The document provided is a Scope of Work for a state and local contract opportunity related to the maintenance, repair, and replacement of Clamshell Boilers at the W.G. Murray Developmental Center in Illinois. The vendor shall furnish labor, equipment, and materials to purchase, remove, and install seven (7) Pebco Model # CSS-16-ML-A4-M Clamshell Simplex or equivalent at the Boiler House Coal Hopper. The vendor must ensure the clamshells meet specific requirements, including a minimum opening of 16" x 16" and the ability to handle coal of a density of 55 pcf. The work must be performed in accordance with Illinois Department of Labor, OSHA, and MSHA codes and standards, and the vendor must be licensed, insured, and bonded.
The contract is subject to Public Works requirements and Prevailing Wages. The vendor must provide all labor, materials, tools, equipment, and incidentals for the project and perform the work during normal business hours, Monday through Friday, excluding weekends and holidays. The vendor must provide daily work progress reports to the facility Chief Engineer.
Text of this file
SCOPE OF WORK
The vendor shall furnish labor/equipment/materials to maintain, repair, and replace including, but not limited to, the following:
W.G. Murray Developmental Center is seeking bids for purchase/removal of existing Clamshells and the installation of seven (7) Pebco Model # CSS-16-ML-A4-M Clamshell Simplex or equivalent at the Boiler House Coal Hopper.
Vendor must insure the clamshell meet a minimum opening of 16” x 16” with handling coal of a density of 55 pcf. Clamshell mounts to the discharge of hopper.
Vendor must insure construction is of 3/8” thick AR400 Class Abrasion Resistant Steel Plate.
Vendor must insure all welds meet AWS Standards.
Vendor must insure Gate Pivot Shafts are C-1045 Steel Shafting and are attached to heavy backing plates welded to the Gate Body.
Vendor must insure that re-greaseable bearings are utilized at pivot points attached to the gate blade. Bearings must be greaseable via pressure lubrication zerk fittings at the bearings.
Vendor must insure Gate Valve Flange includes a 3/8” thick Carbon Steel Flange that matches existing bolt pattern on Coal Hopper.
Vendor must insure manual actuation is performed by means of a lever arm attached to the blade arms which includes a mechanical bolt on blade stop.
Vendor must insure Clamshell is cleaned and prepped following SSPC-SP6 and painted using DTM alkyd, single coat system, 2-4ml DFT, RAL 6018 Green.
Vendor must follow all Illinois Dept. of Labor/OSHA/MSHA Codes and Standards that apply.
Vendor must be licensed, insured and bonded.
Vendor must provide all labor, materials, tools, equipment and all incidentals for project.
Vendor/Employee(s) must adhere to rules, regulations and policies of W.G. Murray Developmental Center.
W.G. Murray Developmental Center will not be held liable for any lost, stolen, broken tools, materials and equipment.
Vendor must perform repairs during normal business hours of 7:00AM to 4:00PM, Monday thru Friday excluding Weekends and Holidays.
Vendor must give facility Chief Engineer an daily work progress report of project performed.
This procurement is subject to Public Works requirements-810 ILCS 130/4 and Prevailing Wages 30 ILCS 500/25-60.
Other files
| File | Type | Posted |
|---|---|---|
| Mandatory Onsite Visit Guidance for Vendors Murray~11.docx | DOCX document | |
| Standard Terms and Conditions v.20.1~43.pdf | ||
| RMU50 - Prevailing Wage~3.pdf | ||
| FormsBSectionV201~30.docx | DOCX document | |
| StandardCertificationsV181~81.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .