Salient Characteristics Evapco Cooling Tower.docx
DOCX document 26 KB Posted
- Attached to
- RFI - Evapco AT212-2H9 Cooling Towers
- Solicitation number
- FA301626Q7023
About this file
This is a Request for Information (RFI) issued by the Department of the Air Force Air Education and Training Command for market research purposes to identify qualified suppliers of an Evapco AT212-2H9 cooling tower. The government seeks delivery of one (1) unit consisting of a two-cell, induced draft cooling tower to Joint Base San Antonio, Texas. The RFI explicitly states this is for equipment delivery only with no labor for removal or installation required. Responses were due by Friday, February 13, at 16:00 PM CST. The government clarified that this RFI does not constitute a solicitation, Request for Quotation, or promise to issue future procurement and that no contract will be awarded based on responses.
The Evapco AT212-2H9 cooling tower must meet specific salient characteristics including all type 304 stainless steel upper panel and basin construction with factory-welded seams, one 7-horsepower inverter duty motor per cell with AEGIS shaft grounding rings, PVC drift eliminators limiting drift loss to 0.001%, non-corrosive SCH 40 PVC spray distribution system, PVC cross-fluted fill, stainless steel-framed air inlet louvers, 8-inch end inlet and outlet connections with grooved couplings, vibration cutout switches, 5-kilowatt electric basin heaters per cell with low water cutoff and thermostat, equalizer connections, an external service platform with vertical ladder and safety cage, and a five-year total product warranty. The unit dimensions are 12 feet 4 7/8 inches wide by 8 feet 5 inches long by 11 feet 4 inches high.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI_Cooling Tower_.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics: The Cooling Tower Brand: Evapco Model: AT212-2H9 two (2) Cell induced draft shall be an exact replacement counterflow cooling tower and a full-featured commercial-industrial product for the purpose of supporting a replacement for the current Cooling Tower. The Cooling Tower needs to have the following characteristics:
Evapco AT212-2H9 Two (2) Cells:
· All type 304 Stainless steel upper panel construction including mechanical support assembly and fan screen.
· All type 304 stainless steel basins with factory welded seams.
· One (1) – 7 ½ HP inverter duty TEFC fan motor per cell. Fan motors are located out of moist air stream. Each motor is equipped with a factory installed AEGIS shaft grounding ring.
· PVC drift eliminators with drift loss of .001% of recirculating water rate.
· Non-corrosive SCH 40 PVC Spray Distribution System with non-clog nozzles.
· PVC cross-fluted fill, totally enclosed and protected bottom supported.
· PVC air inlet louvers, with stainless steel frames, ¾ openings to prevent trash and debris from entering the cold-water basins
· End inlet connection, BFW/Grooved, 8”
· End outlet connection, BFW/Grooved, 8”
· Vibration cut out switch per motor, factory mounted for field wiring by others
· Electric basin heater with LWCO & TSTAT (5Kw per cell)
· Equalizer connections per cell, BFW/Grooved
· External Service Platform with Vertical Ladder/Safety Cage for ease of service. Platform and ladder are shipped loose for field installation by others. Platform provides access to all drive components including fan motor.
· Five Year Total Product Warranty including Fan Motor
· Dimensions – 12’ 4 7/8” W x 8’ 5 ½” L x 11’ 4 ¼” H