Statement of Work Replacement of Three AHU’s and four non-working Condensing Units

Beaufort Laboratory 101 Pivers Island Rd Beaufort, NC 28516

The National Centers for Coastal Ocean Science Beaufort Laboratory has a requirement to replace three

(3) non-working Air Handling Units and four (4) Condensing Units that are located in the Auditorium, Classroom and Lobby.

Objective

The objective is to replace the existing, failed HVAC units in the Auditorium, Classroom and Lobby area that have failed due to corrosion from the salt water environment on Pivers Island. In performing this work, the Contractor shall comply with all applicable federal, state, and local laws and regulations. The contractor shall perform the replacement with factory-trained, skilled, professional technicians who are familiar with balancing, inspection, maintenance, and repair procedures. All work performed under this contract shall be performed by a licensed contractor who is registered to do business in the State of North Carolina.

Scope of Work (SOW)

The purpose of this contract is to replace the existing malfunctioned three (3) AHU’s and four (4) condensing units that are listed below.

Auditorium

A/C unit # 1 Air Handler Model # 2tta0048a4000aa Model # twe090b300el Serial # 613181x3f Serial # 6303nrhbd 3 phase 4 ton

A/C unit# 2 Air Handler Model # 2tta0048a4000aa Same as above Serial# 6104t473f 3 Phase 4 Ton Above units for the auditorium are all made by Trane.

Classroom A/C unit # 2 for the classroom. Air handler Model # 2tta0084a40000aa Model # 2tec3f48a1000aa Serial# # 62352473f Serial # 6283fll2v 4 ton unit Above unit is for the classroom made by Trane.

Lobby A/C Unit #3 Lobby Air Handler Model# 2tta3060a4000aa Model# twe060a400el Serial # 6194s7r4f Serial# 6284nrnbd 5 ton unit Above unit is for lobby made by Trane

The Contractor will secure the above existing HVAC equipment and recover the refrigerant as required.

The Contractor will remove the three Air Handling Units and four Condensing Units that supply conditioned air to the auditorium, the lobby and one classroom. The recovered refrigerant and the units will be properly disposed of per EPA and State Regulations. The Contractor will then install the new Trane Heat Pump Equipment that is identified in the (25) twenty five page Manufactures’ specification sheets that will be attached so that the existing Line sets and ducting can be reutilized in all of the existing locations. The Contractor will install new drain pans, float switches, drain lines and new refrigerant lines and utilize existing Trane matching line sets unless it is determined that they need replacement during the inspection prior to providing the quote. The Contractor will reconnect all ductwork using transitions as required and insulated to match existing. The Contractor will then reconnect to the existing high voltage electrical at the disconnect for each piece of equipment. The Contractor will install new thermostats and reconnect the low voltage wiring. Once all units are installed and complete the Contractor will complete a startup of the equipment and demonstrate to the COR and Client that all equipment operates and meets factory specifications. At this time the Government is not considering BAS Controls and there is no slated modifications to existing electrical systems.

The Contractor is responsible to start the units and test them for proper operation and provide the client with a complete check list along with a factory recommendation for preventative maintenance on the unit

Approved locations for dumpsters will be identified by the Beaufort building maintenance staff for Contractors use, and the frequency for removal from the facility shall be described in the Contractor’s demolition plan. Dismantled equipment and materials shall not be stored on-site. The requirements for disposal of special materials such as lubricants shall be in accordance with all applicable County, State, and Federal laws, regulations, and codes.

Prior to mobilization for Beaufort Laboratory, the Contractor shall identify any special requirements for equipment access into the building, construction fencing, parking areas for contractor vehicles and equipment, security, temporary site lighting, and material storage trailers and coordinate those with the COR so that timely and appropriate accommodations can made. Prior to the final inspection and project acceptance, the Contractor shall restore the site landscaping, roadways, and any other adversely impacted facility components to their original condition.

Tasks: The Contractor shall provide a schedule for the following tasks:

1. Dismantling and replacement of the existing three Air Handling Units and four Condensing Units.

2. Perform complete start up and operation of the newly installed system.

3. Provide the Government with a complete copy of verification documentation for systems operation and performance.

4. Ensure that all rewiring meet current Federal and State regulations and codes.

Host a post-installation inspection of the complete three Air Handling Units and four Condensing Units project with the Operations Director and Contracting Officers Representative.

5. Properly dispose of all removed parts and material per Federal, State, and local regulations and codes.

6. Remove defective three Air Handling Units and four Condensing Units as identified above.

7. Will install new drain pans, float switches, drain lines and new refrigerant lines and utilize existing Trane matching line sets.

8. The electrical system is a 460v/60hz/3phase.

9. Install new A1, A2 & B2 units and equipment that is identified below along with piping and electrical wiring.

10. Replace filter grill with correct size if required and install transitions were needed in ductwork. To provide pressure test, pull vacuum, and charge the new systems with refrigerant.

11. To provide labor and materials to provide a complete installation and testing of the new units listed below along with the filter rack (TEM).

Odyssey Split System indoor units

Item Description Model # Quantity Location

A1 7.5 Ton Odyssey Split System Indoor Unit

TWE09043BAA--

A10000000000000000000000000

1 EA Auditorium AHU

Field Installed Option Description Part Number

14.96kW (460/60/3) BAYHTRR415A

A2 5 Ton Odyssey Split System Indoor Unit

TWE06044AAA--

A10000000000000000000000000

1 EA Lobby AHU

Field Installed Option Description Part Number

9.96kW (460/60/3) BAYHTRR410A

B2 4 Ton 460/3 Split System Air Conditioning Unit (Small)

4TWA4048A4-TEM4A0C48S41S 1 EA Class Room

Field Installed Option Description Part Number

External Filter Rack (TEM) BAYSF1235BAA

Security/Safety/Environmental Considerations

Work must be completed while observing all applicable federal, state, local laws and regulations pertaining to safety, security, and environmental considerations of the project.

Conformance with Environmental Management Systems

The Contractor shall perform work under this contract consistent with the relevant policies and objectives identified in the agency, organizational, or facility environmental management systems (EMS) set forth in the contract. The Contractor shall perform work in a manner that conforms to all appropriate Environmental Management Programs and Operational Controls identified by the agency, organizational, or facility EMS.

The Contractor shall provide monitoring and measurement information as necessary for the organization to address environmental performance relative to the environmental, energy, and transportation management goals. In the event an environmental nonconformance or noncompliance associated with the contracted services is identified, the Contractor shall expeditiously take all necessary corrective or preventative actions. In the case of a noncompliance, the Contractor shall respond and take corrective action immediately. In the case of a nonconformance, the Contractor shall respond and take corrective action based on the time schedule established by the EMS Site Coordinator. In addition, the Contractor shall ensure that its employees are aware of the roles and responsibilities identified for them by the environmental management system and how those requirements affect the work performed under this contract. Those responsibilities shall include the following:

1. Registration at front desk and receipt of a temporary pass for one day (if needed, a door pass card will also be furnished at that time).

2. Receipt and acceptance of the brief statement concerning the EMS that will be provided by the front desk personnel at the time of the temporary pass issuance.

3. Compliance with the Facility Engineer or designated maintenance staff member on any other actions that need to be taken to protect Beaufort Laboratory and the environment.

Additional Requirements and Provisions

Period of Performance:

Deliverables:

Item Description Qty. Due Date Deliver To 1 Schedule of work shall be delivered to Contracting Officer and Contracting Officer’s Representative ten days prior to commencing work.

1 each 10 days prior to commencing work.

Randy Grady Beaufort Laboratory 101 Pivers Island Rd

(252) 725-3541

2 Host post-Repair inspection of A1, A2 & B2 Auditorium, lobby and Classroom HVAC Units with Contracting Officers Representative and client.

1 job NLT 90 days from receipt of Contracting Officer’s notice to proceed.

Randy Grady Beaufort Laboratory 101 Pivers Island Rd Beaufort, NC 28516

(252) 725-3541

3 Inspection and acceptance of the A1, A2 & B2 Auditorium, lobby and Classroom HVAC Units and associated equipment and filter rack.

1 job NLT 90 days from receipt of Contracting Officer’s notice to proceed.

Randy Grady Beaufort Laboratory 101 Pivers Island Rd

4 Commencement of Prime

Contractor’s warranty.

1 each NLT 90 days from receipt of Contracting Officer’s notice to proceed.

Randy Grady Beaufort Laboratory 101 Pivers Island Rd

Personnel: The Contractor shall provide proof that all on-site employees are U.S. citizens or legal aliens.

The Contractor shall not employ personnel with felony convictions, or with a record of narcotics use, for work at Beaufort Laboratory. The Contractor is responsible for completing a security investigation on all employees prior to their commencement of work at the Beaufort Laboratory in connection with this contract.

Conduct of Contractor Personnel: The Contractor’s employees are subject to and shall observe and comply with all applicable regulations, policies, and procedures. In accordance with established security regulations and safety policies, Contractor employees shall not enter restricted areas. The Contractor shall be responsible for the selection, certification, assignment, supervision, management, and control of employees with the advice of the CO and the COR in the performance of all contract work. The removal from the job site of any employee shall not relieve the Contractor of the requirement to provide enough personnel to perform the terms and conditions of the contract. The Contractor’s employees shall not use offices, rooms, work areas, or any other undesignated areas for their own use. When a task is completed, such employees shall immediately leave the area. Contract personnel shall not use or operate telephones, radios, computer terminals, or any other Government or privately-owned equipment or property without the express permission of the Beaufort Laboratory COR. The Contractor’s employees shall not disturb papers on desks, nor open desk drawers or cabinets. Breaks shall not be spent in offices or room areas, but taken only in the assigned rest areas. While waiting for transportation, or while on work breaks, they shall not block or impede movement on ramps, doorways, corridors, or walkways.

IT Security Requirements The Assessment and Authorization (A&A) requirements of Clause 48 CFR 1352.239-72 do not apply, and a Security Accreditation Package is not required.

The contractor will not access, store, process or transmit any government privileged information. The contractor will not have access to any non-public government information, systems and/or networks.

Work Schedules/Shifts: The Contractor shall accomplish all work for the Beaufort Laboratory during the hours of 0600 and 1700, Monday through Friday, excluding Federal Holidays. This allows the flexibility for the Contractor to schedule eight hours of work during a time when Beaufort Maintenance staff will be at the facility. If weekend work is required, a meeting with the CO of record and the Beaufort management will be held to address the best way to accommodate that requirement, and the Contractor will be notified of the outcome of that meeting.

Point of Contact: The Contracting Officers Representative (COR, Mr. Martin Burnett, will serve as the point of contact for specific questions concerning this SOW. He can be reached at Martin.Burnett@NOAA.gov or (843) 619-1009.

mailto:Martin.Burnett@NOAA.gov

Prepared For:

All Bidders

Date: June 17, 2021

Customer P.O. Number:

Customer Project Number:

Sold To:

Job Number:

Job Name:

HML-NOAA-NOS Building

Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.

Product Summary Qty Product 2 Odyssey Split System Indoor Unit 4 Split System Air Conditioning Units (Small)

1 BAYHTR4510AUT

Inside Sales - Columbia Trane U.S. Inc.

111 Lott Court West Columbia, SC 29169-3051 Phone: (803) 936-4700 Cell:

Fax: (803) 936-4715

The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.

Product performance and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed between submittal generation and equipment release, the product performance and submittal data will need to be verified. It is the customer’s responsibility to obtain such verification.

Submittal

C:\Users\TEMP.AD.001\AppData\Local\Trane\LDG\HML-NOAA-NOS Building.doc

Table Of Contents Product Summary Odyssey Split System Indoor Unit (Items A1, A2)

Tag Data Product Data Mechanical Specifications Unit Dimensions Weight, Clearance & Rigging Diagram Accessory Field Wiring

Split System Air Conditioning Units (Small) (Items B1 - B3) Tag Data Product Data Mechanical Specifications Unit Dimensions Weight, Clearance & Rigging Diagram

BAYHTR4510AUT (Item C1) Tag Data Product Data

Field Installed Options - Part/Order Number Summary Odyssey Split System Indoor Unit Split System Air Conditioning Units (Small)

HML-NOAA-NOS Building June 17, 2021

FLD = Furnished by Trane U.S. Inc. / Installed by Others © 2021 Trane Technologies All rights reserved

Equipment Submittal Page 3 of 25

Tag Data - Odyssey Split System Indoor Unit (Qty: 2) Item Tag(s) Qty Description Model Number A1 7.5 ton Ody_I 1 Auditorium AHU TWE09043BAA--A10000000000000000000000000 A2 5 ton Ody_I 1 Lobby AHU TWE06044AAA--A10000000000000000000000000

Product Data - Odyssey Split System Indoor Unit All Units Air Handler R-410A Generation A (DOE 2018) Constant Volume Standard Motor Symbio options module

Item: A1 Qty: 1 Tag(s): 7.5 ton Ody_I

7.5 Ton

208-230/60/3 Dual Circuit 14.96kW (460/60/3) (Fld)

Item: A2 Qty: 1 Tag(s): 5 ton Ody_I 5 Tons 460/60/3 Single Circuit 9.96kW (460/60/3) (Fld)

Equipment Submittal Page 4 of 25

Mechanical Specifications - Odyssey Split System Indoor Unit Item: A1, A2 Qty: 2 Tag(s): 7.5 ton Ody_I, 5 ton Ody_I

General - TWE Completely Factory Assembled Convertible for Horizontal or Vertical Configuration Convertible for Cooling Only or Heat Pump Application Convertible for Left or Right External Connections (Refrigerant and/or Electrical) Convertible for Front or Bottom Air Return Nitrogen Holding Charge Certified and Rated in Accordance with AHRI and DOE Standards Certified to UL 1995 for Indoor Blower Coil Units

Casing - TWE Zinc Coated, Heavy Gauge, Galvanized Steel Weather Resistant Baked Enamel Finish Access Panels with Captive Screws Completely Insulated with Foil Faced, Cleanable, Fire Retardant, Permanent, Odorless Glass Fiber Material Captured or Sealed Insulation Edges Electrical Connection Bushings or Plugs Refrigerant Connection Bushings or Plugs Withstand Elevated Internal Static Pressure

Refrigeration System - TWE Single or Dual Circuit Distributor(s) Thermal Expansion Valves (TXVs)

Evaporator Coil - TWE 3/8" Internally Enhanced Copper Tube Mechanically Bonded to Lanced Aluminum Plate Fins Factory Pressure and Leak Tested to 449 psig.

Draw-Through Airflow Dual Circuits Are Interlaced/Intertwined Double Sloped, Removable, Cleanable, Composite Drain Pan Four Drain Pan Positions

Indoor Fan - TWE Double Inlet, Double Width, Forward Curved, Centrifugal Type Fan Dual Fans On 10.4-20.912.5-25 Ton Air Handlers Adjustable Belt Drive Permanently Lubricated Bearings

Indoor Motor - TWE Adjustable Motor Sheaves Fixed Motors Sheaves (SZVAV and 2-Speed VFD) Thermal Overload Protection Permanently Lubricated Bearings Meet Energy Policy of 1992 (EPACT) Optional Over Sized Motors for High Static Applications

Controls - TWE Completely Internally Wired Numbered and Colored Wires Magnetic Indoor Fan Contractor Low Voltage Terminal Strip Single Point Power Entry Evaporator Defrost Control

Filters - TWE Access From Side Coil Panels Filters Slide on Rack One Inch (1"), Throw-Away Filters on 4.6-8.335-10 Ton Units Filter Rack Convertible to Two Inch (2") Capability on 5-10 Ton Units Two Inch (2"), Throw-Away Filters on 10.4-20.912.5-25 Ton Units

Electric Heaters TWE Heavy Duty Nickel Chromium Elements cETL Approved Installs Directly On Fan Discharge One or Two Stage Control (Dependent Upon Capacity) Single Point Power Entry Terminal Strip Connections 208-230V Heaters Internally Wye Connected Automatic Line Break High Limit Controls 230V Heaters Internally Delta Connected Automatic Reset of High Limit Controls Through Pilot Duty with Secondary Backup Fuse Links

Equipment Submittal Page 5 of 25

Unit Dimensions - Odyssey Split System Indoor Unit Item: A1 Qty: 1 Tag(s): 7.5 ton Ody_I

16 7/8"

1 13/16"

2 3/4" 42"42"2 3/4"

1 9/16"

16 1/16"

20 1/16" 16 3/4" 16 1/4" 13 3/4"

3 5/8"

1 5/8"

1 5/16"

11 1/16" 13 3/4" 16 1/4" 16 3/4" 19 1/16" 20 1/16"

3 5/8"

1 5/8"

1 5/16"

16" 8 13/16"

3 1/2"

1 3/16"

22 7/8"

45 1/8"

6 3/4"

36 7/8"

10 7/16"

54 1/16"

1 3/16"

25 1/2"

24 1/16"

16 1/4"

70"

25 1/2"

47 1/2"

11 11/16"

BOTTOM RETURNSIDE RETURN

BUSHING LOW

VOLTAGE ENTRANCE

BUSHING HIGH

VOLTAGE ENTRANCE

CONTROL BOX

ACCESS PANEL

NOTES:

1 PANEL DEPTH 1/2" (TYP.ALL PANELS).

2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN

ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO

SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER

SLIDING DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF

DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.

5. 1" FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

DIMENSIONAL DRAWING

6 - 7.5 TON AIR HANDLER (DUAL CIRCUIT)

SEE NOTES 2,3,4

SEE NOTES 2,3,4

(4) - HOLE FOR HORIZONTAL

SUSPENSION

COPPER LIQUID LINE

FIELD CONNECTION

COPPER SUCTION LINE

FIELD CONNECTION

LIQUID LINES

CONNECTION

SUCTION LINE CONNECTION

(2) REMOTE BULB TXV

FILTER ACCESS PANEL

22" MIN. DISTANCE

BOTH SIDE

DRAIN CONNECTION

FOR HORIZONTAL

(SEE NOTE 2,3,5)

FILTER

SUPPLY OPENING

BOTTOM RETURN

SIDE RETURN

BOTTOM RETURN

SUPPLY VERTICAL -

RETURN HORIZONTAL /

RETURN VERTICAL

SUPPLY HORIZONTAL -

RETURN VERTICAL /

RETURN HORIZONTAL

(4) HOLE FOR

HORIZONTAL

SUSPENSION

SIDE RETURN

DUCT FLANGE

1" HEIGHT

SUPPLY

OPEN

Equipment Submittal Page 6 of 25

THROWAWAY

YES

(3) 16"X25"X1"

14.96 460/60/3 26.0 30.0 30.0

3/8" 8 1/8" 4 / 14

EXPANSION VALVE

1" PVC

CENTRIFUGAL

1 / 15"X15"

BELT/ADJUSTABLE

1.5 / 2.0 / 3.0 56H

Convertible 460 Voltages Convertible 460 Voltages

1 1/8" 1/2"

4. With motor field converted to 460V.

Model:

Unit Operating Voltage:

Minimum Circuit Ampacity:

Maximun Fuse Size:

Maximun Circuit Breaker:

EVAPORATOR FAN MOTOR (9)

No.:

Volts:

Phase:

Motor HP:

Amp-FLA:

Amp-LRA:

NOTES:

1. Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb.

2. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Ratings shown are tested and certified in accordance with AHRI Standard 340/360 or 365 certification program.

3. Condensing Unit Only Gross Cooling Capacity rate at 45 F saturated suction temperature and at 95 F ambient.

4. AHRI Net Cooling Capacity is calculated with matched blower coil and 25 ft. of OD interconnecting tubing.

EER is rated at AHRI conditions and in accordance with DOE test procedures.

5. Integrated Part Load Value is based on AHRI Standard 340/360 or 365. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at AHRI rated CFM.

6. Sound Rating shown is tested in accordance with AHRI Standard 270.

7. Refer to refrigerant piping program for line sizing and line length.

8. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft.

of interconnecting refrigerant lines. All units are shipped with a small nitrogen holding charge only.

9. Second Column data Coverable to 460 volt

SYSTEM DATA

No. Refrigerant Circuits Suction Line (in.) OD Liquid Line (in.) OD

ELECTRICAL DATA

AIR HANDLER ELECTRICAL DATA

GENERAL DATA

INDOOR COIL - TYPE

Tude Size:

Face Area:

Row/FPI Refrigerant Control Drain Connection Size

INDOOR FAN

Type:

No. Used/Diameter x Width:

Drive Type/No. Speed:

CFM:

No. Motor:

Motor HP - Standard/Oversized:

Motor RPM:

Motor Frame Size:

FILTER

Type:

Furnished:

No. Size Recommended:

Heat Rating (kW):

Control Stages:

Power Supply:

Minimum Circuit Ampacity:

Maximun Fuse Size:

Maximun Circuit Breaker:

ELECTRICAL DATA Notes:

1. KW ratings are at: 208/240V for 208-230V air handlers 480V for 460V air handlers 600V for 575V air handlers

For other than rated voltage, capacity = ( Voltage

Rated Vpltage ) x 2 Rated Capacity

2. Any power supply and circuits must be wired and protected in accordance with local electrical codes.

3. The HACR circuit breaker is for U.S.A. installations only.

HEATER DATA

Equipment Submittal Page 7 of 25

Item: A2 Qty: 1 Tag(s): 5 ton Ody_I

3"

48 1/16"

10 7/16"

34 9/16"

35 5/8"1 1/8"

12" 13 9/16" 20 1/16"

1 11/16"

5 15/16" 13 3/16"

12"13 9/16"

13 5/16"

1 3/4"

2 3/4"32 1/2"

DRAIN CONNECTION

FOR HORIZONTAL

(SEE NOTE 2,3,5)

32 1/2"

12 7/16"

1 3/8"

993" 990"

1 3/8"

3 3/16"

3 7/16"

22 5/8"

22 5/8"

38" 24 1/16"

7"

16 1/4"

768"

500"

BOTTOM RETURNSIDE RETURN

CONTROL BOX

ACCESS PANEL

NOTES:

1 PANEL DEPTH 1/2" (TYP.ALL PANELS).

2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END

OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN

ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO

SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER

SLIDING DRAIN PAN BACK INTO UNIT.

3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF

DRAIN PAN CONNECTION AT END OF UNIT.

4. 1" FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.

5. 1" FEMALE SCHED. 40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

DIMENSIONAL DRAWING

5 TON AIR HANDLER (SINGLE CIRCUIT)

SEE NOTES 2,3,4

SEE NOTES 2,3,4 (4) - HOLE FOR HORIZONTAL

SUSPENSION

KNOCKOUT FOR

COPPER LIQUID LINE

FIELD CONNECTION

KNOCKOUT FOR

COPPER SUCTION LINE

FIELD CONNECTION

LIQUID LINES

CONNECTION

SUCTION LINE CONNECTION

REMOTE BULB TXV

FILTER ACCESS PANEL

22" MIN. DISTANCE

BOTH SIDE

FILTER

SUPPLY OPENING

BOTTOM RETURN

SIDE RETURN

BOTTOM RETURN

SUPPLY VERTICAL -

RETURN HORIZONTAL /

RETURN VERTICAL

SUPPLY HORIZONTAL -

RETURN VERTICAL /

RETURN HORIZONTAL

(4) FOR HORIZONTAL

SUSPENSION

SIDE RETURN

CONTROL WIRING

LINE VOLTAGE

DUCT FLANGE

1" HEIGHT

SUPPLY

OPEN

Equipment Submittal Page 8 of 25

THROWAWAY

YES

(1) 16"X20"X1"

(1) 20"X20"X1"

9.96 460/60/3 17.0 20.0 20.0

3/8" 5" 4 / 14

EXPANSION VALVE

1" PVC

CENTRIFUGAL

1 / 12"X12"

BELT/ADJUSTABLE

0.75 / 1.5

1 1/8" 1/2"

4. With motor field converted to 460V.

Model:

Unit Operating Voltage:

Minimum Circuit Ampacity:

Maximun Fuse Size:

Maximun Circuit Breaker:

EVAPORATOR FAN MOTOR (9)

No.:

Volts:

Phase:

Motor HP:

Amp-FLA:

Amp-LRA:

NOTES:

1. Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb.

2. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Ratings shown are tested and certified in accordance with AHRI Standard 340/360 or 365 certification program.

3. Condensing Unit Only Gross Cooling Capacity rate at 45 F saturated suction temperature and at 95 F ambient.

4. AHRI Net Cooling Capacity is calculated with matched blower coil and 25 ft. of OD interconnecting tubing.

EER is rated at AHRI conditions and in accordance with DOE test procedures.

5. Integrated Part Load Value is based on AHRI Standard 340/360 or 365. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at AHRI rated CFM.

6. Sound Rating shown is tested in accordance with AHRI Standard 270.

7. Refer to refrigerant piping program for line sizing and line length.

8. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft.

of interconnecting refrigerant lines. All units are shipped with a small nitrogen holding charge only.

9. Second Column data Coverable to 460 volt

SYSTEM DATA

No. Refrigerant Circuits Suction Line (in.) OD Liquid Line (in.) OD

ELECTRICAL DATA

AIR HANDLER ELECTRICAL DATA

GENERAL DATA

INDOOR COIL - TYPE

Tude Size:

Face Area:

Row/FPI Refrigerant Control Drain Connection Size

INDOOR FAN

Type:

No. Used/Diameter x Width:

Drive Type/No. Speed:

CFM:

No. Motor:

Motor HP - Standard/Oversized:

Motor RPM:

Motor Frame Size:

FILTER

Type:

Furnished:

No. Size Recommended:

Heat Rating (kW):

Control Stages:

Power Supply:

Minimum Circuit Ampacity:

Maximun Fuse Size:

Maximun Circuit Breaker:

ELECTRICAL DATA Notes:

1. KW ratings are at: 208/240V for 208-230V air handlers 480V for 460V air handlers 600V for 575V air handlers

For other than rated voltage, capacity = ( Voltage

Rated Vpltage ) x 2 Rated Capacity

2. Any power supply and circuits must be wired and protected in accordance with local electrical codes.

3. The HACR circuit breaker is for U.S.A. installations only.

HEATER DATA

Equipment Submittal Page 9 of 25

Weight, Clearance & Rigging Diagram - Odyssey Split System Indoor Unit

360.0 lb

323.0 lb

67.0 lb

99.0 lb

75.0 lb

82.0 lb

56.0 lb

92.0 lb

87.0 lb

88.0 lb

C

DA

B#1

#2

#4

#3

AIR FLOW

HORIZONTAL

RETURN

HORIZONTAL

RETURN

VERTICAL

RETURN AIR FLOW

VERTICAL

RETURN

WEIGHT AND RIGGING

WEIGHTS AND LOAD POINT LOCATION FOR CONDENSOR

WEIGHTS AND CORNER WEIGHTS

Shipping:

Net

VERTICAL

Corner 1:

Corner 2:

Corner 3:

Corner 4:

HORIZOTNAL

Corner A:

Corner B:

Corner C:

Corner D:

Equipment Submittal Page 10 of 25

Weight, Clearance & Rigging Diagram - Odyssey Split System Indoor Unit

285.0 lb

232.0 lb

55.0 lb

71.0 lb

51.0 lb

55.0 lb

54.0 lb

67.0 lb

50.0 lb

61.0 lb

C

DA

B#1

#2

#4

#3

AIR FLOW

HORIZONTAL

RETURN

HORIZONTAL

RETURN

VERTICAL

RETURN AIR FLOW

VERTICAL

RETURN

WEIGHT AND RIGGING

WEIGHTS AND LOAD POINT LOCATION FOR CONDENSOR

WEIGHTS AND CORNER WEIGHTS

Shipping:

Net

VERTICAL

Corner 1:

Corner 2:

Corner 3:

Corner 4:

HORIZOTNAL

Corner A:

Corner B:

Corner C:

Corner D:

Equipment Submittal Page 11 of 25

Accessory - Odyssey Split System Indoor Unit

6 - 7 1/2 TON ELECTRIC HEATER

13 1/2"

1 3/4" 2 7/16"

9/16"

23 15/16"

9/16"16 1/8"

15/16"

30 3/4" 1/2"

9/16"

30 13/16"

67 9/16"

13 1/2"

DIMENSIONAL DRAWING

(12) 1/4" DIA HOLE

SAME PATTERN AS TOP

3 KNOCKOUT FOR 7/8", 1 3/8" AND 2"

DIA CONDUIT POWER SUPPLY ENTRY

REMOVABLE

PANEL

(12) 1/4" DIA HOLE

SAME PATTERN AS TOP

AIR HANDLER

ELECTRIC HEATER

Equipment Submittal Page 12 of 25

Accessory - Odyssey Split System Indoor Unit

13 1/2"

1 3/4"

15/16"

23 15/16"

9/16"

16 1/8" 9/16"

30 13/16"

30 1/4" 1/2"

9/16"

24 5/8"

61 9/16"

13 1/2"

5 TON ELECTRIC HEATER

DIMENSIONAL DRAWING

3 KNOCKOUT FOR 7/8", 1 3/8" AND 2"

DIA CONDUIT POWER SUPPLY ENTRY

(12) 1/4" DIA HOLE

SAME PATTERN AS TOP

(12) 1/4" DIA HOLE

SAME PATTERN AS TOP

REMOVABLE

PANEL

ELECTRIC HEATER

AIR HANDLER

Equipment Submittal Page 13 of 25

Field Wiring - Odyssey Split System Indoor Unit

B2 B1

Y G

W2 W1

J

EDC

SUPPLY HEATER

CONTROL BOX

TO POWER SUPPLY

PER LOCAL CODES

TO POWER SUPPLY

PER LOCAL CODES

SEE NOTE 5 & 6

R

SEE NOTE 9

SEE NOTE 8

STAGE 1 HEAT

STAGE 2 HEAT

FAN

COMPRESSOR

24 VAC

24 VAC COMMON

THEAT ANTICIPATOR

3 PHASE

ONLY

3 PHASE

ONLY

AIR HANDLER

OCOOLING REVERSING VALVE

TO OUTDOOR UNIT

FIELD OPTIONAL. SINGLE POINT POWER ENTRY OPTION IS THROUGH ELECTRIC HEATER ONLY.

9. WHEN ELECTRIC HEATER ACCESSORY IS USED, SINGLE POINT POWER ENTRY OR DUAL POINT POWER ENTRY IS

1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.

2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE.

3. LOW VOLTAGE WIRING TO BE 18 A.W.G. MINIMUM CONDUCTOR.

4. USE COPPER CONDUCTORS ONLY.

5. IF TWO STAGE ELECTRIC HEATERS AND THERMOSTAT ARE USED, REMOVE JUMPER BETWEEN W1 AND W2.

NOTES:

FACTORY WIRINGLINE VOLT

LINE VOLT

24 VOLT

FIELD WIRING

INTER-COMPONENT WIRING

24 VOLT

6. FOR SINGLE STAGE ELECTRIC HEATER, OMIT WIRE BETWEEN W2 AND THERMOSTAT AND W2 AND ELECTRIC

HEATER.

7. FOR COOLING ONLY, OMIT WIRES BETWEEN W1,W2 AND THERMOSTAT AND OMIT ELECTRIC HEATER.

8. IF THE EDC SWITCH IS TO BE CONNECTED IN THE CIRCUIT, THE EDC WIRE MUST BE REMOVED FROM THE B1 TERMINAL AND RECONNECTED TO THE "Y" TERMINAL ON THE INDOOR SECTION LOW VOLTAGE TERMINAL

BOARD AS SHOWN.

Equipment Submittal Page 14 of 25

Tag Data - Split System Air Conditioning Units (Small) (Qty: 4)

B1 4 ton cond 2 Auditorium condenser 1,2

----------4TWA4048A4-0000000000-00--------------0000-----00

000000000000000--00-0--0

B2 4 ton 460/3 1 Classroom ----------4TWA4048A4-TEM4A0C48S41S--------------0000----- 00000000000000000--00-0--0

B3 5 ton 460/3 1 Lobby Condenser ----------4TWA4060A4-0000000000-00--------------0000-----00 000000000000000--00-0--0

Product Data - Split System Air Conditioning Units (Small) Item: B1 Qty: 2 Tag(s): 4 ton cond 4TWA4 Heat Pump Outdoor Unit 4 Ton - Nominal Cooling Capacity 460 Volt 3 Phase 60 Hertz

Item: B2 Qty: 1 Tag(s): 4 ton 460/3 4TWA4 Heat Pump Outdoor Unit 4 Ton - Nominal Cooling Capacity 460 Volt 3 Phase 60 Hertz Low cost Multi-poise 4-way Better, Retail replacement Mid EFF Footprint - C 4 Ton air handler Low EFF

3.5 ton to 4.0 ton airflow 208-230/1/60 Standard Coil External filter rack (TEM) (Fld)

Item: B3 Qty: 1 Tag(s): 5 ton 460/3 4TWA4 Heat Pump Outdoor Unit 5 Ton - Nominal Cooling Capacity 460 Volt 3 Phase 60 Hertz

Equipment Submittal Page 15 of 25

Mechanical Specifications - Split System Air Conditioning Units (Small) Item: B1 - B3 Qty: 4 Tag(s): 4 ton cond, 4 ton 460/3, 5 ton 460/3

4TWA4 - General The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115.0 F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.

4TWA4 - Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint finish on all louvered panels and the fan top panel. The corner panels are prepainted. All panels are subjected to our 1,000 hour salt spray test . The base is made of a CMBP-G30 weatherproof material to resist corrosion.

4TWA4 - Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and high pressure switch. High and low pressure controls are inherent to the compressor. A factory supplied liquid line drier is standard. Some models may require field installation.

4TWA4- Compressor The compressor features internal over temperature, pressure protection and total dipped hermetic motor. Other features include: Centrifugal oil pump and low vibration and noise.

4TWA4 - Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.

Equipment Submittal Page 16 of 25

Unit Dimensions - Split System Air Conditioning Units (Small) Item: B1, B2 Qty: 3 Tag(s): 4 ton cond, 4 ton 460/3

4TWA7048 - NOTES:

1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED

FOR AT LEAST 60"

ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF

RUN-OFF WATER DOES NOT POUR DIRECTLY ON

UNIT, AND SHOULD BE AT LEAST 12"

FROM WALL AND ALL SURROUNDING SHRUBBERY

ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.

2. ELECTRICAL AND REFRIGERANT COMPONENT

CLEARANCES PER PREVAILING CODES.

3. GAS LINE SIZE (7/8")

4. ALL WEIGHTS ARE APPROXIMATE.

5.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION

WITH INSTALLER DOCUMENTS BEFORE INSTALLATION

33 1/8"

8 5/8" 5 5/8"

3 3/8"

3 7/8"

20"

37 1/4"

34 1/4"

SEE NOTE 1

GAS LINE 1/4" TURN SERVICE, SEE TABLE I.D FEMALE

BRAZED CONNECTION WITH 1/4" SEA FLARE PRESSURE

TAP FITTING

K.O. FOR ALTERNATE

ELECTRICAL ROUTING

LIQUID LINE SERVICE VALVE

3/8" I.D FEMALE BRAZE

CONNECT WITH 1/4" SEA

FLARE PRESSURE TAP FITTING

7/8" DIA. HOLE

LOW VOLTAGE

1 1/8" DIA K.O. WITH 7/8"

DIA HOLE IN CONTROL

BOX BOTTOM FOR

ELECTRICAL POWER SUPPLY

SERVICE PANEL

ELECTRICAL SERICE PANEL

Equipment Submittal Page 17 of 25

Item: B1, B2 Qty: 3 Tag(s): 4 ton cond, 4 ton 460/3

4TWA4048A4000A 8.0

15.0 15.0

414-506

0.20 0.60

R-410A

8.1 lb 7/8" 3/8"

261.0 lb

295.0 lb

6.2 41.0

D

IS

C H

AR

G

E

1. Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240.

2. Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses.

3. Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line.

For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0

4. * = 15, 20, 25, 30, 40 and 50 foot lineset available.

NOTES:

REFRIGERANT

OUTDOOR MOTOR

GENERAL

ELECTRICAL / GENERAL DATA

POWER CONN.

NET

SHIPPING

WEIGHT AND CLEARANCE

C4

C1

C3

Model:

Operating Voltage:

Unit Primary Voltage:

Unit Secondary Voltage Unit Hertz:

Unit Phase:

Minimum Circuit Ampacity:

Maximum Circuit Breaker:

Minimum Protection Rating:

Number:

Horsepower:

Motor Speed (RPM):

Phase:

Full Load Amps:

Locked Rotor Amps:

Type:

Charge:

Line Size O.D. Gas:

Line Size O.D. LIQ:

NOTES:

C1. TOP DISCHARGE SHOULD BE UNRESTRICTED

FOR AT LEAST 60" ABOVE UNIT

C2. PLACE UNIT FROM WALL

C3. PLACE SHRUBBERY AT LEAST 12"

FROM UNIT ON TWO SIDES, OTHER SIDES

UNRESTRICTED

C4. PLACE UNIT SO ROOF RUN-OFF DOES NOT

FALL DIRECTLY ON UNIT

COMPRESSOR

Number:

Phase:

Rated Load Amps:

Locked Rotor Amps:

C3

C2

WEIGHT

Equipment Submittal Page 18 of 25

Item: B2 Qty: 1 Tag(s): 4 ton 460/3

B

B

7/8" 7/8"

7/8"

7/8"

21 3/4"

18 3/4" 1 1/16"

3/8"

51 1/4"

6 15/16"

2 1/16"

2 1/8"

24 9/16"

9 11/16"

7"1 5/16"

4 5/16"

6 3/4"

1 7/16"

5 1/4"

2 3/4" 2 1/16"

2"

2 9/16" 5"

23 1/2" 21 1/2"

21 1/16"

12 1/8" 7 7/8"1"

1"

1"

21 13/16"19 3/8"

2 1/8"

5 13/16"

9 11/16"

7"1 7/16" 1 9/16"

3 5/16"

24 13/16"

2.00

1.38

0.88

1.50 TYP

GAS LINE 7/8"

LIQUID LINE 3/8"

2.00

1.38

NOTES:

1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH

INSTALLER DOCUMENTS BEFORE INSTALLATION

AIRHANDLER

DRAWING

LIQUID LINE 3/8"

GAS LINE 7/8"

VERTICAL DOWNFLOW CONNECTIONS

Equipment Submittal Page 19 of 25

TEM4A0C48S21SA

8.0/8.0 15.0/15.0

R-410A 7/8" 3/8"

138.0 lb

145.0 lb

N/A N/A N/A

N/A N/A

N/A N/A N/A

N/A N/A N/A

N/A N/A N/A

0.75 6.3

Remote filter No

1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps (ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data.

2. 3/4" male plastic pipe (ref.: astm 1785-76)

3. Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows:

low velocity filter: face area (sq. ft.) = cfm / 300 high velocity filter: face area (sq. ft.) = cfm / 500

4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be installed for horizontal applications. airflow should not exceed the face value of the filter being used

5. Standard mca and mop without electric heat.

NOTES:

REFRIGERANT

Number:

Horsepower:

Motor Speed (RPM):

Phase:

Full Load Amps:

Locked Rotor Amps:

Type:

Furnished:

Number:

Recommended:

FILTERS INDOOR MOTOR

Model:

Unit Primary Voltage:

Unit Secondary Voltage:

Unit Hertz:

Unit Phase:

GENERAL

(1)(2)(4)

ELECTRIC HEAT

240 Volt / 208 Volt

ELECTRICAL / GENERAL DATA

STANDARD

Minimum Circuit Ampacity:

Maximum Overload Protection:

230 Volt / 208 Volt

(1) (3)

Capacity Circuit #1:

Capacity Circuit #2:

Capacity Circuit #3:

# of Circuit:

Phase:

Heater Amps Per Circuit Circuit #1:

Heater Amps Per Circuit Circuit #2:

Heater Amps Per Circuit Circuit #3:

Minimum Circuit Ampacity Circuit #1:

Minimum Circuit Ampacity Circuit #2:

Minimum Circuit Ampacity Circuit #3:

Maximum Overload Protection Circuit #1:

Maximum Overload Protection Circuit #2:

Maximum Overload Protection Circuit #3:

(5) Weights Shipping:

Net:

Type:

REF. Line Connections Coupling or Conn. Size - Gas:

Coupling or Conn. Size - Liq.:

Equipment Submittal Page 20 of 25

Item: B3 Qty: 1 Tag(s): 5 ton 460/3

4TWA7060 - NOTES:

1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED

FOR AT LEAST 60"

ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF

RUN-OFF WATER DOES NOT POUR DIRECTLY ON

UNIT, AND SHOULD BE AT LEAST 12"

FROM WALL AND ALL SURROUNDING SHRUBBERY

ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.

2. ELECTRICAL AND REFRIGERANT COMPONENT

CLEARANCES PER PREVAILING CODES.

3. GAS LINE SIZE (1 1/8")

4. ALL WEIGHTS ARE APPROXIMATE.

5.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION

WITH INSTALLER DOCUMENTS BEFORE INSTALLATION

45 1/8"

8 5/8" 6"

3 3/8"

3 7/8"

32"

37 1/4"

34 1/4"

SEE NOTE 1

GAS LINE 1/4" TURN SERVICE, SEE TABLE I.D FEMALE

BRAZED CONNECTION WITH 1/4" SEA FLARE PRESSURE

TAP FITTING

K.O. FOR ALTERNATE

ELECTRICAL ROUTING

LIQUID LINE SERVICE VALVE

3/8" I.D FEMALE BRAZE

CONNECT WITH 1/4" SEA

FLARE PRESSURE TAP FITTING

7/8" DIA. HOLE

LOW VOLTAGE

1 1/8" DIA K.O. WITH 7/8"

DIA HOLE IN CONTROL

BOX BOTTOM FOR

ELECTRICAL POWER SUPPLY

SERVICE PANEL

ELECTRICAL SERICE PANEL

Equipment Submittal Page 21 of 25

Item: B3 Qty: 1 Tag(s): 5 ton 460/3

4TWA4060A4000A 9.0

15.0 15.0

414-506

0.20 0.60

R-410A

10.6 lb 1 1/8" 3/8"

248.0 lb

298.0 lb

7.1 52.0

D

IS

C H

AR

G

E

1. Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240.

2. Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses.

3. Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line.

For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0

4. * = 15, 20, 25, 30, 40 and 50 foot lineset available.

NOTES:

REFRIGERANT

OUTDOOR MOTOR

GENERAL

ELECTRICAL / GENERAL DATA

POWER CONN.

NET

SHIPPING

WEIGHT AND CLEARANCE

C4

C1

C3

Model:

Operating Voltage:

Unit Primary Voltage:

Unit Secondary Voltage Unit Hertz:

Unit Phase:

Minimum Circuit Ampacity:

Maximum Circuit Breaker:

Minimum Protection Rating:

Number:

Horsepower:

Motor Speed (RPM):

Phase:

Full Load Amps:

Locked Rotor Amps:

Type:

Charge:

Line Size O.D. Gas:

Line Size O.D. LIQ:

NOTES:

C1. TOP DISCHARGE SHOULD BE UNRESTRICTED

FOR AT LEAST 60" ABOVE UNIT

C2. PLACE UNIT FROM WALL

C3. PLACE SHRUBBERY AT LEAST 12"

FROM UNIT ON TWO SIDES, OTHER SIDES

UNRESTRICTED

C4. PLACE UNIT SO ROOF RUN-OFF DOES NOT

FALL DIRECTLY ON UNIT

COMPRESSOR

Number:

Phase:

Rated Load Amps:

Locked Rotor Amps:

C3

C2

WEIGHT

Equipment Submittal Page 22 of 25

Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small)

NOTES

1. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION.

2. BADGE ROTATION WILL BRAND IN CORRECT POSITION.

VERTICAL DOWNFLOW

FRONT

SIDE

BACK

INLET DUCT

OUTLET DUCT

TO COMBUSTIBLE

MATERIALS (REQUIRED)

SERVICE CLEARANCE

(RECOMMENDED)

1"

2" 21"

1"

MINIMUM UNIT CLEARANCE TABLE

CLEARANCE NOTES:

* 1" FOR THE FIRST 36". OF OUTLET DUCT WHEN

ELECTRIC HEATERS ARE INSTALED 0" AFTER THE FIRST <<36.00~LN>>

VERTICAL UPFLOW

REFRIGERANT CONNECTION

UPFLOW CONDENSATE DRAIN

REFRIGERANT

CONNECTION

DOWNFLOW

CONDENSATE

DRAIN

HORIZONTAL CONDENSATE DRAIN

REFRIGERANT CONNECTION

HORIZONTAL RIGHT FLOW HORIZONTAL LEFT FLOW

HORIZONTAL CONDENSATE DRAIN

Equipment Submittal Page 23 of 25

Tag Data - BAYHTR4510AUT (Qty: 1) Item Tag(s) Qty C1 No Tag 1

Product Data - BAYHTR4510AUT Item: C1 Qty: 1

Equipment Submittal Page 24 of 25

Equipment Submittal Page 25 of 25

Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job.

Product Family - Odyssey Split System Indoor Unit Item Tag(s) Qty Description Model Number A1 7.5 ton Ody_I 1 Auditorium AHU TWE09043BAA--A

100000000000000 00000000000

Field Installed Option Description Part/Ordering Number 14.96kW (460/60/3) BAYHTRR415A

A2 5 ton Ody_I 1 Lobby AHU TWE06044AAA--A

100000000000000 00000000000

9.96kW (460/60/3) BAYHTRR410A

Product Family - Split System Air Conditioning Units (Small)

B2 4 ton 460/3 1 Classroom ----------4TWA4048

A4-TEM4A0C48S4

1S--------------0000- ----0000000000000 0000--00-0--0

External filter rack (TEM) BAYSF1235BAA