Scope of Work.pdf
PDF 13 MB Posted
- Attached to
- BECKMAN MHC'S HVAC MAINTENANCE
- Solicitation number
- 5400020310
- Issued by
- Richland County, South Carolina
About this file
This Scope of Work document outlines an HVAC maintenance and repair agreement for the South Carolina Department of Mental Health covering three Beckman Mental Health Center facilities located in Greenwood, Clinton (Laurens), and Newberry. The contract solicits bids from licensed mechanical contractors to provide comprehensive maintenance and repair services for HVAC systems including split system DX dedicated outside air units with hot water heat, air-cooled chillers, natural gas boilers, pumps, chilled water/hot water fan coil units, blower coil units, ductless split systems, and associated controls and ductwork. The agreement requires a minimum of four annual inspections with documentation, and contractors are encouraged to visit all three facilities prior to bidding for equipment verification. The selected contractor will have thirty days to review existing equipment conditions and submit a list of items requiring correction with cost estimates before commencing work. The contract term and renewal options are not specified in the document; however, the scope indicates this is an ongoing maintenance agreement covering normal and preventive maintenance as an all-inclusive, one-price-covers-all arrangement for parts and labor with specific exceptions for lightning damage, acts of God, and vandalism.
The maintenance and repair agreement explicitly excludes exterior painting of non-moving parts, lightning damage, acts of God, and vandalism from coverage; the contractor bears responsibility for these items as contract extras but assists the owner with insurance claim filing. All maintenance calls placed before 9:00 AM require same-day onsite service, while calls after 9:00 AM require same or next-day service, with lack of response potentially grounds for contract cancellation. The contractor must carry insurance as specified in the bid solicitation, provide a Certificate of Insurance, utilize approved water treatment services (preferably Nalco Water), and comply with all EPA refrigerant recovery and recycling requirements per 40 CFR Part 82, Subpart F and ASHRAE guidelines. The contractor must use Merv 8 filters or higher as specified, work with Trane factory-trained technicians for the existing EMS control system, and route all correspondence, billings, and quarterly reports to the contract manager Paul Wilson at Physical Plant Services. Specific equipment lists detailing manufacturers, model numbers, tonnages, and voltages are provided for all three facilities, and the contractor is responsible for hauling and lawful disposal of all used parts, oils, and refrigerants.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation.doc | DOC document | |
| Amendment 1.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC MAINTENANCE REQUEST PROPOSAL
BECKMAN MENTAL HEALTH CENTER (Three Locations)
Beckman Mental Health Center HVAC Maintenance Proposal Page 1 of 6
1.0 INVITATION
A. Licensed mechanical contractors are invited to submit bids on a maintenance and repair agreement for the three (3) facilities listed below that are part of the Beckman Center for Mental Health Services.
Name: Beckman Center Administration Address: 1547 Parkway, Suite 100, Greenwood, SC 29646 Phone: 864-229-7120 or 864-993-9338 Contact: Koshay Arnold
Name: Laurens MHC Address: 442 Professional Park Road, Clinton, SC 29325 Phone: 864-547-8280 or 864-980-6553 Contact: Heidi Hoogstraal
Name: Newberry MHC Address: 2043 Medical Park Drive, Newberry, SC 29108 Phone: 803-768-8106 or 803-940-6203 Contact: Lori Pruitt
B. Equipment in scope under this contract includes moving and non-moving parts for split system DX dedicated outside air units with hot water heat, air-cooled chiller, natural gas boiler, pumps, chilled water/hot water fan coil units and blower coil units, ceiling style and inline fans, ductless split system, intake/relief units zone dampers, time-clocks, controls, control systems, piping, filters, ductwork and other components listed in requirements.
C. Contractor is encouraged to visit the buildings indicated above prior to the bid for observation and verification of the information provided in this document.
1.1 AGREEMENT INTENT
A. The maintenance and repair agreement to cover all aspects of HVAC normal and preventive maintenance as a one price covers all agreement to include parts and labor on moving and non-moving parts with the following exceptions:
1. Lighting Damage: While the contractor will be reimbursed for lightning damage claims, the contractor will be expected to accomplish the following at no charge to the owner.
a. Provide immediate information to the owner’s representative that equipment has been damaged before repairs are begun.
b. Provide photographic evidence that the lightning damage has occurred.
c. Assist the owner in filing insurance claims.
2. Acts of God.
3. Vandalism.
Beckman Mental Health Center HVAC Maintenance Proposal Page 2 of 6
1.2 FORMAT
A. The agreement is a multi-page document which is to be signed by both the Department of Mental Health and the maintenance contractor. The following items will be attached to the contract agreement.
1. A listing of the equipment to be covered under this agreement.
2. Each piece of HVAC equipment will be listed to include the following as available.
Equipment Capacity Manufacturer’s Name Model Number Voltage
B. A Certificate of Insurance from the contractor to the Owner is required as listed in the DMH bid solicitation document.
C. Equipment inspection sheet. This sheet will be completed at each quarterly inspection visit.
See suggested attached sheet.
D. Additional items to be covered at the request of the Owner (see EE on page 5).
1. Cover all items requested by the owner not mentioned in the annual maintenance agreement.
2. Reference EE on page 5 for additional installed equipment.
1.3 REQUIREMENTS OF THE STANDARD MAINTENANCE & REPAIR AGREEMENT
A. The maintenance and repair contractor will provide a minimum of four (4) inspections annually which are to be documented (see attached inspection sheet). Timing for equipment or system shut-downs necessary for proper inspections to be coordinated with the facility prior to inspections.
B. Furnish all labor and supplies necessary to make repairs, adjustments, routine and preventive maintenance (PM) to keep the equipment operating efficiently year-round.
C. Furnish coverage on non-moving parts that included but not limited to starters, controls, control systems, oil and refrigerant piping. All ductwork either fiberglass or sheet metal is covered. Exterior painting of non-moving parts is excluded from this contract.
D. Conduct an evaporator coil and condenser coil cleaning on an annual basis. The contractor will visually inspect each coil on the quarterly visit and clean more often if needed.
E. Provide coverage for motor starters and/or variable speed drives.
F. Provide seasonal startup/shutdown/change over inspection of all air type and water type air conditioning equipment including economizer controls.
G. Supply new compressor oil, oil filters, refrigerant filters and dryers after any compressor failure or change.
HVAC Maintenance Proposal Page 3 of 6
H. Check for refrigerant leaks, repair leaks and replace any refrigerant lost to ensure optimum performance of the HVAC equipment.
I. Provide coverage for miscellaneous replacement of controls components for all HVAC equipment.
J. Check superheat on expansion valve and calibrate as required.
K. Check refrigerant circuit for expansion valve operations.
L. Lubricate all moving parts.
M. Clean all drain pans and drains as needed with a minimum of once per year.
N. Check operating pressures with gauges and record on quarterly inspection report. At the time the pressure readings are taken, note the supply air temperature, return air temperature and the outdoor air temperature. List outdoor temperature under remarks.
O. Calibrate and adjust operating and safety controls.
P. Check all belts and adjust or replace as needed.
Q. Check all equipment for unusual noise and vibration and repair or replace the causes of the noise condition as needed.
R. Check electrical connections for tightness.
S. Provide filter changes quarterly or more frequently if needed. Merv 8 filters by Farr/Camfil or equal are required unless higher efficiency rated filters are required as noted on plans.
Contractor to field verify sizes and thickness of filters in each facility.
T. Exhaust fan grilles and internal blower / cabinet to be cleaned annually.
U. Keep the Owner informed or upgrades and improvements to prolong equipment life and reduce the cost of operation during the life of the contract.
V. Specific to natural gas-fired boilers and furnaces, and in conjunction with the quarterly inspections and PM (routine, listed and per manufacturer) : prior to the heating season, test and adjust combustion efficiency in gas fired equipment to optimum performance.
Corrective actions performed to be included in the reports along with checklist in the unit report.
W. The maintenance and repair contractor will carry insurance as required in the bid solicitation.
X. Specific to the air-cooled chiller, inspections and PM to include and not limited to refrigerant pressures, oil tested for acidity with corrective actions as necessary for proper operation, amps readings, water pressures, water temperatures, controls, etc. This data and other checklist items along with manufacturer specific PM measures and corrective actions performed to be included in the reports.
HVAC Maintenance Proposal Page 4 of 6
Y. Chemical treatment of the chilled and hot water loops to be properly maintained by independent laboratory providing labor and chemicals complete. Water samples of each loop to be analyzed quarterly or more frequently if required for proper water quality. Test to include dissolved solids and PPM levels for corrosion inhibitor and biocide with chemicals added to the loops to achieve and maintain the recommended water chemistry of the preferred chemical treatment company.
Z. As provided under this maintenance contract, the preferred water treatment company for the South Carolina Department of Mental Health is:
Nalco Water Josh Frady (local rep) 118 S. Stallion Drive Cowpens, SC 29330 864-612-3090
Joshua.frady@ecolab.com
It is not mandatory that Nalco Water be utilized. However, other firms deemed qualified to be vetted by the agency and engineer for approval prior to work being performed.
AA. The maintenance and repair contractor will not release, nor cause to be released, accidentally or otherwise, any chlorofluorocarbons (refrigerant) into the air. All refrigerant must be reclaimed and recycled according to the latest state and federal governmental requirements and guidelines as published by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
BB. Lightning damage, acts of God, and vandalism are not covered under this agreement. The contractor will be responsible for any repairs needed due to these causes as an extra to the contract. The contractor will assist the Owner in filing insurance claims and will notify the Owner prior to repairs to allow for documentation to the insurance company. Lack of notice prior to repairs may void the ability of the contractor to be paid for collectible repairs.
CC. All calls to Department of Mental Health should be deemed a priority call. All maintenance repair calls placed before 9:00 AM will have same day onsite service. All maintenance repair calls placed after 9:00 AM will have same or next day onsite service. Lack of response by the contractor may be considered cause to cancel the contract.
DD. The contractor is responsible for the hauling and lawful disposal of all used parts, oil, refrigerant, etc.
EE. The maintenance contractor will be required at the beginning of each contract year and prior to the first quarterly inspection to contact physical plant services (Paul Wilson, Project Manager) at 803-935-5636 and set up a meeting with a representative from Physical Plant Services to conduct one or more joint inspections of the HVAC system maintenance.
HVAC Maintenance Proposal Page 5 of 6
FF. All correspondence between the mental health facility and the maintenance contract including billings, letters, and quarterly reports to be emailed in PDF to the contract manager and designated facility representative.
South Carolina Department of Mental Health Physical Plant Services Mr. Paul Wilson (Contract Manager) 7901 Farrow Road, Building 4 PPSE, Columbia SC 29203 Phone: 803-835-5636 Cell: 803-667-2893 Email: paul.wilson@scdmh.org
GG. The contractor selected to do the work will be allowed thirty (30) days in which to review the condition of the existing equipment in all locations. The contractor will be expected to generate a list of any items which need to be corrected before his firm begins the contract.
Along with the list of items, the contractor is expected to send the cost estimated to remedy the problem. The Department of Mental Health has several options:
1. If DMH does not agree with any of the items presented, they may veto its implementation.
2. If DMH does not agree with the pricing, there are several options.
a. They may elect to correct the items with in-house personnel.
b. They may authorize the contractor to proceed with corrections at the price quoted.
c. They may take bids from other contractors in hopes of getting a price lower than the quoted amount and getting repairs done by other.
HH. When parts are no longer available, all repair request must be directed in advance of equipment order or work performed to the agency contract manager. Labor continues to be covered under the terms of this contract.
II: Questions arising from this agreement should be referred to the Director of Physical Plant Services for the South Carolina Department of Mental Health or his designated representative. Attachments to this agreement include.
1. A listing of the equipment to be covered under this agreement.
2. A certificate of insurance from the contractor to the owner.
3. HVAC drawings in PDF are included where they are available.
4. Equipment inspection sheet.
5. Attached filter checklist must be posted and updated on site.
JJ. Should additional HVAC equipment be added to a facility, the additional equipment will be added to this contract in the same unit pricing ($ / ton) as the equipment originally covered under the original terms of this contract.
KK. For reference, an EMS system is utilized at Beckman; Trane controls is the vendor. The contractor to be fully knowledgeable with the system with Trane factory trained technicians.
HVAC Maintenance Proposal Page 6 of 6
THIS AGREEMENT IS ENTERED INTO BY:
CONTRACTOR:
Signature Date
Name Title
OWNER:
South Carolina Department of Mental Health
Signature Date
Name Title
S.C DEPARTMENT OF MENTAL HEALTH
SUGGESTED SAMPLE HVAC UNIT REPORT
Date: _________________
Facility: __________________________ Address _______________________________________________
Manufacturer ______________ Unit Model ___________________________________ Tag _____________
Age (yrs) ________________
Discharge press __________________ Suction press _______________ Suction temp___________________
Liquid temp _____________________ Superheat _________________ Subcooling ____________________
Evap. temp in ____________________ Evap. temp out _____________ Outdoor duct temp ______________
Ambient Temp ___________________ Chilled water EWT _________ Chilled water LWT ______________
Hot water EWT __________________ Hot water LWT ____________
Evap. fan FLA _______________ Condenser fan FLA _______________
Compressor RLA ____________ LRA ___________________________
Unit voltage ________________
Yes / No
Properly charged: ________
Suction drier installed: ________
Condenser coil clean: ________
Are fins bent: ________
Evaporator coil clean: ________
Any duct leaks: ________
T’stats / controls OK: ________
Boiler burners sequenced: _____
Yes / No
Dampers operation OK: ________
Insulation OK: ________
Pump bearings OK: ________
Pump couplings OK: ________
Chiller operation OK: ________
Compressor oil OK: ________
Boiler burners cleaned: ________
Gas leaks: ________
Yes / No
Electrical components & safety controls confirmed: ________
Electrical connections properly installed/secured: ________
Confirm condensate overflow switch operation: ________
Chemical treatment in water loops properly maintained: ________ continued
S.C DEPARTMENT OF MENTAL HEALTH
SUGGESTED SAMPLE HVAC UNIT REPORT
Yes / No
Condensate drain and pan properly installed and draining: ________
Check evaporator fan condition, motor operation and bearings: ________
Check condenser fan condition, motor operation and bearings: ________
Relubrication of dirty bearings necessary: ________
Crackcase heater installed and operating: ________
Air filters installed and clean: ________
Is unit operating properly: ________
Unit panels properly installed and secured: ________ ________
Electrical panel and boxes properly installed and secured: ________
O&M manual / PM checklist reviewed & completed: ________
Boiler vent and intake properly installed: ________
Boiler and combustion system in proper condition and operating at peak performance: ________________
The following corrective action is required:
Additional comments:
Technician’s name: ______________________________________________________
Customer’s signature: _______________________________________________________
Phone: _______________________
S.A.#______________
FILTER CHANGE LOG
HVAC UNIT NO. ___________
Date Existing filter (clean / dirty) Signature of technician Date changed
Note: Filter Change Log is required on all HVAC Units at all locations.
Beckman MHC Equipment Summary
Air Cooled Chiller
Symbol Model Number MFG Type Voltage Nom. Tonnage
CH-1 RTAA100 4XM01A3 Trane Air-Cooled Chiller 460-3-60 100
Gas Boiler
Symbol Model Number MFG Type Voltage Total Input AFUE
B-1 H3-1125 Raypack hot water boiler 120-1-60 1,124,700 BTUH 82
Pumps
Symbol Model Number MFG Type Voltage Flow / TDH
HWP-1 FE1510E2E1FA0 Taco End Suction Pump per label 90 GPM @ 80 FT
CWP-1 FE2510E2F1F4L0A Taco End Suction Pump per label 240 GPM @ 90 FT
CWPB-1 FE2510E2F1F4L0A Taco End Suction Pump per label 240 GPM @ 90 FT
Blower Coils (chilled and hot water)
Symbol Model Number MFG Type Voltage Cooling Coil Capacity Htg Coil Capacity Arflow (CFM)
BC-1 BCHB0542DF0A Trane Blower Coil per unit label 59,100 42,900 1,800
BC-2 BCHB0362DF0A Trane Blower Coil per unit label 41,200 35,200 1,200
BC-3 BCHB0182D Trane Blower Coil per unit label 22,200 11,500 600
BC-6 BCHB0242 Trane Blower Coil per unit label 30,200 22,900 800
BC-7 F3EH090A33A Trane Blower Coil per unit label 61,300 90,500 1,800
BC-10 BCHBO24 - confirm Trane Blower Coil per unit label 34,500 24,000 800
BC-11 BCHB242DF Trane Blower Coil per unit label 25,500 11,000 800
BC-13 BCHB0362D Trane Blower Coil per unit label 42,000 28,200 1,200
BC-14 BCHB182DF Trane Blower Coil per unit label 22,000 9,500 600
BC-17 BCHB0362D Trane Blower Coil per unit label 43,200 28,500 1,200
BC-19 BCHB0242D Trane Blower Coil per unit label 27,500 16,900 800
BC-20 BCHB05442 Trane Blower Coil per unit label 72,800 54,400 1800
BC-21 BCHB0242D Trane Blower Coil per unit label 33,200 24,800 800
BC-24 BCHB024D Trane Blower Coil per unit label 25,200 13,200 800
BC-25 BCHB0362D Trane Blower Coil per unit label 35,900 17,600 1200
BC-30 BCHB0362D Trane Blower Coil per unit label 39,600 28,200 1200
BC-36 BCHB0542D Trane Blower Coil per unit label 62,900 36,700 1800
BC-37 BCHB0542D Trane Blower Coil per unit label 67,600 40,500 1800
BC-40 BCHB0182D Trane Blower Coil per unit label 22,200 8,400 600
BC-43 BCHB0182D Trane Blower Coil per unit label 24,200 16,000 600
Fan Coils (chilled and hot water)
Symbol Model Number or S/N MFG Type Voltage Cooling Coil Capacity Htg Coil Capacity Arflow (CFM)
FC-4 F5A594AU Trane Fan Coil per unit label 5300 5800 220
FC-5 F5A594AT Trane Fan Coil per unit label 18,700 16,700 610
FC-8 FTSA594AV Trane Fan Coil per unit label 24,900 18,700 1,025
FC-9 F5A594AW Trane Fan Coil per unit label 24,900 18,700 1,025
LPC-12 CPCAA08D2C Trane Fan Coil per unit label 134,900 96,900 4,000
FC-15 F5HS94AX Trane Fan Coil per unit label 11,700 6400 390
FC-16 FCCB1003KN0F Trane Fan Coil per unit label 27,600 18,100 1,025
FC-18 FCCB1003KNOF Trane Fan Coil per unit label 16,800 13,500 4,000
FC-22 FCCB1003KNQFQ Trane Fan Coil per unit label 24,900 18,700 1,025
FC-23 FCCB100-confirm Trane Fan Coil per unit label 20,000 12,000 735
FC-26 FCCB0603K Trane Fan Coil per unit label 15,000 8,900 610
FC-27 F5A594AF Trane Fan Coil per unit label 9,500 5,800 390
FC-28 F5A594AG Trane Fan Coil per unit label 11,500 6,500 390
FC-29 F5A94AH Trane Fan Coil per unit label 16,200 9,200 610
FC-31 F5A594AJ Trane Fan Coil per unit label 15,300 10,800 610
FC-32 FCCB0403K Trane Fan Coil per unit label 8600 5700 390
FC-33 FCCB0403K Trane Fan Coil per unit label 10000 6000 390
FC-34 FCCB0403K Trane Fan Coil per unit label 12600 6500 390
FC-38 FCCB0803K Trane Fan Coil per unit label 20200 11400 735
FC-39 FCCB0403D Trane Fan Coil per unit label 11400 6100 390
FC-41 FCCB0603KN Trane Fan Coil per unit label 21000 16000 735
FC-42 ASURL2 Trane Fan Coil per unit label field verify field verify field verify
FC-44 F5A594AS Trane Fan Coil per unit label 14600 12400 610
Ductless Split Outdoor AC
Symbol Model Number MFG Type Voltage Nom. Tonnage
DSS-42 MU09TW Mitsubishi DX Outdoor CU 115-1-60 0.75
Ductless Split Indoor AC Unit
Symbol Model Number MFG Type Voltage Nom. Tonnage
DSS-42 MS09TW Mitsubishi DX Indoor Wall Mount 115-1-60 0.75
DOAU Outdoor Condensing Units
Symbol Model Number MFG Type Voltage Nom. Tonnage Low Ambient HGRH
CU-1 TTA12044CAB--AE Trane DX Condensing Unit 460-3-60 10 Yes Yes
CU-1 TTA12044CAB--AE Trane DX Condensing Unit 460-3-60 10 Yes Yes
CU-1 TTA12044CAB--AE Trane DX Condensing Unit 460-3-60 10 Yes Yes
DOAU Air Handling Units (DX coil with hot water heating coil)
Symbol Model Number MFG Type Voltage Cooling Coil Capacity Htg Coil Capacity Arflow (CFM)
DOAU-1 BCCD060G1--E53L4Z Trane Blower Coil 460-3-60 116,460 126,670 1,200
DOAU-1 BCCD060G1--E53L4Z Trane Blower Coil 460-3-60 116,460 126,670 1,200
DOAU-1 BCCD060G1--E53L4Z Trane Blower Coil 460-3-60 116,460 126,670 1,200
Fans
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
CCF-1 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-2 VCDD020C Carnes T-stat 120-1-60 190 0.125
CCF-3 GC-166 COOK Wall Switch 120-1-60 140 0.25
CCF-4 GC-186 COOK Wall Switch 120-1-60 210 0.25
CCF-5 VCDD020C Carnes T-stat 120-1-60 190 0.125
CCF-6 VCDD015C Carnes Wall Switch 120-1-60 105 0.25
CCF-7 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-8 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-9 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-10 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-11 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-12 VCDD030C Carnes T-stat 120-1-60 285 0.125
CCF-13 VCDD040C Carnes T-stat 120-1-60 400 0.125
CCF-14 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-15 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-16 GC-148 COOK Wall Switch 120-1-60 70 0.25
CCF-17 VCDD020C Carnes T-stat 120-1-60 190 0.125
CCF-18 VCDD020C Carnes T-stat 120-1-60 190 0.125
CCF-19 GC-166 COOK Wall Switch 120-1-60 140 0.25
CCF-20 GC-166 COOK Wall Switch 120-1-60 140 0.25
CCF-21 VCDD020C Carnes T-stat 120-1-60 190 0.125
CCF-22 GC-166 COOK Wall Switch 120-1-60 140 0.25
CCF-23 VCDD015C Carnes Wall Switch 120-1-60 105 0.25
ILF-1 VIBK06 Carnes EMS 120-1-60 280 0.375
ILF-2 VIBK08 Carnes EMS 120-1-60 360 0.375
ILF-3 VIBK06 Carnes EMS 120-1-60 200 0.375
ILF-4 VIBK06 Carnes EMS 120-1-60 240 0.375
ILF-5 VIBK08 Carnes EMS 120-1-60 600 0.375
ILF-6 VIBK06 Carnes EMS 120-1-60 295 0.375
Laurens MHC Equipment Summary
Outdoor Condensing Unit
Symbol Model Number MFG Type Voltage Nom. Tonnage
CU - 1 4TTA3060D3 Trane DX Condensing Unit 200/230-3-60 5
CU - 2 4TTA4042A3 Trane DX Condensing Unit 200/230-3-60 3.5
CU - 3 4TTA3060D3 Trane DX Condensing Unit 200/230-3-60 5
CU - 4 4TTA3060D3 Trane DX Condensing Unit 200/230-3-60 5
CU - 5 4TTA4036A3 Trane DX Condensing Unit 200/230-3-60 3
Gas Furnace
Symbol Model Number MFG Type Voltage 2nd Stage Input AFUE
GF - 1 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97
GF - 2 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97
GF - 3 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97
GF - 4 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97
GF - 5 S9V2B060U5PSB Trane Gas Furnace (horizontal) 120-1-60 60,000 BTUH 96
Cooling Coil
Symbol Model Number MFG Type Airflow (cfm) Nom. Tonnage
SHP - 1 4TXCC009DS3-C Trane DX Cooling Coil 1750 5
SHP - 2 4TXCB006DS3-C Trane DX Cooling Coil 1225 3.5
SHP - 3 4TXCC009DS3-C Trane DX Cooling Coil 1750 5
SHP - 4 4TXCC009DS3-C Trane DX Cooling Coil 1750 5
SHP - 5 4TXCB004DS3-C Trane DX Cooling Coil 1050 3
Fan
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
EF-1 CSP-A2150 Greenheck Existing 120-1-60 525 0.625
Drawing List:
CS-1 Cover Sheet
M-100 Mechanical Existing Conditions
M-101 Mechanical Demolition and Renovation Plan
M-200 Mechanical Schedules and Details
Site Location Map
International Existing Building Code: 2015 Edition
International Building Code: 2015 Edition
International Mechanical Code: 2015 Edition
National Electric Code: 2014 Edition
International Energy Conservation Code: 2009 Edition
New Construction X Renovation (Existing Building) Upfit Addition
Code Compliance:
Project #: J12-N072-FW
MECA
Charleston Office
451-D Jessen Lane
Wando, South Carolina
Phone: (843) 725-1086
Columbia Office
P.O. Box 50644
Columbia, South Carolina
Phone: (803) 765-9421
BID DOCUMENT DATE:
MECA Project Number: 118181
MARCH 13, 2019
SCDMH LAURENS HVAC REPLACEMENT
442 PROFESSIONAL PARK ROAD
CLINTON, SC 29325
AutoCAD SHX Text Mechanical Engineering
AutoCAD SHX Text Consulting Associates, Inc.
AutoCAD SHX Text The State of
AutoCAD SHX Text South Carolina
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text Q
AutoCAD SHX Text
AutoCAD SHX Text
LAPSA
AutoCAD SHX Text
MELIOREM
AutoCAD SHX Text S
AutoCAD SHX Text
LOCAVIT
AutoCAD SHX Text
MARCH
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text R
AutoCAD SHX Text
JULY
AutoCAD SHX Text
AH-1
AH-2
AH-3
AH-5
AH-4
CU-1 CU-2
CU-3 CU-5 CU-4
TRANSFORMER
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
151617181920 2123 2224
2526272829 303132
3435363738 33
LOCATION NO.
A & E FIRM
A & E STATE NO.
SHEET TITLE
DIVISION
PROJECT TITLE
PROJECT #:
DRAWING NO.
SHEET
DATE:
The State of
South Carolina
S
O
U
T
H
C A
R
O
L
I
N
A
A N
I
M
I
S
O
P
I
B
U S
Q
U
E
P
A
R
A
T
I
J
U
L
Y4
M
A
R
C
H
MELIOREM LAPSA LOCAVIT
Q
U I
S
S
E
P
A
R B
I
T
AGENCY OR INSTITUTION
NO. LOCATION
REVISION DATE BY APP
APPROVAL
DRAWN BY
CHECKED BY
LANDSCAPE ARCHITECT
ENGINEERING DESIGN
ARCHITECTURAL DESIGN
PROJECT MANAGER
PROFESSIONAL SEAL (S)
PLOT DATE: 13 MARCH 2019
N:\118181\TEMPLATES - *.dwg
SCDMH NEWBERRY MHC HVAC REPLACEMENT
13 MARCH 2019
BID DOCUMENTS
REVISION DATE BY APP
MECA
CONDENSING
UNIT YARD
AREA OF
WORK
J12-N072-FW
MECHANICAL EXISTING
CONDITIONS
M100
MECHANICAL EXISTING CONDTIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
AutoCAD SHX Text
NO. C00097
AutoCAD SHX Text
ASSOCIATES
AutoCAD SHX Text
CONSULTING
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text Z
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text U
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text No. 18709
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text Mechanical Engineering
AutoCAD SHX Text Consulting Associates, Inc.
AutoCAD SHX Text P.O. Box 50644
AutoCAD SHX Text Columbia, SC
AutoCAD SHX Text 451-D Jessen Lane
AutoCAD SHX Text
(843) 725-1086
AutoCAD SHX Text
(803) 765-9421
AutoCAD SHX Text Columbia
AutoCAD SHX Text Charleston
Wando, SC
AH-1
AH-2
AH-3
AH-5
AH-4
CONTRACTOR TO REMOVE COOLING
COIL/GAS FURNACE AS INDICATED.
EXISTING CONDENSATE ,REFRIGERANT,
GAS LINE TO REMAIN IN PLACE. REPLACE
EXISTING FLUE.
EXISTING REFRIGERANT TO BE
RECLAIMED/RECOVERED AND DISPOSED
OF PROPERLY. EXISTING LINES TO BE
CLEANED, TESTED, AND RE-USED FOR
NEW SYSTEM. (TYPICAL OF 5)
EXISTING RETURN AIR
DUCTS AND OUTSIDE AIR
DUCTS TO REMAIN.
RE-CONNECT BACK TO
NEW UNIT AS INDICATED.
(TYPICAL OF 5)
CONTRACTOR TO REMOVE
EXISTING EXHAUST FAN-
DUCTWORK TO REMAIN IN
PLACE
GF/CC-1
GF/CC-2
GF/CC-3
GF/CC-5
GF/CC-4
CONTRACTOR TO TRANSITION
FROM UNIT OPENING TO EXISTING
SUPPLY DUCT. VERIFY EXACT
DUCT SIZE IN FIELD WITH EXISTING
CONDITIONS PRIOR TO DUCT
FABRICATION. (TYPICAL OF 5)
CONTRACTOR TO TRANSITION
FROM UNIT OPENING TO EXISTING
RETURN DUCT. VERIFY EXACT
DUCT SIZE IN FIELD WITH EXISTING
CONDITIONS PRIOR TO DUCT
FABRICATION. (TYPICAL OF 5)
M
M
M
M
M
CONTRACTOR TO PROVIDE
NEW MOTORIZED DAMPER
IN EXISTING OUTSIDE AIR
DUCT. VERIFY EXACT
VOLTAGE WITH EXISTING
CONDITIONS PRIOR TO
ORDERING. SEE GF/CC
DETAIL. (TYPICAL OF 5)
EXISTING OUTSIDE AIR GRAVITY
HOOD AND DUCTWORK TO REMAIN
IN PLACE. REBALANCE OUTSIDE
AIR TO CFM DESIGNATED ON
PLANS (TYPICAL OF 5)
CONTRACTOR TO RE-CONNECT
TO EXISTING FLUE. CONFIRM
MFG FLUE SIZE WITH EXISTING
FLUES. REPLACE AS
NECESSARY (TYPICAL OF 5)
EF-1
CONTRACTOR TO
RE-CONNECT NEW EF-1 TO
EXISTING DUCTWORK.
TRANSITION TO EXISTING
DUCT. VERIFY DUCT SIZE IN
FIELD.
CU-1 CU-2
CU-3 CU-5 CU-4
TRANSFORMER
CONTRACTOR TO REMOVE EXISTING
CONDENSING UNITS. DISPOSITION PER
OWNER'S DIRECTION. REFER TO
MECHANICAL RENOVATION PLAN FOR
NEW WORK. (TYPICAL OF 5)
CU-1 CU-2
CU-3 CU-5 CU-4
CONTRACTOR TO RE-CONNECT TO EXISTING
REFRIGERANT LINES. CONTRACTOR TO ENSURE
EXISTING REFRIGERANT IS PROPERLY
EVACUATED, DISPOSED OF PROPERLY, AND LINES
CLEANED THOROUGHLY TO MEET NEW
REFRIGERANT REQUIREMENTS. (TYPICAL OF 5)
TRANSFORMER
EXISTING REFRIGERANT
SLEEVES THRU SLAB.
CONNECT EXISTING
REFRIGERANT LINES TO
NEW CU- (TYPICAL)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
151617181920 2123 2224
2526272829 303132
3435363738 33
LOCATION NO.
A & E FIRM
A & E STATE NO.
SHEET TITLE
DIVISION
PROJECT TITLE
PROJECT #:
DRAWING NO.
SHEET
DATE:
The State of
South Carolina
S
O
U
T
H
C A
R
O
L
I
N
A
A N
I
M
I
S
O
P
I
B
U S
Q
U
E
P
A
R
A
T
I
J
U
L
Y4
M
A
R
C
H
MELIOREM LAPSA LOCAVIT
Q
U I S
S
E
P
A
R
B
I
T
AGENCY OR INSTITUTION
NO. LOCATION
REVISION DATE BY APP
APPROVAL
DRAWN BY
CHECKED BY
LANDSCAPE ARCHITECT
ENGINEERING DESIGN
ARCHITECTURAL DESIGN
PROJECT MANAGER
PROFESSIONAL SEAL (S)
PLOT DATE: 13 MARCH 2019
N:\118181\TEMPLATES - *.dwg
SCDMH NEWBERRY MHC HVAC REPLACEMENT
13 MARCH 2019
BID DOCUMENTS
REVISION DATE BY APP
MECA
CONDENSING
UNIT YARD
AREA OF
WORK
J12-N072-FW
MECHANICAL RENOVATION AND
DEMOLITION PLAN
SCALE : 1/8" = 1' ---- 0"
M101
MECHANICAL DEMOLITION PLAN (MEZZANINE LEVEL)
SCALE : 1/8" = 1' ---- 0"
MECHANICAL RENOVATION PLAN (MEZZANINE LEVEL)
SCALE : 1/8" = 1' ---- 0"
MECHANICAL DEMOLITION PLAN (CONDENSING UNIT YARD )
SCALE : 1/8" = 1' ---- 0"
MECHANICAL RENOVATION PLAN (CONDENSING UNIT YARD )
SCALE : 1/8" = 1' ---- 0"
1 GENERAL REVISIONS 4/17/19 JAS
AutoCAD SHX Text
NO. C00097
AutoCAD SHX Text
ASSOCIATES
AutoCAD SHX Text
CONSULTING
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text Z
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text U
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text No. 18709
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text Mechanical Engineering
AutoCAD SHX Text Consulting Associates, Inc.
AutoCAD SHX Text P.O. Box 50644
AutoCAD SHX Text Columbia, SC
AutoCAD SHX Text 451-D Jessen Lane
AutoCAD SHX Text
(843) 725-1086
AutoCAD SHX Text
(803) 765-9421
AutoCAD SHX Text Columbia
AutoCAD SHX Text Charleston
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
151617181920 2123 2224
2526272829 303132
3435363738 33
LOCATION NO.
A & E FIRM
A & E STATE NO.
SHEET TITLE
DIVISION
PROJECT TITLE
PROJECT #:
DRAWING NO.
SHEET
DATE:
The State of
South Carolina
S
O
U
T
H
C A
R
O
L
I
N
A
A N
I
M
I
S
O
P
I
B
U S
Q
U
E
P
A
R
A
T
I
J
U
L
Y4
M
A
R
C
H
MELIOREM LAPSA LOCAVIT
Q
U I
S
S
E
P
A
R
B
I
T
AGENCY OR INSTITUTION
NO. LOCATION
REVISION DATE BY APP
APPROVAL
DRAWN BY
CHECKED BY
LANDSCAPE ARCHITECT
ENGINEERING DESIGN
ARCHITECTURAL DESIGN
PROJECT MANAGER
PROFESSIONAL SEAL (S)
PLOT DATE: 13 MARCH 2019
N:\118181\TEMPLATES - *.dwg
SCDMH NEWBERRY MHC HVAC REPLACEMENT
13 MARCH 2019
BID DOCUMENTS
REVISION DATE BY APP
MECA
J12-N072-FW
MECHANICAL SCHEDULES AND
DETAILS
M200
SPLIT SYSTEM AIR CONDITIONING SCHEDULE
SYMBOL
MANUFACTURER
MODEL NUMBER
BLOWER FAN HP
INPUT (B.T.U.H.)
OUTPUT (B.T.U.H.)
A.F.U.E.
TEMP RISE (DEG.F)
FLUE SIZE (IN.)
GAS CONN. SIZE (IN.)
MIN CIRC AMPS
MAX FUSE SIZE
VOLTAGE
UNIT WEIGHT (LBS.)
OUTSIDE AIRFLOW (C.F.M.)
REMARKS:
FURNACE
EXTERNAL S.P. (IN)
COMBUSTION FAN HP
- PRIOR TO ORDERING, CONTRACTOR SHALL VERIFY VOLTAGE AND ALL ELECTRICAL REQUIREMENTS.
- PROVIDE FURNACE WITH VARIABLE SPEED BLOWER AND COMBUSTION FAN MOTORS.
SET FURNACE AIRFLOW CONTROL DIP SWITCHES FOR CONSTANT CFM PER SCHEDULE AND ENHANCED MODE FOR
DEHUMIDIFICATION.
- PROVIDE ALUMINUM STEEL PRIMARY AND STAINLESS STEEL SECONDARY HEAT EXCHANGER AND 2 STAGE GAS
VALVE.
- PROVIDE FURNACE WITH FACTORY INSTALLED INTERNAL FILTER RACK
- COIL SHALL BE CONVERTIBLE, FIT FLUSH WITH FURNACE WITHOUT TRANSITION AND HAVE FACTORY INSTALLED TXV
AND DOUBLE SLOPED NON CORROSIVE DRAIN PAN.
- COIL TO BE OF SAME MANUFACTURER AS FURNACE AND CONDENSING UNIT AND FACTORY PAINTED TO MATCH
FURNACE
- PROVIDE WITH FULL LOUVERED COIL GUARD, CRANKCASE HEATER, HARD START KIT, 5 YR. COMPRESSOR
WARRANTY AND LOW AMBIENT COOLING OPERATION DOWN TO 30°F.
- PROVIDE MANUAL/ AUTO./ PROGRAMMABLE SELECTABLE THERMOSTAT WITH COOLING DEHUMIDIFICATION FEATURE.
SET TO MODE PER OWNER AND 50% R.H. (COORDINATE WITH EXISTING FACILITY CONTROLS)
SYMBOL
MANUFACTURER
MODEL NUMBER
AIR PRESS DROP (IN)
WIDTH (IN)
DEPTH (IN)
HEIGHT (IN)
FACE AREA (SQ. FT.)
ROWS/ F.P.I.
SEER/ EER RATING @ ARI
WEIGHT (LBS.)
DRAIN CONN. (IN.)
AIRFLOW (CFM)
GAS
COIL
COOLING
SYMBOL
MANUFACTURER
F.L.A.
MODEL NUMBER
E.A.T. (DB/WB) °F
L.A.T. (DB/WB/DP) °F
TOTAL CAP. (NET BTUH)
SENS. CAP. (NET BTUH)
R.L.A. / L.R.A.
WEIGHT (LBS.)
FAN QTY / H.P.
COMPRESSOR QTY
AMBIENT (°F.)
CONDENSING
AIR COOLED
VOLTAGE
M.C.A. / M.F.S.
UNIT
GF-5
S9V2B060U3VSA
.5
0.5
60,000
59,000
97%
36.7
3"
7.9
120/1/60
CC-5
4TXC036
77/64.5
55.1/53.4/
33,654
24,571
0.015
17-1/2
22-3/4
5.0
3/14
CU-5
TRANE
4TTA4036A3000A
1-1/8
0.77
17.0-82
208/3/60
12/20
6.1
15/12.5
GF-2
TRANE
S9V2B080U3VSA
.5
0.5
80,000
77,000
97%
50.9
3"
7.9
120/1/60
CC-2
TRANE
4TXB006DS3
77/64.5
54.9/53.3/
39,591
28,949
0.015
17-1/2
26-3/4
5.0
3/14
CU-2
TRANE
4TTA4042A3
1-1/8
0.77
11.2-84
208/3/60
15/25
6.7
14.12.2
GF-1,3,4
S9V2B080U3VSA
.5
0.5
80,000
78,000
97%
44.75
3"
13.0
120/1/60
CC-1,3,4
4TXCC009DS3
77/64.5
54.6/52.80
58,793
41,963
0.015
19-1/4
30-11/16
5.0
3/14
CU-1,3,4
TRANE
4TTA3060D3
1-1/8
0.77
11.2-84
208/3/60
15/25
7.10
13.75/11.3
NEOPRENE VIBRATION
ISOLATION PADS
CONDENSING UNIT SUPPORT DETAIL
NO SCALE
EXISTING EQUIPMENT YARD SLAB
LOUVERED COIL GUARD
SUPPORT REFRIGERANT
LINES INDEPENDENT OF UNIT
SECURE UNIT TO SLAB
THRU BASE PAN
CONDENSING UNIT.
FC
CC-1
GF-1
FC
FLOOR
HORIZONTAL CONDENSING GAS
FURNACE/COOLING COIL DETAIL
NOT TO SCALE
RE-CONNECT TO EXISTING
RETURN AIR PLENUM BOX
12" HIGH EQUIPMENT SUPPORT EQUAL TO DIVERSITECH
MODEL# HPR-12. QUANTITY AND LOCATION PER UNIT
MFG INSTALLATION INSTRUCTIONS.
M
NEW 2-POSITION
DAMPER-INTERLOCK
MOTORIZED DAMPER WITH UNIT
COMPRESSOR AND GAS VALVE.
RE-CONNECT BACK
TO EXISTING FLUE
RE-CONNECT BACK TO
EXISTING REFRIGERANT -
SEE FLOOR PLANS FOR
SPECIFIC INSTRUCTIONS
1/2" NEOPRENE ISOLATOR.
MANUAL DAMPER
24ga WELDED GALVANIZED STEEL AUXILIARY DRAIN FAN PAINTED
WITH GALVANNEAL PAINT TO PREVENT RUST. PAN TO BE 2" DEEP
AND EXTEND 3" BEYOND FURNACE AND COIL ON ALL SIDES.
MOISTURE SENSOR (SEE P-TRAP DETAIL)
FURNACE CONDENSATE DRAIN
LOCATED BELOW CABINET PER MFG
RECOMMENDATIONS
RE-CONNECT TO
EXISTING GAS PIPING
RE-CONNECT BACK TO
FURNACE CONDENSATE
REINSTALL SMOKE DETECTOR IN RETURN
AIR DUCTWORK UPSTREAM OF OUTSIDE AIR
DUCT CONNECTION. COORDINATE WITH FIRE
ALARM COMPANY.
PROVIDE BALANCING
DAMPER IN RETURN
AIR DUCT UPSTREAM
OF PLENUM
UNION
CAP
TYPICAL GAS PIPING DETAIL
NO SCALE
CAP
10 PIPE DIAMETERS
(MIN)
GAS MAIN SHUT-OFF
VALVE (TYP.)
TEE (TYP.)
DRIP LEG AND PRESSURE
MEASURING PORT
OVER-PRESSURE PROTECTION
DEVICE (OPD) PER ANSI Z21-80
PRESSURE MEASURING PORT
ROUTE AS INDICATED ON PLANS AND REDUCE
TO UNIT GAS CONNECTION AT APPLIANCE(S)
GAS SUPPLY INLET
3"MIN.
GAS PRESSURE REGULATOR
VENT DESIGNED TO PREVENT INSECT, WATER
AND FOREIGN OBJECT ENTRY. ROUTE FULL
SIZE TO APPROVED EXTERIOR LOCATION.
APPLIANCE
UNION
SEDIMENT TRAP TO BE INSTALLED
DOWNSTREAM OF THE SHUT-OFF
VALVE AND AS CLOSE TO
EQUIPMENT INLET AS PRACTICAL
DRIP LEG
3"MIN.
VERIFY GAS PRESSURE IN FIELD
PRIOR TO CONSTRUCTION
REFRIGERANT PIPE CHANNEL SUPPORT DETAIL
HANGER SPACING AND ROD SIZE
BASED ON MSS-SP69, TABLE 3 & 4
SECURE TO STRUCTURE WITH
MECHANICAL FASTENERS
PROVIDE K-FLEX 360 INSULATED
PIPE SUPPORT. PIPE SUPPORT TO
BE SAME THICKNESS AS PIPE
INSULATION AND SEALED WITH
CONTACT ADHESIVE AT ALL JOINTS.
SECURE UNINSULATED REFRIGERANT
LINE TO SUPPORT WITH B-LINE B2000
PIPE CLAMPS OR EQUAL.
SECURE THREADED RODS
TO STRUT WITH CHANNEL
NUTS WITH SPRINGS
PROVIDE B-LINE B1999
VIBRA-CUSHION OR EQUAL.
PROVIDE B-LINE B2000
PIPE CLAMPS OR EQUAL.
NO SCALE
WEIGHT (EXCLUDING CURB) (LBS.)
DAMPER SIZE (IN)
REMARKS:
LOCATION
ROOF/WALL OPENING SIZE (IN.)
DRIVE TYPE
VOLTAGE
FAN R.P.M.
MOTOR HORSEPOWER
STATIC PRESSURE (IN.)
AIRFLOW (C.F.M.)
MODEL NUMBER
MANUFACTURER
SYMBOL
SONES
*PRIOR TO ORDERING, CONTRACTOR SHALL VERIFY
VOLTAGE AND ALL ELECTRICAL REQUIREMENTS.
FANS DESIGNED AROUND 75CFM PER FIXTURE
PROVIDE WITH SPEED CONTROLLER, MOUNT TO SIDE
OF CABINET AND SET FOR CFM AS SPECIFIED
FAN SCHEDULE
DISCHARGE CAP NUMBER
CSP EXHAUST FAN DETAIL
CEILING
NO SCALE
FAN SHALL BE
INTERNALLY ISOLATED.
THREADED ROD.
SECURE TO STRUCTURE.
SIZE PER SCHEDULE.
EXHAUST FAN
SIZE PER SCHEDULE
EF-1
GREENHECK
CSP-A2150
.625
DIRECT
28x6
EXIST GH
3.0
FRACT
115/1/60
MEZZANINE
REFRIG (CHARGE)
CONDENSATE "P-TRAP" DETAIL
J = SCHEDULE FAN STATIC + 1"
H = TWO PIPE DIAMETERS
L = H + J + ONE PIPE DIAMETER
H
J
NO SCALE
L
UNIT
CLEAN OUT UNION (TYP.)
SIZE PER
FLOOR PLANS.
CAPPED CLEAN OUT TEE
ROUTE INSULATED CONDENSATE
DRAIN PER FLOOR PLANS. SLOPE
1/8" PER FOOT.
NO SCALE
THREADED
ROD
MECHANICAL
FASTNERS
WALL
INSULATION
CONDENSATE
PIPE
EXTENSION SPLIT
PIPE CLAMP EQUAL
TO B-LINE 3198R
FLANGE EQUAL
TO B-LINE B3199
PIPE SUPPORT STAND OFF
DETAIL (WALL)
REFRIGERANT PIPE SUPPORT DETAIL
2'-0"
NO SCALE
SECURE GALVANIZED CORNER
ANGLES TO UNI-STRUT SUPPORT
AND TUBING WITH MECHANICAL
FASTENERS.
1-1/2"x1-1/2" MECHANICAL TUBING, 3'-0" LONG. CEMENT IN PLACE.
12 GA. GALVANIZED STEEL
CHANNEL EQUAL TO B-LINE B22A
PROVIDE K-FLEX 360 INSULATED PIPE
SUPPORT. PIPE SUPPORT TO BE SAME
THICKNESS AS PIPE INSULATION AND
SEALED WITH CONTACT ADHESIVE AT
ALL JOINTS.
SECURE INSULATED REFRIGERANT
LINE TO SUPPORT WITH B-LINE
B2000 PIPE CLAMPS OR EQUAL.
SECURE UNINSULATED
REFRIGERANT LINE TO
SUPPORT WITH B-LINE B2000
PIPE CLAMPS OR EQUAL.
PROVIDE B-LINE B1999
VIBRA-CUSHION OR EQUAL.
ALL EXTERIOR PIPING TO HAVE TWO COATS OF
GRAY FINISH WITH A .016" THICK ALUMINUM
JACKET SECURED WITH STAINLESS STEEL
BANDS FOR PROTECTION OF INSULATION.
1 GENERAL REVISIONS 4/17/19 JAS
AutoCAD SHX Text
NO. C00097
AutoCAD SHX Text
ASSOCIATES
AutoCAD SHX Text
CONSULTING
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text Z
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text U
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text No. 18709
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text Mechanical Engineering
AutoCAD SHX Text Consulting Associates, Inc.
AutoCAD SHX Text P.O. Box 50644
AutoCAD SHX Text Columbia, SC
AutoCAD SHX Text 451-D Jessen Lane
AutoCAD SHX Text
(843) 725-1086
AutoCAD SHX Text
(803) 765-9421
AutoCAD SHX Text Columbia
AutoCAD SHX Text Charleston
Newberry MHC Equipment Summary
Outdoor Condensing Unit
Symbol Model Number MFG Type Voltage Nom. Tonnage
CU - 1 4TTA4060A3 Trane DX Condensing Unit 200/230-3-60 5
CU - 2 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4
CU - 3 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4
CU - 4 4TTA4060A3 Trane DX Condensing Unit 200/230-3-60 5
CU - 5 4TTA4060A3 Trane DX Condensing Unit 200/230-3-60 5
CU - 6 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4
CU - 7 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4
Gas Furnace
Symbol Model Number MFG Type Voltage 2nd Stage Input AFUE
GF-1 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
GF - 2 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
GF - 3 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
GF - 4 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
GF - 5 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
GF - 6 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
GF - 7 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96
Cooling Coil
Symbol Model Number MFG Type Airflow (cfm) Nom. Tonnage
SHP - 1 4TXCC009DS3HC Trane DX Cooling Coil 1750 5
SHP - 2 4TXCC007DS3HC Trane DX Cooling Coil 1400 4
SHP - 3 4TXCC007DS3HC Trane DX Cooling Coil 1400 4
SHP - 4 4TXCC009DS3HC Trane DX Cooling Coil 1750 5
SHP - 5 4TXCC009DS3HC Trane DX Cooling Coil 1750 5
SHP - 6 4TXCC007DS3HC Trane DX Cooling Coil 1400 4
SHP - 7 4TXCC007DS3HC Trane DX Cooling Coil 1400 4
Fan
Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)
EF-1 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-2 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237
EF-3 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-4 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237
EF-5 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-5 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-6 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-7 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-8 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-9 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25
EF-10 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237
EF-11 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237
Drawing List:
CS-1 Cover Sheet
M-100 Mechanical Existing Conditions
M-101 Mechanical Demolition and Renovation Plan
M-102 Mechanical Exhaust Fan Demo and Renovation Plan
M-200 Mechanical Schedules and Details
Site Location Map
International Existing Building Code: 2015 Edition
International Building Code: 2015 Edition
International Mechanical Code: 2015 Edition
National Electric Code: 2014 Edition
International Energy Conservation Code: 2009 Edition
New Construction X Renovation (Existing Building) Upfit Addition
Code Compliance:
Project #: J12-9774-FW
MECA
Charleston Office
451-D Jessen Lane
Wando, South Carolina
Phone: (843) 725-1086
Columbia Office
P.O. Box 50644
Columbia, South Carolina
Phone: (803) 765-9421
BID DOCUMENT DATE:
MECA Project Number: 118180
SEPTEMBER 10, 2019
SCDMH NEWBERRY MHC HVAC REPLACEMENT
2043 Medical Park Dr, Newberry, SC 29108
AutoCAD SHX Text Mechanical Engineering
AutoCAD SHX Text Consulting Associates, Inc.
AutoCAD SHX Text The State of
AutoCAD SHX Text South Carolina
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text Q
AutoCAD SHX Text
AutoCAD SHX Text
LAPSA
AutoCAD SHX Text
MELIOREM
AutoCAD SHX Text S
AutoCAD SHX Text
LOCAVIT
AutoCAD SHX Text
MARCH
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text R
AutoCAD SHX Text
JULY
BREAK
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
151617181920 2123 2224
2526272829 303132
3435363738 33
LOCATION NO.
A & E FIRM
A & E STATE NO.
SHEET TITLE
DIVISION
PROJECT TITLE
PROJECT #:
DRAWING NO.
SHEET
DATE:
The State of
South Carolina
S
O
U
T
H
C A
R
O
L
I
N
A
A N
I
M
I
S
O
P
I
B
U S
Q
U
E
P
A
R
A
T
I
J
U
L
Y4
M
A
R
C
H
MELIOREM LAPSA LOCAVIT
Q
U I S
S
E
P
A
R
B
I
T
AGENCY OR INSTITUTION
NO. LOCATION
REVISION DATE BY APP
APPROVAL
DRAWN BY
CHECKED BY
LANDSCAPE ARCHITECT
ENGINEERING DESIGN
ARCHITECTURAL DESIGN
PROJECT MANAGER
PROFESSIONAL SEAL (S)
PLOT DATE: 10 SEPTEMBER 2019
N:\118180\TEMPLATES - *.dwg
SCDMH NEWBERRY MHC HVAC REPLACEMENT
06 AUGUST 2019
BID DOCUMENTS
REVISION DATE BY APP
MECA
CONDENSING
UNIT YARD
AREA OF
WORK
J12-9774-FW
JAS
BGW JOB#: 118180
MECHANICAL EXISTING
CONDITIONS
M100
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS (CONDENSING UNIT YARD)
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
MECHANICAL EXISTING CONDITIONS
AutoCAD SHX Text
NO. C00097
AutoCAD SHX Text
ASSOCIATES
AutoCAD SHX Text
CONSULTING
AutoCAD SHX Text
ENGINEERING
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text Z
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text U
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text No. 18709
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text Mechanical Engineering
AutoCAD SHX Text Consulting Associates, Inc.
AutoCAD SHX Text P.O. Box 50644
AutoCAD SHX Text Columbia, SC
AutoCAD SHX Text
(803) 765-9421
Columbia
CONTRACTOR TO REMOVE COOLING COIL/GAS FURNACE
AS INDICATED. EXISTING CONDENSATE ,REFRIGERANT,
GAS LINE TO REMAIN IN PLACE. RECONNECT TO
EXISTING FLUE. VERIFY CONNECTION PLACEMENTS IN
FIELD.
EXISTING REFRIGERANT TO BE RECLAIMED/RECOVERED
AND DISPOSED OF PROPERLY AND IN ACCORDANCE
WITH THE REQUIREMENTS OF 40 CFR PART 82, SUBPART
F. EXISTING LINES TO BE CLEANED, TESTED, AND
RE-USED FOR NEW SYSTEM. (TYPICAL OF 7)
EXISTING RETURN AIR
DUCTS AND OUTSIDE AIR
DUCTS TO REMAIN.
RE-CONNECT BACK TO
NEW UNIT AS INDICATED.
(TYPICAL OF 5)
CONTRACTOR TO REMOVE
EXISTING MOTORIZED DAMPER
IN EXISTING GRAVITY HOOD.
EXISTING GRAVITY HOOD TO
REMAIN. (TYPICAL OF 2) REFER
TO RENOVATION PLANS FOR
NEW WORK.
CONTRACTOR TO TRANSITION
FROM UNIT OPENING TO EXISTING
SUPPLY DUCT. VERIFY EXACT
DUCT SIZE IN FIELD WITH EXISTING
CONDITIONS PRIOR TO DUCT
FABRICATION. (TYPICAL OF 7)
CONTRACTOR TO TRANSITION
FROM UNIT OPENING TO
EXISTING RETURN DUCT.
VERIFY EXACT DUCT SIZE IN
FIELD WITH EXISTING
CONDITIONS PRIOR TO DUCT
FABRICATION. (TYPICAL OF 7)
M
CONTRACTOR TO PROVIDE NEW
MOTORIZED DAMPER IN
EXISTING OUTSIDE AIR DUCT.
VERIFY EXACT VOLTAGE WITH
EXISTING CONDITIONS PRIOR TO
ORDERING. SEE GF/CC DETAIL.
(TYPICAL OF 7)
EXISTING OUTSIDE AIR
GRAVITY HOOD AND
DUCTWORK TO REMAIN IN
PLACE. (TYPICAL OF 2)
GF/CC-1
G F
C
C
GF/CC-2
G F
C
C
GF/CC-3
GF/CC-5
G F
C
C
M
M
M
M
M
M
CU-1
CONTRACTOR TO RE-CONNECT TO EXISTING
REFRIGERANT LINES. CONTRACTOR TO ENSURE
EXISTING REFRIGERANT IS PROPERLY
EVACUATED, DISPOSED OF PROPERLY, AND LINES
CLEANED THOROUGHLY TO MEET NEW
REFRIGERANT REQUIREMENTS. (TYPICAL OF 7)
CU-4
CU-7
CU-6
EXISTING REFRIGERANT
SLEEVES THRU SLAB.
CONNECT EXISTING
REFRIGERANT LINES TO
NEW CU- (TYPICAL)
CU-5CU-3
CU-2
CU-6
CU-4
CU-3
CU-2
CU-5
CU-1
CU-7
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
151617181920 2123 2224
2526272829 303132
3435363738 33
LOCATION NO.
A & E FIRM
A & E STATE NO.
SHEET TITLE
DIVISION
PROJECT TITLE
PROJECT #:
DRAWING NO.
SHEET
DATE:
The State of
South Carolina
S
O
U
T
H
C A
R
O
L
I
N
A
A N
I
M
I
S
O
P
I
B
U S
Q
U
E
P
A
R
A
T
I
J
U
L
Y4
M
A
R
C
H
MELIOREM LAPSA LOCAVIT
Q
U I S
S
E
P
A
R
B
I
T
AGENCY OR INSTITUTION
NO. LOCATION
REVISION DATE BY APP
APPROVAL
DRAWN BY
CHECKED BY
LANDSCAPE ARCHITECT
ENGINEERING DESIGN
ARCHITECTURAL DESIGN
PROJECT MANAGER
PROFESSIONAL SEAL (S)
PLOT DATE: 10 SEPTEMBER 2019
N:\118180\TEMPLATES - *.dwg
SCDMH NEWBERRY MHC HVAC REPLACEMENT
06 AUGUST 2019
BID DOCUMENTS
REVISION DATE BY APP
MECA
CONDENSING
UNIT YARD
AREA OF
WORK
J12-9774-FW
JAS
BGW JOB#: 118180
MECHANICAL RENOVATION AND
DEMOLITION PLAN
SCALE : 1/8" = 1' ---- 0"
M101
MECHANICAL DEMOLITION PLAN (MEZZANINE LEVEL)
SCALE : 1/4" = 1' ---- 0"
MECHANICAL RENOVATION PLAN (MEZZANINE…