S02 SPECS 6.pdf
PDF 572 KB Posted
- Solicitation number
- 36C24221B0061
About this file
This document contains a statement of work and specifications for a federal construction project to replace condenser water piping in Building 4 at the VA Brooklyn Medical Center in New York.
The project scope includes replacing condenser water piping from the chiller plant to the cooling towers on the roof of Building 4, replacing valves and controls, installing electrical heat tracing of piping, and supporting piers for roof piping. Work must be performed according to the statement of work, drawings, specifications and within 260 days of notice to proceed. The general contractor must submit a preliminary schedule and comply with safety, security and infection control requirements, including utilizing containment carts for above-ceiling work. Hazardous materials must be inventoried and environmental protection procedures followed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S02 SPECS 5.pdf | ||
| S02 SPECS 1.pdf | ||
| S02 DRAWINGS 5.pdf | ||
| S02 DRAWINGS 4.pdf | ||
| S02 DRAWINGS 3.pdf | ||
| S02 SPECS 3.pdf | ||
| S02 SPECS 4.pdf | ||
| S02 SPECS 2.pdf | ||
| S02 ALL POSTERS.pdf | ||
| S02 ADDITIONAL INSERTS.pdf | ||
| S02 Participation Goals for Minorities and Females.pdf | ||
| S02 DRAWINGS 2.pdf | ||
| S02 DRAWINGS 1.pdf | ||
| 36C24221B0061.docx | DOCX document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA New York Harbor Healthcare System February 19, 2021 Install Generator for B85, B86 & B87 Bid Documents
Jamaica, NY Project No. 630A4-18-415
28 23 00 - 7 the extent referenced. The publications are referenced in the text by the basic designation only.
B. American National Standards Institute (ANSI)/Electronic Industries
Alliance (EIA):
330-09..................Electrical Performance Standards for CCTV
Cameras
375A-76.................Electrical Performance Standards for CCTV
Monitors
C. Institute of Electrical and Electronics Engineers (IEEE):
C62.41-02...............IEEE Recommended Practice on Surge Voltages in
Low-Voltage AC Power Circuits
802.3af-08..............Power over Ethernet Standard
D. Federal Communications Commision (FCC):
(47 CFR 15) Part 15 Limitations on the Use of Wireless Equipment/Systems
E. National Electrical Contractors Association (NECA):
303-2005................Installing Closed Circuit Television (CCTV)
Systems
F. National Fire Protection Association (NFPA):
70-17...................Article 780-National Electrical Code
G. Federal Information Processing Standard (FIPS):
140-2-02................Security Requirements for Cryptographic Modules
H. Underwriters Laboratories, Inc. (UL):
983-06..................Standard for Surveillance Camera Units
3044-01.................Standard for Surveillance Closed Circuit
Television Equipment
1.7 COORDINATION
A. Coordinate arrangement, mounting, and support of video surveillance equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping and conduit installed at required slope.
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.
28 23 00 - 8
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
C. Coordinate location of access panels and doors for video surveillance items that are behind finished surfaces or otherwise concealed.
1.8 WARRANTY OF CONSTRUCTION
A. Warrant VASS System work subject to the Article “Warranty of
Construction” of FAR clause 52.246-21.
B. Demonstration and training shall be performed prior to system acceptance.
PART 2 – PRODUCTS
2.1 GENERAL
A. Video signal format shall comply with IP and shall termination shall be
100 ohms.
B. Surge Protection: Protect components from voltage surges originating external to equipment housing and entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor entry connection to components.
C. Power Connections: Comply with requirements in Section 28 05 00 COMMON
WORK REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY, Part 2, as recommended by manufacturer for type of line being protected.
D. Tamper Protection: Tamper switches on enclosures, control units, pull boxes, junction boxes, cabinets, and other system components shall initiate a tamper-alarm signal when unit is opened or partially disassembled. Control-station, control-unit alarm display shall identify tamper alarms and indicate locations.
2.2 CAMERAS
A. All Cameras will be EIA 330 and UL 1.Minimum Protection for Power
Connections 120 V and more: Auxiliary panel suppressors shall comply with requirements in Section 28 05 00 COMMON WORK REQUIREMENTS FOR
ELECTRONIC SAFETY AND SECURITY, Part 2.
B. Minimum Protection for Communication, Signal, Control, and Low-Voltage
983 compliant as well as:
1. Will be charge coupled device (CCD cameras and shall conform to
National Television System Committee (NTSC) formatting.
28 23 00 - 9
2. Fixed cameras shall be color and the primary choice for monitoring following the activities described below. Pan/Tilt/Zoom (P/T/Z) cameras shall be color and are to be utilized to complement the fixed cameras.
3. Shall be powered over Ethernet. Network switches supporting PoE cameras shall have a back-up power source to ensure cameras are still operational in the event of loss of primary power to the VASS
System.
4. Shall be rated for continuous operation under the environmental conditions listed in Part 1, Project Conditions.
5. Will be home run to a monitoring and recording device via a controlling device such as a matrix switcher or network server and monitored on a 24 hour basis at a designated Security Management
System location.
6. Each function and activity shall be addressed within the system by a unique user defined name, with minimum of twenty (20) characters.
The use of codes or mnemonics identifying the VASS action shall not be accepted.
7. Shall come with built-in video motion detection that shall automatically monitor and process information from each camera. The camera motion detection shall detect motion within the camera's field of view and provide automatic visual, remote alarms as a result of detected motion.
8. Shall be programmed to digitally flip from color to black and white at dusk and vice versa at low light conditions.
9. Will be fitted with AI/DC lenses to ensure the image quality under different light conditions.
10. P/T/Z cameras shall be utilized in a manner that they complement fixed cameras and shall not be used as a primary means of monitoring activity.
11. Dummy or fake cameras will not be utilized at any time.
12. Appropriate signage shall be designed, provided, and posted that notifies people that an area is under camera surveillance.
28 23 00 - 10
2.3 DIGITAL BASED VIDEO MANAGEMENT SYSTEM EXISTING
2.4 VIDEO DISPLAY EQUIPMENT EXISTING2.5 CONTROLLING EQUIPMEN EXISTING
2.6 AUTOMATIC COLOR DOME CAMERA
A. The camera shall be a high-resolution color video camera with wide dynamic range capturing capability.
B. Comply with UL 639.
C. Pickup Device: 1/3 CCD interline transfer.
D. Horizontal Resolution: see cameras specs.
E. Signal-to-Noise Ratio: Not less than 50 dB, with the camera AGC off.
F. With AGC, manually selectable on or off.
G. Sensitivity: Camera shall provide usable images in low-light conditions, delivering an image at a scene illumination of see camera specs.
H. Sensitivity: Camera shall deliver 1-V peak-to-peak video signal at the minimum specified light level. The illumination for the test shall be with lamps rated at approximately 2200-K color temperature, and with the camera AGC off.
I. Manually selectable modes for backlight compensation or normal lighting.
J. Pan and Tilt: Direct-drive motor, 360-degree rotation angle, and 180-degree tilt angle. Pan-and-tilt speed shall be variable controlled by operator. Movement from preset positions shall be not less than 300 degrees per second.
K. Preset positioning: 64 user-definable scenes. Controls shall include the following:
1. In "sequence mode," camera shall continuously sequence through preset positions, with dwell time and sequencing under operator control.
2. Motion detection shall be available at each camera position.
L. Scanning Synchronization: Determined by external synch over the coaxial cable. Camera shall revert to internally generated synchronization on loss of external synch signal.
M. White Balance: Auto-tracing white balance, with manually settable fixed balance option.
N. Motion Detector: Built-in digital.
O. Dome shall support multiplexed control communications using coaxial cable recommended by manufacturer.
28 23 00 - 11
P. Megapixel High Definition Integrated Digital Network Camera
1. The network camera shall offer dual video streams with up to 3.1 megapixel resolution (2048 x 1536) in progressive scan format.
2. An alarm input and relay output shall be built in for integration with hard wired external sensors.
3. The network camera shall be capable of firmware upgrades through a network using a software-based device utility.
4. The network camera shall offer auto back focus (ABF) functionality through a push button on the camera. ABF parameters shall also be configurable through a standard Web browser interface.
5. The network camera shall offer a video output port providing an
NTSC/PAL analog video output signal for adjusting field of view and focus at the camera.
6. The network camera shall provide advanced low-light capabilities for color and day/night models with sensitivity down to 0.12 lux in color and 0.03 lux in black-white (B-W).
7. The network camera shall have removable IR cut filter mechanism for increased sensitivity in low-light installations. The sensitivity of IR cut filter removal shall be configurable through a Web browser.
8. The network camera shall support two simultaneous, configurable video streams. H.264 and MJPEG compression formats shall be available for primary and secondary streams with selectable unicast and multicast protocols. The streams shall be configurable in a variety of frame rates and bit rates.
9. The network camera shall support industry standard Power over
Ethernet (PoE)
10. IEEE 802.3af to supply power to the camera over the network. The network camera shall also offer a 24 VAC power input for optional use.
11. The network camera shall use a standard Web browser interface for remote administration and configuration of camera parameters.
12. The network camera shall have a window blanking feature to conceal user-defined privacy areas that cannot be viewed by an operator. The network camera shall support up to four blanked windows. A blanked area shall appear on the screen as a solid gray window.
13. The network camera shall support standard IT protocols.
28 23 00 - 12
14. The network camera shall support open architecture best practices with a published API available to third-party network video recording and management systems.
15. Megapixel High Definition Integrated Digital Network Camera
Technical Specifications:
Imaging Device 1/3-inch, effective
Imager Type CMOS, Progressive scan
Maximum Resolution 2048 x 1536
Signal-to-Noise Ratio 50 dB
Auto Iris Lens Type DC drive
Electronic Shutter Range 1~1/100,000 sec
Wide Dynamic Range 60 dB
White Balance Range 2,000° to 10,000°K
Sensitivity f/1.2; 2,850K; SNR >24dB Color
(1x/33ms) 0.50 lux Color SENS
(15x/500 ms) 0.12 lux
Mono SENS (15x/500 ms) Mono
(1x/33ms)0.25 lux 0.03 lux
Dome Attenuation Clear Zero light loss
Smoke f/1.0 light loss
Compression H.264 in base profile and MJPEG
Video Streams Up to 2 simultaneous streams, the second Stream variable based on the setup of the primary stream
Frame Rate Up to 30, 25, 24, 15, 12.5, 12, 10, 8, 7.5, 6.5, 4, 3, 2, and 1
(depending upon coding, resolution, and stream configuration
Available Resolutions 3.1 MPx2048 x 1536; 4:3 aspect ratio; 2.0 ips max., 10.0 Mbps bit rate for MJPEG; 3.0 ips max., 2.6
Mbps bit rate H.264
2.1 MPx1920 x 1080; 16:9 aspect
ratio: 15.0 ips max.,10.0 Mbps bit rate for MJPEG; 5.0 ips max., 2.7
Mbps bit rate H.264 3.1.9 MPx1600 x 1200; 4:3 aspect ratio; 15.0 ips max.,10.0 Mbps bit rate for MJPEG;
6.0 ips max., 2.6 Mbps bit rate
H.264
1.3 MPx1280 x 1024; 5:4 aspect
ratio; 15.0 ips max.,10.0 Mbps bit
28 23 00 - 13 rate for MJPEG; 8.0 ips max., 2.5
Mbps bit rate H.264
1.2 MPx1280 x 960; 4:3 aspect
ratio; 15.0 ips max., 9.8 Mbps bit rate for MJPEG; 9.8 ips max., 8.5
Mbps bit rate H.264 6.0.9 MPx1280 x
720; 16:9 aspect ratio; 30.0 ips max.,10.0 Mbps bit rate for MJPEG;
12.5 ips max., 2.5 Mbps bit rate
H.264
0.5 MPx800 x 600; 4:3 aspect ratio;
30.0 ips max., 5.8 Mbps bit rate for MJPEG; 25.0 ips max., 2.0 Mbps bit rate H.264 8.0.3 MPx640 x 480;
4:3 aspect ratio; 30.0 ips max.,
3.7 Mbps bit rate for MJPEG; 30.0
ips max.,1.6 Mbps bit rate H.264
0.1 MPx320 x 240; 4:3 aspect ratio;
30.0 ips max., 0.9 Mbps bit rate for MJPEG; 30.0 ips max., 0.4 Mbps bit rate H.264
Additional640 x 512, 640 x 352, 480 x 368, 480 x 272, 320 x 256, 320 x
Supported Protocols TCP/IP, UDP/IP (Unicast, Multicast
IGMP), UPnP, DNS, DHCP, RTP, RTSP, NTP,IPv4, SNMP, QoS, HTTP, HTTPS, LDAP(client), SSH, SSL, STMP, FTP, MDNS(Bonjour), and 802.1x (EAP)
Security Access Password protected
Software Interface Web browser view and setup, up to
16 cameras
Connectors RJ-45 for 1000Base-TX, Auto
MDI/MDI-X
Cable Cat6 cable or better for 100Base-TX
Input Voltage PoE (IEEE802.3af class 3)
Power Consumption 15.4 W
Current Consumption PoE <200 mA maximum
24 VAC <295 mA nominal; <390 mA maximum
Alarm Input 10 VDC maximum, 5 mA maximum
Alarm Output 0 to 15 VDC maximum, 75 mA maximum
Lens Mount CS mount, adjustable
Pan/Tilt Adjustment Pan 368°
Tilt 160° (10° to 170°)
Rotate 355°
28 23 00 - 14
16. Accessories
a. Pendant mount
b. Wall mount for pendant
c. Corner adapter for wall mount
d. Dome.
17. Recommended Lenses
a. Megapixel lens, varifocal, 2.2~6.0 mm, f/1.3~2.0
b. Megapixel lens, varifocal, 2.8~8.0 mm,f/1.1~1.9
c. Megapixel lens, varifocal, 2.8~12.0 mm, f/1.4~2.7
Q. LENSES
1. Camera Field of View shall be set by the Contractor to produce full view of door or window opening and anyone entering or leaving through it. Follow the project construction drawings for design intent.
2. Camera Lenses shall be of the type supplied with the camera from the manufacture. All cameras which are not supplied with lenses from the factory are specified in this specification. The lens shall be equipped with an auto-iris mechanism unless otherwise specified.
Lenses having auto-iris, DC iris, or motor zoom functions shall be supplied with connectors, wiring, receiver/drivers, and controls as needed to operate the lens functions. Lenses shall have sufficient circle of illumination to cover the image sensor evenly. Lenses shall not be used on a camera with an image format larger than the lens is designed to cover. Lenses shall be provided with pre-set capability.
3. Lenses shall have optical-quality coated optics, designed specifically for video surveillance applications, and matched to specified camera. Provide color-corrected lenses with color cameras, megapixel lenses for megapixel cameras, and lenses with day/night for color/b&w cameras.
4. Auto-Iris Lens: Electrically controlled iris with circuit set to maintain a constant video level in varying lighting conditions.
5. Zoom Lenses: Motorized, remote-controlled units, rated as "quiet operating." Features include the following:
a. Electrical Leads: Filtered to minimize video signal interference.
28 23 00 - 15
b. Motor Speed: Variable.
c. Lens shall be available with preset positioning capability to recall the position of specific scenes.
6. Lenses: Shall be utilized in a manner that provides maximum coverage of the area being monitored by the camera. The lenses shall:
a. Be 1/3” to fit CCD fixed camera.
b. Be all glass with coated optics.
c. Have mounts that are compatible with the camera selected.
d. Be packaged and supplied with the camera.
e. Have a maximum f-stop of f/1.3 for fixed lenses, and a maximum f-stop of f/1.6 for variable focus lenses.
f. Be equipped with an auto-iris mechanism.
g. Have sufficient circle of illumination to cover the image sensor evenly.
h. Not be used on a camera with an image format larger than the lens is designed to cover.
i. Be provided with pre-set capability.
7. Two types of lenses shall be utilized for both interior and exterior fixed cameras:
a. Manual Variable Focus
b. Auto Iris Fixed
8. Manual Variable Focus:
a. Shall be utilized in large areas that are being monitored by the camera. Examples of this are perimeter fence lines, vehicle entry points, parking areas.
b. Shall allow for setting virtually any angle of field, which maximizes surveillance effects.
c. Technical Characteristics:
Image format 1/3 inch
Focal length 5–50mm
Iris range F1.4 to close
Focus range 1m (3.3 ft)
Back focus distance 10.05 mm (0.4 in)
Angle view Wide (1/3 in) 53.4 x 40.1
Angle view Tele (1/3 in) 5.3 x 4.1
Iris control manual
28 23 00 - 16
Focus ctrl manual
Zoom ctrl manual
R. CAMERA HOUSINGS AND MOUNTS
1. This section pertains to all interior and exterior housings, domes, and applicable wall, ceiling, corner, pole, and rooftop mounts associated with the housing. Housings and mounts shall be specified in accordance to the type of cameras used.
2. All cameras and lenses shall be enclosed in a tamper resistant housing. Any additional mounting hardware required to install the camera housing at its specified location shall be provided along with the housing.
3. The camera and lens contained inside the housing shall be installed on a camera mount. All additional mounting hardware required to install the camera housing at its specified location shall be provided along with the housing.
4. Shall be manufactured in a manner that are capable of supporting a maximum of three (3) cameras with housings, and meet environmental requirements for the geographical area the camera support equipment is being installed on or within.
5. Environmentally Sealed
a. Shall be designed in manner that it provides a condensation free environment for correct camera operation.
b. Shall be operated in a 100 percent condensing humidity atmosphere.
c. Shall be constructed in a manner that:
1) Has a fill valve to allow for the introduction of nitrogen into the housing to eliminate existing atmospheric air and pressurize the housing to create moisture free conditions.
2) Has an overpressure valve to prevent damage to the housing in the event of over pressurization.
3) Is equipped with a humidity indicator that is visible to the eye to ensure correct atmospheric conditions at all times.
4) The leak rate of the housing is not to be greater than 13.8kPa or 2 pounds per square inch at sea level within a 90 day period.
28 23 00 - 17
5) It shall contain camera mounts or supports as needed to allow for correct positioning of the camera and lens.
6) The housing and sunshield are to be white in color.
6. All electrical and signal cables required for correct operations shall be supplied in a hardened carrier system from the controller to the camera.
7. The mounting bracket shall be adjustable to allow for the housing weight of the camera and the housing unit it is placed in.
8. Accessibility to the camera and mounts shall be taken into consideration for maintenance and service purposes.
S. Indoor Mounts
1. Ceiling Mounts:
a. This enclosure and mount shall be installed in a finished or suspended ceiling.
b. The enclosure and mount shall be fastened to the finished ceiling, and shall not depend on the ceiling tile grid for complete support.
c. Suspended ceiling mounts shall be low profile, and shall be suitable for replacement of 610mm x 610mm (2 foot by 2 foot) ceiling tiles.
2. Wall Mounts:
a. The enclosure shall be installed in manner that it matches the existing décor and placed at a height that it will be unobtrusive, unable to cause personal harm, and prevents tampering and vandalism.
b. The mount shall contain a manual pan/tilt head that will provide
360 degrees of horizontal and vertical positioning from a horizontal position, and has a locking bar or screw to maintain its fixed position once it has been adjusted.
T. Interior Domes
1. The interior dome shall be a pendant mount, pole mount, ceiling mount, surface mount, or corner mounted equipment.
2. The lower portion of the dome that provides camera viewing shall be made of black opaque acrylic and shall have a light attenuation factor of no more that 1 f-stop.
3. The housing shall be equipped with integral pan/tilt capabilities complete with wiring, wiring harness, connectors, receiver/driver, 28 23 00 - 18 pan/tilt control system, pre-position cards, or any other hardware and equipment as needed to fully provide a fully functional pan/tilt dome.
4. The pan/tilt mechanism shall be:
a. Constructed of heavy duty bearings and hardened steel gears.
b. Permanently lubricated to ensure smooth and consistent movement of all parts throughout the life of the product.
c. Equipped with motors that are thermally or impedance protected against overload damage.
d. Pan movements shall be 360 degrees and tilt movement shall no be less than +/- 90 degrees.
e. Pan speed shall be a minimum of 10 degrees per second.
2.7 POWER SUPPLIES
A. Power supplies shall be thru enhanced power over Ethernet switches.
2.8 NETWORK SERVER
A. Allow for the transmission of live video, data, and audio over either an existing Ethernet network or a dedicated security system network, requiring an IP address or Internet Explorer 5.5 or higher, or shall work as an analog-to-Ethernet “bridge” controlling matrices, multiplexers, and pan/tilt/zoom cameras. The network shall operate in a box-to-box configuration allowing for encoded video to be decoded and displayed on an analog monitor.
B. If a VASS System network is going to be utilized as the primary means of monitoring, operating, and recording cameras then the following equipment shall be required as part of the system:
1. System Server
2. Computer Workstation
3. Recording Device
4. Encoder/Decoder
5. Monitor
6. Hub/Switch
7. Router
8. Encryptor
C. Shall provide overall control, programming, monitoring, and recording of all cameras and associated devices within the VASS System.
D. All equipment on the network shall be IP addressable.
28 23 00 - 19
E. The VASS System network shall meet or exceed the following design and performance specifications:
1. Two MPEG-4 video streams for a total of 40 images per second will be provided.
2. PC Software that manages the installation and maintenance of all hardware transmitters and receivers on the network shall be provided.
3. Video Source that supports any NTSC video source to the computer network shall be addressed.
4. Receivers that could be used to display the video on a standard analog NTSC or PAL monitor will be addressed.
F. The system shall support the following network protocols:
1. Internet connections: RTP, Real Time Control Protocol (RTCP), UDP, IP, TCP, ICMP, HTTP, Simple Network Management Protocol (SNMP), IGMP, DHCP, and ARP.
2. Video Display: MPEG-4, M-JPEG in server push mode only.
3. Have the ability to adjust bandwidth, image quality and image rate.
4. Support image sizes of either 704 x 576 pixels or 352 x 288 pixels.
5. Have an audio coding format of G.711 or G.728.
6. Provide a video frame rate of at least 30 images per second.
7. Support LAN Interface Ethernet 10/100BaseT and be auto sensing.
8. Have a LAN Data Rate of 9.6 Kbps to 5.0 Mbps.
9. Utilize data interface RS-232/RS-422/RS-485.
G. All connections within the system shall be via CAT-5 cable and RJ-45 jacks. If analog equipment is used as part of the system, then either an encoder or a decoder will be utilized to convert the analog signal to a digital one.
H. The VASS network system shall conform to all VA agency wide security standards for administrator and operator use.
J. Network enhanced PoE Switch Technical Characteristics
Protocol and standard
IEEE802.3
IEEE802.3u
IEEE802.3ab
IEEE802.3af
IEEE802.3n
Ports 24 10/100/1000M auto-negotiation RJ-
48 ports with auto MDI/MDI-X
Network media Cat 6 UTP for 1,000Mbps
28 23 00 - 20
Transmission method store-and-forward
LED indicator power, act/link, speed
2.9 RECORDING DEVICES
A. All cameras on the VASS System shall be recorded in real time using a
Digital Video Recorder (DVR), Network Video Recorder (NVR), with 9 TB of attached storage. The type of recording device utilized should be determined by the size and type of VASS System designed and installed, and to what extent the system is to be utilized.
B. All recording devices shall be 47.5 cm (19 inch) rack-mountable.
C. All DVR’s and NVR’s that are viewable over an Intranet or Internet will be routed through an encryptor.
D. Encryptors shall:
1. Comply with FIPS PUB 140-2.
2. Support TCP/IP.
3. Directly interfaces to low-cost commercial routers.
4. Provide packet-based crypto synchronization.
5. Encrypt source and destination IP addresses.
6. Support web browser based management requiring no additional software.
7. Have a high data sustained throughput — 1.544 Mbps (T1) full duplex data rate.
8. Provide for both bridging and routing network architecture support.
9. Support Electronic Key Management System (EKMS) compatible.
10. Have remote management ability.
11. Automatically reconfigure when secure network or wide area network changes.
E. Digital Video Recorder (DVR)
1. Shall record video to a hard drive-based digital storage medium in either NTSC or MPEG format.
2. Shall meet the following minimum requirements:
a. Record at minimum rate of 30 images per second (IPS).
b. Have a minimum of eight (8) to 16 looping inputs.
c. Have a minimum of eight (8) to 16 alarm inputs and two (2) relay outputs.
d. Shall provide instantaneous playback of all recorded images.
e. Be IP addressable, if part of a VASS network.
28 23 00 - 21
f. Have built-in digital motion detection with masking and sensitivity adjustments.
g. Provide easy playback and forward/reverse search capabilities.
h. Complete audit trail database, with minimum of a six-month history that tracks all events related to the alarm; specifically who, what, where and when.
i. DVR management capability providing automatic video routing to a back-up spare recorder in case of failure.
j. Accessible locally and remotely via the Internet, Intranet, or a personal digital assistant (PDA).
k. Records all alarm events in real time, ensuring 60 seconds before and after the event are included in the recording.
l. Utilize RS-232 or fiber optic connections for integration with the SMS computer station via a remote port on a network hub.
m. Allow for independently adjustable frame rate settings.
n. Be compatible with the matrix switcher utilized to operate the cameras. The DVR could be utilized as a matrix switcher only if it meets all of the requirements listed in the matrix switcher section.
3. Technical Characteristics:
Compression MPEG-4
Internal Storage
Capacities.
2 TB. Available USB hard drive up to
250 GB.
Optional internal DVD available
Digital Recording Up to 16 video and 8 audio channels.
Full real-time video recording
Up to 400 IPS@352 x 288: PAL
Up to 200 IPS@352 x 288: PAL
Multiple simultaneous functions
Live viewing, Recording, playback, network transmission, back-up
Search functions Date/time search, event search, bookmark search, smart (pixel) Search
PTZ Control Third party PTZ control
User ID security 3 levels
Connectivity to external devices:
Eight 8 video input and looping output channels.
VGA and dual monitor BNC outputs.
28 23 00 - 22
Four 4 audio inputs and one 1 audio output.
Ethernet 10/100BaseT network connection.
Eight 8 alarm inputs and four 4 relay outputs.
Biphase connection to control Bosch PTZ cameras.
Third party PTZ control via RS-422/RS-
485 connection.
Front and back USB connectors to connect to a PC mouse, or archive video to a USB memory stick or similar device.
PC requirements Windows 2000 or above; DirectX 8.1 or above.
Intel Pentium III or above, AMD Athlon with 800 MHz or faster CPU.
512 MB or more RAM.
50 MB hard drive.
AGP VGA with 64 MB video RAM or above.
100/1000-BaseT network interface.
Electrical
Power Input: 100 to 240 VAC; 50/60 Hz
Power consumption: 120W
Max. 1.2 A
Video Video standard: PAL or NTSC selectable.
Resolution: 704 x 576 PAL, 704 x 480
NTSC
Compression: MPEG-4
Inputs: 8 or 16 composite video 0.5-2
Vpp, 75 Ohm automatic termination.
Outputs 8 or 16 composite video 1 Vpp, 75 Ohm.
Audio
Inputs: 4 or 8 line in, 30 kOhm
Output: 1 line, 100 kOhm
Monitors VGA: analog RGB 800x600
MON A: CVBS 1 Vpp 0.1 V, 75 Ohm, BNC
Monitor A multi-screen (VGA or CVBS)
MON B: CVBS 1 Vpp 0.1 V, 75 Ohm, BNC
Monitor B spot/alarm
Frame Rate and
Resolution
16-channels PAL: Up to 400 IPS@352x288, up to 200 IPS@704x288, up to 100
IPS@704x576.
Alarm inputs 16 configurable NO/NC, max. input 5
VDC.
28 23 00 - 23
Alarm outputs 8 relay outputs, configurable NO/NC, max. rated 1A, 125 VAC.
Connections
Ethernet: RJ45 modular jack 8 pins shielded, 10/100 Base-T.
Biphase: Screw terminal connector (5 outputs).
Maximum 5 controllable cameras per
Biphase output.
PTZ control interfaces: RS485/RS422.
Serial interface: RS232 output signal, DB9 male connector
Keyboard: RJ11 modular jack 6 pins
Network: Transmission speed: up to 120
IPS@352x240
Bandwidth control: Automatic
Remote users: Maximum 5 simultaneous connected Control Center users.
Processor Intel Pentium III 1330 MHz
Memory 512 MB RAM or better
Operating System Windows NT, ME, 2000, and XP
Video Card 32 MB of RAM capable of 24-bit true color display
Free Hard Disk
Space
640 MB for software installation
Network Card 1000 Base-T network for LAN operation
Archiving 640 GB Hard Drive or better; CD-RW
Video Input 1.0 Vpp (signal 714mV, sync 286mV) 75 ohms (BNC unbalanced)
Video Output Level 1.0 Vpp +/-10%,75 ohms(BNC unbalanced)
Impedance 75 ohms/Hi- impedance x 16 switchable
Network Interface Ethernet (RJ-45, 100/1000M)
Network Protocol TCP/IP, DHCP, HTTP, UDP
Network
Capabilities
Live/Playback/P/T/Z control
Recording Rate 30 ips for 720 x 240 (NTSC)
Password
Protection
Menu Setup, Remote Access
Recording Capacity 640 (1 or 2 fixed HDD) 1 CD-RW
Power Interrupt Auto recovered to recording mode
28 23 00 - 24
F. Network Video Recorder (NVR)
1. Shall record video to a hard drive-based digital storage medium in
MPEG, MPEG4 or H.264 format.
2. Shall meet the following minimum requirements:
a. Record at minimum rate of 30 IPS.
b. Have a minimum of eight (8) to 16 looping inputs.
c. Have a minimum of eight (8) to 16 alarm inputs and two (2) relay outputs.
d. Shall provide instantaneous playback of all recorded images.
e. Be IP addressable, if part of a VASS network.
f. Have built-in digital motion detection with masking and sensitivity adjustments.
g. Easy playback and forward/reverse search capabilities.
h. Complete audit trail database, with minimum of a six-month history that tracks all events related to the alarm; specifically who, what, where and when.
i. NVR management capability providing automatic video routing to a back-up spare recorder in case of failure.
j. Accessible locally and remotely via the internet, intranet, or a personal digital assistant (PDA).
k. Records all alarm events in real time, ensuring 60 seconds before and after the event are included in the recording.
l. Utilize RS-232 or fiber optic connections for integration with the SMS computer station via a remote port on a network hub.
m. Allow for independently adjustable frame rate settings.
n. Be compatible with the matrix switcher utilized to operate the cameras.
3. Technical Characteristics:
Hardware/CPU Pentium III Xeon or IV, 1.8 GHz
HDD Interface IDE or better; optional: SCSI II, SCSI Ultra, or Fiber Channel
RAM 1024 MB
Operating System Windows 2000/XP Professional/Server 2003
Standard
Graphic Card VGA
Ethernet Card 100/1000 MB
Memory 960 MB or better
28 23 00 - 25
Software Setup Centralized setup from each authorized PC;
access via integrated web server
Storage Media All storage media possible (e.g., HD, RAID), depending on operating system
Storage Mode Linear mode, ring mode (capacity-based)
Recording Configuration Camera name assignment, bandwidth limit, frame rate, video quality
Recording Content Video and/or audio data
Search Parameters Time, date, event
Playback Playback via any IP network (LAN/WAN) simultaneous recording, playback, and backup
Network Interface Ethernet (RJ-45, 10/100M)
Network Protocol TCP/IP, DHCP, HTTP, UDP
Network Capabilities Live/Playback/P/T/Z control
Recording Rate 30 ips for 720 x 240 (NTSC)
Password Protection Menu Setup, Remote Access
Recording Capacity 640 (1 or 2 fixed HDD) 1 CD-RW
Power Interrupt Auto recovered to recording mode
2.10 WIRES AND CABLES
A. Shall meet or exceed the manufactures recommendation for power and signal.
B. Will be carried in an enclosed conduit system, utilizing electromagnetic tubing (EMT) to include the equivalent in flexible metal, rigid galvanized steel (RGS) to include the equivalent of liquid tight, polyvinylchloride (PVC) schedule 40 or 80.
C. All conduits will be sized and installed per the NEC. All security system signal and power cables that traverse or originate in a high security office space will contained in either EMT or RGS conduit.
D. All conduit, pull boxes, and junction boxes shall be clearly marked with colored permanent tape or paint that will allow it to be distinguished from all other conduit and infrastructure.
E. Conduit fills shall not exceed 50 percent unless otherwise documented.
F. A pull string shall be pulled along and provided with signal and power cables to assist in future installations.
28 23 00 - 26
G. At all locations where there is a wall penetration or core drilling is conducted to allow for conduit to be installed, fire stopping materials shall be applied to that area
H. High voltage and signal cables shall not share the same conduit and shall be kept separate up to the point of connection. High voltage for the security system shall be defined as any cable or sets of cables carrying 30 VDC/VAC or higher.
I. For all equipment that is carrying digital data between the Physical
Access Control System and Database Management or at a remote monitoring station, shall not be less that 20 AWG and stranded copper wire for each conductor. The cable or each individual conductor within the cable shall have a shield that provides 100% coverage. Cables with a single overall shield shall have a tinned copper shield drain wire.
J. All cables and conductors, except fiber optic cables, that act as a control, communication, or signal lines shall include surge protection.
Surge protection shall be furnished at the equipment end and additional triple electrode gas surge protectors rated for the application on each wire line circuit shall be installed within 1 m. (3 ft.) of the building cable entrance. The inputs and outputs shall be tested in both normal and common mode using the following wave forms:
1. A 10 microsecond rise time by 1000 microsecond pulse width waveform with a peak voltage of 1500 watts and peak current of 60 amperes.
2. An 8 microsecond rise time by 20 microsecond pulse width wave form with a peak voltage of 1000 volts and peak current of 500 amperes.
K. The surge suppression device shall not attenuate or reduce the video or sync signal under normal conditions. Fuses and relays shall not be used as a means of surge protection.
L. Cables
1. All video signal cables for the VASS System, shall be 4 PR UTP.
2. Camera Cables:
a. Signal wiring for PoE cameras depends on the distance the camera is being installed from either a hub or the server.
b. If the camera is up to 300 ft from the server, then use a shielded UTP category 6 (CAT-VI) cable a with standard RJ-45 connector at each end. The cable with comply with the Power over
Ethernet, IEEE802.3af, Standard.
28 23 00 - 27
c. If the camera is over 300 ft from the server then utilize a multimode fiber optic cable with a minimum size of 50 microns.
d. Provide a separate cable for power.
e. CAT-6 see Division 27 for cable specifications.
2.11 SPARE PARTS
A. Provide 2-3.1 Megapixels dome indoor camera.
B. Provide 1-24 port enhanced PoE switch.
PART 3 - EXECUTION
3.1. GENERAL
A. Installation: The Contractor shall install all system components including Owner furnished equipment, and appurtenances in accordance with the manufacturer’s instructions, ANSI C2 and as shown, and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable data transmission system.
B. Identification and Labeling: The Contractor shall supply permanent identification labels for each cable at each end that will appear on the as-built drawings. The labeling format shall be identified and a complete record shall be provided to the Owner with the final documentation. Each cable shall be identified by type or signal being carried and termination points. The labels shall be printed on letter size label sheets that are self laminated vinyl that can be printed from a computer data base or spread sheet. The labels shall be E-Z code WES12112 or equivalent.
1. The Contractor shall provide all personnel, equipment, instrumentation, and supplies necessary to perform all testing.
C. Transient Voltage Surge Suppressors (TVSS): The Contractor shall mount
TVSS within 3 m (118 in) of equipment to be protected inside terminal cabinets or suitable NEMA 1 enclosures. Terminate off-premise conductors on input side of device. Connect the output side of the device to the equipment to be protected. Connect ground lug to a low impedance earth ground (less than 10 ohms) via Number 12 AWG insulated, stranded copper conductor.
D. Contractor’s Field Test: The Contractor shall verify the complete operation of the data transmission system during the Contractor’s Field
Testing. Field test shall include a bit error rate test. The
Contractor shall perform the test by sending a minimum of 1,000,000
28 23 00 - 28 bits of data on each DTM circuit and measuring the bit error rate. The bit error rate shall not be greater than one (1) bit out of each
100,000 bits sent for each dial-up DTM circuit, and one (1) bit out of
1,000,000 bits sent for each leased or private DTM circuit. The
Contractor shall submit a report containing results of the field test.
E. Acceptance Test and Endurance Test: The wire line data transmission system shall be tested as a part of the completed IDS and EECS during the Acceptance test and Endurance Test as specified.
F. Identification and Labeling: The Contractor shall supply identification tags or labels for each cable. Cable shall be labeled at both end points and at intermediate hand holes, manholes, and junction boxes. The labeling format shall be identified and a complete record shall be provided to the Owner with the final documentation.
Each cable shall be identified with type of signal being carried and termination points.
3.2 INSTALLATION
A. System installation shall be in accordance with NECA 303, manufacturer and related documents and references, for each type of security subsystem designed, engineered and installed.
B. Components shall be configured with appropriate “service points” to pinpoint system trouble in less than 30 minutes.
C. The Contractor shall install all system components including Government furnished equipment, and appurtenances in accordance with the manufacturer's instructions, documentation listed in Sections 1.5 of this document, and shall furnish all necessary connectors, terminators, interconnections, services, and adjustments required for a complete and operable system.
D. The VASS System will be designed, engineered, installed, and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the system is a stand alone or a complete network.
E. For integration purposes, the VASS System shall be integrated where appropriate with the following associated security subsystems:
1. PACS:
a. Provide 24 hour coverage of all entry points to the perimeter and agency buildings, as well as all emergency exits utilizing a fixed color camera.
28 23 00 - 29
b. Record cameras on a 24 hours basis.
c. Be programmed go into an alarm state when an emergency exit is opened, and notify the Physical Access Control System and
Database Management of an alarm event.
2. Security Access Detection:
a. Provide full coverage of all vehicle and lobby entrance screening areas utilizing a fixed color camera.
b. Record cameras on a 24 hours basis.
c. The VASS System should have facial recognition software to assist in identifying individuals for current and future purposes.
3. EPPS:
a. Provide a recorded alarm event via a color camera that is connected to the EPPS system by either direct hardwire or a security system computer network.
b. Record cameras on a 24 hours basis.
c. Be programmed to go into an alarm state when an emergency call box or duress alarm/panic device is activated, and notify the
Physical Access Control System and Database Management of an alarm event.
F. Integration with these security subsystems shall be achieved by computer programming or the direct hardwiring of the systems.
G. For programming purposes refer to the manufacturers requirements for correct system operations. Ensure computers being utilized for system integration meet or exceed the minimum system requirements outlined on the systems software packages.
H. A complete VASS System shall be comprised of the following components:
1. Cameras
2. Lenses
3. Video Display Equipment
4. Camera Housings and Mounts
5. Controlling Equipment
6. Recording Devices
7. Wiring and Cables
I. The Contractor shall visit the site and verify that site conditions are in agreement/compliance with the design package. The Contractor shall report all changes to the site or conditions that will affect performance of the system to the Contracting Officer in the form of a
28 23 00 - 30 report. The Contractor shall not take any corrective action without written permission received from the Contracting Officer.
J. Existing Equipment
1. The Contractor shall connect to and utilize existing video equipment, video and control signal transmission lines, and devices as outlined in the design package. Video equipment and signal lines that are usable in their original configuration without modification may be reused with Contracting Officer approval.
2. The Contractor shall perform a field survey, including testing and inspection of all existing video equipment and signal lines intended to be incorporated into the VASS System, and furnish a report to the Contracting Officer as part of the site survey report. For those items considered nonfunctioning, provide (with the report) specification sheets, or written functional requirements to support the findings and the estimated cost to correct the deficiency. As part of the report, the Contractor shall include a schedule for connection to all existing equipment.
3. The Contractor shall make written requests and obtain approval prior to disconnecting any signal lines and equipment, and creating equipment downtime. Such work shall proceed only after receiving
Contracting Officer approval of these requests. If any device fails after the Contractor has commenced work on that device, signal or control line, the Contractor shall diagnose the failure and perform any necessary corrections to the equipment.
4. The Contractor shall be held responsible for repair costs due to
Contractor negligence, abuse, or incorrect installation of equipment.
5. The Contracting Officer shall be provided a full list of all equipment that is to be removed or replaced by the Contractor, to include description and serial/manufacturer numbers where possible.
The Contractor shall dispose of all equipment that has been removed or replaced based upon approval of the Contracting Officer after reviewing the equipment removal list. In all areas where equipment is removed or replaced the Contractor shall repair those areas to match the current existing conditions.
K. Enclosure Penetrations: All enclosure penetrations shall be from the bottom of the enclosure unless the system design requires penetrations
28 23 00 - 31 from other directions. Penetrations of interior enclosures involving transitions of conduit from interior to exterior, and all penetrations on exterior enclosures shall be sealed with rubber silicone sealant to preclude the entry of water and will comply with VA Master
Specification 07 84 00, Firestopping. The conduit riser shall terminate in a hot-dipped galvanized metal cable terminator. The terminator shall be filled with an approved sealant as recommended by the cable manufacturer and in such a manner that the cable is not damaged.
L. Cold Galvanizing: All field welds and brazing on factory galvanized boxes, enclosures, and conduits shall be coated with a cold galvanized paint containing at least 95 percent zinc by weight.
M. Interconnection of Console Video Equipment: The Contractor shall connect signal paths between video equipment as specified by the OEM.
Cables shall be as short as practicable for each signal path without causing strain at the connectors. Rack mounted equipment on slide mounts shall have cables of sufficient length to allow full extension of the slide rails from the rack.
N. Cameras:
1. Install the cameras with the focal length lens as indicated for each zone.
2. Connect power and signal lines to the camera.
3. Aim camera to give field of view as needed to cover the alarm zone.
4. Aim fixed mounted cameras installed outdoors facing the rising or setting sun sufficiently below the horizon to preclude the camera looking directly at the sun.
5. Focus the lens to give a sharp picture (to include checking for day and night focus and image quality) over the entire field of view
6. Synchronize all cameras so the picture does not roll on the monitor when cameras are selected.
7. PTZ cameras shall have all preset positions and privacy areas defined and programmed.
O. Monitors:
1. Install the monitors as shown and specified in design and construction documents.
2. Connect all signal inputs and outputs as shown and specified.
3. Terminate video input signals as required.
4. Connect the monitor to AC power.
28 23 00 - 32
P. Switcher:
1. Install the switcher as shown in the design and construction documents, and according to the OEM.
2. Connect all subassemblies as specified by the manufacturer and as shown.
3. Connect video signal inputs and outputs as shown and specified;
terminate video inputs as required.
4. Connect alarm signal inputs and outputs as shown and specified;
connect control signal inputs and outputs for ancillary equipment or secondary control/monitoring sites as specified by the manufacturer and as shown.
5. Connect the switcher CPU and switcher subassemblies to AC power.
6. Load all software as specified and required for an operational VASS
System configured for the site and building requirements, including data bases, operational parameters, and system, command, and application programs.
7. Provide the original and 2 backup copies for all accepted software upon successful completion of the endurance test.
8. Program the video annotation for each camera.
Q. Video Encoder/Decoder
1. Install the Video Encoder/Decoder per design and construction documents, and as specified by the OEM.
2. Connect analog camera inputs to video encoder.
3. Connect network camera to video decoder.
4. Connect video encoder to VASS network.
5. Connect video decoder to video matrix, DVR, monitor.
6. Connect unit to AC power (UPS).
7. Configure the video encoder/decoder per manufacturer’s recommendation and project requirements.
R. Video Server:
1. Install the video server per design and construction documents, and as specified by the OEM.
2. Connect video server to AC power (UPS).
3. Connect to VASS network.
4. Install operating system and Video Management Software.
5. Provide Video Management Software programming per VA guidance and the requirements provided by the Owner. Programming shall include:
28 23 00 - 33
a. Camera names
b. Screen views
c. Camera recording schedules (continuous and event) driven recording. Events include alarms from other systems (sensors), manual input, and video motion detection.
d. Video detection zones for each camera requiring video motion detection
e. Alarm interface
f. Alarm outputs
g. GUI maps, views, icons and actions
h. PTZ controls (presets, time schedules for privacy zones)
i. Reports
S. Video Workstation:
1. Install the video workstation per design and construction documents, and as specified by the OEM.
2. Connect video workstation to AC power (UPS).
3. Connect to VASS network.
4. Install operating system and application software.
5. Provide application software programming per VA guidance and the requirements provided by the Owner. Programming shall include:
a. Screen views
b. Graphical User Interface (GUI) maps, views, icons and actions
c. Alarm outputs
d. Reports
T. Network Switch:
1. Install the network switch per design and construction documents, and as specified by the OEM.
2. Connect network switch to AC power (UPS).
3. Connect network cameras to network switch.
4. Configure the network switch per manufacturer’s recommendation and project requirements.
U. Network Recording Equipment
1. Install the NVR or video storage unit as shown in the design and construction documents, and as specified by the OEM.
2. Connect recording device to AC power (UPS).
3. Connect recording device to network switch as shown and specified.
4. Configure network connections
28 23 00 - 34
5. Provide recording unit programming per VA guidance and the requirements provided by the Owner. Programming shall include:
a. Camera names
b. Screen views
c. Camera recording schedules (continuous and event) driven recording. Events include alarms from other systems (sensors), manual input, and video motion detection.
d. Video detection zones for each camera requiring video motion detection
e. Alarm interface
f. Alarm outputs
g. GUI maps, views, icons and actions
h. PTZ controls (presets, time schedules for privacy zones)
i. Reports
V. Video Recording Equipment:
1. Install the video recording equipment as shown in the design and construction documents, and as specified by the OEM.
2. Connect video signal inputs and outputs as shown and specified.
3. Connect alarm signal inputs and outputs as shown and specified.
4. Connect video recording equipment to AC power.
5. Program the video recording equipment;
a. Recording schedules
b. Camera caption
W. Video Signal Equipment:
1. Install the video signal equipment as shown in the design and construction documents, and as specified by the OEM.
2. Connect video or signal inputs and outputs as shown and specified.
3. Terminate video inputs as required.
4. Connect alarm signal inputs and outputs as required.
5. Connect control signal inputs and outputs as required
6. Connect electrically powered equipment to AC power.
X. Camera Housings, Mounts, and Poles:
1. Install the camera housings and mounts as specified by the manufacturer and as shown, provide mounting hardware sized appropriately to secure each camera, housing and mount with maximum wind and ice loading encountered at the site.
2. Provide a foundation for each camera pole as specified and shown.
28 23 00 - 35
3. Provide a ground rod for each camera pole and connect the camera pole to the ground rod as specified in Division 26 of the VA Master
Specification and the VA Electrical Manual 730.
4. Provide electrical and signal transmission cabling to the mount location via a hardened carrier system from the Physical Access
Control System…
This is the start of the file's text. The full file is on GovTribe.