Scope of Work.pdf

PDF 13 MB Posted

Attached to
BECKMAN MHC'S HVAC MAINTENANCE
Solicitation number
5400020310
Issued by
Richland County, South Carolina

About this file

This Scope of Work document outlines an HVAC maintenance and repair agreement for the South Carolina Department of Mental Health covering three Beckman Mental Health Center facilities located in Greenwood, Clinton (Laurens), and Newberry. The contract solicits bids from licensed mechanical contractors to provide comprehensive maintenance and repair services for HVAC systems including split system DX dedicated outside air units with hot water heat, air-cooled chillers, natural gas boilers, pumps, chilled water/hot water fan coil units, blower coil units, ductless split systems, and associated controls and ductwork. The agreement requires a minimum of four annual inspections with documentation, and contractors are encouraged to visit all three facilities prior to bidding for equipment verification. The selected contractor will have thirty days to review existing equipment conditions and submit a list of items requiring correction with cost estimates before commencing work. The contract term and renewal options are not specified in the document; however, the scope indicates this is an ongoing maintenance agreement covering normal and preventive maintenance as an all-inclusive, one-price-covers-all arrangement for parts and labor with specific exceptions for lightning damage, acts of God, and vandalism.

The maintenance and repair agreement explicitly excludes exterior painting of non-moving parts, lightning damage, acts of God, and vandalism from coverage; the contractor bears responsibility for these items as contract extras but assists the owner with insurance claim filing. All maintenance calls placed before 9:00 AM require same-day onsite service, while calls after 9:00 AM require same or next-day service, with lack of response potentially grounds for contract cancellation. The contractor must carry insurance as specified in the bid solicitation, provide a Certificate of Insurance, utilize approved water treatment services (preferably Nalco Water), and comply with all EPA refrigerant recovery and recycling requirements per 40 CFR Part 82, Subpart F and ASHRAE guidelines. The contractor must use Merv 8 filters or higher as specified, work with Trane factory-trained technicians for the existing EMS control system, and route all correspondence, billings, and quarterly reports to the contract manager Paul Wilson at Physical Plant Services. Specific equipment lists detailing manufacturers, model numbers, tonnages, and voltages are provided for all three facilities, and the contractor is responsible for hauling and lawful disposal of all used parts, oils, and refrigerants.

View the file

Other files

File Type Posted
Solicitation.doc DOC document
Amendment 1.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC MAINTENANCE REQUEST PROPOSAL

BECKMAN MENTAL HEALTH CENTER (Three Locations)

Beckman Mental Health Center HVAC Maintenance Proposal Page 1 of 6

1.0 INVITATION

A. Licensed mechanical contractors are invited to submit bids on a maintenance and repair agreement for the three (3) facilities listed below that are part of the Beckman Center for Mental Health Services.

Name: Beckman Center Administration Address: 1547 Parkway, Suite 100, Greenwood, SC 29646 Phone: 864-229-7120 or 864-993-9338 Contact: Koshay Arnold

Name: Laurens MHC Address: 442 Professional Park Road, Clinton, SC 29325 Phone: 864-547-8280 or 864-980-6553 Contact: Heidi Hoogstraal

Name: Newberry MHC Address: 2043 Medical Park Drive, Newberry, SC 29108 Phone: 803-768-8106 or 803-940-6203 Contact: Lori Pruitt

B. Equipment in scope under this contract includes moving and non-moving parts for split system DX dedicated outside air units with hot water heat, air-cooled chiller, natural gas boiler, pumps, chilled water/hot water fan coil units and blower coil units, ceiling style and inline fans, ductless split system, intake/relief units zone dampers, time-clocks, controls, control systems, piping, filters, ductwork and other components listed in requirements.

C. Contractor is encouraged to visit the buildings indicated above prior to the bid for observation and verification of the information provided in this document.

1.1 AGREEMENT INTENT

A. The maintenance and repair agreement to cover all aspects of HVAC normal and preventive maintenance as a one price covers all agreement to include parts and labor on moving and non-moving parts with the following exceptions:

1. Lighting Damage: While the contractor will be reimbursed for lightning damage claims, the contractor will be expected to accomplish the following at no charge to the owner.

a. Provide immediate information to the owner’s representative that equipment has been damaged before repairs are begun.

b. Provide photographic evidence that the lightning damage has occurred.

c. Assist the owner in filing insurance claims.

2. Acts of God.

3. Vandalism.

Beckman Mental Health Center HVAC Maintenance Proposal Page 2 of 6

1.2 FORMAT

A. The agreement is a multi-page document which is to be signed by both the Department of Mental Health and the maintenance contractor. The following items will be attached to the contract agreement.

1. A listing of the equipment to be covered under this agreement.

2. Each piece of HVAC equipment will be listed to include the following as available.

Equipment Capacity Manufacturer’s Name Model Number Voltage

B. A Certificate of Insurance from the contractor to the Owner is required as listed in the DMH bid solicitation document.

C. Equipment inspection sheet. This sheet will be completed at each quarterly inspection visit.

See suggested attached sheet.

D. Additional items to be covered at the request of the Owner (see EE on page 5).

1. Cover all items requested by the owner not mentioned in the annual maintenance agreement.

2. Reference EE on page 5 for additional installed equipment.

1.3 REQUIREMENTS OF THE STANDARD MAINTENANCE & REPAIR AGREEMENT

A. The maintenance and repair contractor will provide a minimum of four (4) inspections annually which are to be documented (see attached inspection sheet). Timing for equipment or system shut-downs necessary for proper inspections to be coordinated with the facility prior to inspections.

B. Furnish all labor and supplies necessary to make repairs, adjustments, routine and preventive maintenance (PM) to keep the equipment operating efficiently year-round.

C. Furnish coverage on non-moving parts that included but not limited to starters, controls, control systems, oil and refrigerant piping. All ductwork either fiberglass or sheet metal is covered. Exterior painting of non-moving parts is excluded from this contract.

D. Conduct an evaporator coil and condenser coil cleaning on an annual basis. The contractor will visually inspect each coil on the quarterly visit and clean more often if needed.

E. Provide coverage for motor starters and/or variable speed drives.

F. Provide seasonal startup/shutdown/change over inspection of all air type and water type air conditioning equipment including economizer controls.

G. Supply new compressor oil, oil filters, refrigerant filters and dryers after any compressor failure or change.

HVAC Maintenance Proposal Page 3 of 6

H. Check for refrigerant leaks, repair leaks and replace any refrigerant lost to ensure optimum performance of the HVAC equipment.

I. Provide coverage for miscellaneous replacement of controls components for all HVAC equipment.

J. Check superheat on expansion valve and calibrate as required.

K. Check refrigerant circuit for expansion valve operations.

L. Lubricate all moving parts.

M. Clean all drain pans and drains as needed with a minimum of once per year.

N. Check operating pressures with gauges and record on quarterly inspection report. At the time the pressure readings are taken, note the supply air temperature, return air temperature and the outdoor air temperature. List outdoor temperature under remarks.

O. Calibrate and adjust operating and safety controls.

P. Check all belts and adjust or replace as needed.

Q. Check all equipment for unusual noise and vibration and repair or replace the causes of the noise condition as needed.

R. Check electrical connections for tightness.

S. Provide filter changes quarterly or more frequently if needed. Merv 8 filters by Farr/Camfil or equal are required unless higher efficiency rated filters are required as noted on plans.

Contractor to field verify sizes and thickness of filters in each facility.

T. Exhaust fan grilles and internal blower / cabinet to be cleaned annually.

U. Keep the Owner informed or upgrades and improvements to prolong equipment life and reduce the cost of operation during the life of the contract.

V. Specific to natural gas-fired boilers and furnaces, and in conjunction with the quarterly inspections and PM (routine, listed and per manufacturer) : prior to the heating season, test and adjust combustion efficiency in gas fired equipment to optimum performance.

Corrective actions performed to be included in the reports along with checklist in the unit report.

W. The maintenance and repair contractor will carry insurance as required in the bid solicitation.

X. Specific to the air-cooled chiller, inspections and PM to include and not limited to refrigerant pressures, oil tested for acidity with corrective actions as necessary for proper operation, amps readings, water pressures, water temperatures, controls, etc. This data and other checklist items along with manufacturer specific PM measures and corrective actions performed to be included in the reports.

HVAC Maintenance Proposal Page 4 of 6

Y. Chemical treatment of the chilled and hot water loops to be properly maintained by independent laboratory providing labor and chemicals complete. Water samples of each loop to be analyzed quarterly or more frequently if required for proper water quality. Test to include dissolved solids and PPM levels for corrosion inhibitor and biocide with chemicals added to the loops to achieve and maintain the recommended water chemistry of the preferred chemical treatment company.

Z. As provided under this maintenance contract, the preferred water treatment company for the South Carolina Department of Mental Health is:

Nalco Water Josh Frady (local rep) 118 S. Stallion Drive Cowpens, SC 29330 864-612-3090

Joshua.frady@ecolab.com

It is not mandatory that Nalco Water be utilized. However, other firms deemed qualified to be vetted by the agency and engineer for approval prior to work being performed.

AA. The maintenance and repair contractor will not release, nor cause to be released, accidentally or otherwise, any chlorofluorocarbons (refrigerant) into the air. All refrigerant must be reclaimed and recycled according to the latest state and federal governmental requirements and guidelines as published by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

BB. Lightning damage, acts of God, and vandalism are not covered under this agreement. The contractor will be responsible for any repairs needed due to these causes as an extra to the contract. The contractor will assist the Owner in filing insurance claims and will notify the Owner prior to repairs to allow for documentation to the insurance company. Lack of notice prior to repairs may void the ability of the contractor to be paid for collectible repairs.

CC. All calls to Department of Mental Health should be deemed a priority call. All maintenance repair calls placed before 9:00 AM will have same day onsite service. All maintenance repair calls placed after 9:00 AM will have same or next day onsite service. Lack of response by the contractor may be considered cause to cancel the contract.

DD. The contractor is responsible for the hauling and lawful disposal of all used parts, oil, refrigerant, etc.

EE. The maintenance contractor will be required at the beginning of each contract year and prior to the first quarterly inspection to contact physical plant services (Paul Wilson, Project Manager) at 803-935-5636 and set up a meeting with a representative from Physical Plant Services to conduct one or more joint inspections of the HVAC system maintenance.

HVAC Maintenance Proposal Page 5 of 6

FF. All correspondence between the mental health facility and the maintenance contract including billings, letters, and quarterly reports to be emailed in PDF to the contract manager and designated facility representative.

South Carolina Department of Mental Health Physical Plant Services Mr. Paul Wilson (Contract Manager) 7901 Farrow Road, Building 4 PPSE, Columbia SC 29203 Phone: 803-835-5636 Cell: 803-667-2893 Email: paul.wilson@scdmh.org

GG. The contractor selected to do the work will be allowed thirty (30) days in which to review the condition of the existing equipment in all locations. The contractor will be expected to generate a list of any items which need to be corrected before his firm begins the contract.

Along with the list of items, the contractor is expected to send the cost estimated to remedy the problem. The Department of Mental Health has several options:

1. If DMH does not agree with any of the items presented, they may veto its implementation.

2. If DMH does not agree with the pricing, there are several options.

a. They may elect to correct the items with in-house personnel.

b. They may authorize the contractor to proceed with corrections at the price quoted.

c. They may take bids from other contractors in hopes of getting a price lower than the quoted amount and getting repairs done by other.

HH. When parts are no longer available, all repair request must be directed in advance of equipment order or work performed to the agency contract manager. Labor continues to be covered under the terms of this contract.

II: Questions arising from this agreement should be referred to the Director of Physical Plant Services for the South Carolina Department of Mental Health or his designated representative. Attachments to this agreement include.

1. A listing of the equipment to be covered under this agreement.

2. A certificate of insurance from the contractor to the owner.

3. HVAC drawings in PDF are included where they are available.

4. Equipment inspection sheet.

5. Attached filter checklist must be posted and updated on site.

JJ. Should additional HVAC equipment be added to a facility, the additional equipment will be added to this contract in the same unit pricing ($ / ton) as the equipment originally covered under the original terms of this contract.

KK. For reference, an EMS system is utilized at Beckman; Trane controls is the vendor. The contractor to be fully knowledgeable with the system with Trane factory trained technicians.

HVAC Maintenance Proposal Page 6 of 6

THIS AGREEMENT IS ENTERED INTO BY:

CONTRACTOR:

Signature Date

Name Title

OWNER:

South Carolina Department of Mental Health

Signature Date

Name Title

S.C DEPARTMENT OF MENTAL HEALTH

SUGGESTED SAMPLE HVAC UNIT REPORT

Date: _________________

Facility: __________________________ Address _______________________________________________

Manufacturer ______________ Unit Model ___________________________________ Tag _____________

Age (yrs) ________________

Discharge press __________________ Suction press _______________ Suction temp___________________

Liquid temp _____________________ Superheat _________________ Subcooling ____________________

Evap. temp in ____________________ Evap. temp out _____________ Outdoor duct temp ______________

Ambient Temp ___________________ Chilled water EWT _________ Chilled water LWT ______________

Hot water EWT __________________ Hot water LWT ____________

Evap. fan FLA _______________ Condenser fan FLA _______________

Compressor RLA ____________ LRA ___________________________

Unit voltage ________________

Yes / No

Properly charged: ________

Suction drier installed: ________

Condenser coil clean: ________

Are fins bent: ________

Evaporator coil clean: ________

Any duct leaks: ________

T’stats / controls OK: ________

Boiler burners sequenced: _____

Yes / No

Dampers operation OK: ________

Insulation OK: ________

Pump bearings OK: ________

Pump couplings OK: ________

Chiller operation OK: ________

Compressor oil OK: ________

Boiler burners cleaned: ________

Gas leaks: ________

Yes / No

Electrical components & safety controls confirmed: ________

Electrical connections properly installed/secured: ________

Confirm condensate overflow switch operation: ________

Chemical treatment in water loops properly maintained: ________ continued

S.C DEPARTMENT OF MENTAL HEALTH

SUGGESTED SAMPLE HVAC UNIT REPORT

Yes / No

Condensate drain and pan properly installed and draining: ________

Check evaporator fan condition, motor operation and bearings: ________

Check condenser fan condition, motor operation and bearings: ________

Relubrication of dirty bearings necessary: ________

Crackcase heater installed and operating: ________

Air filters installed and clean: ________

Is unit operating properly: ________

Unit panels properly installed and secured: ________ ________

Electrical panel and boxes properly installed and secured: ________

O&M manual / PM checklist reviewed & completed: ________

Boiler vent and intake properly installed: ________

Boiler and combustion system in proper condition and operating at peak performance: ________________

The following corrective action is required:

Additional comments:

Technician’s name: ______________________________________________________

Customer’s signature: _______________________________________________________

Phone: _______________________

S.A.#______________

FILTER CHANGE LOG

HVAC UNIT NO. ___________

Date Existing filter (clean / dirty) Signature of technician Date changed

Note: Filter Change Log is required on all HVAC Units at all locations.

Beckman MHC Equipment Summary

Air Cooled Chiller

Symbol Model Number MFG Type Voltage Nom. Tonnage

CH-1 RTAA100 4XM01A3 Trane Air-Cooled Chiller 460-3-60 100

Gas Boiler

Symbol Model Number MFG Type Voltage Total Input AFUE

B-1 H3-1125 Raypack hot water boiler 120-1-60 1,124,700 BTUH 82

Pumps

Symbol Model Number MFG Type Voltage Flow / TDH

HWP-1 FE1510E2E1FA0 Taco End Suction Pump per label 90 GPM @ 80 FT

CWP-1 FE2510E2F1F4L0A Taco End Suction Pump per label 240 GPM @ 90 FT

CWPB-1 FE2510E2F1F4L0A Taco End Suction Pump per label 240 GPM @ 90 FT

Blower Coils (chilled and hot water)

Symbol Model Number MFG Type Voltage Cooling Coil Capacity Htg Coil Capacity Arflow (CFM)

BC-1 BCHB0542DF0A Trane Blower Coil per unit label 59,100 42,900 1,800

BC-2 BCHB0362DF0A Trane Blower Coil per unit label 41,200 35,200 1,200

BC-3 BCHB0182D Trane Blower Coil per unit label 22,200 11,500 600

BC-6 BCHB0242 Trane Blower Coil per unit label 30,200 22,900 800

BC-7 F3EH090A33A Trane Blower Coil per unit label 61,300 90,500 1,800

BC-10 BCHBO24 - confirm Trane Blower Coil per unit label 34,500 24,000 800

BC-11 BCHB242DF Trane Blower Coil per unit label 25,500 11,000 800

BC-13 BCHB0362D Trane Blower Coil per unit label 42,000 28,200 1,200

BC-14 BCHB182DF Trane Blower Coil per unit label 22,000 9,500 600

BC-17 BCHB0362D Trane Blower Coil per unit label 43,200 28,500 1,200

BC-19 BCHB0242D Trane Blower Coil per unit label 27,500 16,900 800

BC-20 BCHB05442 Trane Blower Coil per unit label 72,800 54,400 1800

BC-21 BCHB0242D Trane Blower Coil per unit label 33,200 24,800 800

BC-24 BCHB024D Trane Blower Coil per unit label 25,200 13,200 800

BC-25 BCHB0362D Trane Blower Coil per unit label 35,900 17,600 1200

BC-30 BCHB0362D Trane Blower Coil per unit label 39,600 28,200 1200

BC-36 BCHB0542D Trane Blower Coil per unit label 62,900 36,700 1800

BC-37 BCHB0542D Trane Blower Coil per unit label 67,600 40,500 1800

BC-40 BCHB0182D Trane Blower Coil per unit label 22,200 8,400 600

BC-43 BCHB0182D Trane Blower Coil per unit label 24,200 16,000 600

Fan Coils (chilled and hot water)

Symbol Model Number or S/N MFG Type Voltage Cooling Coil Capacity Htg Coil Capacity Arflow (CFM)

FC-4 F5A594AU Trane Fan Coil per unit label 5300 5800 220

FC-5 F5A594AT Trane Fan Coil per unit label 18,700 16,700 610

FC-8 FTSA594AV Trane Fan Coil per unit label 24,900 18,700 1,025

FC-9 F5A594AW Trane Fan Coil per unit label 24,900 18,700 1,025

LPC-12 CPCAA08D2C Trane Fan Coil per unit label 134,900 96,900 4,000

FC-15 F5HS94AX Trane Fan Coil per unit label 11,700 6400 390

FC-16 FCCB1003KN0F Trane Fan Coil per unit label 27,600 18,100 1,025

FC-18 FCCB1003KNOF Trane Fan Coil per unit label 16,800 13,500 4,000

FC-22 FCCB1003KNQFQ Trane Fan Coil per unit label 24,900 18,700 1,025

FC-23 FCCB100-confirm Trane Fan Coil per unit label 20,000 12,000 735

FC-26 FCCB0603K Trane Fan Coil per unit label 15,000 8,900 610

FC-27 F5A594AF Trane Fan Coil per unit label 9,500 5,800 390

FC-28 F5A594AG Trane Fan Coil per unit label 11,500 6,500 390

FC-29 F5A94AH Trane Fan Coil per unit label 16,200 9,200 610

FC-31 F5A594AJ Trane Fan Coil per unit label 15,300 10,800 610

FC-32 FCCB0403K Trane Fan Coil per unit label 8600 5700 390

FC-33 FCCB0403K Trane Fan Coil per unit label 10000 6000 390

FC-34 FCCB0403K Trane Fan Coil per unit label 12600 6500 390

FC-38 FCCB0803K Trane Fan Coil per unit label 20200 11400 735

FC-39 FCCB0403D Trane Fan Coil per unit label 11400 6100 390

FC-41 FCCB0603KN Trane Fan Coil per unit label 21000 16000 735

FC-42 ASURL2 Trane Fan Coil per unit label field verify field verify field verify

FC-44 F5A594AS Trane Fan Coil per unit label 14600 12400 610

Ductless Split Outdoor AC

Symbol Model Number MFG Type Voltage Nom. Tonnage

DSS-42 MU09TW Mitsubishi DX Outdoor CU 115-1-60 0.75

Ductless Split Indoor AC Unit

Symbol Model Number MFG Type Voltage Nom. Tonnage

DSS-42 MS09TW Mitsubishi DX Indoor Wall Mount 115-1-60 0.75

DOAU Outdoor Condensing Units

Symbol Model Number MFG Type Voltage Nom. Tonnage Low Ambient HGRH

CU-1 TTA12044CAB--AE Trane DX Condensing Unit 460-3-60 10 Yes Yes

CU-1 TTA12044CAB--AE Trane DX Condensing Unit 460-3-60 10 Yes Yes

CU-1 TTA12044CAB--AE Trane DX Condensing Unit 460-3-60 10 Yes Yes

DOAU Air Handling Units (DX coil with hot water heating coil)

Symbol Model Number MFG Type Voltage Cooling Coil Capacity Htg Coil Capacity Arflow (CFM)

DOAU-1 BCCD060G1--E53L4Z Trane Blower Coil 460-3-60 116,460 126,670 1,200

DOAU-1 BCCD060G1--E53L4Z Trane Blower Coil 460-3-60 116,460 126,670 1,200

DOAU-1 BCCD060G1--E53L4Z Trane Blower Coil 460-3-60 116,460 126,670 1,200

Fans

Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)

CCF-1 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-2 VCDD020C Carnes T-stat 120-1-60 190 0.125

CCF-3 GC-166 COOK Wall Switch 120-1-60 140 0.25

CCF-4 GC-186 COOK Wall Switch 120-1-60 210 0.25

CCF-5 VCDD020C Carnes T-stat 120-1-60 190 0.125

CCF-6 VCDD015C Carnes Wall Switch 120-1-60 105 0.25

CCF-7 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-8 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-9 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-10 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-11 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-12 VCDD030C Carnes T-stat 120-1-60 285 0.125

CCF-13 VCDD040C Carnes T-stat 120-1-60 400 0.125

CCF-14 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-15 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-16 GC-148 COOK Wall Switch 120-1-60 70 0.25

CCF-17 VCDD020C Carnes T-stat 120-1-60 190 0.125

CCF-18 VCDD020C Carnes T-stat 120-1-60 190 0.125

CCF-19 GC-166 COOK Wall Switch 120-1-60 140 0.25

CCF-20 GC-166 COOK Wall Switch 120-1-60 140 0.25

CCF-21 VCDD020C Carnes T-stat 120-1-60 190 0.125

CCF-22 GC-166 COOK Wall Switch 120-1-60 140 0.25

CCF-23 VCDD015C Carnes Wall Switch 120-1-60 105 0.25

ILF-1 VIBK06 Carnes EMS 120-1-60 280 0.375

ILF-2 VIBK08 Carnes EMS 120-1-60 360 0.375

ILF-3 VIBK06 Carnes EMS 120-1-60 200 0.375

ILF-4 VIBK06 Carnes EMS 120-1-60 240 0.375

ILF-5 VIBK08 Carnes EMS 120-1-60 600 0.375

ILF-6 VIBK06 Carnes EMS 120-1-60 295 0.375

Laurens MHC Equipment Summary

Outdoor Condensing Unit

Symbol Model Number MFG Type Voltage Nom. Tonnage

CU - 1 4TTA3060D3 Trane DX Condensing Unit 200/230-3-60 5

CU - 2 4TTA4042A3 Trane DX Condensing Unit 200/230-3-60 3.5

CU - 3 4TTA3060D3 Trane DX Condensing Unit 200/230-3-60 5

CU - 4 4TTA3060D3 Trane DX Condensing Unit 200/230-3-60 5

CU - 5 4TTA4036A3 Trane DX Condensing Unit 200/230-3-60 3

Gas Furnace

Symbol Model Number MFG Type Voltage 2nd Stage Input AFUE

GF - 1 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97

GF - 2 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97

GF - 3 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97

GF - 4 S9V2B080U3VSA Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 97

GF - 5 S9V2B060U5PSB Trane Gas Furnace (horizontal) 120-1-60 60,000 BTUH 96

Cooling Coil

Symbol Model Number MFG Type Airflow (cfm) Nom. Tonnage

SHP - 1 4TXCC009DS3-C Trane DX Cooling Coil 1750 5

SHP - 2 4TXCB006DS3-C Trane DX Cooling Coil 1225 3.5

SHP - 3 4TXCC009DS3-C Trane DX Cooling Coil 1750 5

SHP - 4 4TXCC009DS3-C Trane DX Cooling Coil 1750 5

SHP - 5 4TXCB004DS3-C Trane DX Cooling Coil 1050 3

Fan

Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)

EF-1 CSP-A2150 Greenheck Existing 120-1-60 525 0.625

Drawing List:

CS-1 Cover Sheet

M-100 Mechanical Existing Conditions

M-101 Mechanical Demolition and Renovation Plan

M-200 Mechanical Schedules and Details

Site Location Map

International Existing Building Code: 2015 Edition

International Building Code: 2015 Edition

International Mechanical Code: 2015 Edition

National Electric Code: 2014 Edition

International Energy Conservation Code: 2009 Edition

New Construction X Renovation (Existing Building) Upfit Addition

Code Compliance:

Project #: J12-N072-FW

MECA

Charleston Office

451-D Jessen Lane

Wando, South Carolina

Phone: (843) 725-1086

Columbia Office

P.O. Box 50644

Columbia, South Carolina

Phone: (803) 765-9421

BID DOCUMENT DATE:

MECA Project Number: 118181

MARCH 13, 2019

SCDMH LAURENS HVAC REPLACEMENT

442 PROFESSIONAL PARK ROAD

CLINTON, SC 29325

AutoCAD SHX Text Mechanical Engineering

AutoCAD SHX Text Consulting Associates, Inc.

AutoCAD SHX Text The State of

AutoCAD SHX Text South Carolina

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text Q

AutoCAD SHX Text

AutoCAD SHX Text

LAPSA

AutoCAD SHX Text

MELIOREM

AutoCAD SHX Text S

AutoCAD SHX Text

LOCAVIT

AutoCAD SHX Text

MARCH

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text

JULY

AutoCAD SHX Text

AH-1

AH-2

AH-3

AH-5

AH-4

CU-1 CU-2

CU-3 CU-5 CU-4

TRANSFORMER

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

151617181920 2123 2224

2526272829 303132

3435363738 33

LOCATION NO.

A & E FIRM

A & E STATE NO.

SHEET TITLE

DIVISION

PROJECT TITLE

PROJECT #:

DRAWING NO.

SHEET

DATE:

The State of

South Carolina

S

O

U

T

H

C A

R

O

L

I

N

A

A N

I

M

I

S

O

P

I

B

U S

Q

U

E

P

A

R

A

T

I

J

U

L

Y4

M

A

R

C

H

MELIOREM LAPSA LOCAVIT

Q

U I

S

S

E

P

A

R B

I

T

AGENCY OR INSTITUTION

NO. LOCATION

REVISION DATE BY APP

APPROVAL

DRAWN BY

CHECKED BY

LANDSCAPE ARCHITECT

ENGINEERING DESIGN

ARCHITECTURAL DESIGN

PROJECT MANAGER

PROFESSIONAL SEAL (S)

PLOT DATE: 13 MARCH 2019

N:\118181\TEMPLATES - *.dwg

SCDMH NEWBERRY MHC HVAC REPLACEMENT

13 MARCH 2019

BID DOCUMENTS

REVISION DATE BY APP

MECA

CONDENSING

UNIT YARD

AREA OF

WORK

J12-N072-FW

MECHANICAL EXISTING

CONDITIONS

M100

MECHANICAL EXISTING CONDTIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

AutoCAD SHX Text

NO. C00097

AutoCAD SHX Text

ASSOCIATES

AutoCAD SHX Text

CONSULTING

AutoCAD SHX Text

ENGINEERING

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text No. 18709

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text H

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text Mechanical Engineering

AutoCAD SHX Text Consulting Associates, Inc.

AutoCAD SHX Text P.O. Box 50644

AutoCAD SHX Text Columbia, SC

AutoCAD SHX Text 451-D Jessen Lane

AutoCAD SHX Text

(843) 725-1086

AutoCAD SHX Text

(803) 765-9421

AutoCAD SHX Text Columbia

AutoCAD SHX Text Charleston

Wando, SC

AH-1

AH-2

AH-3

AH-5

AH-4

CONTRACTOR TO REMOVE COOLING

COIL/GAS FURNACE AS INDICATED.

EXISTING CONDENSATE ,REFRIGERANT,

GAS LINE TO REMAIN IN PLACE. REPLACE

EXISTING FLUE.

EXISTING REFRIGERANT TO BE

RECLAIMED/RECOVERED AND DISPOSED

OF PROPERLY. EXISTING LINES TO BE

CLEANED, TESTED, AND RE-USED FOR

NEW SYSTEM. (TYPICAL OF 5)

EXISTING RETURN AIR

DUCTS AND OUTSIDE AIR

DUCTS TO REMAIN.

RE-CONNECT BACK TO

NEW UNIT AS INDICATED.

(TYPICAL OF 5)

CONTRACTOR TO REMOVE

EXISTING EXHAUST FAN-

DUCTWORK TO REMAIN IN

PLACE

GF/CC-1

GF/CC-2

GF/CC-3

GF/CC-5

GF/CC-4

CONTRACTOR TO TRANSITION

FROM UNIT OPENING TO EXISTING

SUPPLY DUCT. VERIFY EXACT

DUCT SIZE IN FIELD WITH EXISTING

CONDITIONS PRIOR TO DUCT

FABRICATION. (TYPICAL OF 5)

CONTRACTOR TO TRANSITION

FROM UNIT OPENING TO EXISTING

RETURN DUCT. VERIFY EXACT

DUCT SIZE IN FIELD WITH EXISTING

CONDITIONS PRIOR TO DUCT

FABRICATION. (TYPICAL OF 5)

M

M

M

M

M

CONTRACTOR TO PROVIDE

NEW MOTORIZED DAMPER

IN EXISTING OUTSIDE AIR

DUCT. VERIFY EXACT

VOLTAGE WITH EXISTING

CONDITIONS PRIOR TO

ORDERING. SEE GF/CC

DETAIL. (TYPICAL OF 5)

EXISTING OUTSIDE AIR GRAVITY

HOOD AND DUCTWORK TO REMAIN

IN PLACE. REBALANCE OUTSIDE

AIR TO CFM DESIGNATED ON

PLANS (TYPICAL OF 5)

CONTRACTOR TO RE-CONNECT

TO EXISTING FLUE. CONFIRM

MFG FLUE SIZE WITH EXISTING

FLUES. REPLACE AS

NECESSARY (TYPICAL OF 5)

EF-1

CONTRACTOR TO

RE-CONNECT NEW EF-1 TO

EXISTING DUCTWORK.

TRANSITION TO EXISTING

DUCT. VERIFY DUCT SIZE IN

FIELD.

CU-1 CU-2

CU-3 CU-5 CU-4

TRANSFORMER

CONTRACTOR TO REMOVE EXISTING

CONDENSING UNITS. DISPOSITION PER

OWNER'S DIRECTION. REFER TO

MECHANICAL RENOVATION PLAN FOR

NEW WORK. (TYPICAL OF 5)

CU-1 CU-2

CU-3 CU-5 CU-4

CONTRACTOR TO RE-CONNECT TO EXISTING

REFRIGERANT LINES. CONTRACTOR TO ENSURE

EXISTING REFRIGERANT IS PROPERLY

EVACUATED, DISPOSED OF PROPERLY, AND LINES

CLEANED THOROUGHLY TO MEET NEW

REFRIGERANT REQUIREMENTS. (TYPICAL OF 5)

TRANSFORMER

EXISTING REFRIGERANT

SLEEVES THRU SLAB.

CONNECT EXISTING

REFRIGERANT LINES TO

NEW CU- (TYPICAL)

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

151617181920 2123 2224

2526272829 303132

3435363738 33

LOCATION NO.

A & E FIRM

A & E STATE NO.

SHEET TITLE

DIVISION

PROJECT TITLE

PROJECT #:

DRAWING NO.

SHEET

DATE:

The State of

South Carolina

S

O

U

T

H

C A

R

O

L

I

N

A

A N

I

M

I

S

O

P

I

B

U S

Q

U

E

P

A

R

A

T

I

J

U

L

Y4

M

A

R

C

H

MELIOREM LAPSA LOCAVIT

Q

U I S

S

E

P

A

R

B

I

T

AGENCY OR INSTITUTION

NO. LOCATION

REVISION DATE BY APP

APPROVAL

DRAWN BY

CHECKED BY

LANDSCAPE ARCHITECT

ENGINEERING DESIGN

ARCHITECTURAL DESIGN

PROJECT MANAGER

PROFESSIONAL SEAL (S)

PLOT DATE: 13 MARCH 2019

N:\118181\TEMPLATES - *.dwg

SCDMH NEWBERRY MHC HVAC REPLACEMENT

13 MARCH 2019

BID DOCUMENTS

REVISION DATE BY APP

MECA

CONDENSING

UNIT YARD

AREA OF

WORK

J12-N072-FW

MECHANICAL RENOVATION AND

DEMOLITION PLAN

SCALE : 1/8" = 1' ---- 0"

M101

MECHANICAL DEMOLITION PLAN (MEZZANINE LEVEL)

SCALE : 1/8" = 1' ---- 0"

MECHANICAL RENOVATION PLAN (MEZZANINE LEVEL)

SCALE : 1/8" = 1' ---- 0"

MECHANICAL DEMOLITION PLAN (CONDENSING UNIT YARD )

SCALE : 1/8" = 1' ---- 0"

MECHANICAL RENOVATION PLAN (CONDENSING UNIT YARD )

SCALE : 1/8" = 1' ---- 0"

1 GENERAL REVISIONS 4/17/19 JAS

AutoCAD SHX Text

NO. C00097

AutoCAD SHX Text

ASSOCIATES

AutoCAD SHX Text

CONSULTING

AutoCAD SHX Text

ENGINEERING

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text No. 18709

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text H

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text Mechanical Engineering

AutoCAD SHX Text Consulting Associates, Inc.

AutoCAD SHX Text P.O. Box 50644

AutoCAD SHX Text Columbia, SC

AutoCAD SHX Text 451-D Jessen Lane

AutoCAD SHX Text

(843) 725-1086

AutoCAD SHX Text

(803) 765-9421

AutoCAD SHX Text Columbia

AutoCAD SHX Text Charleston

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

151617181920 2123 2224

2526272829 303132

3435363738 33

LOCATION NO.

A & E FIRM

A & E STATE NO.

SHEET TITLE

DIVISION

PROJECT TITLE

PROJECT #:

DRAWING NO.

SHEET

DATE:

The State of

South Carolina

S

O

U

T

H

C A

R

O

L

I

N

A

A N

I

M

I

S

O

P

I

B

U S

Q

U

E

P

A

R

A

T

I

J

U

L

Y4

M

A

R

C

H

MELIOREM LAPSA LOCAVIT

Q

U I

S

S

E

P

A

R

B

I

T

AGENCY OR INSTITUTION

NO. LOCATION

REVISION DATE BY APP

APPROVAL

DRAWN BY

CHECKED BY

LANDSCAPE ARCHITECT

ENGINEERING DESIGN

ARCHITECTURAL DESIGN

PROJECT MANAGER

PROFESSIONAL SEAL (S)

PLOT DATE: 13 MARCH 2019

N:\118181\TEMPLATES - *.dwg

SCDMH NEWBERRY MHC HVAC REPLACEMENT

13 MARCH 2019

BID DOCUMENTS

REVISION DATE BY APP

MECA

J12-N072-FW

MECHANICAL SCHEDULES AND

DETAILS

M200

SPLIT SYSTEM AIR CONDITIONING SCHEDULE

SYMBOL

MANUFACTURER

MODEL NUMBER

BLOWER FAN HP

INPUT (B.T.U.H.)

OUTPUT (B.T.U.H.)

A.F.U.E.

TEMP RISE (DEG.F)

FLUE SIZE (IN.)

GAS CONN. SIZE (IN.)

MIN CIRC AMPS

MAX FUSE SIZE

VOLTAGE

UNIT WEIGHT (LBS.)

OUTSIDE AIRFLOW (C.F.M.)

REMARKS:

FURNACE

EXTERNAL S.P. (IN)

COMBUSTION FAN HP

- PRIOR TO ORDERING, CONTRACTOR SHALL VERIFY VOLTAGE AND ALL ELECTRICAL REQUIREMENTS.

- PROVIDE FURNACE WITH VARIABLE SPEED BLOWER AND COMBUSTION FAN MOTORS.

SET FURNACE AIRFLOW CONTROL DIP SWITCHES FOR CONSTANT CFM PER SCHEDULE AND ENHANCED MODE FOR

DEHUMIDIFICATION.

- PROVIDE ALUMINUM STEEL PRIMARY AND STAINLESS STEEL SECONDARY HEAT EXCHANGER AND 2 STAGE GAS

VALVE.

- PROVIDE FURNACE WITH FACTORY INSTALLED INTERNAL FILTER RACK

- COIL SHALL BE CONVERTIBLE, FIT FLUSH WITH FURNACE WITHOUT TRANSITION AND HAVE FACTORY INSTALLED TXV

AND DOUBLE SLOPED NON CORROSIVE DRAIN PAN.

- COIL TO BE OF SAME MANUFACTURER AS FURNACE AND CONDENSING UNIT AND FACTORY PAINTED TO MATCH

FURNACE

- PROVIDE WITH FULL LOUVERED COIL GUARD, CRANKCASE HEATER, HARD START KIT, 5 YR. COMPRESSOR

WARRANTY AND LOW AMBIENT COOLING OPERATION DOWN TO 30°F.

- PROVIDE MANUAL/ AUTO./ PROGRAMMABLE SELECTABLE THERMOSTAT WITH COOLING DEHUMIDIFICATION FEATURE.

SET TO MODE PER OWNER AND 50% R.H. (COORDINATE WITH EXISTING FACILITY CONTROLS)

SYMBOL

MANUFACTURER

MODEL NUMBER

AIR PRESS DROP (IN)

WIDTH (IN)

DEPTH (IN)

HEIGHT (IN)

FACE AREA (SQ. FT.)

ROWS/ F.P.I.

SEER/ EER RATING @ ARI

WEIGHT (LBS.)

DRAIN CONN. (IN.)

AIRFLOW (CFM)

GAS

COIL

COOLING

SYMBOL

MANUFACTURER

F.L.A.

MODEL NUMBER

E.A.T. (DB/WB) °F

L.A.T. (DB/WB/DP) °F

TOTAL CAP. (NET BTUH)

SENS. CAP. (NET BTUH)

R.L.A. / L.R.A.

WEIGHT (LBS.)

FAN QTY / H.P.

COMPRESSOR QTY

AMBIENT (°F.)

CONDENSING

AIR COOLED

VOLTAGE

M.C.A. / M.F.S.

UNIT

GF-5

S9V2B060U3VSA

.5

0.5

60,000

59,000

97%

36.7

3"

7.9

120/1/60

CC-5

4TXC036

77/64.5

55.1/53.4/

33,654

24,571

0.015

17-1/2

22-3/4

5.0

3/14

CU-5

TRANE

4TTA4036A3000A

1-1/8

0.77

17.0-82

208/3/60

12/20

6.1

15/12.5

GF-2

TRANE

S9V2B080U3VSA

.5

0.5

80,000

77,000

97%

50.9

3"

7.9

120/1/60

CC-2

TRANE

4TXB006DS3

77/64.5

54.9/53.3/

39,591

28,949

0.015

17-1/2

26-3/4

5.0

3/14

CU-2

TRANE

4TTA4042A3

1-1/8

0.77

11.2-84

208/3/60

15/25

6.7

14.12.2

GF-1,3,4

S9V2B080U3VSA

.5

0.5

80,000

78,000

97%

44.75

3"

13.0

120/1/60

CC-1,3,4

4TXCC009DS3

77/64.5

54.6/52.80

58,793

41,963

0.015

19-1/4

30-11/16

5.0

3/14

CU-1,3,4

TRANE

4TTA3060D3

1-1/8

0.77

11.2-84

208/3/60

15/25

7.10

13.75/11.3

NEOPRENE VIBRATION

ISOLATION PADS

CONDENSING UNIT SUPPORT DETAIL

NO SCALE

EXISTING EQUIPMENT YARD SLAB

LOUVERED COIL GUARD

SUPPORT REFRIGERANT

LINES INDEPENDENT OF UNIT

SECURE UNIT TO SLAB

THRU BASE PAN

CONDENSING UNIT.

FC

CC-1

GF-1

FC

FLOOR

HORIZONTAL CONDENSING GAS

FURNACE/COOLING COIL DETAIL

NOT TO SCALE

RE-CONNECT TO EXISTING

RETURN AIR PLENUM BOX

12" HIGH EQUIPMENT SUPPORT EQUAL TO DIVERSITECH

MODEL# HPR-12. QUANTITY AND LOCATION PER UNIT

MFG INSTALLATION INSTRUCTIONS.

M

NEW 2-POSITION

DAMPER-INTERLOCK

MOTORIZED DAMPER WITH UNIT

COMPRESSOR AND GAS VALVE.

RE-CONNECT BACK

TO EXISTING FLUE

RE-CONNECT BACK TO

EXISTING REFRIGERANT -

SEE FLOOR PLANS FOR

SPECIFIC INSTRUCTIONS

1/2" NEOPRENE ISOLATOR.

MANUAL DAMPER

24ga WELDED GALVANIZED STEEL AUXILIARY DRAIN FAN PAINTED

WITH GALVANNEAL PAINT TO PREVENT RUST. PAN TO BE 2" DEEP

AND EXTEND 3" BEYOND FURNACE AND COIL ON ALL SIDES.

MOISTURE SENSOR (SEE P-TRAP DETAIL)

FURNACE CONDENSATE DRAIN

LOCATED BELOW CABINET PER MFG

RECOMMENDATIONS

RE-CONNECT TO

EXISTING GAS PIPING

RE-CONNECT BACK TO

FURNACE CONDENSATE

REINSTALL SMOKE DETECTOR IN RETURN

AIR DUCTWORK UPSTREAM OF OUTSIDE AIR

DUCT CONNECTION. COORDINATE WITH FIRE

ALARM COMPANY.

PROVIDE BALANCING

DAMPER IN RETURN

AIR DUCT UPSTREAM

OF PLENUM

UNION

CAP

TYPICAL GAS PIPING DETAIL

NO SCALE

CAP

10 PIPE DIAMETERS

(MIN)

GAS MAIN SHUT-OFF

VALVE (TYP.)

TEE (TYP.)

DRIP LEG AND PRESSURE

MEASURING PORT

OVER-PRESSURE PROTECTION

DEVICE (OPD) PER ANSI Z21-80

PRESSURE MEASURING PORT

ROUTE AS INDICATED ON PLANS AND REDUCE

TO UNIT GAS CONNECTION AT APPLIANCE(S)

GAS SUPPLY INLET

3"MIN.

GAS PRESSURE REGULATOR

VENT DESIGNED TO PREVENT INSECT, WATER

AND FOREIGN OBJECT ENTRY. ROUTE FULL

SIZE TO APPROVED EXTERIOR LOCATION.

APPLIANCE

UNION

SEDIMENT TRAP TO BE INSTALLED

DOWNSTREAM OF THE SHUT-OFF

VALVE AND AS CLOSE TO

EQUIPMENT INLET AS PRACTICAL

DRIP LEG

3"MIN.

VERIFY GAS PRESSURE IN FIELD

PRIOR TO CONSTRUCTION

REFRIGERANT PIPE CHANNEL SUPPORT DETAIL

HANGER SPACING AND ROD SIZE

BASED ON MSS-SP69, TABLE 3 & 4

SECURE TO STRUCTURE WITH

MECHANICAL FASTENERS

PROVIDE K-FLEX 360 INSULATED

PIPE SUPPORT. PIPE SUPPORT TO

BE SAME THICKNESS AS PIPE

INSULATION AND SEALED WITH

CONTACT ADHESIVE AT ALL JOINTS.

SECURE UNINSULATED REFRIGERANT

LINE TO SUPPORT WITH B-LINE B2000

PIPE CLAMPS OR EQUAL.

SECURE THREADED RODS

TO STRUT WITH CHANNEL

NUTS WITH SPRINGS

PROVIDE B-LINE B1999

VIBRA-CUSHION OR EQUAL.

PROVIDE B-LINE B2000

PIPE CLAMPS OR EQUAL.

NO SCALE

WEIGHT (EXCLUDING CURB) (LBS.)

DAMPER SIZE (IN)

REMARKS:

LOCATION

ROOF/WALL OPENING SIZE (IN.)

DRIVE TYPE

VOLTAGE

FAN R.P.M.

MOTOR HORSEPOWER

STATIC PRESSURE (IN.)

AIRFLOW (C.F.M.)

MODEL NUMBER

MANUFACTURER

SYMBOL

SONES

*PRIOR TO ORDERING, CONTRACTOR SHALL VERIFY

VOLTAGE AND ALL ELECTRICAL REQUIREMENTS.

FANS DESIGNED AROUND 75CFM PER FIXTURE

PROVIDE WITH SPEED CONTROLLER, MOUNT TO SIDE

OF CABINET AND SET FOR CFM AS SPECIFIED

FAN SCHEDULE

DISCHARGE CAP NUMBER

CSP EXHAUST FAN DETAIL

CEILING

NO SCALE

FAN SHALL BE

INTERNALLY ISOLATED.

THREADED ROD.

SECURE TO STRUCTURE.

SIZE PER SCHEDULE.

EXHAUST FAN

SIZE PER SCHEDULE

EF-1

GREENHECK

CSP-A2150

.625

DIRECT

28x6

EXIST GH

3.0

FRACT

115/1/60

MEZZANINE

REFRIG (CHARGE)

CONDENSATE "P-TRAP" DETAIL

J = SCHEDULE FAN STATIC + 1"

H = TWO PIPE DIAMETERS

L = H + J + ONE PIPE DIAMETER

H

J

NO SCALE

L

UNIT

CLEAN OUT UNION (TYP.)

SIZE PER

FLOOR PLANS.

CAPPED CLEAN OUT TEE

ROUTE INSULATED CONDENSATE

DRAIN PER FLOOR PLANS. SLOPE

1/8" PER FOOT.

NO SCALE

THREADED

ROD

MECHANICAL

FASTNERS

WALL

INSULATION

CONDENSATE

PIPE

EXTENSION SPLIT

PIPE CLAMP EQUAL

TO B-LINE 3198R

FLANGE EQUAL

TO B-LINE B3199

PIPE SUPPORT STAND OFF

DETAIL (WALL)

REFRIGERANT PIPE SUPPORT DETAIL

2'-0"

NO SCALE

SECURE GALVANIZED CORNER

ANGLES TO UNI-STRUT SUPPORT

AND TUBING WITH MECHANICAL

FASTENERS.

1-1/2"x1-1/2" MECHANICAL TUBING, 3'-0" LONG. CEMENT IN PLACE.

12 GA. GALVANIZED STEEL

CHANNEL EQUAL TO B-LINE B22A

PROVIDE K-FLEX 360 INSULATED PIPE

SUPPORT. PIPE SUPPORT TO BE SAME

THICKNESS AS PIPE INSULATION AND

SEALED WITH CONTACT ADHESIVE AT

ALL JOINTS.

SECURE INSULATED REFRIGERANT

LINE TO SUPPORT WITH B-LINE

B2000 PIPE CLAMPS OR EQUAL.

SECURE UNINSULATED

REFRIGERANT LINE TO

SUPPORT WITH B-LINE B2000

PIPE CLAMPS OR EQUAL.

PROVIDE B-LINE B1999

VIBRA-CUSHION OR EQUAL.

ALL EXTERIOR PIPING TO HAVE TWO COATS OF

GRAY FINISH WITH A .016" THICK ALUMINUM

JACKET SECURED WITH STAINLESS STEEL

BANDS FOR PROTECTION OF INSULATION.

1 GENERAL REVISIONS 4/17/19 JAS

AutoCAD SHX Text

NO. C00097

AutoCAD SHX Text

ASSOCIATES

AutoCAD SHX Text

CONSULTING

AutoCAD SHX Text

ENGINEERING

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text No. 18709

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text H

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text Mechanical Engineering

AutoCAD SHX Text Consulting Associates, Inc.

AutoCAD SHX Text P.O. Box 50644

AutoCAD SHX Text Columbia, SC

AutoCAD SHX Text 451-D Jessen Lane

AutoCAD SHX Text

(843) 725-1086

AutoCAD SHX Text

(803) 765-9421

AutoCAD SHX Text Columbia

AutoCAD SHX Text Charleston

Newberry MHC Equipment Summary

Outdoor Condensing Unit

Symbol Model Number MFG Type Voltage Nom. Tonnage

CU - 1 4TTA4060A3 Trane DX Condensing Unit 200/230-3-60 5

CU - 2 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4

CU - 3 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4

CU - 4 4TTA4060A3 Trane DX Condensing Unit 200/230-3-60 5

CU - 5 4TTA4060A3 Trane DX Condensing Unit 200/230-3-60 5

CU - 6 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4

CU - 7 4TTA4048A3 Trane DX Condensing Unit 200/230-3-60 4

Gas Furnace

Symbol Model Number MFG Type Voltage 2nd Stage Input AFUE

GF-1 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

GF - 2 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

GF - 3 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

GF - 4 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

GF - 5 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

GF - 6 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

GF - 7 S9V2C080U5PSB Trane Gas Furnace (horizontal) 120-1-60 80,000 BTUH 96

Cooling Coil

Symbol Model Number MFG Type Airflow (cfm) Nom. Tonnage

SHP - 1 4TXCC009DS3HC Trane DX Cooling Coil 1750 5

SHP - 2 4TXCC007DS3HC Trane DX Cooling Coil 1400 4

SHP - 3 4TXCC007DS3HC Trane DX Cooling Coil 1400 4

SHP - 4 4TXCC009DS3HC Trane DX Cooling Coil 1750 5

SHP - 5 4TXCC009DS3HC Trane DX Cooling Coil 1750 5

SHP - 6 4TXCC007DS3HC Trane DX Cooling Coil 1400 4

SHP - 7 4TXCC007DS3HC Trane DX Cooling Coil 1400 4

Fan

Symbol Model Number MFG Control Voltage Airflow (cfm) SP (in)

EF-1 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-2 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237

EF-3 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-4 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237

EF-5 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-5 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-6 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-7 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-8 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-9 SP-A90 Greenheck Motion Detector 120-1-60 70 0.25

EF-10 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237

EF-11 SP-A210 Greenheck Wall Switch 120-1-60 100 0.237

Drawing List:

CS-1 Cover Sheet

M-100 Mechanical Existing Conditions

M-101 Mechanical Demolition and Renovation Plan

M-102 Mechanical Exhaust Fan Demo and Renovation Plan

M-200 Mechanical Schedules and Details

Site Location Map

International Existing Building Code: 2015 Edition

International Building Code: 2015 Edition

International Mechanical Code: 2015 Edition

National Electric Code: 2014 Edition

International Energy Conservation Code: 2009 Edition

New Construction X Renovation (Existing Building) Upfit Addition

Code Compliance:

Project #: J12-9774-FW

MECA

Charleston Office

451-D Jessen Lane

Wando, South Carolina

Phone: (843) 725-1086

Columbia Office

P.O. Box 50644

Columbia, South Carolina

Phone: (803) 765-9421

BID DOCUMENT DATE:

MECA Project Number: 118180

SEPTEMBER 10, 2019

SCDMH NEWBERRY MHC HVAC REPLACEMENT

2043 Medical Park Dr, Newberry, SC 29108

AutoCAD SHX Text Mechanical Engineering

AutoCAD SHX Text Consulting Associates, Inc.

AutoCAD SHX Text The State of

AutoCAD SHX Text South Carolina

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text Q

AutoCAD SHX Text

AutoCAD SHX Text

LAPSA

AutoCAD SHX Text

MELIOREM

AutoCAD SHX Text S

AutoCAD SHX Text

LOCAVIT

AutoCAD SHX Text

MARCH

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text R

AutoCAD SHX Text

JULY

BREAK

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

151617181920 2123 2224

2526272829 303132

3435363738 33

LOCATION NO.

A & E FIRM

A & E STATE NO.

SHEET TITLE

DIVISION

PROJECT TITLE

PROJECT #:

DRAWING NO.

SHEET

DATE:

The State of

South Carolina

S

O

U

T

H

C A

R

O

L

I

N

A

A N

I

M

I

S

O

P

I

B

U S

Q

U

E

P

A

R

A

T

I

J

U

L

Y4

M

A

R

C

H

MELIOREM LAPSA LOCAVIT

Q

U I S

S

E

P

A

R

B

I

T

AGENCY OR INSTITUTION

NO. LOCATION

REVISION DATE BY APP

APPROVAL

DRAWN BY

CHECKED BY

LANDSCAPE ARCHITECT

ENGINEERING DESIGN

ARCHITECTURAL DESIGN

PROJECT MANAGER

PROFESSIONAL SEAL (S)

PLOT DATE: 10 SEPTEMBER 2019

N:\118180\TEMPLATES - *.dwg

SCDMH NEWBERRY MHC HVAC REPLACEMENT

06 AUGUST 2019

BID DOCUMENTS

REVISION DATE BY APP

MECA

CONDENSING

UNIT YARD

AREA OF

WORK

J12-9774-FW

JAS

BGW JOB#: 118180

MECHANICAL EXISTING

CONDITIONS

M100

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS (CONDENSING UNIT YARD)

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

MECHANICAL EXISTING CONDITIONS

AutoCAD SHX Text

NO. C00097

AutoCAD SHX Text

ASSOCIATES

AutoCAD SHX Text

CONSULTING

AutoCAD SHX Text

ENGINEERING

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text Z

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text U

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text R

AutoCAD SHX Text No. 18709

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text Y

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text H

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text Mechanical Engineering

AutoCAD SHX Text Consulting Associates, Inc.

AutoCAD SHX Text P.O. Box 50644

AutoCAD SHX Text Columbia, SC

AutoCAD SHX Text

(803) 765-9421

Columbia

CONTRACTOR TO REMOVE COOLING COIL/GAS FURNACE

AS INDICATED. EXISTING CONDENSATE ,REFRIGERANT,

GAS LINE TO REMAIN IN PLACE. RECONNECT TO

EXISTING FLUE. VERIFY CONNECTION PLACEMENTS IN

FIELD.

EXISTING REFRIGERANT TO BE RECLAIMED/RECOVERED

AND DISPOSED OF PROPERLY AND IN ACCORDANCE

WITH THE REQUIREMENTS OF 40 CFR PART 82, SUBPART

F. EXISTING LINES TO BE CLEANED, TESTED, AND

RE-USED FOR NEW SYSTEM. (TYPICAL OF 7)

EXISTING RETURN AIR

DUCTS AND OUTSIDE AIR

DUCTS TO REMAIN.

RE-CONNECT BACK TO

NEW UNIT AS INDICATED.

(TYPICAL OF 5)

CONTRACTOR TO REMOVE

EXISTING MOTORIZED DAMPER

IN EXISTING GRAVITY HOOD.

EXISTING GRAVITY HOOD TO

REMAIN. (TYPICAL OF 2) REFER

TO RENOVATION PLANS FOR

NEW WORK.

CONTRACTOR TO TRANSITION

FROM UNIT OPENING TO EXISTING

SUPPLY DUCT. VERIFY EXACT

DUCT SIZE IN FIELD WITH EXISTING

CONDITIONS PRIOR TO DUCT

FABRICATION. (TYPICAL OF 7)

CONTRACTOR TO TRANSITION

FROM UNIT OPENING TO

EXISTING RETURN DUCT.

VERIFY EXACT DUCT SIZE IN

FIELD WITH EXISTING

CONDITIONS PRIOR TO DUCT

FABRICATION. (TYPICAL OF 7)

M

CONTRACTOR TO PROVIDE NEW

MOTORIZED DAMPER IN

EXISTING OUTSIDE AIR DUCT.

VERIFY EXACT VOLTAGE WITH

EXISTING CONDITIONS PRIOR TO

ORDERING. SEE GF/CC DETAIL.

(TYPICAL OF 7)

EXISTING OUTSIDE AIR

GRAVITY HOOD AND

DUCTWORK TO REMAIN IN

PLACE. (TYPICAL OF 2)

GF/CC-1

G F

C

C

GF/CC-2

G F

C

C

GF/CC-3

GF/CC-5

G F

C

C

M

M

M

M

M

M

CU-1

CONTRACTOR TO RE-CONNECT TO EXISTING

REFRIGERANT LINES. CONTRACTOR TO ENSURE

EXISTING REFRIGERANT IS PROPERLY

EVACUATED, DISPOSED OF PROPERLY, AND LINES

CLEANED THOROUGHLY TO MEET NEW

REFRIGERANT REQUIREMENTS. (TYPICAL OF 7)

CU-4

CU-7

CU-6

EXISTING REFRIGERANT

SLEEVES THRU SLAB.

CONNECT EXISTING

REFRIGERANT LINES TO

NEW CU- (TYPICAL)

CU-5CU-3

CU-2

CU-6

CU-4

CU-3

CU-2

CU-5

CU-1

CU-7

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

151617181920 2123 2224

2526272829 303132

3435363738 33

LOCATION NO.

A & E FIRM

A & E STATE NO.

SHEET TITLE

DIVISION

PROJECT TITLE

PROJECT #:

DRAWING NO.

SHEET

DATE:

The State of

South Carolina

S

O

U

T

H

C A

R

O

L

I

N

A

A N

I

M

I

S

O

P

I

B

U S

Q

U

E

P

A

R

A

T

I

J

U

L

Y4

M

A

R

C

H

MELIOREM LAPSA LOCAVIT

Q

U I S

S

E

P

A

R

B

I

T

AGENCY OR INSTITUTION

NO. LOCATION

REVISION DATE BY APP

APPROVAL

DRAWN BY

CHECKED BY

LANDSCAPE ARCHITECT

ENGINEERING DESIGN

ARCHITECTURAL DESIGN

PROJECT MANAGER

PROFESSIONAL SEAL (S)

PLOT DATE: 10 SEPTEMBER 2019

N:\118180\TEMPLATES - *.dwg

SCDMH NEWBERRY MHC HVAC REPLACEMENT

06 AUGUST 2019

BID DOCUMENTS

REVISION DATE BY APP

MECA

CONDENSING

UNIT YARD

AREA OF

WORK

J12-9774-FW

JAS

BGW JOB#: 118180

MECHANICAL RENOVATION AND

DEMOLITION PLAN

SCALE : 1/8" = 1' ---- 0"

M101

MECHANICAL DEMOLITION PLAN (MEZZANINE LEVEL)

SCALE : 1/4" = 1' ---- 0"

MECHANICAL RENOVATION PLAN (MEZZANINE…