S02 Fire Alarm System Servicing MVAHCS 36C26327Q0013.docx
DOCX document 248 KB Posted
- Solicitation number
- 36C26327Q0013
About this file
This is a Statement of Work for fire alarm system servicing at the Minneapolis VA Healthcare System (VAHCS). The contractor shall provide comprehensive maintenance, inspection, and repair services for the facility's fire alarm system, including all associated equipment, devices, and components. Services encompass routine preventive maintenance, emergency repairs, system testing and inspection to ensure compliance with applicable codes and standards, documentation and record-keeping of all service activities, and 24/7 emergency response capabilities. The contractor must maintain current certifications and licenses as required by state and local regulations, coordinate with facility management on scheduling, and ensure minimal disruption to healthcare operations. All work must be performed by qualified technicians with demonstrated expertise in fire alarm system servicing.
The solicitation (36C26327Q0013) is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The question deadline is September 14, 2024, at 5:00 PM Central Time, and the offer deadline is September 21, 2024, at 12:00 PM Central Time. Offerors are strongly encouraged to conduct a site visit at the Minneapolis VAHCS facility (details provided on pages 57-58 of the solicitation). All submission instructions, including forms and requirements, are detailed in the Addendum to Instructions to Offerors FAR 52.212-1. Interested vendors should reference the most current version of the solicitation on SAM.gov to ensure compliance with all requirements and avoid using outdated forms or information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06 Response to Vendor Questions MVAHCS 36C26327Q0013 0001.docx | DOCX document | |
| S02 Fire Alarm System Inventory and Testing Table.xlsx | XLSX spreadsheet | |
| S02 DOL WD 2015-4945 R33 08222026.txt | TXT text file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUBJECT*
MVAHCS Fire Alarm Maintenance Combined Synopsis/Solicitation Notice
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 55101 |
| SOLICITATION NUMBER* |
| 36C26327Q0013 |
| RESPONSE DATE/TIME/ZONE |
| 09-21-2026 12:00 CENTRAL TIME, CHICAGO, USA |
| ARCHIVE |
| 15 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
SET-ASIDE
| PRODUCT SERVICE CODE* |
| J063 |
| NAICS CODE* |
| 561621 |
| CONTRACTING OFFICE ADDRESS |
| DEPARTMENT OF VETERANS AFFAIRS |
NETWORK CONTRACTING OFFICE 23
316 ROBERT STREET N, SUITE 506
SAINT PAUL MN 55101
POINT OF CONTACT*
Contracting Officer Jeffrey Brown Jeffrey.Brown8@va.gov
PLACE OF PERFORMANCE
| ADDRESS |
| Minneapolis VA Health Care System |
1 Veterans Drive
Minneapolis Minnesota
| POSTAL CODE |
| 55417 |
| COUNTRY |
| USA |
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
Combined Synopsis/Solicitation Notice
| *= Required Field |
| Combined Synopsis/Solicitation Notice |
PAGE 1 OF
1. REQUISITION NO.
2. CONTRACT NO.
3. AWARD/EFFECTIVE DATE
4. ORDER NO.
5. SOLICITATION NUMBER
6. SOLICITATION ISSUE DATE
a. NAME
b. TELEPHONE NO. (No Collect Calls)
8. OFFER DUE DATE/LOCAL
TIME
9. ISSUED BY
CODE
10. THIS ACQUISITION IS
UNRESTRICTED OR
SET ASIDE:
% FOR:
SMALL BUSINESS
HUBZONE SMALL
BUSINESS
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
WOMEN-OWNED SMALL BUSINESS
(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
8(A)
NAICS:
SIZE STANDARD:
11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS
13a. THIS CONTRACT IS A
RATED ORDER UNDER
DPAS (15 CFR 700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ
IFB
RFP
15. DELIVER TO
CODE
16. ADMINISTERED BY
CODE
17a. CONTRACTOR/OFFEROR
CODE
FACILITY CODE
18a. PAYMENT WILL BE MADE BY
CODE
TELEPHONE NO.
UEI:
EFT:
PHONE:
FAX:
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED
SEE ADDENDUM
19.
20.
21.
22.
23.
24.
ITEM NO.
SCHEDULE OF SUPPLIES/SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT
(Use Reverse and/or Attach Additional Sheets as Necessary)
25. ACCOUNTING AND APPROPRIATION DATA
26. TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA
ARE
ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA
ARE
ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________
29. AWARD OF CONTRACT: REF. ___________________________________ OFFER
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND
DATED ________________________________. YOUR OFFER ON SOLICITATION
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY
(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED
SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION
(REV. NOV 2021)
PREVIOUS EDITION IS NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.212
7. FOR SOLICITATION
INFORMATION CALL:
STANDARD FORM 1449
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
618-26-4-6023-0040
36C26327Q0013 09-03-2026 Jeffrey Brown 651-293-3009 09-21-2026 12:00
CDT
36C263
DEPARTMENT OF VETERANS AFFAIRS
NETWORK CONTRACTING OFFICE 23
X
Y 561621 $25 Million
N/A
DEPARTMENT OF VETERANS AFFAIRS
Minneapolis VA Health Care System
1 Veterans Drive Minneapolis MN 55417
DEPARTMENT OF VETERANS AFFAIRS
NETWORK CONTRACTING OFFICE 23
Y
FINANCIAL SERVICES CENTER
PO BOX 149971
AUSTIN TX 78714-9971
See CONTINUATION Page The Contractor shall provide fire alarm inspection, maintenance and repair services in accordance with the terms and conditions below.
Prior to submitting a quote, review all documentation within
Review and follow the instructions in the INSTRUCTIONS TO OFFERORS in the Clause 52.212-1 Addendum.
Contract Ordering Period with estimated pricing periods of:
Base Pricing Period: 09/30/2026-09/29/2027 Year One Pricing Period: 09/30/2027-09/29/2028 Year Two Pricing Period: 09/30/2028-09/29/2029 Year Three Pricing Period: 09/30/2029-09/29/2030 Year Four Pricing Period: 09/30/2030-09/29/2031
See CONTINUATION Page
Jeffrey Brown
VA-VHA-RPOC-2024-0033
Table of Contents
| SECTION A | 2 |
| A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES | 2 |
| SECTION B - CONTINUATION OF SF 1449 BLOCKS | 5 |
| B.1 CONTRACT ADMINISTRATION DATA | 5 |
| B.2 SINGLE AWARD ORDER CONTRACT | 6 |
| B.3 PRICE/COST SCHEDULE | 6 |
| ITEM INFORMATION | 6 |
| B.4 Statement of Work | 8 |
| B.4 IT CONTRACT SECURITY | 17 |
| SECTION C - CONTRACT CLAUSES | 27 |
| C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION) | 27 |
| C.2 52.216-18 ORDERING (AUG 2020) | 32 |
| C.3 52.216-19 ORDER LIMITATIONS (OCT 1995) | 33 |
| C.4 52.216-22 INDEFINITE QUANTITY (NOV 2025) (DEVIATION) ALTERNATE II (NOV 2025) | 33 |
| C.5 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999) | 34 |
| C.6 52.222-40 NOTIFICATION OF EMPLOYEE RIGHTS UNDER THE NATIONAL LABOR RELATIONS ACT (NOV 2025) (DEVIATION) | 34 |
| C.7 52.222-42 STATEMENT OF EQUIVALENT RATES FOR FEDERAL HIRES (MAY 2014) | 36 |
| C.8 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS (DEVIATION APR 2026) | 36 |
| C.9 SUPPLEMENTAL INSURANCE REQUIREMENTS | 37 |
| C.10 52.240-91 SECURITY PROHIBITIONS AND EXCLUSIONS (NOV 2025) (DEVIATION) | 37 |
| C.11 VAAR 852.204-72 PERSONNEL VETTING AND CREDENTIALING (DEVIATION) (MAR 2026) | 47 |
| C.12 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998) | 50 |
| SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS | 51 |
| See attached document: S02 DOL WD 2015-4945 R33 08222026. | 51 |
| See attached document: S02 Fire Alarm System Inventory and Testing Table. | 51 |
| SECTION E - SOLICITATION PROVISIONS | 51 |
| E.1 52.212-1 Instructions to Offerors—Commercial Products and Commercial Services (DEVIATION OCT 2025) | 52 |
| ADDENDUM to 52.212-1 Instructions to Offerors—Commercial Products and Commercial Services. | 56 |
| E.2 52.209-7 INFORMATION REGARDING RESPONSIBILITY MATTERS (OCT 2018) | 58 |
| E.3 52.216-1 TYPE OF CONTRACT (NOV 2025) (DEVIATION) | 59 |
| E.4 52.225-6 TRADE AGREEMENTS CERTIFICATE (FEB 2021) | 60 |
| E.5 52.233-2 SERVICE OF PROTEST (SEP 2006) | 60 |
| E.6 52.240-90 SECURITY PROHIBITIONS AND EXCLUSIONS REPRESENTATIONS AND CERTIFICATIONS (NOV 2025) (DEVIATION) | 61 |
| E.7 VAAR 852.233-71 ALTERNATE PROTEST PROCEDURE (OCT 2018) | 65 |
| E.8 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB 1998) | 65 |
| E.9 52.212-2 Evaluation—Commercial Products and Commercial Services. (July 2026) | 66 |
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
1. Contract Administration: All contract administration matters will be handled by the following individuals:
a. CONTRACTOR:
b. GOVERNMENT: Contracting Officer 36C263 Jeffrey Brown
NETWORK CONTRACTING OFFICE 23
316 ROBERT STREET N, SUITE 506
SAINT PAUL MN 55101
2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:
| [X] |
| 52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or |
| [] |
| 52.232-36, Payment by Third Party |
3. INVOICES: Invoices shall be submitted in arrears:
| a. Quarterly | [] |
| b. Semi-Annually | [] |
| c. Other | [X] Monthly |
4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.
ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:
| AMENDMENT NO |
| DATE |
B.2 SINGLE AWARD ORDER CONTRACT
Quantities listed are estimated only and are not guaranteed.
This is a 5-year Commercial Firm Fixed Price, Single Award Indefinite Delivery / Indefinite Quantity (IDIQ) contract, for fire alarm system inspection, maintenance and repairs services to support the Minneapolis VA Health Care System.
Accordingly, funds are not obligated on this contract at the award; rather, funds are obligated via orders issued against the contract. Orders shall only be issued by a warranted VA Contracting Officer (CO). VA CO will issue task orders to the contractor authorizing services via Standard Form 1449. Each order shall clearly identify the dollar amount authorized under the individual task order and the period of performance of the individual order. When an order period of performance is completed, additional services shall not be provided unless a new order is issued in accordance with this IDIQ.
References to options in the schedule below refers to the pricing periods identified on the 1449 form of this document as this contract does not contain options.
The minimum dollar amount guaranteed under this contract for the performance period of the five year is $1,000.00. The maximum dollar amount or contract ceiling for this contract is $800,000.00. The maximum amount is not guaranteed. The combined total of all orders placed against this contract cannot exceed the maximum amount/ceiling of this contract.
(End of Clause)
B.3 PRICE/COST SCHEDULE
ITEM INFORMATION
| ITEM NUMBER |
| DESCRIPTION OF SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1,779,806.00 |
| SF |
| __________________ |
| __________________ |
MVAHCS Fire Alarm Systems inspection, maintenance and repair services Contract Period: Base POP Begin: 09-30-2026 POP End: 09-29-2027 PRINCIPAL NAICS CODE: 561621 - Security Systems Services (except Locksmiths) PRODUCT/SERVICE CODE: J063 - Maintenance, Repair, and Rebuilding of Equipment - Alarm, Signal, and Security Detection Systems
| 1,779,806.00 |
| SF |
| __________________ |
| __________________ |
MVAHCS Fire Alarm Systems inspection, maintenance and repair services Contract Period: Option 1 POP Begin: 09-30-2027 POP End: 09-29-2028
PRODUCT/SERVICE CODE: J063 - Maintenance, Repair, and Rebuilding of Equipment - Alarm, Signal, and Security Detection Systems
| 1,779,806.00 |
| SF |
| __________________ |
| __________________ |
MVAHCS Fire Alarm Systems inspection, maintenance and repair services Contract Period: Option 2 POP Begin: 09-30-2028 POP End: 09-29-2029
PRODUCT/SERVICE CODE: J063 - Maintenance, Repair, and Rebuilding of Equipment - Alarm, Signal, and Security Detection Systems
| 1,779,806.00 |
| SF |
| __________________ |
| __________________ |
MVAHCS Fire Alarm Systems inspection, maintenance and repair services Contract Period: Option 3 POP Begin: 09-30-2029 POP End: 09-29-2030
PRODUCT/SERVICE CODE: J063 - Maintenance, Repair, and Rebuilding of Equipment - Alarm, Signal, and Security Detection Systems
| 1,779,806.00 |
| SF |
| __________________ |
| __________________ |
MVAHCS Fire Alarm Systems inspection, maintenance and repair services Contract Period: Option 4 POP Begin: 09-30-2030 POP End: 09-29-2031
PRODUCT/SERVICE CODE: J063 - Maintenance, Repair, and Rebuilding of Equipment - Alarm, Signal, and Security Detection Systems
| GRAND TOTAL |
| __________________ |
B.4 Statement of Work Minneapolis VA Health Care System Fire Alarm Testing, Inspection, Maintenance, and Repairs
1. SCHEDULE OF SUPPLIES:
a. Fire Alarm System Maintenance Services
i. Contracted fire alarm services shall perform all inspections, testing, maintenance, and repairs of the facility fire alarm necessary to keep the Minneapolis VAHCS fire alarm system in compliance with the most current edition of NFPA 72: National Fire Alarm and Signaling Code.
ii. The Contractor shall provide tools, materials and labor necessary to properly perform services on this contract.
iii. Contractor shall inspect the entire fire alarm system annually. All battery chargers and the smoke detectors located in the Community Living Center will be inspected and tested on a semi-annually basis.
iv. Contractor shall include Emergency Callback Services for normal and off-hours repair of the fire alarm system and/or components. Contractor shall respond to emergencies within 4 hours and 8 hours for non-emergency calls.
v. Contracted fire alarm services shall provide twenty-four hours per day, seven days per week monitoring of the Minneapolis VAHCS alarm system.
vi. The Contractor shall provide all parts and materials necessary to effect maintenance and repairs of the fire alarm system.
vii. During the term of the contract, the VA may replace, renovate, or improve systems and equipment by means not associated with this contract. All replaced, improved, updated, modernized, or renovated systems and equipment shall be maintained and/or repaired by the Contractor at no additional cost to the VA unless there is a resulting increase or decrease in contract requirements.
viii. Buildings are protected by a Gamewell/FCI (Fire Control Instruments) E3 addressable fire alarm system with a Network Graphic Annunciator (NGA) LCD touch screen that serves as the primary interface with the control panel in room 1T-108. Remote NGAs are located near the Employee Entrance and in the VA Police Office.
ix. The Contractor shall be responsible for providing inspection, maintenance and repair of the fire alarm systems’ wiring and circuitry during the inspection, maintenance and repair of the fire alarm systems themselves. The cost of this work shall be included in the cost of the servicing of the individual systems.
x. The Contractor shall ensure that all software/firmware of the fire alarm systems are up to date to the most current version during inspection and testing and complete all software/firmware updates as necessary to bring them up to date.
xi. Inspection, testing, maintenance and repairs of the fire alarm system shall be performed between September 1st and December 31st, to be consistent with the completion of previous year testing timeframes. The CLC fire alarm system shall also be inspected, tested, maintained and repaired between April 1st and April 30th.
xii. Contractor is responsible for scheduling and associated costs for elevator technicians to assist with the servicing of the fire alarm system(s) associated with elevators.
2. GENERAL INFORMATION:
a. Safety Procedures – The contractor shall comply with all VA and OSHA safety code requirements.
b. Hazardous Conditions – If the inspector encounters equipment that is in a condition that may endanger the life or property, the inspector shall immediately notify the Engineering Department POC of the condition requiring immediate action. Within 24 hours the inspector shall provide a written report to the COR or Site Safety Officer of the hazardous condition and recommended corrective action.
c. Employee Number and Qualifications - The Contractor shall provide a minimum of 2 Certification in Engineering Technologies (NICET) Level II (minimum) certified technicians and one service manager with NICET level III to perform services under this contract. At least one of the technicians will be trained and certified to service/program Gamewell/FCI E3 fire alarm systems. Contractor employee certifications shall be provided upon request to VA officials.
d. The Contractor shall not interrupt or interfere with the operation of any existing activity on the premises or at the location of the work.
e. The Contractor shall clean up, all refuse, rubbish, scrap materials and debris caused by its operation, to the extent that at all times the site of the work shall present a neat, orderly and workmanlike appearance.
f. Contractor employees shall present a professional appearance at all times and their conduct shall not reflect discredit upon the United States and or the VA/VHA.
g. Employees shall not disturb desks or any administrative spaces. Employee will not use VA/VHA telephones, copiers, or any other office equipment intended for official Medical Center use. Employees will not disturb drawers, cabinets, or other storage areas.
3. DESCRIPTION/SPECIFICATIONS:
a. Notification
i. Contractor shall provide a minimum of two weeks-notice to the Site Safety Officer before proceeding with services and then a notice at two days prior and after the testing.
b. Inspection and Testing Requirements
i. Inspection and Testing frequencies from the most current edition of NFPA 72: National Fire Alarm and Signaling Code.
ii. Contractor shall provide an implementation plan that details how all the Inspections and Testing of equipment will be conducted.
iii. During the inspection and testing process, conduct a review of the software and firmware being used by the MVAHCS. Contractor shall provide recommendations to the VA regarding the costs vs. benefits of upgrading software and firmware to newer versions.
iv. Identify potentially detrimental site conditions that could compromise the performance of mechanical and/or electronic components of the fire alarm system.
v. Inquire about any changes or modifications of the fire alarm system.
vi. Inquire about changes in the general occupancy environment, operations and conditions relating to the fire alarm system.
vii. Compile a complete report of the Inspection and Testing, explaining any deficiencies and corrective action taken in accordance with recognized codes for care and maintenance.
viii. Contractor shall work with the VA on periodic programming of messages into the Voice Alarm Channels.
c. Maintenance and Repair of Fire Detection and Alarm System
i. Contractor shall provide preventative maintenance services on the fire alarm systems at the MVAHCS.
ii. The contractor shall provide Emergency Callback Services (ECS):
iii. ECS consists of responding to a service call and beginning to take corrective action within four (4) hours.
iv. ECS shall be provided twenty-four (24) hours a day, seven (7) days a week.
v. Service Tickets:
vi. Contractor shall have service ticket on each service call signed by the MVAHCS designated representative.
vii. Service ticket shall describe the work performed and provide the date and time of service.
viii. Contractor personnel shall check in and out with an MVAHCS representative when arriving and leaving the site check via email or phone call.
ix. Any incomplete work shall be reported to an MVAHCS representative prior to leaving MVAHCS property.
x. Equipment malfunctions shall be corrected within at least two days, or longer upon MVAHCS approval.
d. Inspection, Testing, Maintenance, and Repair Records
i. After completing regular inspection, testing, and maintenance, the Contractor shall furnish written list of deficiencies in the fire alarm system to the COR or Site Safety Officer within two (2) business days.
ii. Within 14 calendar days of the inspection, testing, and maintenance, the Contractor shall provide a formal written report to the COR and Site Safety Officer that includes the following (1 hard copy and 1 electronic copy):
1. Contractor’s Inspection and Testing Form that includes all the information required by the most current edition of NFPA 72, Chapter 7: National Fire Alarm and Signaling Code.
2. A record of the completed inspection, maintenance and/or repair items.
3. The record shall include any problems noted with the system, including inoperable or unsupervised devices or equipment, or devices that cannot be calibrated, tested, serviced in accordance with the manufacturer’s recommendations.
4. Reports shall include the software and firmware version, system address, physical location, device description, operational status and condition of the device.
5. Reports shall include all fire alarm system deficiencies found and suggested corrective action.
6. Maintenance log report summarizing preventive and non-preventive maintenance performed on equipment covered by this contract.
iii. The Contractor must be able to properly troubleshoot and diagnose all aspects of fire alarm system failures.
iv. When fire alarm systems fail completely (i.e. irreparable system failure), the technician’s Supervisor shall provide the MVAHCS with a written statement and itemized quote assessing the fire alarm system failure and that they have verified the fire alarm system has been properly diagnosed and concur with the technician’s assessment.
v. The VA reserves the right to enlist a third-party expert to provide a 2nd opinion. It is the responsibility of the Contractor to reassess their proposed repairs and either reaffirm or correct their proposal based on the expert’s notes. The reassessment shall include at a minimum, a substantive analysis of the third-party expert’s points that contradict the Contractor’s original conclusion. This reassessment shall be submitted within 5 business days of receipt of the third-party expert’s opinion.
vi. The Contractor shall furnish testing to the following auxiliary Fire Alarm devices and systems which communicates/signals the main Fire Alarm System in Bldg. 70:
1. Data Center Suppression System 2B105.
2. Fire Alarm Roll Down Doors in Outpatient Pharmacy (1R-101), SCI Pharmacy (SC, & Uniform Issue (1N-104).
3. Dust collector
4. QUALITY CONTROL: The contractor shall develop and maintain an effective quality control program to ensure services are performed in accordance with this SOW. The quality control program plan shall be supplied to an MVAHCS representative upon request.
5. RECOGNIZED HOLIDAYS:
a. Unless contacted for an ESC, the contractor is not required to perform services on the following holidays:
i. New Year’s Day
ii. Martin Luther King Jr.’s Birthday
iii. President’s Day
iv. Memorial Day
v. Juneteenth
vi. Independence Day
vii. Labor Day
viii. Columbus Day
ix. Veteran’s Day
x. Thanksgiving Day
xi. Christmas Day
6. HOURS OF OPERATION:
a. The contractor shall coordinate with the COR, ATS Shop and Site Safety Officer to determine when inspection, testing, maintenance or repair can be performed.
b. Normal business hours, when regular Contractor service shall be available to the government, are Monday through Friday, from 7:30 am to 4:00 pm, federal holidays excluded.
c. When inspection, testing, maintenance, or repair will interfere with building operations; it shall be performed after normal business hours.
7. SECURITY REQUIREMENTS:
a. Contractor staff are required to conform to MVAHCS’s security and privacy requirements as described below.
b. The following security language is applicable to Contractor staff who will enter MVAHCS facilities.
c. Contractor staff will utilize a temporary vendor’s security badge until a permanent security PIV badge can be issued. Temporary badge use will not exceed 30 calendar days.
d. The Contractor shall comply with MVAHCS security, access, and badging requirements. Employees must provide fingerprints and be able to pass a background check so they can obtain a security access badge.
e. All Contractor staff will need a valid individual personal or professional email account that can be easily checked. Notifications regarding fingerprint scheduling/appointments, background investigation tasks, and Training Management System (TMS) required classes will be sent to their email address throughout the badging process.
f. Appropriate vendor staff (as determined by the VA) performing the duties of the Statement of Work shall complete the computer-based training course “TMS 10176 Infosec/Rules of Behavior”.
g. Contractor staff shall be escorted while on VHA property.
h. The Contractor will submit all required security badging documents for each employee within five (5) business days from the award date of contract. All documents must be legible. The following documents will be sent to the Contractor via email after contract is awarded.
i. OF 306 – Must be Typed. Submission of handwritten forms will not be acceptable.
ii. Self-Certification
iii. VA 10-2417
iv. Employee Fingerprint Resource Form
i. Adhere to the following sections of the IT Contract Security Clause below:
i. Section 1, General
ii. Section 2, VA Information Custodial Language.
iii. Section 3, Access to VA Information and VA Information Systems.
iv. Section 4, Training
8. BUILDING DESCRIPTIONS:
a. Building 9: Approximately 30,000 ft2, multistory building. Building is fully sprinkled (dry sprinkler system) and has a single elevator. Fire alarm system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
b. Building 10: Approximately 25,000 ft2, multistory building. Building is fully sprinkled (dry sprinkler system) and has a single elevator. Fire alarm system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
c. Building 47: Approximately 3,600 ft2, multistory building. Building is fully sprinkled. Fire alarm system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
d. Building 49/49A: Approximately 75,000 ft2, multistory building. Building is fully sprinkled and has 2 elevator banks. Fire alarm system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
e. Building 68: Approximately 30,000 ft2, multistory building. Building is fully sprinkled and has a single elevator. Fire alarm system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
f. Building 69: Approximately 30,000 ft2, multistory building. Building is fully sprinkled. Fire alarm system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
g. Building 70: Approximately 1,200,000 ft2, multistory building is fully sprinkled, has smoke control zones, multi-elevator banks, door controllers, kitchen interconnections, and dry pipe systems. Fire alarm system is networked with the Fire Alarm Network System located within the building, but has a separate DACT for standalone operation.
h. Building 72: Approximately 10,000 ft2, single story building. Building is fully sprinkled and has a gas detection system. The new system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
i. Building 73: Approximately 5,000 ft2, single story building. Building is fully sprinkled. The new system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
j. Building 74: Approximately 5,000 ft2, single story building. Building is fully sprinkled. The new system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
k. Building 75: Fisher House II is approximately 14,606 ft2, two-story building. Building is fully sprinkled. The new system has its own DACT for standalone operation with dial-up operation to St. Paul Fire.
l. Building 76: Spinal Cord Injury/Disorder Center is approximately 62,000 ft2, two-story building (including basement). Building is fully sprinkled. The new system has its own DACT for standalone operation with dial-up operation to St. Paul Fire.
m. Building 78: Parking ramp elevator areas only. Fire alarm system is networked with the Fire Alarm Network System located in Building 70.
n. Building 79: Approximately 13,550 ft2.
o. Building 80: Approximately 15,550 ft2.
p. Building 89: Business office space. Fire alarm system is networked with the Fire Alarm Network System located in Building 70.
q. Building 222: Approximately 62,000 ft2, multi-story building. Building is fully sprinkled. The new system shall be networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
r. Building 224: Approximately 13,500 ft2, single story building. Building is not sprinkled. The new system is networked with the Fire Alarm Network System located in Building 70, but has its own DACT for standalone operation.
9. Description of Existing System
a. Fire-alarm signal initiation occurs by one or more of the following devices and systems:
i. Manual stations.
ii. Heat detectors.
iii. Smoke detectors.
iv. Duct smoke detectors.
v. Verified automatic alarm operation of smoke detectors.
vi. Automatic sprinkler system water flow.
vii. Heat detectors in elevator shaft and pit.
viii. Fire-extinguishing system operation.
ix. Fire standpipe system.
x. Line loss.
xi. Generator start-up.
xii. FACP circuit trouble.
xiii. 1 degree and 2 degree power loss.
xiv. Dry Air System
b. Fire-alarm signal initiates the following actions:
i. Activates voice/alarm communication system.
ii. Identifies alarm at fire-alarm control unit and remote annunciators.
iii. Transmits an alarm signal to the remote alarm receiving station.
iv. Unlocks electric door locks in designated egress paths.
v. Releases fire and smoke doors held open by magnetic door holders.
vi. Recalls elevators to primary or alternate recall floors. Activates elevator bank shunt trip.
vii. Records events in the system memory.
viii. Records events by the system printer.
c. Supervisory signal initiation is caused by one or more of the following devices:
i. Valve supervisory switches (Sprinkler, Standpipe Control, PIV, Main Gate). Operation of valve shall sound a supervisory signal at the Main Control Unit until silenced by manual off switch.
ii. Low-air-pressure switch of a dry-pipe sprinkler system.
iii. Elevator shunt-trip supervision.
d. System trouble signal initiation is caused by one or more of the following devices and actions:
i. Open circuits, shorts, and grounds in designated circuits.
ii. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices.
iii. Loss of primary power at fire-alarm control unit.
iv. Ground or a single break in fire-alarm control unit internal circuits.
v. Abnormal ac voltage at fire-alarm control unit.
vi. Break in standby battery circuitry.
vii. Failure of battery charging.
viii. Abnormal position of any switch at fire-alarm control unit or annunciator.
ix. Fire-pump power failure, including a dead-phase or phase-reversal condition.
x. Low-air-pressure switch operation on a dry-pipe or pre-action sprinkler system.
e. System Trouble and Supervisory Signal Actions:
i. Annunciates at fire-alarm control unit and remote annunciators.
ii. Records the event on system printer.
iii. Arranges trouble signals for automatic reset (non-latching).
iv. Alarm signals from smoke detectors at pressurization air supplies have a higher priority than other alarm signals that start the system.
f. Smoke-Alarm Verification:
i. Initiates audible and visible indication of an "alarm-verification" signal at fire-alarm control unit.
ii. Activates an NRTL-listed and -approved "alarm-verification" sequence at fire-alarm control unit and detector.
iii. Records events by the system printer.
iv. Sounds general alarm if the alarm is verified.
v. Cancels fire-alarm control unit indication and system reset if the alarm is not verified.
g. Elevator Recall:
i. Smoke detectors at the following locations initiate automatic elevator recall.
1. Elevator lobby detectors except the lobby detector on the designated floor.
2. Smoke/Heat detector(s) in elevator machine room.
ii. Elevator lobby detectors located on the designated recall floors are programmed to move the cars to the alternate recall floor.
iii. Water-flow alarm connected to sprinkler in an elevator shaft and elevator machine room shut down elevators associated with the location without time delay.
iv. Water-flow switch associated with the sprinkler in the elevator pit may have a delay to allow elevators to move to the designated floor.
h. Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in smoke barrier walls are connected to fire-alarm system.
i. Remote Smoke-Detector Sensitivity Adjustment: Controls select specific addressable smoke detectors for adjustment, displays their current status and sensitivity settings, and changes those settings. Allows controls to be used to program repetitive, time-scheduled, and automated changes in sensitivity of specific detector groups. Records sensitivity adjustments and sensitivity-adjustment schedule changes in system memory and print out the final adjusted values on system printer.
j. Remote Control Capability: Each building fire alarm control unit is installed and programmed so that each must be reset locally after an alarm, before the main fire alarm control unit can be reset. After the local building fire alarm control unit has been reset, then the system acknowledge, reset, silence or disabling functions can be operated by the main fire alarm control unit.
k. General:
i. An emergency voice communication system is installed throughout Building 49, 49A, 70, 76, 79 and 80.
ii. Upon receipt of an alarm signal from the building fire alarm system, the VCS automatically transmits a pre-recorded fire alarm message throughout the floor in alarm, the floor above, and the floor below.
iii. A digitized voice module is used to store each prerecorded message.
iv. The VCS is arranged as a dual channel system capable of transmitting two different messages simultaneously.
v. The VCS supervises all speaker circuits, control equipment, remote audio control equipment, and amplifiers.
l. Speaker Circuit Control Unit:
i. The speaker circuit control unit includes switches to manually activate or deactivate speaker circuits grouped by floor in the system.
ii. Speaker circuit control switches provide on, off, and automatic positions and indications.
iii. The speaker circuit control unit includes visual indication of active or trouble status for each group of speaker circuits in the system.
iv. A trouble indication is provided if a speaker circuit group is disabled.
v. A lamp test switch is provided to test all indicator lamps.
vi. A single "all call" switch is provided to activate all speaker circuit groups simultaneously.
vii. A push-to-talk microphone is provided for manual voice messages.
viii. Remote microphones are provided at the Outpatient Entrance Manned Station (Building 70, near room C1-183) for manual "all call" messages.
ix. A voice message disconnect switch is provided to disconnect automatic digitized voice messages from the system. The system is arranged to allow manual voice messages and indicate a system trouble condition when activated.
m. Speaker Circuit Arrangement:
i. Speaker circuits are arranged such that there is one speaker circuit per smoke zone.
ii. Audio amplifiers and control equipment are electrically supervised for normal and abnormal conditions.
iii. Speaker circuits are either 25 VRMS or 70.7 VRMS with a minimum of 50% spare power available.
iv. Speaker circuits and control equipment are arranged such that loss of any one speaker circuit will not cause the loss of any other speaker circuit in the system.
n. Digitized Voice Module (DVM):
i. The Digitized Voice Module provides prerecorded digitized evacuation and instructional messages. The messages shall be professionally recorded and approved by the COTR prior to programming.
ii. The DVM is configured to automatically output to the desired circuits following a 10-second slow whoop alert tone.
iii. The DVM is supervised for operational status.
iv. Failure of the DVM will result in the transmission of a constant alarm tone.
o. Audio Amplifiers
i. Audio Amplifiers provide a minimum of 50 Watts at either 25 or 70.7 VRMS output voltage levels.
ii. Amplifiers are continuously supervised for operational status.
iii. Amplifiers are configured for either single or dual channel application.
p. Tone Generator(s):
i. Tone Generator(s) are capable of providing a distinctive three-pulse temporal pattern fire alarm signal as well as a slow whoop.
ii. Tone Generator(s) are continuously supervised for operational status.
q. Notification Appliances: Individually addressed, connected to a signaling line circuit, equipped for mounting as indicated and with screw terminals for system connections.
r. Addressable Interface Devices:
i. Microelectronic monitor modules, NRTL listed for use in providing a system address for alarm-initiating devices for wired applications with normally open contacts.
ii. Have unique addresses that report directly to the building fire alarm panel.
iii. Monitors normally open or normally closed devices for both alarm and trouble conditions.
iv. Terminal designations differentiate between the circuit to which they are reporting from and the device that they are monitoring.
s. Smoke Barrier Door Control:
i. Door holder control circuits are electrically supervised.
ii. Smoke detectors are not an integral part of door holders. Each door holder has two (2) adjacent smoke detectors.
t. Digital Alarm Communicator Transmitter
i. Digital alarm communicator transmitters shall be acceptable to the remote central station and shall comply with UL 632 and be listed and labeled by an NRTL.
ii. Unit receives an alarm, supervisory, or trouble signal from fire-alarm control unit. It automatically captures two telephone line(s) and dials a preset number for a remote central station. When contact is made with central station(s), signals are transmitted. If service on either line is interrupted for longer than 45 seconds, transmitter initiates a local trouble signal and transmits the signal indicating loss of telephone line to the remote alarm receiving station over the remaining line. Transmitter automatically reports telephone service restoration to the central station. If service is lost on both telephone lines, transmitter initiates the local trouble signal.
iii. DACT has an integral rechargeable battery and automatic charger.
iv. DACT conducts a self-test automatically every 24 hours with report transmitted to central station.
B.4 IT CONTRACT SECURITY
VA INFORMATION AND INFORMATION SYSTEM SECURITY/PRIVACY
1. GENERAL
Contractors, contractor personnel, subcontractors, and subcontractor personnel shall be subject to the same Federal laws, regulations, standards, and VA Directives and Handbooks as VA and VA personnel regarding information and information system security.
2. ACCESS TO VA INFORMATION AND VA INFORMATION SYSTEMS
a. A contractor/subcontractor shall request logical (technical) or physical access to VA information and VA information systems for their employees, subcontractors, and affiliates only to the extent necessary to perform the services specified in the contract, agreement, or task order.
b. All contractors, subcontractors, and third-party servicers and associates working with VA information are subject to the same investigative requirements as those of VA appointees or employees who have access to the same types of information. The level and process of background security investigations for contractors must be in accordance with VA Directive and Handbook 0710, Personnel Suitability and Security Program. The Office for Operations, Security, and Preparedness is responsible for these policies and procedures.
c. Contract personnel who require access to national security programs must have a valid security clearance. National Industrial Security Program (NISP) was established by Executive Order 12829 to ensure that cleared U.S. defense industry contract personnel safeguard the classified information in their possession while performing work on contracts, programs, bids, or research and development efforts. The Department of Veterans Affairs does not have a Memorandum of Agreement with Defense Security Service (DSS). Verification of a Security Clearance must be processed through the Special Security Officer located in the Planning and National Security Service within the Office of Operations, Security, and Preparedness.
d. Custom software development and outsourced operations must be located in the U.S. to the maximum extent practical. If such services are proposed to be performed abroad and are not disallowed by other VA policy or mandates, the contractor/subcontractor must state where all non-U.S. services are provided and detail a security plan, deemed to be acceptable by VA, specifically to address mitigation of the resulting problems of communication, control, data protection, and so forth. Location within the U.S. may be an evaluation factor.
e. The contractor or subcontractor must notify the Contracting Officer immediately when an employee working on a VA system or with access to VA information is reassigned or leaves the contractor or subcontractor's employ. The Contracting Officer must also be notified immediately by the contractor or subcontractor prior to an unfriendly termination.
3. VA INFORMATION CUSTODIAL LANGUAGE
a. Information made available to the contractor or subcontractor by VA for the performance or administration of this contract or information developed by the contractor/subcontractor in performance or administration of the contract shall be used only for those purposes and shall not be used in any other way without the prior written agreement of the VA. This clause expressly limits the contractor/subcontractor's rights to use data as described in Rights in Data - General, FAR 52.227-14(d) (1).
b. VA information should not be co-mingled, if possible, with any other data on the contractors/subcontractor's information systems or media storage systems in order to ensure VA requirements related to data protection and media sanitization can be met. If co-mingling must be allowed to meet the requirements of the business need, the contractor must ensure that VA's information is returned to the VA or destroyed in accordance with VA's sanitization requirements. VA reserves the right to conduct on site inspections of contractor and subcontractor IT resources to ensure data security controls, separation of data and job duties, and destruction/media sanitization procedures are in compliance with VA directive requirements.
c. Prior to termination or completion of this contract, contractor/ subcontractor must not destroy information received from VA, or gathered/ created by the contractor in the course of performing this contract without prior written approval by the VA. Any data destruction done on behalf of VA by a contractor/subcontractor must be done in accordance with National Archives and Records Administration (NARA) requirements as outlined in VA Directive 6300, Records and Information Management and its Handbook 6300.1 Records Management Procedures, applicable VA Records Control Schedules, and VA Handbook 6500.1, Electronic Media Sanitization. Self-certification by the contractor that the data destruction requirements above have been met must be sent to the VA Contracting Officer within 30 days of termination of the contract.
d. The contractor/subcontractor must receive, gather, store, back up, maintain, use, disclose and dispose of VA information only in compliance with the terms of the contract and applicable Federal and VA information confidentiality and security laws, regulations and policies. If Federal or VA information confidentiality and security laws, regulations and policies become applicable to the VA information or information systems after execution of the contract, or if NIST issues or updates applicable FIPS or Special Publications (SP) after execution of this contract, the parties agree to negotiate in good faith to implement the information confidentiality and security laws, regulations and policies in this contract.
e. The contractor/subcontractor shall not make copies of VA information except as authorized and necessary to perform the terms of the agreement or to preserve electronic information stored on contractor/subcontractor electronic storage media for restoration in case any electronic equipment or data used by the contractor/subcontractor needs to be restored to an operating state. If copies are made for restoration purposes, after the restoration is complete, the copies must be appropriately destroyed.
f. If VA determines that the contractor has violated any of the information confidentiality, privacy, and security provisions of the contract, it shall be sufficient grounds for VA to withhold payment to the contractor or third party or terminate the contract for default or terminate for cause under Federal Acquisition Regulation (FAR) part 12.
g. If a VHA contract is terminated for cause, the associated BAA must also be terminated and appropriate actions taken in accordance with VHA Handbook 1600.01, Business Associate Agreements. Absent an agreement to use or disclose protected health information, there is no business associate relationship.
h. The contractor/subcontractor must store, transport, or transmit VA sensitive information in an encrypted form, using VA-approved encryption tools that are, at a minimum, FIPS 140-2 validated.
i. The contractor/subcontractor's firewall and Web services security controls, if applicable, shall meet or exceed VA's minimum requirements. VA Configuration Guidelines are available upon request.
j. Except for uses and disclosures of VA information authorized by this contract for performance of the contract, the contractor/subcontractor may use and disclose VA information only in two other situations: (i) in response to a qualifying order of a court of competent jurisdiction, or (ii) with VA's prior written approval. The contractor/subcontractor must refer all requests for, demands for production of, or inquiries about, VA information and information systems to the VA contracting officer for response.
k. Notwithstanding the provision above, the contractor/subcontractor shall not release VA records protected by Title 38 U.S.C. 5705, confidentiality of medical quality assurance records and/or Title 38 U.S.C. 7332, confidentiality of certain health records pertaining to drug addiction, sickle cell anemia, alcoholism or alcohol abuse, or infection with human immunodeficiency virus. If the contractor/subcontractor is in receipt of a court order or other requests for the above mentioned information, that contractor/subcontractor shall immediately refer such court orders or other requests to the VA contracting officer for response.
l. For service that involves the storage, generating, transmitting, or exchanging of VA sensitive information but does not require C&A or an MOU-ISA for system interconnection, the contractor/subcontractor must complete a Contractor Security Control Assessment (CSCA) on a yearly basis and provide it to the COR.
4. INFORMATION SYSTEM DESIGN AND DEVELOPMENT
a. Information systems that are designed or developed for or on behalf of VA at non-VA facilities shall comply with all VA directives developed in accordance with FISMA, HIPAA, NIST, and related VA security and privacy control requirements for Federal information systems. This includes standards for the protection of electronic PHI, outlined in 45 C.F.R. Part 164, Subpart C, information and system security categorization level designations in accordance with FIPS 199 and FIPS 200 with implementation of all baseline security controls commensurate with the FIPS 199 system security categorization (reference Appendix D of VA Handbook 6500, VA Information Security Program). During the development cycle a Privacy Impact Assessment (PIA) must be completed, provided to the COR, and approved by the VA Privacy Service in accordance with Directive 6507, VA Privacy Impact Assessment.
b. The contractor/subcontractor shall certify to the COR that applications are fully functional and operate correctly as intended on systems using the VA Federal Desktop Core Configuration (FDCC), and the common security configuration guidelines provided by NIST or the VA. This includes Internet Explorer 7 configured to operate on Windows XP and Vista (in Protected Mode on Vista) and future versions, as required.
c. The standard installation, operation, maintenance, updating, and patching of software shall not alter the configuration settings from the VA approved and FDCC configuration. Information technology staff must also use the Windows Installer Service for installation to the default "program files" directory and silently install and uninstall.
d. Applications designed for normal end users shall run in the standard user context without elevated system administration privileges.
e. The security controls must be designed, developed, approved by VA, and implemented in accordance with the provisions of VA security system development life cycle as outlined in NIST Special Publication 800-37, Guide for Applying the Risk Management Framework to Federal Information Systems, VA Handbook 6500, Information Security Program and VA Handbook 6500.5, Incorporating Security and Privacy in System Development Lifecycle.
f. The contractor/subcontractor is required to design, develop, or operate a System of Records Notice (SOR) on individuals to accomplish an agency function subject to the Privacy Act of 1974, (as amended), Public Law 93-579, December 31, 1974 (5 U.S.C. 552a) and applicable agency regulations. Violation of the Privacy Act may involve the imposition of criminal and civil penalties.
g. The contractor/subcontractor agrees to:
(1) Comply with the Privacy Act of 1974 (the Act) and the agency rules and regulations issued under the Act in the design, development, or operation of any system of records on individuals to accomplish an agency function when the contract specifically identifies:
(a) The Systems of Records (SOR); and
(b) The design, development, or operation work that the contractor/ subcontractor is to perform;
(1) Include the Privacy Act notification contained in this contract in every solicitation and resulting subcontract and in every subcontract awarded without a solicitation, when the work statement in the proposed subcontract requires the redesign, development, or operation of a SOR on individuals that is subject to the Privacy Act; and
(2) Include this Privacy Act clause, including this subparagraph (3), in all subcontracts awarded under this contract which requires the design, development, or operation of such a SOR.
h. In the event of violations of the Act, a civil action may be brought against the agency involved when the violation concerns the design, development, or operation of a SOR on individuals to accomplish an agency function, and criminal penalties may be imposed upon the officers or employees of the agency when the violation concerns the operation of a SOR on individuals to accomplish an agency function.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .