’ supervisory personnel shall be always available to report to and confer with the District. Vendor shall submit to the District such records as may be identified in this Specification or such other records and reports as the District may require.
- Vendor shall have a Supervisor regularly conduct a field audit of the performance of Vendor’s field personnel. A field audit schedule will be agreed upon by the successful vendor and the District. Vendor shall semi-annually survey all equipment covered by this Contract to conform compliance to the requirements of the Contract.
- On all elevator shutdowns involving passenger entrapments, a comprehensive report shall be prepared and submitted to the District within 24 hours of the entrapment. The report shall include building location, exact location in building where passengers were released, cause of entrapment and corrective action taken by the Vendor.
- Vendor shall restore the property to its original condition and shall leave the property clean and free of all tools, equipment, waste materials and rubbish.
- ALL in-car emergency phones to be programmed by the vendor to call the vendor. The emergency hotline is to be included in the initial takeover cost.
- Compatible iPhone application for creating and monitoring service requests, preferred.
- Provide the number of service technicians employed by your firm.
- Provide the name(s) of dedicated service technicians assigned to our elevators, if applicable.
- What are the warranties on repairs and replacement components?
- Provide a list of service agreement coverage including:
o Response times for Service Calls o Response times for Entrapments o Exclusions o Additional Charges o Rate List o On Call Stand by
- Explain if you provide chairlifts and maintenance on chairlifts. We reserve the right to outsource chairlifts and chairlift maintenance to another vendor
- How many facilities is each service technician responsible for?
- What is the service radius for each service technician?
- Provide a breakdown of pricing per year to include emergency and after-hour rates
- We reserve the right to contact another vendor if the awarded vendor cannot provide service in a timely manner and habitual failure to meet contractual requirements
7. PLEDGE OF PURCHASER SATISFACTION
The Purchaser and the Vendor shall appoint appropriate personnel to meet as needed at local and global levels and at such intervals as is deemed necessary to enable the parties to review and discuss the performance of both parties of their respective obligations.
All services to be provided during Vendors regular working hours, Monday through Wednesday, 7:00 am - 5:00 pm and Thursday through Friday, 7:00 am – 10:00 pm, of its regular working days unless otherwise specified below.
8. TERMINATION PROVISIONS
We reserve the right to terminate this agreement due to:
- breach of contract (for example: poor performance, maintenance neglect, misconduct) and/or mutual agreement,
- non-appropriation of funds, or
- term for convenience
9. YEARLY INSPECTIONS
Included in the contract shall be the annual inspection, as required by the Texas Department of Licensing and Regulations. All inspections must comply with the most current requirements at the time and date of inspection. Contactor must provide current copy of license issued to Inspector by the Texas Department of Licensing and Regulations prior to annual inspection.
1. Inspection procedures:
a. The inspector must inspect all equipment for compliance with the applicable ASME Safety Codes or ASCE Standards as adopted in §74.100.
b. Inspectors must use the most current published edition of ASME A17.2, and the “Guide for Inspection of Elevators, Escalators, and Moving Walks” to conduct inspections and witness tests for compliance with the ASME Safety Codes or ASCE Standards adopted in §74.100.
c. The inspector shall report to the Contract Administrator before beginning any inspections.
d. The inspector shall not perform any of the tests.
2. Forms:
a. The inspector must use current State approved forms for reporting inspections. The forms shall be filled out completely, and comply with all rules, regulations, and laws.
b. The inspector must list all ASME Code violations by code number and code edition for each unit inspected and include a written description of the violation on the State’s approved form. If the ASME Code refers to another code, the inspector must list both code numbers and include a written description of the violation.
3. Inspector’s Equipment:
a. All test tags and decals must conform to no less than the State of
Texas Licensing and Regulation requirements, including but not limited to:
i. Verifying that a vendor’s test tag(s) is/are placed on the equipment in conformance with the ASME Safety Codes or ASCE Standards adopted in §74.100;
b. Follow all current State tagging requirements at time of inspection, including but not limited to, all devices and adjustments required to be sealed by the adopted standard shall be sealed with wire rope and lead seal by the inspector witnessing the test(s). Once a device or adjustment has been sealed, there shall be no need to replace the seal unless it is broken for whatever reason. If broken, an inspector shall witness the test and provide a seal in accordance with the State’s rules, regulations, and law prior to the unit being returned to service;
c. Verify and affix the required identification decal issued by the State, to the upper right-hand corner of the control panel. The decal shall remain on the control panel for the life of the equipment. There shall be no additional decal will be affixed to equipment that has a current State decal displayed;
d. The replacement of a new decal being required on a unit of equipment, due to loss or destruction of the decal, the inspector must report the equipment’s location, old decal number, and new decal number to the Department within ten calendar days of placing the new decal number upon the equipment, and;
e. All correspondence and inspection reports shall reference the decal number and Campus/Department ID number, as reflected on the Certificate of Compliance.
10. SIGNAGE
No elevators are to be removed from service, including lockout, except in cases of hazard to life, and/or extensive equipment damage without prior approval by District.
When an elevator is out of service for any reason, the Awarded Vendor shall place signage at all floor entrances to that elevator indicating that the elevator is out of service. Placement of signage will be mandatory. Signage should be legible and well defined as to the elevator being out of service.
11. RESPONSE TIME
Vendor shall respond to calls for repair service within two (2) hours of the receipt of the call. If unable to provide this level of response, vendor shall state in the operation plan the minimum time achievable. Bid price for each location shall include labor costs and response time.
12. AFTER HOUR/OVERTIME
A separate hourly rate shall be quoted for after-hours emergency services. Normal business hours are Monday through Wednesday, 7:00 am - 5:00 pm and Thursday through Friday, 7:00 am – 10:00 pm. All work performed outside these hours shall be billed as overtime rates or an emergency call if necessary.
District will provide a calendar of normal operating days and times each year.
Provide a breakdown of pricing per year to include emergency and after-hour rates.
13. REPORTING
A Service Report must accompany every invoice issued for each individual location. If a Service Report is not included with invoice at time of billing, that invoice will not be paid until a Service Report is provided.
14. INFORMATION OF STATE OF TEXAS REQUIREMENTS
- Annual Inspections every 12 months for all passenger elevators, escalators, chairlifts, and moving walks, witnessed by the TDLR-registered QEI
- Monthly Fire Fighter Service Checks: Elevators equipped with firefighter service must undergo monthly operational checks with written logs kept on-site
- Five-Year Tests: Electric traction and roped hydraulic elevators require rigorous full-load safety tests and inspections every five years
15. ADDITIONAL INFORMATION
- Location of all elevators and chairlifts, is a separate document within
Attachments.
- Once awarded, Maintenance will provide a work calendar annually.