S02-NLV Bid Set Combined Drawings - 20220517.pdf
PDF 12 MB Posted
- Solicitation number
- 36C26123R0035
About this file
This document outlines a federal solicitation for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21 is seeking a firm-fixed price contract to upgrade Pharmacy areas at the North Las Vegas VA Medical Center to meet USP 800 codes and compounding standards. The solicitation is a total SDVOSB set aside. Offerors must be verified in VIP/SBA at the time of proposal submission and prior to award. The period of performance is 180 days after notice to proceed. Proposals are due no later than May 4, 2023 at 2:00pm PDT and shall be submitted to the identified Contract Specialist and Contracting Officer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI-Answers the Questions Final_17May2023.pdf | ||
| 36C26123R0035 0004.docx | DOCX document | |
| 36C26123R0035 0003.docx | DOCX document | |
| 36C26123R0035 0002.docx | DOCX document | |
| S04-Attachment Site Vistit Present_Pharmacy_12Apr2023.pdf | ||
| S02-Attachment_Pharmacy Photos.pdf | ||
| S04-Site Visit Attendees_12Apr2023.pdf | ||
| 36C26123R0035 0001.docx | DOCX document | |
| S02-Wage Rate_NV20230038_17Mar2023.pdf | ||
| S02-Price Breakdown Worksheet1.pdf | ||
| 36C26123R0035.docx | DOCX document | |
| S02-ATTACHMENT - Contractor Certification Regarding Safety and Environmental.docx | DOCX document | |
| S02-Request for Information (RFI) Form.docx | DOCX document | |
| S02-NLV Bid Set Combined Specs - 20220517 - 1(28Mar2023).pdf | ||
| S02-SOW - Main Pharmacy_FINAL.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
U N I T
E D
STAT ES OF
A M
E R I C A
S
RI
A F F A
SN
AR
ETEVFO
TN
E
M T R
A P
E
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o n e o e q u a rt e r in c h o th re e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
G001
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 MW STL
COVER SHEET NLV UPGRADE
INPATIENT PHARMACY
1 24
NORTH LAS VEGAS, NEVADA
NORTH
LOCATION MAP
PROJECT TEAM DRAWING SHEET INDEX
ENGINEERING:
ARCHITECTURE:
OWNER:
BUILDING OCCUPANCY:
CONSTRUCTION TYPE: DESCRIPTIONSHEET
PHONE: 269.927.0144
SEVEN GENERATIONS A+E
KALAMAZOO, MI 49007
600 E. MICHIGAN AVENUE - SUITE B
1A, AUTOMATIC SPRINKLER SYSTEM
WEB:
FIRST FLOOR: I-2
WWW.7GENAE.COM
PHONE: 619.770.5882
DAVENERGY SOLUTIONS
SAN DIEGO, CA 92102
2207 GARNET AVE, SUITE 1
NORTH LAS VEGAS, NV, 89086
VA NORTH LAS VEGAS
6900 NORTH PECOS RD
PROJECT INFORMATION
M401 MECHANICAL SCHEDULES
M501 MECHANICAL DETAILS
M-502 MECHANICAL SEQUENCE OF OPERATIONS - GENERAL
M-503 MECHANICAL SEQUENCE OF OPERATIONS - AIR HANDLER UNIT
M-504 MECHANICAL SEQUENCE OF OPERATIONS
E001 ELECTRICAL GENERAL INFO & SYMBOL LEGEND
E101 FIRST FLOOR POWER PLAN
E201 FIRST FLOOR LIGHTING PLAN
E301 FIRST FLOOR SYSTEMS PLAN
G001 COVER SHEET
G002 GENERAL INFORMATION AND WALL TYPES
A002 HAUL ROUTE AND ICRA PLAN
A101 DEMO PLAN, FLOOR PLAN
A102 EQUIPMENT PLAN, REFLECTED CEILING PLAN
A600 DOOR AND FRAME SCHEDULE
A701 FIRST FLOOR FINISH PLAN
P-001 PLUMBING COVER SHEET
P101 PLUMBING 1ST FLOOR PLAN
M-001 MECHANICAL COVER SHEET
MD-101 MECHANICAL 1ST FLOOR DEMOLITION PLAN
M-101 MECHANICAL 1ST FLOOR PLAN
M-101A MECHANICAL 1ST FLOOR PLAN - DIFFUSER CALLOUTS
MP-101 MECHANICAL 1ST FLOOR PIPING PLAN
M-102 MECHANICAL ROOF FLOOR PLAN
PROJECT NO. 593-18-104 NLV UPGRADE INPATIENT PHARMACY
NORTH LAS VEGAS, NEVADA
100% BID DOCUMENTS
DEPARTMENT OF VETERANS AFFAIRS
OFFICE OF CONSTRUCTION AND
FACILITIES MANAGEMENT
DEPARTMENT OF VETERANS AFFAIRS
MEDICAL CENTER
6900 NORTH PECOS ROAD
PHONE: 269.585.2255
STEELHEAD ENGINEERING CO.
KALAMAZOO, MI 49007
259 E MICHIGAN AVE
PHONE: 415.495.3700
SIMPSON GUMPERTZ & HEGER
OAKLAND CA, 94612
1999 HARRISON ST, SUITE 2400
DESCRIPTIONSHEET
REVISIONS DATE
A300
A320
ARCHITECTURAL SYMBOLS & PLAN INDICATORS
ABBREVIATIONS
BARRIER-FREE DESIGN INFORMATION
ROOMNAME
XXX
A
A
A
A
8'-0"
TOP OF STEEL
ELEV. 10'-0"
A200
TITLE
SCALE X" = 1'-0"
OBSTRUCTED APPROACH
UNOBSTRUCTED APPROACH
TYP. CODE REGULATED MOUNTING HEIGHTS
SCALE: NONE
TYP. EQUIPMENT MOUNTING HEIGHTS
SCALE: NONE
ELEVATION INDICATION
SHEET NO.
ELEVATION NUMBER
SECTION INDICATOR
ENLARGED PLAN OR
ELEVATION
PROPOSED SPOT
EXISTING SPOT
ELEVATION
100.57'
100.57'
STRUCTURAL SPAN
ROOF TRUSSES
FLOOR JOIST OR
RAMP
@ 16" O.C.
2 x 12
1" per 12"
SLOPE UP
REVISION TAG W/
REVISION NUMBER
KEYNOTE TAG
WINDOW TAG W/
WINDOW TYPE
INDICATOR
WALL SECTION CUT
COLUMN LINE
WALL TYPES
ELEVATION
BUILDING SECTION CUT
SHEET LOCATION
DETAIL NUMBER
TYPICAL
DIMENSIONING
SET-BACK LINE
PROPERTY LINE
EXISTING
CONTOUR
TOPOGRAPHY
CONTOUR
100'
100'
TOPOGRAPHY
PROPOSED
SECTIONS & DETAILS
TYPICAL TITLE FOR
DOOR NUMBER
DOOR TAG W/
ROOM NUMBER
ROOM NAME/
NORTH ARROW
60" DIAMETER CLEAR
WHEELCHAIR TURNING
SPACE - REFER TO PLAN
- REFER TO PLAN
AND GROUND SPACE
30" x 48" CLEAR FLOOR
CEILING HEIGHT TAG
GENERAL NOTES:
OPERATING MECHANISMS & HARDWARE
SHALL COMPLY WITH SECTION 309 OF
ICC/ANSI A117.1.
ACCESSIBLE SIGNAGE FURNISHED BY OWNER,
SHALL COMPLY WITH SECTION 703 OF
ICC/ANSI A117.1.
RECEPTACLE
LIGHT
SWITCH
HVAC
CONTROLS
FIRE
ALARM
FEC
LESS THAN 40#
TEL
PUSH PAD
RH/CH
GBX
SH1
CL
OT
SPH
CRK SND
PT
SD
HS
XR COM4 MR
CRBG
WP
4'-4"
TV
MOUNTING HEIGHT GENERAL NOTES:
1. REFER TO INTERIOR ELEVATIONS FOR
ADDITIONAL INFORMATION.
2. ITEMS ON THIS SHEET ARE NOT NECESSARILY
INCLUDED IN THIS PROJECT.
3. CONTRACTOR TO VERIFY ALL EQUIPMENT
MOUNTING HEIGHTS WITH OWNER/AE
PRIOR TO INSTALLATION.
4. REFER TO MECHANICAL/ELECTRICAL
DRAWINGS FOR DEVICE MOUNTING
HEIGHTS.
XXXNORTH
M A
X
M
IN
" 4
" 5
M A
X
SIDE FRONT
M
A X
M
A X
20" - 25"
M
A X
FRONT
M
A X
20" MAX
SIDE
SIDE FRONT
M
IN
M
A X
M
IN
M
A X
@ AT
A/C AIR CONDITIONING/AIR CONDITIONER
ACOUS ACOUSTICAL
AD AREA DRAIN, AUTOMATIC DAMPER
ADJ ADJUST, ADJUSTABLE
ALUM ALUMINUM
AP ACCESS PANEL
ACT ACOUSTICAL CEILING
B BASE
BAR BARRIER
BD BOARD
BF BARRIER FREE
BKT BRACKET
BLDG BUILDING
BLKG BLOCKING
BOTT BOTTOM
C TO C CENTER TO CENTER
CAB CABINET
CE COLUMN ENCLOSURE
CIR CIRCLE
CIR CIRCUIT
CL CENTER LINE, CLEARANCES
CLG CEILING
CJ CONTROL JOINT
CLKG CAULKING
CLO CLOSET
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CSS CLINICAL SERVICE SINK
CT CERAMIC TILE
CTR CENTER
CUH CABINET UNIT HEATER
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA, D DIAMETER
DIM DIMENSION
DN DOWN
DR DRAIN
DS DOWNSPOUT
ELECT ELECTRICAL
ELEV ELEVATION
ENTR ENTRANCE
EQ EQUAL
EP ELECTRICAL PANEL
EXH EXHAUST
EXP EXPOSED
EXIST EXISTING, EXSIST'G
EXT EXTERIOR
EW EACH WAY
FA FIRE ALARM
FD FIRE DAMPER OR FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FINISH
FL, FLR FLOOR FINISH
FLG, FLRG FLOORING, FLOOR'G
FURN FURNITURE, FURNACE
FWC FABRIC WALL COVERING
FT FEET, FOOT
GALV GALVANIZE(D)
GL GLASS
GSB GYPSUM SHEATHING BOARD
GWB GYPSUM WALLBOARD
GYP. BD GYPSUM BOARD
O.C. ON CENTER
OPN'G OPENING
O, O2 OXYGEN
PLAST PLASTIC
PNT PAINT
PREFAB PREFABRICATED
PST PACIFIC STANDARD TIME
PLYWD PLYWOOD, PLYW'D
R RADIUS
RA RETURN AIR
REQ'D REQUIRED
RM ROOM
S SINK, SOUTH, SHINGLE
SA SUPPLY AIR
SAN SANITARY
SMKD SMOKE DAMPER
SECT SECTION
SHWR SHOWER
SIM SIMILAR
SPEC SPECIFICATION
SQ SQUARE
SS SERVICE SINK, STAINLESS STEEL
STD STANDARD
STOR STORAGE
SUSP SUSPEND(ED)
SYM SYMBOL, SYMMETRICAL
T TEMPERED
TBD TO BE DETERMINED BY COR
TOIL TOILET
TYP TYPICAL
UNFIN UNFINISHED
UTIL UTILITY
VAC VACUUM
VAV VARIABLE AIR VOLUME
VCT VINYL COMPOSITION TILE
VD VOLUME DAMPER
VERT VERTICAL
V.I.F. VERIFY IN FIELD
VT VINYL TILE
VWC VINYL WALL COVERING
W/ WITH
WC WATER CLOSET
WD WOOD
WNDW WINDOW
W. HTR WATER HEATER
W/O WITHOUT
WP WALL PROTECTION
A420
A320
IF
B A
R R
IE
R
F R
E E
ID INSIDE DIAMETER
INSUL INSULATION
IN INCH(ES)
JAN JANITOR'S CLOSET
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HANDRAIL
HT HEIGHT
HW HEADWALL
LAM LAMINATED
LF LINEAL FEET
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MANUF MANUFACTURED, MANUFACTURER
MIN MINIMUM
MLD'G MOLDING
MTL METAL
N NORTH
NAT NATURAL
NIC NOT IN CONTRACT
NORM NORMAL
NTS NOT TO SCALE
NOTE: 15" MINIMUM DIMENSION FOR OBSTUCTED APPROACH
APPLIES AT GRASPED ITEMS (I.E. HANDLES)
(1) LAYER OF 5/8" TYPE GYP. BD.
EACH SIDE OF METAL STUDS @ 16"
O.C. (MAX.); WRAP GYP. BD.
AROUND ENDS/ CORNERS WHERE
EXPOSED
CEILING LINE
FLOOR LINE
UNDERSIDE OF DECK
STEEL STUD DEFLECTION
TRACK ANCHORED TO DECK
NOTE: REFERENCE FINISH SCHEDULE FOR CEILING, WALL, BASE AND FLOOR
FINAL FINISH. PARTITION WIDTH DOES NOT INCLUDE FINAL FINISH.
STEEL STUD CHANNEL
RUNNER FASTENED TO FLOOR
PLAN
TYPE STUD SIZE
PARTITION
WIDTH
FIRE RATING
SOUND
ATTENUATION
BACKER ROD AND
SEALANT BOTH SIDES
BACKER ROD AND
SEALANT BOTH SIDES
FILL ENTIRE CAVITY WITH
SOUND BATT INSULATION
8" 9-1/4" NONE
BATTS
STC 49 MINA8
3-5/8" 4-7/8" NONEA4
BATTS
STC 49 MIN
COPE AROUND STRUCTURE
AND SEAL SMOKE TIGHT
ALL PENETRATIONS
REFER TO REFLECTED CEILING PLAN
(1) LAYERS OF 5/8" GYP. BD. ON
METAL STUDS @ 16" O.C. (MAX.)
CEILING LINE
FLOOR LINE
UNDERSIDE OF DECK
STEEL STUD DEFLECTION
TRACK ANCHORED TO DECK
STEEL STUD CHANNEL
RUNNER FASTENED TO FLOOR
PLAN
TYPE STUD SIZE
PARTITION
WIDTH
FIRE RATING
SOUND
ATTENUATION
2-1/2" 3-1/8" NONEB3
BACKER ROD AND SEALANT
BACKER ROD AND SEALANT
BOTH SIDES
COPE AROUND STRUCTURE
AND SEAL SMOKE TIGHT
ALL PENETRATIONS
BATTS
FILL ENTIRE CAVITY WITH SOUND
BATT INSULATION
/2
3-5/8" 4-1/4" NONEB4 BATTS
REFER TO REFLECTED CEILING PLAN
NOTE: REFERENCE FINISH SCHEDULE FOR CEILING, WALL, BASE AND FLOOR
FINAL FINISH. PARTITION WIDTH DOES NOT INCLUDE FINAL FINISH.
FLOOR LINE
TYPE WYTHE SIZE
PARTITION
WIDTH
FIRE RATING
SOUND
ATTENUATION
EXIST. EXIST. EXIST. 1 HR NONE
EXISTING CMU WALL CONSTRUCTION
AND METAL STUD FRAMING TO
REMAIN; CONTRACTOR TO ADD
BLOCKING AT ALL WALL MOUNTED
EQUIPMENT LOCATIONS (REFER TO
EQUIPMENT PLAN). CONTRACTOR TO
PROVIDE SUPPLEMENTAL METAL
STUDS WHERE REQUIRED THAT MATCH
EXISTING TYPE.
PLAN
D1
UNDERSIDE OF DECK
NEW (1) LAYER OF
5/8" TYPE GYP. BD.
CEILING LINE
REFER TO REFLECTED CEILING PLAN
NOTE: REFERENCE FINISH SCHEDULE FOR CEILING, WALL, BASE AND FLOOR
FINAL FINISH. PARTITION WIDTH DOES NOT INCLUDE FINAL FINISH
BACKER ROD AND SEALANT
1 LAYER OF 5/8" GYP. BD. ON
METAL STUDS @ 16" O.C. (MAX.);
WRAP GYP. BD. AROUND ENDS/
CORNERS WHERE EXPOSED
CEILING LINE
FLOOR LINE
UNDERSIDE OF DECK
STEEL STUD DEFLECTION
TRACK ANCHORED TO DECK
STEEL STUD CHANNEL
RUNNER FASTENED TO FLOOR
PLAN
TYPE STUD SIZE
PARTITION
WIDTH
FIRE RATING
SOUND
ATTENUATION
3-5/8" 4-1/4" -
BATTS
STC 52 MIN.
C4
BACKER ROD AND SEALANT
BACKER ROD AND 'QUIETSEAL'
SEALANT BOTH SIDES
FILL ENTIRE CAVITY WITH
SOUND BATT INSULATION
COPE AROUND STRUCTURE
AND SEAL SMOKE TIGHT
ALL PENETRATIONS
REFER TO REFLECTED CEILING PLAN
NOTE: REFERENCE FINISH SCHEDULE FOR CEILING, WALL, BASE AND FLOOR
FINAL FINISH. PARTITION WIDTH DOES NOT INCLUDE FINAL FINISH.
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
G002
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 MH MH
GENERAL INFORMATION
AND WALL TYPES
NLV UPGRADE
INPATIENT PHARMACY
2 24
SCALE: 1 1/2" = 1'-0"
WALL TYPE A
SCALE: 1 1/2" = 1'-0"
WALL TYPE B
SCALE: 1 1/2" = 1'-0"
WALL TYPE D
SCALE: 1 1/2" = 1'-0"
WALL TYPE C
D
Y
H
D
Y
H
VAN
VAN
VA
N
PARKING LOT
D
PARKING LOT
CPARKING LOT
B
PARKING LOT
A
PARKING LOT
F
PARKING LOT
E
GOV
PARKING LOT
G
PARKING LOT
H
PARKING LOT
J
PARKING LOT
I
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A
A
A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
VAN
VAN
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
V A N
VA
N
VA
N
VA
N
VAN
VAN
VAN
26HC
14HC
BLDG
#1
BLDG
#5
BLDG
#2
BLDG
#3
BLDG
#6
BLDG
#4
EAST DEER SPRINGS
WAY
HOSPITAL
ADMINISTRATION
EMERGENCY
DEPARTMENT
ENERGY
PLANT
GENERATORS
WATER
TANKS
(4 Typ)
WAREHOUSE
HOSPITAL
AUDITORIUM
EMERGENCY
MANAGEMENT
&RESIDENT ENGINEER
BLDG
BLDG
#7 EDUCATION
SOLAR FARM (1.8
MW)
FISHER
HOUSE
BLDG
#8
MAIN
HOSPITAL
BLDG
#9
MENTAL HEALTH
CLINIC
EMERGENCY
MANAGEMENT
YARD
SPECIALTY
CLINICS
BELTWAY
EM
ERGENCY D
EPT
PARKIN
G
GENERAL
PROJECT
LOCATION
LEGEND
HAUL ROUTE
LAYDOWN AREA
LOADING DOCK
168 SF
1D352C
NON-HAZARDOUS
COMPOUNDING
BUFFER ROOM
72 SF
1D352A
DONNING/DOFFING
183 SF
1D352D
HAZARDOUS
COMPOUNDING
BUFFER ROOM
113 SF
1D352B
ANTE
3' - 6" MIN. 4' - 8" 2' - 5"
TEMPORARY WALL
PARTITION
TEMPORARY HOLLOW METAL 45
MIN. FRAME AND WOOD DOOR
(36"x72"). DOOR TO REMAIN
LOCKED AND BE KEYED W/ VA
STANDARD LOCKSET.
STICKY MATS TO BE PROVIDED AND
MAINTAINED DURING DURATION OF
CONSTRUCTION BY CONTRACTOR
D E
TE
R M
IN
E w
C O
R O
N S
IT
E P
R
IO
R T
O I N
S
TA
LL
"TEMPORARY WALL PARTITION
CONTRACTOR TO REPAIR
AND REPLACE ALL DAMAGED
FLOORING AND CEILING
TILES/GRID AT THE DURATION
OF THE PROJECT AND WHEN
THE TEMPORARY WALL
PARTITION IS REMOVED
EXISTING PICKER
EXISTING PYXIS
CODE COMPLIANCE LEGEND
1-HOUR FIRE RATED PARTITION - UL DES U419
2-HOUR FIRE RATED BARRIER - UL DES U419
1-HOUR SMOKE BARRIER - NFPA 101 - 8.3
3-HOUR FIRE RATED BARRIER - UL DES U419
4-HOUR FIRE RATED BARRIER - UL DES U419
ROOM NAME
XXX SF
ROOM NAME
ROOM NUMBER
ROOM AREA
CODE ROOM TAG INFORMATION
PATH OF EGRESS
EXIT
OCCUPANT LOAD PER EXIT
OCCUPANT LOAD
EGRESS CORRIDOR
ROOM OCCUPANT LOADXX
EXISTING CEILING
3 5/8" METAL STUDS @ 16''
OC WITH FULL BATT SOUND
ATTENUATIONG INSULATION
COMPRESSIBLE
INSULATION
COMPRESSIBLE
INSULATION
SEAL PERIMETER
COMPRESSIBLE
INSULATION
(1) LAYER 5/8" GYP. BOARD
EACH SIDE. FINISH OCCUPIED
SIDE WITH GLOSS PAINT TO
MATCH EXISTING ADJACENT
CONTINUOUS DUCT
TAPE SEAL EACH SIDE
EXISTING FINISHED
FLOOR
OCCUPIED SIDE OF BARRIER''WORK'' SIDE OF BARRIER
CONTINUOUS FIRE
RETARDANT TREATED
WOOD NAILER
CONTINUOUS DUCT
TAPE SEAL EACH SIDE
AT CEILING
3 5/8" METAL STUDS @ 16''
OC WITH FULL BATT SOUND
ATTENUATIONG INSULATION
CLOSE OPEN DUCTS WITH 6
MIL POLYETHLENE BARRIER.
SEAL EDGES WITH
CONTINUOUS DUCT TAPE
CLOSE INTERSTITIAL SPACE
WITH 6 MIL POLYETHLENE
BARRIER. SEAL ALL JOINTS,
PENETRATIONS AND ENTIRE
PERIMETER OF BARRIER WITH
CONTINUOUS DUCT TAPE
CONTINUOUS FIRE
RETARDANT TREATED
WOOD NAILER
ICRA GENERAL NOTES
1. REFER TO 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL
INFORMATION.
2. CONSTRUCT ICRA BARRIER PRIOR TO ANY DEMOLITION
WORK.
3. THE INTENT OF INFECTION CONTROL ISOLATION IS TO
CONTAIN DUST AND PARTICULATE MATTER FROM THE
CONSTRUCTION AREA. PERIMETER TO BE SEALED
COMPLETELY WITH SHEET PLASTIC WHEN NO TEMPORARY
PARTITION IS CALLED OUT.
4. REFER TO DEMOLITION PLANS FOR PRESSURE MONITORS
DRUING CONSTRUCTION OPERATIONS.
5. CONTROL BARRIERS TO BE INSTALLED AND REMOVED ONLY
DURING AFTER HOURS (5:30 PM PST - 6:00 AM PST)
6. LIFE SAFETY EGRESS IS TO BE MAINTAINED AT ALL TIMES.
7. EXACT TEMPORARY WALL PARTITION LAYOUT AND
DIMENSIONS TO BE REVIEWED AT THE CONSTRUCTION SITE
WITH COR APPROVAL.
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
A002
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 MH MH
HAUL ROUTE AND ICRA
PLAN
NLV UPGRADE
INPATIENT PHARMACY
3 24
NORTH
SCALE: 1" = 10'-0"
CAMPUS MAP
NORTH
SCALE: 1/4" = 1'-0"
ICRA/ CODE COMPLIANCE
PLAN
SCALE: 1 1/2" = 1'-0"
TEMPORARY WALL PARTITION
FLOOR PLAN LEGEND
EXISTING NON-FIRE RATED WALL
NEW NON-FIRE RATED WALL
EXISTING DOOR
NEW DOOR
1-HOUR FIRE RATED PARTITION - UL DES U419
2-HOUR FIRE RATED BARRIER - UL DES U419
1-HOUR SMOKE BARRIER - NFPA 101 - 8.3
EXISTING FIRE RATED CMU WALL
FLOOR PLAN GENERAL NOTES
1. PROVIDE BLOCKING IN WALLS FOR EQUIPMENT AS SHOWN ON EQUIPMENT PLANS AND/OR
ON INTERIOR ELEVATIONS. COORDINATE FINAL EQUIPMENT AND SUBSEQUENT BLOCKING
LOCATIONS WITH OWNER PRIOR TO INSTALL.
2. ALL WALLS CARRYING PLUMBING FIXTURES SHALL BE 5/8" MOISTURE RESISTANT GYP BOARD.
3. CONTRACTOR SHALL PATCH, REPAIR, AND INFILL ALL APPLIED FIREPROOFING MATERIAL IN
AREAS LEFT UNPROTECTED DUE TO REMOVAL OF EXISTING ELEMENTS OR AREAS DAMAGED
DURING NEW WORK AND DEMOLITION. MATCH EXISTING FIREPROOFING MATERIAL TYPE AND
THICKNESS TO MAINTAIN REQUIRED LEVEL OF PROTECTION.
4. THIS FLOOR TO BE SEPARATED FROM FLOORS ABOVE & BELOW BY 2-HR SEPARATION. ANY
PENETRATION CREATED OR OBSERVED IN THE AREA OF RENOVATION TO BE PATCHED AND
INFILLED WITH APPLIED FIREPROOFING MATERIALS.
5. WHERE A WALL TYPE IS CALLED OUT IN PLAN CONTINUE THE FRAMING AND PROVIDE
ADDITIONAL SUPPORT FRAMING FOR THE HEAD, JAMB AND SILL. THIS ADDITIIONAL SUPPORT
FRAMING SHALL BE INCLUDED AT ALL BORROWED LIGHTS AND SLIDING DOOR LOCATIONS.
SLIDING DOORS IN PARTICULAR WILL REQUIRE ADDITIONAL 2x WOOD FRAMING AS PER
MANUFACTURER REQUIREMENTS.
EXISTING BREAK OUT
EXISTING SOLUTIONS
SHELVING TO REMAIN
EXISTING STAFF TOILET
/8
/8
EXISTING LOCKERS
TO REMAIN
168 SF
1D352C
NON-HAZARDOUS
COMPOUNDING
BUFFER ROOM
72 SF
1D352A
DONNING/DOFFING
183 SF
1D352D
HAZARDOUS
COMPOUNDING
BUFFER ROOM
113 SF
1D352B
ANTE
REWORK EXISTING
STUD FRAMING AND
PROVIDE NEW
FRAMING AS
REQUIRED FOR NEW
DUCT; TYP.
16' - 2"
7' - 10" +/-
SINK W/ EYE WASH,
REFER TO PLUMBING
4' - 5 5/8" +/- 5' - 5 7/8" 12' - 8"
11' - 5 3/8" 7' - 6"
D
B
1D352C
1D352D
D1
D1
A8
A8 A4A8
E1
A4
D1
D1
E1
B3
E1
C
LE
A
R
1' - 0" CLEAR
D
A
B3B3
B3B3
B3B3
A8
A
LI
G N
EXISTING CORRIDOR
WALL CONSTRUCTION
TO REMAIN
EXISTING CORRIDOR
WALL CONSTRUCTION
TO REMAIN
E1
E1
E1
B3
A
LI
G N
C
LE
A
R
1' - 3" CLEAR
A
LI
G N
C
LE
A
R
C4
A101 03
A101 02
2' - 4" 2"
REWORK EXISTING STUD
FRAMING AND PROVIDE
NEW BORROWED LIGHT
OPENING
1' - 4"
3' - 4"
2' - 6" 2' - 4"
B3
D1
B3B3
CC
CC
DD
BB
AA
EXISTING PICKER
TO REMAIN
8"
A101
1' - 5"
COORDINATE ALL MECHANICAL CHASES WITH
MECHANICAL DRAWINGS. A MINIMUM 1"
CLEARANCE AROUND DUCTS TO BE REOVIDED.
A101
A101
A101
A101
4 5 6 9
4 5 6
4 5 6 9
4 5
6 9
4 5
6 9
2 2
EXISTING LOCKERS
TO REMAIN
12 13
1D354
IV CLEAN ROOM
1D355
CHEMO PREP
1D361
HAC
1D338
STORAGE CARROUSEL
1D353
VESTIBULE
1D352
ANTE ROOM
EXISTING PICKER
TO REMAIN
NOTE: REFER TO ICRA PLAN
FOR TEMPORARY
CONSTRUCTION BARRIER
ASSEMBLY AND FURTHER
INFORMATION NOT
SHOWN ON THIS PLAN
EXISTING SOLUTIONS
SHELVING TO REMAIN
DEMOLITION KEY NOTES
REMOVE EXISTING WALL CONSTRUCTION COMPLETE FROM FLOOR TO DECK INCLUDING GYP
BOARD(BOTH SIDES), STUD FRAMING AND ALL ITEMS ATTACHED TO THE WALLS (INCLUDING
BUT NOT LIMITED TO BASE, CORNER GUARDS, DOOR STOPS, SHELVES, RACKS, SIGNAGE,
CLOCKS, PPE). PATCH & REPAIR ADJACENT SURFACES TO REMAIN AS NECESSARY TO PREPARE
FOR NEW CONSTRUCTION AND/OR NEW FINISHES.
REMOVE (1) SIDE OF EXISTING GYPSUM BOARD IN ITS ENTIREY BACK TO EXISTING WALL
FRAMING. REMOVE ALL ITEMS ATTACHED TO THE WALLS (INCLUDING BUT NOT LIMITED TO
BASE, CORNER GUARDS, DOOR STOPS, SHELVES, RACKS, SIGNAGE, CLOCKS, PPE) EXISTING
WALL CONSTRUCTION FRAMING TO REMAIN, AND BE REWORKED/ PROVIDE NEW (WIDTH TO
MATCH EXISTING)AS REQUIRED FOR NEW CONSTRUCTION INCLUDING DOORS AND
OPENINGS, AND AS REQUIRED FOR ALL ITEMS IN THE MEP DRAWINGS.
REMOVE EXISTING DOOR(S), FRAME(S), HARDWARE, ETC. TURN OVER TO OWNER UNLESS
DIRECTED OTHERWISE.
REMOVE EXISTING WALL FINISHES, WALL BASE, AND ALL ITEMS ATTACHED TO THE WALLS. TURN
OVER TO OWNER, UNLESS DIRECTED OTHERWISE. PATCH & REPAIR EXPOSED SURFACES TO
REMAIN AS REQUIRED FOR NEW CONSTRUCTION AND/OR NEW FINISHES.
REMOVE EXISTING FLOORING AND FLOOR FINISHES INCLUDING ALL ADHESIVES, SETTING
MATERIALS DOWN TO EXISTING SUBSTRATE. GRIND CONCRETE FLOORS AS REQUIRED TO
PROVIDE A SMOOTH AND UNIFORM SURFACE FOR NEW FINISHES. ALL EXISTING SUBSTRATE TO
RECEIVE NEW SELF-LEVELING UNDERLAYMENT, VERIFY TYPE WITH RESINOUS FLOOR SYSTEM
MANUFACTURER.
REMOVE EXISTING CEILING TILE AND GRID SYSTEM. TURN OVER TO THE OWNER OR SALVAGE
TILE FOR RECYCLING UNLESS DIRECTED OTHERWISE.
REMOVE EXISTING GYPSUM BOARD (BOTH SIDES) AND REWORK STUD WALL FRAMING IN
PREPARATION FOR NEW WINDOW/DOOR PER NEW WORK PLAN. COMPLETE DEMOLITION
AND REWORK FOR JAMB AND HEADER SUPPORT.
DISCONNECT AND REMOVE EXISTING PASS THROUGH COMPLETE INCLUDING ALL BLOCKING
AND RETURN TO COR.
REMOVE EXISTING PLUMBING COMPLETE. REFER TO PLUMBING DEMOLITION PLANS FOR
FURTHER DEMO INFORMATION. REMOVE ASSOCIATED PAPER TOWEL SOAP DISPENSER AND
ANY ADJACENT WALL MOUNTED EQUIPMENT. REPAIR SURFACES TO REMAIN AS REQUIRED TO
RECEIVE NEW CONSTRUCTION AND FINISHES.
REMOVE EXISTING WINDOW SYSTEM AS SHOWN. PATCH & REPAIR ADJACENT SURFACES TO
REMAIN AS NECESSARY TO PREPARE FOR NEW CONSTRUCTION AND/OR NEW FINISHES.
REMOVE EXISTING SLIDING SHELVING COMPLETE INCLUDING FLOOR RAILING. PATCH AND
REPAIR FLOORING AND WALL SURFACES.
REMOVE EXISTING WALL TILE WAINSCOTING COMPLETE GROUT, BACKING MATERIAL,
MORTAR COMPLETE. REPAIR AND REPLACE ANY STUD FRAMING TO REMAIN.
REMOVE EXISTING FLOOR TILE COMPLETE INCLUDING GROUT, MORTAR/THINSET MUD BED
COMPLETE INCLUDING ANY REINFORCING. PATCH AND REPAIR EXISTING FLOOR OPENINGS
WITH A UL APPROVED 2 HOUR RATED FLOOR INFILL.
DEMO A PORTION OF EXISTING STUD FURRING BACK TO CMU AT CHASE ROOM SIDE,
COORDINATE EXACT LOCATION WITH ARCHITECTURAL NEW FLOOR PLAN AND MECHANICAL
PLANS.
EXISTING FULLY FINISHED SPACE THAT ALL WALLS, CEILINGS, FINISHES, FLOORING,
CASEWORK, PLUMBING FIXTURES, ELECTRICAL DEVICES, ETC. ARE TO BE REMOVED.
EXISTING COLUMNS ARE TO REMAIN. REFER TO MECHANICAL, ELECTRICAL, AND
PLUMBING DRAWINGS FOR FURTHER EXTENT OF DEMOLITION. PREPARE ALL SURFACES
FOR NEW CONSTRUCTION. SALVAGE DOORS, FIXTURES, ETC. AND TURN OVER TO COR
UNLESS DIRECTED OTHERWISE.
DEMOLITION GENERAL NOTES
1. ALL DEMOLITION WORK REQUIRED IS NOT
NECESSARILY LIMITED TO WHAT IS SHOWN ON THE
DEMOLITION PLANS. THE INTENT IS TO REMOVE ALL
MATERIALS AND ITEMS AS REQUIRED TO FACILITATE
NEW CONSTRUCTION.
2. ALL DEMOLITION WORK SHALL BE CONDUCTED
AFTER HOURS (5:30 PM PST - 6:00 AM PST)
3. REFER TO HAUL ROUTE AND ICRA PLAN FOR FURTHER
INFORMATION.
4. CONTRACTORS TO BE ESCORTED TO AND FROM
LOADING DOCK AND AREA OF CONSTRUCTION,
COORDINATE w/ COR. CONSTRUCTION ACCESS IN
AND OUT OF THE SPACE WILL BE FROM ID342 TO
C1-89, COORDINATE w/ COR.
5. CONTRACTORS ARE TO VERIFY FIELD CONDITIONS,
IF CONDITIONS DO NOT REFLECT WHAT IS NOTED IN
THE CONTRACT DOCUMENTS, THE CONTRACTOR IS
TO NOTIFY THE ARCHITECT.
6. THIS PLAN IS TO BE USED IN CONJUNCTION WITH THE
ENTIRE SET OF CONSTRUCTION DOCUMENTS. DO
NOT REMOVE ANY ITEMS WITHOUT VERIFYING AND
COORDINATING WITH ALL GENERAL TRADES AS TO
HOW THEY RELATE TO THE OVERALL PROJECT.
7. CONTRACTOR IS RESPONSIBLE FOR PROVIDING
DUMPSTERS. LOCATION OF DUMPSTERS TO BE
DETERMINED BY OWNER WITH CONTRACTORS INPUT.
8. CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL
DEMOLISHED MATERIALS. DO NOT ALLOW
MATERIALS AND DEBRIS GENERATED BY DEMOLITION
ACTIVITIES TO ACCUMULATE ON THE JOBSITE.
REMOVE DAILY AND DISPOSE OF IN A LEGAL
MANNER. NO ONSITE SALE OR BURNING OR
REMOVED ITEMS IS PERMITTED.
9. THE CONTRACTOR MUST TAKE ALL NECESSARY
PRECAUTIONS TO ENSURE THE SAFETY OF THE PUBLIC
AND/OR WORKERS ON THE SITE TO PREVENT
ACCIDENTS OR INJURY TO ANY PERSON ON, ABOUT
OR ADJACENT TO THE PREMISES. THE CONTRACTOR
SHALL COMPLY WITH ALL LAWS, ORDINANCES,
CODES AND REGULATIONS PERTAINING TO SAFETY
AND THE PREVENTION OF ACCIDENTS.
10. THE CONTRACTOR MUST MAINTAIN ADEQUATE
SUPPORT, INSULATION, WATERPROOFING,
EMERGENCY LIGHTING, SECURITY, ALARMS, ETC.
FOR ALL OR PART OF ITEMS WHICH ARE TO REMAIN.
11. THE OWNER RESERVES THE RIGHTS TO ANY
REMOVED MATERIALS OR ITEMS. CONTRACTOR TO
COORDINATE WITH OWNER.
12. DO NOT CUT AND/OR PATCH STRUCTURAL
ELEMENTS IN A MANNER THAT COULD CHANGE
THEIR LOAD-CARRYING CAPACITY OR LOAD-
DEFLECTION RATIO.
13. PATCH/REPAIR OR REPLACE ALL AREAS
DAMAGED BY DEMOLITION, REWORK AS
REQUIRED, PREPARE FOR NEW CONSTRUCTION AS
REQUIRED. BLOCK PATCHING SHALL BE TOOTHED-
IN TO MATCH EXISTING COURSING PATTERN.
14. WHERE WALLS & CEILINGS ARE TO BE REMOVED,
ALL ITEMS THAT FALL WITH THE WALLS &/OR
CEILINGS ARE TO BE REMOVED OR REROUTED.
REFER TO MECHANICAL, ELECTRICAL, AND
PLUMBING PLANS FOR ADDITIONAL DEMOLITION
NOT SHOWN ON THIS SHEET.
15. CONSTRUCTION AREAS TO BE COMPLETELY
SEPARATED FROM OCCUPIED AREAS WITH A ONE-
HOUR FIRE RATED TEMPORARY CONSTRUCTION
BARRIER ASSEMBLY, AND WITH SUITABLE DUST
BARRIER. TEMPORARILY SEAL OFF ALL RETURN &
SUPPLY AIR DIFFUSERS IN CONSTRUCTION AREA.
PROVIDE RECIRCULATING HEPA FILTER IN
CONSTRUCTION AREA. ALL DEMOLISHED
MATERIAL IS TO BE REMOVED FROM SITE IN A
COVERED CONTAINER. NEGATIVE AIR PRESSURE
TO BE MAINTAINED AND MONITORED WITHIN
CONSTRUCTION ZONE DURING ENTIRE
CONSTRUCTION DURATION. ROOM PRESSURE
MONITOR TO BE INSTALLED ON TEMPORARY
CONSTRUCTION BARRIER AND VALUES RECORDED.
EXISTING EXHAUST FANS TO BE RUN AS NEEDED TO
MAINTAIN THE NEGATIVE PRESSURE WITHIN THE
CONSTRUCTION ZONE.
16. IF HAZARDOUS MATERIALS ARE ENCOUNTERED
DURING DEMOLITION, CONTRACTOR SHALL
CONTACT COR FOR ABATEMENT.
17. REMOVE, REPLACE, PATCH, AND REPAIR
MATERIALS AND SURFACES CUT OR DAMAGED
DURING DEMOLITION, BY METHODS AND WITH
MATERIALS SO AS NOT TO VOID EXISTING
WARRANTIES.
18. CLEAN AREAS AND SPACES WHERE CUTTING AND
PATCHING ARE PERFORMED.
19. INTERIOR WALLS TO BE REMOVED, SHALL BE
REMOVED THE ENTIRE HEIGHT OF THE WALL UNLESS
REQUIRED OTHERWISE BY NEW OPENINGS IN
EXISTING WALLS TO REMAIN.
20. CONTRACTOR SHALL PATCH, REPAIR, AND INFILL
ALL APPLIED FIREPROOFING MATERIAL (PLANS
SHOW COLUMNS ONLY BUT THERE COULD BE
OTHER LOCATIONS SUCH AS
BEAMS/GIRDERS/DECKING THAT COULD NEED
PATCHING) IN AREAS LEFT UNPROTECTED DUE TO
REMOVAL OF EXISTING ELEMENTS OR AREAS
DAMAGED DURING NEW WORK AND
DEMOLITION. MATCH EXISTING FIREPROOFING
MATERIAL TYPE AND THICKNESS TO MAINTAIN
REQUIRED LEVEL OR PROTECTION.
CRT
SHV
2 SHV
MRR
M A
X
" BENCH
CONTROL JOINT TYP. AT ALL
DOORS. TO BE LOCATED AT
EACH SIDE OF WALL AND
EACH SIDE OF DOOR
BENCH PROVIDED
BY OWNER
SD
PT
PASS
R O
U G
H O
P E N
IN
G
P E R
B O
R R
O W
E D
L
IG
H T
S C
H E D
U L E
VARIES
REFER TO WALL TYPES FOR WALL DIMENSIONS
CLEAR ANODIZED ALUMINUM FRAMED
BORROWED LIGHT AND GLAZING
RESINOUS SPECIALITY GLAZED COATING
PER THE INTERIOR FINISH PLAN
RESINOUS SPECIALITY GLAZED
COATING PER THE INTERIOR FINISH
PLAN; CONTINUE ON ALL EXPOSED
SIDES (JAMB AND HEAD) UP TO THE
ALUMINUM FRAME.
SOLID SURFACE SILL (REFER
TO INTERIOR FINISH KEY) W/
TURNED DOWN EDGE SILL ON
PLYWOOD SUBFRAME
SEAM TO RECEIVE CONTINUOUS SEALANT
CONTINUOUS BACKER ROD
AND SEALANT (COMPATIBLE
W/ GLAZED COATING)
METAL STUD HEADER
REFER TO BORROWED
LIGHT SCHEDULE FOR
SILL HEIGHT AFF
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
A101
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 MH MH
DEMO PLAN, FLOOR PLAN NLV UPGRADE
INPATIENT PHARMACY
4 24
NORTH
SCALE: 1/4" = 1'-0"
FLOOR PLAN
NORTH
SCALE: 1/4" = 1'-0"
DEMOLITION PLAN
SCALE: 1/4" = 1'-0"A101
ANTE ID352B - EAST03
SCALE: 1/4" = 1'-0"A101
DONNING/DOFFING 1D352A - EAST02
SCALE: 1/4" = 1'-0"A101
DONNING/DOFFING 1D352A - SOUTH01
SCALE: 3/4" = 1'-0"A101
TYPICAL BORROWED LIGHT DETAIL04
S
FA
S
FA
S
FA
183 SF
1D352D
HAZARDOUS
COMPOUNDING
BUFFER ROOM
113 SF
1D352B
ANTE
72 SF
1D352A
DONNING/DOFFING
168 SF
1D352C
NON-HAZARDOUS
COMPOUNDING
BUFFER ROOM
10' - 0"
10' - 0"
10' - 0"
10' - 0"
VERIFY
VERIFY
VERIFY
VERIFY
A102
TYP
A102
SIM
A102
SIM
CONTRACTOR TO REPAIR AND
REPLACE ALL DAMAGED
CEILING TILES/GRID AT THE
DURATION OF THE PROJECT
AND WHEN THE TEMPORARY
WALL PARTITION IS REMOVED
TEMPORARY WALL PARTITION
REFLECTED CEILING PLAN KEY NOTES
JUNCTURES OF CEILINGS AND WALLS ARE TO BE CAULKED.
PROVIDE A NON-SAG, POLYURETHANE SEALANT COMPATIBLE WITH
RESINOUS WALL SYSTEM.
22"x30" ACCESS PANEL TO BE LOCATED IN FIELD w/ COR
AND ENGINEER INPUT.
REFLECTED CEILING PLAN LEGEND
AREAS OF EXISTING SUSPENDED ACOUSTIC TILE
TO INCLUDE NEW GRID AND PADS AND
REWORKED DUE TO CONSTRUCTION PARTITION.
AREAS TO BE FINISHED GYP BOARD W/
RESINOUS SPECIALITY GLAZED COATING
SYSTEMS. REFER TO FINISH PLAN, ON 3/4" COLD
ROLLED FURRING CHANNELS (16" o.c.) ON 1-1/2"
COLD ROLLED MAIN RUNNER CHANNELS
(48"o.c.) SUSPENDED GRID SYSTEM.
LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS
MECHANICAL DIFFUSER - SEE
MECHANICAL DRAWINGS
CEILING HEIGHT ABOVE FINISHED FLOOR8'-0"
GENERAL NOTES - CEILING PLAN
1. CEILINGS IN ROOMS TO BE CENTERED.
2. COORDINATE ALL CEILING EQUIPMENT AND CEILING
CONSTRUCTION WITH HEPA TESTING PORTIONS (REFER TO
MECHANICAL DRAWINGS) NOT SHOWN ON THIS PLAN.
3. ELECTRICAL AND MECHANICAL FIXTURES AND DUCTWORK ARE
SHOWN FOR REFERENCE ONLY. REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS FOR COMPLETE INFORMATION.
4. CONTRACTOR IS RESPONSIBLE FOR CETA CERTIFICATION PRIOR
TO VA ACCEPTANCE. REFER TO MECHANICAL.
5. REFER TO FINISH PLAN FOR CEILING FINISHES.
CEILING HEIGHT ABOVE FINISHED FLOOR -
MATCH EXISTING; FIELD VERIFYVERIFY
SECURITY DEVICE - SEE ELECTRICAL DRAWINGS
FIRE ALARM SPEAKER - SEE ELECTRICAL
DRAWINGSFA
S
EXISTING BREAK OUT
EXISTING STAFF TOILET
EXISTING LOCKERS
168 SF
1D352C
NON-HAZARDOUS
COMPOUNDING
BUFFER ROOM
72 SF
1D352A
DONNING/DOFFING
183 SF
1D352D
HAZARDOUS
COMPOUNDING
BUFFER ROOM
113 SF
1D352B
ANTE
EXISTING
PICKER
SINK W/ EYE WASH
REFER TO PLUMBING
D
B
1D352C
1D352D
C
LE
A
R
D
A
REF
BENCH
CRT
HOOD,
BIOLOGICAL
HOOD,
BIOLOGICAL
TBL
TBL
CACI
CACI CRT
PHARM
TBL
CLEAR
1' - 6"
C
LE
A R
C
LE
A R
5" CLEAR
PASS
PASS
6" CLEAR
CRT
MRR
SHV
SHV
SHV
SHV
SD
PT
SHV
TBL
SHV
PHARM
PROCEDURE CHARTS
LABEL
PRINTER
EXISTING SOLUTIONS
SHELVING TO REMAIN
REFER TO WALL TYPES FOR EXACT CONSTRUCTION
5/8" GYP. BOARD (GLUED AND SCREWED) ON
3/4" COLD ROLLED FURRING CHANNELS @ 16"
o.c. ON 1-1/2" COLD ROLLED MAIN RUNNER
CHANNELS @ 48" o.c. SUSPENDED GRID
SYSTEM. REFER TO RCP FOR HEIGHT.
REFER TO FINISH PLAN/SPECIFICATIONS FOR FINAL FINISH
REFER TO REFLECTED CEILING PLAN KEY NOTES
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
A102
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 Checker Author
EQUIPMENT PLAN,
REFLECTED CEILING PLAN
NLV UPGRADE
INPATIENT PHARMACY
5 24
NORTH
SCALE: 1/4" = 1'-0"
REFLECTED CEILING PLAN
NORTH
SCALE: 1/4" = 1'-0"
FLOOR EQUIPMENT PLAN
EQUIPMENT SCHEDULE
ABBREVIATION EQUIPMENT DESCRIPTION BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL RESPONSIBILITY CODE
MRR WELDED FRAME MIRROR 18"W X 36"H BOBRICK B-290 1836 CFCI
PASS WALL MOUNTED HEPA FILTERED PASS THRU CLEAN AIR PRODUCTS CAP18WHF-SST-12WX12HX12D CFCI
PT PAPER TOWEL DISPENSER, STAINLESS STEEL W/ KNOB LATCH BOBRICK CLASSIC SERIES VERTICAL FOLDED PAPER TOWEL
DISPENSER
CFCI
SD SOAP DISPENSER, STAINLESS STEEL BATTERY OPERATED ASI INDUSTRIES ROVEL AUTOMATIC SOAP DISPENSER 20364 CFCI
SHV 1 STAINLESS STEEL SHELF W/ LIP 36"W X 12"D - WALL MOUNTED GLOBAL INDUSTRIAL ITEM NO. WG49327 CFCI
CACI CAC GERMFREE LFGI-3USP GFCI
HOOD, BIOLOGICAL LAMINAR FLOW HOOD, BIOLOGICAL, 6FT GERMFREE BVBI-4SSRX GFCI
LABEL PRINTER PRINTER 20'' X 24'' INFORMATION AND TECHNOLOGY
SERVICES
VERIFY W/ COR GFCI
PHARM 1 PHARMACIST TABLE 16'' X 48'' VERIFY W/ COR VERIFY W/ COR GFCI
REF REFRIGERATOR, SCIENTIFIC, 1 DOOR BD MEDICAL 305091 GFCI
SHV 2 STAINLESS STEEL SHELVING 42"W X 14"D X 63"H - FREESTANDING GLOBAL INDUSTRIAL ITEM NO. WGB2346011 GFCI
SHV 3 STAINLESS STEEL SHELVING 48"W X 21"D X 63"H - FREESTANDING GLOBAL INDUSTRIAL ITEM NO. T9AB2346216 GFCI
SHV 4 STAINLESS STEEL SHELVING 18''W X 18"D x 63"H - W/ CASTERS GLOBAL INDUSTRIAL ITEM NO. CUSTOM GFCI
SHV 5 STAINLESS STEEL SHELVING 30"W' X14"D X 54"H - FREESTANDING GLOBAL INDUSTRIAL ITEM NO. WGB2346139 GFCI
SHV 6 STAINLESS STEEL SHELVING 60"W X 24"D X 63"H - FREESTANDING GLOBAL INDUSTRIAL ITEM NO. T97189476 GFCI
TBL 4 TABLE W/ LOW SHELF AND/ OR WALL SHELF ABOVE, 10'' X 48'' GFCI
BENCH STAINLESS STEEL GOWNING BENCH 30"W X 16"D X 18"H - FREESTANDING VERIFY W/ COR VERIFY W/ COR GFGI
CRT 1 MICROFIBER PLATFORM CART GLOBAL INDUSTRIAL 26XH-MST2 GFGI
CRT 2 STAINLESS UTILITY CART. INCLUDES THREE 16" X 24" SHELVES WITH 11" CLEARANCE BETWEEN
SHELVES, FULL WIDTH HANDLE AND 4" SWIVEL CASTERS. WEIGHT CAPACITY: 200 LBS.
LAKESIDE MFG. INC. VERIFY W/ COR GFGI
PHARM 2 ALLFLEX 3 HT. ADJUSTABLE BASE W/ 3 LEGS AND WORK SURFACE ESI CONTROL #: 21-178965 - NOTE REVISED WORK SURFACE
DIMENSION
GFGI
TBL 1 TABLE 18'' X 18'' VERIFY W/ COR VERIFY W/ COR GFGI
TBL 2 TABLE 18'' X 48'' VERIFY W/ COR VERIFY W/ COR GFGI
TBL 3 TABLE 18'' X 30'' VERIFY W/ COR VERIFY W/ COR GFGI
NOTES:
CONTRACTOR TO COORDINATE EXACT PLACEMENT IN FIELD WITH COR. CONTRACTOR TO COORDINATE EXACT PLACEMENT WITH ELECTRICAL AND HVAC HEIGHTS IN FIELD.
CONTRACTOR TO PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT.
GOVERNMENT FURNISHED EQUIPMENT ITEMS ARE SHOWN WITH A DASHED LINE - REFER TO EQUIPMENT PLAN.
ABBREVIATIONS:
CFCI = CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
GFCI = GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GFGI = GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
SCALE: 3/4" = 1'-0"A102
TYPICAL CEILING TO WALL DETAIL1
SCHD.
SEE
S E E S
C H
E D
U
LE
SIZE PER DOOR MFR. REQ.
S E E S
C H
E D
U
LE
A 1
DOOR TYPES
SCALE: 1/4" = 1'-0"
DOOR FRAME TYPES
SCALE: 1/4" = 1'-0"
2' - 4"
FLOOR
LINE
4" 4"
BORROWED LIGHT TYPES
SCALE: 1/4" = 1'-0"
FLOOR
LINE
SEE SCHD.
T
T
T
SIZE PER DOOR MFR. REQ.
S E E S
C H
E D
U
LE
FLOOR
LINE
SEE SCHD.
T
T
DOOR
OPENING
DOOR
OPENING
T
2' - 0"
T
3' - 4"
AA CC DD
2' - 0"
T
BB
GLAZING
LG#1
GLAZING
LG#1
GLAZING LG#1
(TYP.)
CLEAR ANODIZED
ALUMINUM FRAME
(TYP.)
SURFACE APPLIED SLIDING DOOR HEAD
SEALANT CONTINUOUS @
PERIMETER (ALL SIDES)
DOUBLE 2x8 WOOD AND
PLYWOOD HEADER
SURFACE APPLIED JAMB
AUTOMATIC SLIDING DOOR
AUTOMATIC SLIDING DOOR
SUPPORT STUD TO
ALIGN W/ JAMB
SEALANT CONTINUOUS @
PERIMETER (BOTH SIDES)
ADJACENT WALL
(WHERE OCCURS)
SURFACE MOUNTED JAMB
SURFACE APPLIED JAMB
SURFACE MOUNTED JAMB
INTERSECTION OF RATED WALLS
LOWER PRIORITY WALL
HIGHER PRIORITY WALL
HIGHER PRIORITY WALL
LOWER PRIORITY WALL
HIGHER PRIORITY
WALL
LOWER PRIORITY WALL
TAPE AND SEAL BEHIND
INTERSECTING
PARTITION (TYP.)
LOWER
PRIORITY WALL
HIGHER
PRIORITY WALL
GYP. BD. ON METAL
STUDS
LOWER PRIORITY WALL
HIGHER PRIORITY WALL
HIGHER PRIORITY WALLS
TO RUN CONTINUOUS PAST
A LOWER PRIORITY WALL
LOWER
PRIORITY WALL
ABUTMENT OF DISSIMILAR WALLS AND EXISTING WALLS
NOTE: REFER TO FLOOR PLANS FOR
LOCATION OF CONSTRUCTION
PARTITIONS
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
A600
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 MH MH
DOOR AND FRAME
SCHEDULE
NLV UPGRADE
INPATIENT PHARMACY
6 24
DOOR AND FRAME SCHEDULE
DOOR NUMBER ROOM NAME SIZE
DOOR FRAME FIRE RATING
(MIN.) HARDWARE SET REMARKSTYPE MATERIAL TYPE MATERIAL
1D352A DONNING/DOFFING 3'-0" x 7'-0" A ALUM. / GLASS 1 ALUM. - 01 GLASS SLIDER W/ INTERLOCKM, CARD
READER
1D352B ANTE 3'-0" x 7'-0" A ALUM. / GLASS 2 ALUM./GLASS - 02 GLASS SLIDER W/ INTERLOCK
1D352C NON-HAZARDOUS COMPOUNDING BUFFER ROOM 3'-0" x 7'-0" A ALUM. / GLASS 1 ALUM. - 02 GLASS SLIDER W/ INTERLOCK
1D352D HAZARDOUS COMPOUNDING BUFFER ROOM 3'-0" x 7'-0" A ALUM. / GLASS 1 ALUM. - 02 GLASS SLIDER W/ INTERLOCK
SCALE: 1 1/2" = 1'-0"A600
DOOR HEAD DETAIL01
SCALE: 1 1/2" = 1'-0"A600
DOOR JAMB DETAIL02
SCALE: 1 1/2" = 1'-0"
EXISTING AND NEW INTERSECTION AND ABUTMENT WALL
DETAIL
EXISTING STAFF TOILET
P A
TH
R
U
NON-HAZARDOUS
COMPOUNDING
BUFFER ROOM
1D352C
RES-1
RES-1
RES-W1
RES-C1
DONNING/DOFFING
1D352A
RES-1/RES-2
RES-1/RES-2
RES-W1
12, 13
RES-C1
HAZARDOUS
COMPOUNDING
BUFFER ROOM
1D352D
RES-1
RES-1
RES-W1
RES-C1
ANTE
1D352B
RES-1
RES-1
RES-W1
RES-C1
7' - 10" +/-
CG-1
CG-1
P -1
P-1
P-1
P -1
P -1
A101
2' - 0"
EXISTING PICKER
EXISTING PYXIS
CONTRACTOR TO REPAIR AND
REPLACE ANY DAMAGED
FLOORING OR CEILING
TILES/GRID AT THE DURATION
OF THE PROJECT AND WHEN
THE TEMPORARY WALL
PARTITION IS REMOVED
A701
A701
CG-2
CG-2
CG-2
CG-2
CG-2
CG-2
FINISH PLAN REMARKS
1. THE MANUFACTURER PRODUCT IDENTIFIED MEETS THE
SALIENT CHARACTERISTICS OF THIS SPECIFICATION. SUCH
INFORMATION IS ONLY TO SHOW AN EXAMPLE OF
PRODUCTS WHICH MEET THE SPECIFICATIONS AND DO NOT,
IN ANY WAY, LIMIT THE OFFEROR FROM PROVIDING
PRODUCTS FROM OTHER MANUFACTURERS WHICH MEET
THE SALIENT CHARACTERISTICS AS IDENTIFIED IN THE
SPECIFICATION.
2. REFERENCE FLOOR PLANS AND INTERIOR ELEVATIONS FOR
INTERIOR SPECIALTY ELEVATIONS.
3. REFERENCE FINISH PLAN FOR FLOOR PATTERNS, ACCENT
PAINT LOCATIONS, AND ROOM FINISH TAGS FOR TYPE AND
PLACEMENT OF INTERIOR FINISHES.
4. REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL
CEILING FINISHES.
5. PATTERN NAME, COLOR, AND NUMBER FOR EACH
MATERIAL ARE GIVEN WHEREVER POSSIBLE ON THE FINISH
PLAN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO BRING ANY DISCREPANCIES TO THE ATTENTION OF THE
ARCHITECT/INTERIOR DESIGNER SO THAT THE CORRECT
MATERIAL IS INSTALLED.
6. ALL FLOORING TRANSITIONS SHALL BE CENTERED UNDER THE
DOOR IN THE CLOSED POSITION.
7. REFER TO SHEET A701 FOR FLOOR TRANSITION AND WALL
BASE DETAILS.
8. THERE SHALL NOT BE PAINT CONDITIONS THAT OCCUR
CAUSING FINISH OR COLOR TO CHANGE ON AN OUTSIDE
CORNER UNLESS SPECIFICALLY NOTED OTHERWISE. IF THIS
CONDITION OCCURS, BRING THIS TO THE DESIGNER'S
ATTENTION IMMEDIATELY.
9. BULKHEADS/SOFFITS/FURDOWNS SHALL BE FINISHED WITH
SAME MATERIAL AND/OR COLOR ON ALL FACES AS
SPECIFIED U.N.O.
10. WIREWAYS, ACCESS PANELS, GRILLES, ELECTRICAL PANELS,
MECHANICAL DEVICES, ETC. SHALL BE FINISHED TO MATCH
THE ADJACENT SURFACE.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADA-COMPLIANT TRANSITIONS AT ALL CHANGES IN FLOOR
FINISH U.N.O
12. PROVIDE SELF LEVELING UNDERLAYMENT WHERE
SUBSURFACE FLATNESS AND LEVELNESS RECOMMENDED BY
THE MANUFACTURERCAN NOT BE ACHEIVED BY THE
RESINOUS FLOOR SYSTEM ALONE. VERIFY TYPE WITH
RESINOUS FLOOR SYSTEM MANUFACTURER.
13. PROVIDE PLASTIC T-STRIP, TO BE SEALED AT RESINOUS
FLOOR COLOR TRANSITION.
14. VERIFY ALL EXISTING MATERIAL COLOR SELECTIONS W/ VA
COR.
FINISH PLAN LEGEND
OFFICE
XXXX
CPT-1
RB-1
PT-1
ACP-1
ROOM NAME
ROOM NUMBER
FLOOR FINISH
BASE FINISH
TYP. WALL FINISH
CEILING FINISH
WALL FINISH
EXTENTS
P-#
1NOTES
RES-1 RES-2
STEEL TROWELED, MULTI
COMPONENT EPOXY MORTAR BASE
RESINOUS FLOOR SYSTEM - REFER TO
SPECIFICATION 09 67 23.30
EXISTING CONCRETE SLAB
EPOXY WALL SYSTEM OVER RAMPED PATCHING
MORTAR AND SEALED W. RESINOUS SPECIALTY GLAZED
COATING SYSTEM - REFER TO SPECIFICATION 09 96 59.
EPOXY PATCHING MORTAR -
FEATHERED EDGE TO ZERO
R
SELF LEVELING UNDERLAYMENT WHERE
REQUIRED - VERIFY TYPE WITH RESINOUS
FLOOR SYSTEM MANUFACTURER
RESINOUS FLOOR SYSTEM, REFER TO
INTERIOR FINISH KEY AND SPECIFICATION
09 67 23.30
DIVIDER STRIP, SEE
SPECIFICATION 09 67 23.30 FOR TYPE
CONCRETE SLAB
FLEXIBLE EPOXY
CRACK ISOLATION
MEMBRANE
MOISTURE-VAPOR
BARRIER
EDGE STRIP, REFER TO
INTERIOR FINISH KEY
VINYL COMPOSITION TILE
FLOORING, REFER TO INTERIOR
FINISH KEY
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: LOCATION
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
7GAE PROJECT NO.: 221160 FILE NAME: TITL-BLK-3042-VA.DWG
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans
STAMP
35% SD 12.22.21
65% DD 02.01.22
#1
95% CD 03.11.22
259 E Michigan Ave
Kalamazoo, MI 49007 www.steelheadengineeringco.com
600 E Michigan Ave, Suite B
Kalamazoo, MI 49007 www.7GenAE.com
100% CD 04.20.22
DAV ENERGY SOLUTIONS
2207 GARNET AVE, SUITE 1
SAN DIEGO, CA 92109
619-770-8552
WWW.DAVENERGY.COM
CONSULTANTS
100% BID
04.20.22
05.16.22
A701
593-18-104
6900 N PECOS RD
NORTH LAS VEGAS, NEVADA 89086
05/16/2022 AA SS
FIRST FLOOR FINISH PLAN NLV UPGRADE
INPATIENT PHARMACY
7 24
INTERIOR FINISH KEY
TAG MATERIAL MANUFACTURER STYLE COLOR REMARKS
08 51 13 ALUMINUM WINDOWS
S-1 SOLID SURFACE CORIAN - GLACIER ICE REFER TO 04/A101
09 51 00 ACOUSTICAL CEILINGS
AT-1 ACOUSTICAL CEILING (TILE) FIELD VERIFY EXISTING FIELD VERIFY EXISTNG FIELD VERIFY EXISTING COORDINATE ATTIC STOCK W/ VA COR
09 65 19 RESILIENT FLOOR TILE
ES-1 EDGE STRIP TARKET REFER TO 1/A701 FIELD VERIFY EXISTING
VCT-1 VERIFY WITH VA COR FIELD VERIFY EXISTING FIELD VERIFY EXISTNG FIELD VERIFY EXISTING COORDINATE ATTIC STOCK W/ VA COR
09 67 23.30 RESINOUS HIGH PERFORMANCE DECORATIVE MORTAR FLOORING
RES-1 RESINOUS FLOOR SYSTEM STONHARD STONBLEND GSI SHALE
RES-2 RESINOUS FLOOR SYSTEM STONHARD STONBLEND GSI WILLOW DONNING/DOFFING ID352 ONLY
09 91 00 PAINTING
P-1 PAINT FIELD VERIFY EXISTING FIELD VERIFY EXISTNG FIELD VERIFY EXISTING TO INCLUDE 1 PRIME COAT, 2 FINISH COATS
09 96 59 RESINOUS SPECIALTY GLAZED COATING SYSTEMS
RES-C1 RESINOUS CEILING SYSTEM STONHARD STONGLAZE VSR WHITE
RES-W1 RESINOUS WALL SYSTEM STONHARD STONGLAZE VSR ASH GRAY
10 26 00 WALL AND DOOR PROTECTION
CG-1 CORNER GUARD CONSTRUCTION SPECIALTIES SM-20 FIELD VERIFY EXISTING
CG-2 CORNER GUARD CONSTRUCTION SPECIALTIES SM-20 #265 FOG
NORTH
SCALE: 1/4" = 1'-0"
FIRST FLOOR FINISH PLAN
SCALE: 12" = 1'-0"A701
RESINOUS FLOOR SYSTEM INTEGRAL COVE BASE02
SCALE: 12" = 1'-0"A701
VCT TO RES01
Scale: NTS
Department of Veteran Affairs
X X X X DEMOLITION
EQUIPMENT
RELOCATE
REVISION
TEXT
BACKGROUND
SCOPE
COLUMN LINE
PLUMBING LAYERS PLUMBING SYMBOLS
B#-FC-# EQUIPMENT TAG (BUILDING NO -
EQUIP NAME - EQUIP NUMBER)
REVISION DELTAS
SHEET NOTES5
RELOCATE
GENERAL NOTES
1. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER. CARE SHALL
BE EXERCISED TO MINIMIZE ALL INCONVENIENCE OR DISTURBANCE TO OTHER AREAS OF
THE BUILDING WHICH ARE TO REMAIN IN OPERATION. ISOLATE WORK AREAS BY MEANS
OF TEMPORARY PARTITIONS AND/OR TARPS TO KEEP DUST AND DIRT WITHIN THE
CONSTRUCTION AREA.
2. NO PIPING, EQUIPMENT, ETC. SHALL BE REMOVED, DISCONNECTED OR SHUT DOWN
WITHOUT PRIOR REVIEW WITH THE COR AND/OR ENGINEER TO CONFIRM THAT AREAS TO
REMAIN IN OPERATION WILL NOT BE AFFECTED. IF AREAS NOT WITHIN THE SCOPE OF
WORK ARE AFFECTED BY ANY SHUTDOWN, REMOVAL OR DISCONNECTION, SUFFICIENT
ADVANCE NOTICE SHALL BE GIVEN TO THE COR AND/OR OWNER INDICATING WHICH
AREAS WILL BE AFFECTED, WHEN THE PROPOSED SHUTDOWN WILL OCCUR, AND FOR
HOW LONG A PERIOD OF TIME.
3. ALL ITEMS INDICATED AS BEING DEMOLISHED OR REMOVED SHALL BE DISPOSED OF
OFF-SITE.
4. THE PLUMBING CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS PRIOR TO PROCEEDING WITH ALL WORK. WHERE DISCREPANCIES OCCUR
BETWEEN THESE DOCUMENTS AND EXISTING CONDITIONS, THE DISCREPANCY SHALL BE
REPORTED TO THE COR AND/OR ENGINEER FOR RESOLUTION.
5. ALL SHUT DOWNS OF EXISTING SYSTEMS SHALL BE SCHEDULED AND APPROVED BY THE
COR PRIOR TO COMMENCEMENT OF SAID WORK.
6. CLEAN THE JOB SITE DAILY AND REMOVE FROM THE PREMISES ALL DIRT AND DEBRIS
CAUSED BY THE PERFORMANCE OF THE WORK INCLUDED IN THIS CONTRACT.
7. USE OF THE OWNER'S ELEVATORS AND BUILDING CORRIDORS FOR THE HANDLING OF
NEW AND/OR REMOVED EQUIPMENT AND MATERIALS SHALL BE AT THE DIRECTION OF THE
COR AND SHALL BE COORDINATED WITH HIS OPERATIONS.
8. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFEKEEPING OF HIS
OWN PROPERTY ON THE JOB SITE. OWNER ASSUMES NO RESPONSIBILITY FOR
PROTECTION OF PROPERTIES AGAINST FIRE, THEFT AND ENVIRONMENTAL CONDITIONS.
9. EXCEPT WHERE INDICATED AS BEING RELOCATED, EXISTING MATERIALS THAT ARE
REMOVED SHALL NOT BE REUSED IN NEW SYSTEMS.
10. PROVIDE ALL NECESSARY TEMPORARY OR PERMANENT CAPS OR PLUGS FOR PIPING. DO
NOT LEAVE PIPING OPEN ENDED.
11. WHERE USED, THE TERM "PROVIDE" SHALL MEAN "FURNISH AND INSTALL".
12. THE PLUMBING CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES
PRIOR TO FABRICATION, PURCHASE AND/OR INSTALLATION OF ANY WORK.
13. THE BALANCING CONTRACTOR SHALL TAKE FLOW (GPM) AND PRESSURE READINGS
PRIOR TO THE START OF WORK ON ALL DUCTWORK THAT SERVES AREAS NOT PART OF
THIS PROJECT BUT WHERE FLOW TO THOSE AREAS IS AFFECTED BY THIS PROJECT'S
WORK. AFTER MODIFICATIONS TO SYSTEMS COVERED UNDER THIS PROJECT ARE
COMPLETED, THE BALANCING CONTRACTOR SHALL BALANCE THE NON-AFFECTED AREAS
TO THEIR ORIGINAL FLOW AND PRESSURE OR NEW FLOW AND PRESSURE IF NOTED.
14. IF PLUMBING CONTRACTOR ENCOUNTERS WHAT APPEARS TO BE A HAZARDOUS OR
QUESTIONABLE MATERIAL, HE SHALL DISCONTINUE WORK IMMEDIATELY AND CONTACT
THE COR AND/OR OWNER'S REPRESENTATIVE.
15. USE OF OWNER'S UTILITIES (I.E. ELECTRICITY, WATER, HVAC, ETC.) FOR WORK INDICATED
ON THESE DOCUMENTS SHALL BE APPROVED BY THE COR PRIOR TO COMMENCEMENT OF
SAID WORK.
16. THE PLUMBING CONTRACTOR SHALL CONFORM TO OWNER'S SAFETY AND SECURITY
GUIDELINES IN THE PERFORMANCE OF ALL WORK INCLUDED IN THIS CONTRACT.
17. ALL BRANCH PIPING SHALL BE FURNISHED WITH SHUT OFF VALVES AND SHALL BE
LOCATED IN ACCESSIBLE LOCATION BY OFFSETTING BRANCH PIPING WITH VALVES DOWN
NEAR CEILING. PROVIDE ACCESS PANEL FOR ALL VALVES, CLEANOUTS, EQUIPMENT, ETC.
IN NON ACCESSIBLE CEILING AREAS.
18. ALL SUSPENDED PIPING, DUCTWORK, CONDUIT AND CABLE TRAYS SHALL BE PROVIDED
WITH, SEISMIC SWAY BRACES IN ACCORDANCE WITH THE MASON INDUSTRIES SEISMIC
RESTRAINT GUIDELINES FOR SUSPENDED PIPING, DUCTWORK AND ELECTRICAL SYSTEMS
AND THE APPLICABLE CODES. INSTALLED SYSTEM SHALL MATCH EXISTING, RIGID OR
CABLE TYPE.
19. GENERAL LOCATION OF FIXTURES ARE INDICATED ON PLUMBING PLANS. REFERENCE
ARCHITECTURAL PLANS AND INTERIOR ELEVATIONS FOR SPECIFIC LOCATIONS.
20. RESTORE EXISTING FIRE PROOFING TO BEAMS, DECKS AND ALL OTHER BUILDING
ELEMENTS WHICH ARE DISTURBED OR MODIFIED AS A RESULT OF NEW WORK BEING
INSTALLED. RESTORED CONDITIONS SHALL MATCH EXISTING PRIOR TO NEW WORK BEING
PERFORMED.
21. ALL EXISTING PIPE INSULATION REMOVED, AS REQUIRED TO PERFORM SCOPE OF WORK,
SHALL BE REPAIRED USING LIKE MATERIAL TO THAT WHICH IS EXISTING.
22. PIPE ROUTINGS ARE DIAGRAMMATIC IN NATURE. PROVIDE OFFSETS, DROPS AND RISERS
AS NECESSARY TO AVOID EXISTING ELECTRICAL, HVAC, PLUMBING, FIRE PROTECTION,
ETC. SYSTEMS WHICH MAY INTERFERE WITH GENERAL ROUTING SHOWN ON DRAWINGS.
23. VERIFY EXISTING PLUMBING SYSTEM SIZES PRIOR TO FABRICATION OF NEW PLUMBING
SYSTEMS. ANY EXISTING PLUMBING SYSTEMS DIFFERING IN SIZE FROM THAT NOTED ON
DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE
AND ENGINEER.
24. NOT ALL SYMBOLS, ABBREVIATIONS AND EQUIPMENT ABBREVIATIONS INDICATED APPEAR
ON THESE CONTRACT DRAWINGS
25. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE
OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.
26. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS. COORDINATE LOCATION WITH
PLUMBING INSTALLATION AND DEMONSTRATE ACCESS TO EQUIPMENT SERVED.
27. ALL PRESSURES LISTED ARE GAGE PRESSURE, UNLESS OTHERWISE NOTED.
28. PRIOR TO CONSTRUCTION, PLUMBING CONTRACTOR TO DETERMINE EXACT INVERT
ELEVATION, SIZE, DEPTH, AND LOCATION OF UTILITIES WHERE CONNECTIONS ARE TO
OCCUR. NOTIFY COR AND ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS AND
FIELD CONDITIONS.
29. PLUMBING CONTRACTOR SHALL KEEP ONE SET OF CONTRACT DRAWINGS ASIDE AT THE
SITE TO MARK UP ALL DEVIATIONS FROM CONTRACT DRAWINGS AND ANY DATA THAT IS
PERTINENT FOR COMPLETION OF DOCUMENTS. AT COMPLETION OF PROJECT, TRANSFER
MARKS TO A SET OF REPRODUCIBLE DRAWINGS AND DELIVER THIS SET OF DRAWINGS TO
OWNER PRIOR TO FINAL ACCEPTANCE.
POINT OF CONNECTION BETWEEN NEW
AND EXISTING WORK
LIMIT OF DEMOLITION
POINT OF CONNECTION
CAP
PIPE UP
PIPING SYMBOLS
PIPE DOWN
TEE
FLOW DIRECTION
FLOOR DRAIN
FLOOR SINK
PUMP
REDUCER
ANGLED GLOBE
AUTOMATIC BALANCING CONTROL
BALANCING
BALL
BUTTERFLY
CHECK
CIRCUIT SETTER
CONTROL - FLOAT OPERATED
FLOW METER
GATE
GLOBE
M
MODULATING CONTROL
ABBREVIATIONS
TABLE OF CONTENTS
DWG # DWG TITLE
P-001 PLUMBING COVER SHEET
P-101 PLUMBING 1ST FLOOR PLAN
GENERAL DEMOLIION NOTES
1. SCHEDULE ALL SHUTDOWNS THAT AFFECT UTILITIES AND PORTIONS OF THE BUILDING
THAT MUST REMAIN IN OPERATION WITH THE COR.
2. DEMOLITION WORK AT ALL TIMES SHALL BE SUBJECT TO THE DIRECTION AND APPROVAL
OF THE COR AND CARRIED OUT IN SUCH A MANNER SO AS NOT TO INTERFERE WITH THE
NORMAL OPERATION OF THE BUILDING.
3. DISPOSE OF ALL REMOVED MATERIALS IN AN APPROVED MANNER.
4. ISOLATE, DRAIN, AND REFILL EXISTING SYSTEMS AS REQUIRED TO ACCOMMODATE
INSTALLATION OF EXISTING AND NEW SYSTEMS.
5. PROVIDE ALL NECESSARY TEMPORARY/PERMANENT CAPS OR PLUGS FOR PIPING. DO
NOT LEAVE PIPING OPEN ENDED.
6. ALL EXISTING PIPING SHALL BE FIELD VERIFIED FOR PROPER DEMOLITION. CONTRACTOR
SHALL NOTIFY ENGINEER IMMEDIATELY IF ANY DISCREPANCIES FROM CONTRACT
DOCUMENTS OCCUR THAT MAY EFFECT EXISTING OPERATIONS.
7. DEMOLITION OF PIPING INCLUDES ALL ASSOCIATED VALVES, ACCESSORIES, INSULATION,
HANGERS, AND SUPPORTS.
8. COORDINATE WITH COR ON REMOVAL AND PLACEMENT OF EQUIPMENT NOTED TO BE
TURNED OVER TO COR. FOR EQUIPMENT NOT DESIRED BY COR, CONTRACTOR SHALL
REMOVE OFF SITE IN AN APPROVED MANNER.
DETAIL NUMBER
DRAWING SYMBOLS
M-XXX
X
DRAWING NUMBER
SECTION LETTER
DRAWING NUMBERM-XXX
X
COLD WATER
HOT WATER
HOT WATER RETURN
SANITARY SEWER (WASTE)
VENT
EXISTING COLD WATER
EXISTING HOT WATER
EXISTING HOT WATER RETURN
EXISTING SANITARY SEWER
EXISTING VENT
MODULATING CONTROL BUTTERFLY
PLUG
PNEUMATIC CONTROL
PRESSURE REDUCING (PRV)
PRESSURE REGULATING
PRESSURE SAFETY
SHUTOFF
THREE-WAY MODULATING CONTROL
THREE-WAY TWO POSITION CONTROL
TWO POSITION CONTROL
WATER BALANCE DEVICE
WYE STRAINER
UNION
TEMPERATURE GAGE
PRESSURE GAGE
TEST PLUG
AUTOMATIC AIR VENT
MANUAL AIR VENTMV
AV
EQUIP. ABBREVIATIONS
AAHX AIR TO AIR HEAT EXCHANGER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
AF AFTER FILTER
AHU AIR-HANDLING UNIT
AS AIR SEPARATOR
B BOILER
BDR BASE BOARD RADIATOR
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT
EXCHANGER
BT BLOWOFF TANK
CC COOLING COIL
CCD COOLING COIL CONDENSATE
DRAIN
CFP CHEMICAL FEED PUMP
CH CHILLER
CHP CHILLED WATER PUMP
COMP COMPRESSOR UNIT
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .