Saginaw Correctional Facility - HVAC Renovations CD Drawings-5.pdf

PDF 3 MB Posted

Attached to
472/22064. CTS; Saginaw CF - HVAC Renovations
Solicitation number
RFQ-171-250000000271-1
Issued by
Wayne County, Flint City, Michigan

About this file

These are mechanical engineering design drawings for HVAC renovations at multiple buildings (Buildings 700, 800, 900, and 1200) for the Saginaw Correctional Facility, prepared by the State of Michigan's Department of Technology, Management and Budget (DTMB), State Facilities Administration, Design and Construction Division. The drawings are dated 1/22/2025 and labeled as a CD (Construction Document) Set, with project number 472SRFMAINTPROJ. The mechanical plans show upper-level floor plans with detailed HVAC modifications, including installation of new dampers, damper actuators, fire/smoke dampers, and associated control systems and wiring.

The key technical specifications include contractor requirements to field verify damper dimensions, install salvaged and new damper actuators, connect new 24-volt fire/smoke DDC (Direct Digital Control) dampers to existing fire alarm systems, and follow manufacturer's installation instructions. The drawings are part of a comprehensive HVAC upgrade project across multiple buildings, with consistent mechanical design approaches evident across the different building floor plans. The project appears to be a state-managed infrastructure improvement initiative focusing on modernizing and standardizing HVAC control systems within the correctional facility.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UPUP

UP

UP

UP

UP

X-EH-1

X-UH-1 M

X-LOUVER

X-SF-1

X-IT RACK

M

T T

X-TG 800

--- TYP. 2

X-TG 500

--- TYP. 2

X-22x12 RA X-22x12 RA X-22x8 RA

X-TG 800

--- TYP. 2

F/S F/S F/S F/S

X-16x12 SA

M-408

D-700-3

D-700-4

2 2 2 2

X-CONCRETE

PAD

X-20x48

LOUVERM

X-20x24 SA

DN TO 6" AFF

M

X-AHU-1

X-EH-2

X-42x42

LOUVER

M X-12x42

LOUVER

X-14x18 SA, ZONE 4

X-12x8 SA, ZONE 2

X-16x12 SA, ZONE 1

X-UH-2

X-DWH-1

X-DWH-2

X-8" VTR

X-24x24

LOUVER

X-SF-2

X-P-2 X-P-1

M

X-8" VTR

X-14x18 SA, ZONE 3

X-P-4

T

X-UH-2

T

X-SF-2 & X-EH-2

B-700-1 B-700-2

6'' VTR

4'' CA VTR 6'' VTR

4'' CA VTR

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

EPO SWITCH

M

T

X-UH-2

T

X-SF-2 & X-EH-2

B-700-1 B-700-2

6'' VTR

4'' CA VTR 6'' VTR

4'' CA VTR

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

EPO SWITCH

D-700-1

D-700-2

HVAC KEY NOTES

INSTALL NEW DAMPER AND ALL ASSOCIATED

ACCESSORIES AT THE LOCATION SHOWN.

CONTRACTOR TO FIELD VERIFY DIMENSIONS FOR

NEW DAMPER PRIOR TO ORDERING. INSTALL

SALVAGED DAMPER ACTUATOR, CONTROLS,

CONTROL WIRING, AND ALL ASSOCIATED

ACCESSORIES ON NEW DAMPER. CONTRACTOR

TO PROVIDE ALL REQUIRED COMPONENTS TO

CONNECT SALVAGED ACTUATOR TO NEW

DAMPER.

INSTALL NEW 24-VOLT FIRE/SMOKE DDC DAMPER

ACTUATOR, CONTROLS, CONTROL WIRING, AND

ALL ASSOCIATED ACCESSORIES PER THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS

IN THE LOCATIONS SHOWN. NEW DDC

ACTUATORS TO BE INSTALLED ON EXISTING

COMBINATION FIRE/SMOKE DAMPER. CONNECT

NEW DDC ACTUATOR TO EXISTING FIRE ALARM

SYSTEM.

22030.01

472/22064.CTS

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

KEY PLAN

SCALE: NTS

N

472SRFMAINTPROJ

1/22/2025 CD SET

M-408

BUILDING 700 UPPER LEVEL

FLOOR PLAN - MECHANICAL

NEW

DBP

CAT

N BUILDING 700 UPPER LEVEL FLOOR PLAN - MECHANICAL NEW

SCALE: 1/8" = 1'-0"

0 1 5 10 20

1 BUILDING 700 MECHANICAL ROOM - MECHANICAL NEW

SCALE: 1/4" = 1'-0"

UP

UP

UP

X-EH-1

X-UH-1 M

X-LOUVER

X-SF-1

X-IT RACK

M

T T

X-TG 800

--- TYP. 2

X-TG 500

--- TYP. 2

X-22x12 RA X-22x12 RA X-22x8 RA

X-TG 800

--- TYP. 2

F/S F/S F/S F/S

X-16x12 SA

M-409

D-800-3

D-800-4

2 2 2 2

X-CONCRETE

PAD

X-20x48

LOUVERM

X-20x24 SA

DN TO 6" AFF

M

X-AHU-1

X-EH-2

X-42x42

LOUVER

M X-12x42

LOUVER

X-14x18 SA, ZONE 4

X-12x8 SA, ZONE 2

X-16x12 SA, ZONE 1

X-UH-2

X-DWH-1

X-DWH-2

X-8" VTR

X-24x24

LOUVER

X-SF-2

X-P-2 X-P-1

M

X-8" VTR

X-14x18 SA, ZONE 3

X-P-4

T

X-UH-2

T

X-SF-2 & X-EH-2

B-700-1 B-700-2

6'' VTR

4'' CA VTR 6'' VTR

4'' CA VTR

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

EPO SWITCH

M

T

X-UH-2

T

X-SF-2 & X-EH-2

B-700-1 B-700-2

6'' VTR

4'' CA VTR 6'' VTR

4'' CA VTR

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

EPO SWITCH

D-800-1

D-800-2

HVAC KEY NOTES

INSTALL NEW DAMPER AND ALL ASSOCIATED

ACCESSORIES AT THE LOCATION SHOWN.

CONTRACTOR TO FIELD VERIFY DIMENSIONS FOR

NEW DAMPER PRIOR TO ORDERING. INSTALL

SALVAGED DAMPER ACTUATOR, CONTROLS,

CONTROL WIRING, AND ALL ASSOCIATED

ACCESSORIES ON NEW DAMPER. CONTRACTOR

TO PROVIDE ALL REQUIRED COMPONENTS TO

CONNECT SALVAGED ACTUATOR TO NEW

DAMPER.

INSTALL NEW 24-VOLT FIRE/SMOKE DDC DAMPER

ACTUATOR, CONTROLS, CONTROL WIRING, AND

ALL ASSOCIATED ACCESSORIES PER THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS

IN THE LOCATIONS SHOWN. NEW DDC

ACTUATORS TO BE INSTALLED ON EXISTING

COMBINATION FIRE/SMOKE DAMPER. CONNECT

NEW DDC ACTUATOR TO EXISTING FIRE ALARM

SYSTEM.

22030.01

472/22064.CTS

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

KEY PLAN

SCALE: NTS

N

472SRFMAINTPROJ

1/22/2025 CD SET

M-409

BUILDING 800 UPPER LEVEL

FLOOR PLAN - MECHANICAL

NEW

DBP

CAT

N BUILDING 800 UPPER LEVEL FLOOR PLAN - MECHANICAL NEW

SCALE: 1/8" = 1'-0"

0 1 5 10 20

1 BUILDING 800 MECHANICAL ROOM - MECHANICAL NEW

UP

UP

UP

UPUP

UP

UP

UP

UP

X-EH-1

X-UH-1 M

X-LOUVER

X-SF-1

X-IT RACK

M

T T

X-TG 800

--- TYP. 2

X-TG 500

--- TYP. 2

X-22x12 RA X-22x12 RA X-22x8 RA

X-TG 800

--- TYP. 2

F/S F/S F/S F/S

X-16x12 SA

M-410

D-900-3

D-900-4

2 2 2 2

X-CONCRETE

PAD

X-20x48

LOUVERM

X-20x24 SA

DN TO 6" AFF

M

X-AHU-1

X-EH-2

X-42x42

LOUVER

M X-12x42

LOUVER

X-14x18 SA, ZONE 4

X-12x8 SA, ZONE 2

X-16x12 SA, ZONE 1

X-UH-2

X-DWH-1

X-DWH-2

X-8" VTR

X-24x24

LOUVER

X-SF-2

X-P-2 X-P-1

M

X-8" VTR

X-14x18 SA, ZONE 3

X-P-4

T

X-UH-2

T

X-SF-2 & X-EH-2

B-700-1 B-700-2

6'' VTR

4'' CA VTR 6'' VTR

4'' CA VTR

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

EPO SWITCH

M

T

X-UH-2

T

X-SF-2 & X-EH-2

B-700-1 B-700-2

6'' VTR

4'' CA VTR 6'' VTR

4'' CA VTR

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

EPO SWITCH

D-900-1

D-900-2

HVAC KEY NOTES

INSTALL NEW DAMPER AND ALL ASSOCIATED

ACCESSORIES AT THE LOCATION SHOWN.

CONTRACTOR TO FIELD VERIFY DIMENSIONS FOR

NEW DAMPER PRIOR TO ORDERING. INSTALL

SALVAGED DAMPER ACTUATOR, CONTROLS,

CONTROL WIRING, AND ALL ASSOCIATED

ACCESSORIES ON NEW DAMPER. CONTRACTOR

TO PROVIDE ALL REQUIRED COMPONENTS TO

CONNECT SALVAGED ACTUATOR TO NEW

DAMPER.

INSTALL NEW 24-VOLT FIRE/SMOKE DDC DAMPER

ACTUATOR, CONTROLS, CONTROL WIRING, AND

ALL ASSOCIATED ACCESSORIES PER THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS

IN THE LOCATIONS SHOWN. NEW DDC

ACTUATORS TO BE INSTALLED ON EXISTING

COMBINATION FIRE/SMOKE DAMPER. CONNECT

NEW DDC ACTUATOR TO EXISTING FIRE ALARM

SYSTEM.

22030.01

472/22064.CTS

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

KEY PLAN

SCALE: NTS

N

472SRFMAINTPROJ

1/22/2025 CD SET

M-410

BUILDING 900 UPPER LEVEL

FLOOR PLAN - MECHANICAL

NEW

DBP

CAT

N BUILDING 900 UPPER LEVEL FLOOR PLAN - MECHANICAL NEW

SCALE: 1/8" = 1'-0"

0 1 5 10 20

1 BUILDING 900 MECHANICAL ROOM - MECHANICAL NEW

UP

UPUP

UP

M

X-LOUVER

X-SF-1

X-UH-1

X-EH-1

M

X-IT RACK

T T

X-TG 550

--- TYP. 2

X-TG 440

--- TYP. 2

X-TG 350

--- TYP. 2

X-22x10 SA X-22x8 SA X-18x10 SAX-22x10 SA

F/S F/S F/S F/S

M-411

D-1200-3

D-1200-4

2 2 2 2

X-UH-2

X-DWH-1

X-8" VTR

X-DWH-2

X-8" VTR

X-78x48

LOUVER

M

X-24x24

LOUVER

X-SF-2

X-AHU-1

M X-42x18 SA

UPX-EH-2

X-P-1 X-P-2

M

X-18x10 SA, ZONE 1

X-10x8 SA, ZONE 2

X-10x10 SA, ZONE 4

X-CONCRETE

PAD

M

X-10x8 SA, ZONE 3

X-P-4

TX-UH-1

T

X-SF-2 & X-EH-2

B-500-2 B-500-1

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

4'' CA VTR

(TYP.)

6'' VTR (TYP.)

EPO SWITCH

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

TX-UH-1

T

X-SF-2 & X-EH-2

B-500-2 B-500-1

MISC. EQUIPMENT DDC

CONTROL PANEL

X-AHU-1 DDC CONTROL

PANEL

4'' CA VTR

(TYP.)

6'' VTR (TYP.)

EPO SWITCH

MULTIZONE DAMPER

ACTUATOR(S), 4 ACTUATORS

D-1200-1

D-1200-2

HVAC KEY NOTES

INSTALL NEW DAMPER AND ALL ASSOCIATED

ACCESSORIES AT THE LOCATION SHOWN.

CONTRACTOR TO FIELD VERIFY DIMENSIONS FOR

NEW DAMPER PRIOR TO ORDERING. INSTALL

SALVAGED DAMPER ACTUATOR, CONTROLS,

CONTROL WIRING, AND ALL ASSOCIATED

ACCESSORIES ON NEW DAMPER. CONTRACTOR

TO PROVIDE ALL REQUIRED COMPONENTS TO

CONNECT SALVAGED ACTUATOR TO NEW

DAMPER.

INSTALL NEW 24-VOLT FIRE/SMOKE DDC DAMPER

ACTUATOR, CONTROLS, CONTROL WIRING, AND

ALL ASSOCIATED ACCESSORIES PER THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS

IN THE LOCATIONS SHOWN. NEW DDC

ACTUATORS TO BE INSTALLED ON EXISTING

COMBINATION FIRE/SMOKE DAMPER. CONNECT

NEW DDC ACTUATOR TO EXISTING

FIRE ALARM SYSTEM.

22030.01

472/22064.CTS

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

M a t r ix funding code sheet description

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O F

M

IC

H

IG

A N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

KEY PLAN

SCALE: NTS

N

472SRFMAINTPROJ

1/22/2025 CD SET

M-411

BUILDING 1200 UPPER

LEVEL FLOOR PLAN -

MECHANICAL NEW

DBP

CAT

N BUILDING 1200 UPPER LEVEL FLOOR PLAN - MECHANICAL NEW

SCALE: 1/8" = 1'-0"

0 1 5 10 20

1 BUILDING 1200 MECHANICAL ROOM - MECHANICAL NEW

Sheets and Views
M408-2203000-M-407
M409-2203000-M-408
M410-2203000-M-409