S02 - Equipment Listing.pdf
PDF 224 KB Posted
- Attached to
- S112--Inspect, Test and Adjust Electrical System/Arc Flash Hazard Analysis Federal contract opportunity
- Solicitation number
- 36C25225Q0484
About this file
Attachment 1 is an inventory of electrical power distribution equipment and cables across multiple buildings for inspection, testing, and maintenance. The document comprehensively lists electrical infrastructure components including switchgear assemblies, liquid-filled transformers, switches, circuit breakers, protective relays, panelboards, and disconnects across Buildings 14, 19, 22, 25, 49, 58, 60, 64/72, 93, 98, 99, 101, 102, 103, 104, 125, 128, 129, 130, 131, 132, 133, 140, 211, 212, 214, and 216.
The inventory details specific electrical equipment with technical specifications such as device IDs, current ratings, voltage levels, circuit numbers, frame sizes, and ampacity. Equipment types range from low-voltage and medium-voltage circuit breakers to electronic protective relays and facility grounding systems. The document provides granular information on electrical infrastructure components, including alternative and main power sources, chillers, generators, and various electrical panels, suggesting a comprehensive maintenance and inspection scope for the facility's electrical systems.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Responses from the VA - Final.docx | DOCX document | |
| Arc Flash Final Report 2022.pdf | ||
| 36C25225Q0484 0004.docx | DOCX document | |
| S02 - 36C25225Q0484 - Final.docx | DOCX document | |
| 36C25225Q0484 0003.docx | DOCX document | |
| 36C25225Q0484 0002.docx | DOCX document | |
| S02 - 36C25225Q0484 - Approved.docx | DOCX document | |
| 36C25225Q0484 0001.docx | DOCX document | |
| S02 - WD 2015-5021 Rev 25 5.13.25.pdf | ||
| 36C25225Q0484.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
April 15, 2025
Attachment 1 - Inventory of Electrical Power Distribution Equipment and Cables to be Maintained, Inspected, and/or Tested Under This Scope of Work
1) Switchgear Assemblies, Low-Voltage.
Location Device ID Current Rating
B14 MDP 1200
B58 Switchgear 58 3200 B98 B98 Service (indoor) 2000 B98 B98 Service (outdoor) 2000 B98 B98 Service (outdoor) 2000
B104 104 Switchboard 1200
B140 MDP 1200
2) Transformers, Liquid-Filled.
Transformer kVA Primary Secondary Circuit
T/13 225 4,160 V 208 V 2 T/14 500 4,160 V 208 V 2 T/19 150 4,160 V 208 V 9 T/22 225 4,160 V 208 V 4 T/26
(old T/48) 300 4,160 V 208 V 9
T/30 112.5 4,160 V 208 V 9 T/33 150 4,160 V 208 V 9
T/33A 75 4,160 V 208 V 9 T/39/40 75 4,160 V 208 V 9
T/49 75 4,160 V 208 V 9 T/58A 2,000 4,160 V 480 V 3 T/58B 300 4,160 V 480 V 9 T/60 112.5 4,160 V 208 V 2
T/64/72 225 4,160 V 208 V 9 T/68 75 4,160 V 208 V 9 T/93 150 4,160 V 208 V 2 T/98 1,500 4,160 V 480 V 3
T/100 300 4,160 V 480 V 3 T/101 1,000 4,160 V 480 V 6 T/102 1,000 4,160 V 480 V 5 T/103 1,000 4,160 V 480 V 7 T/104 2,000 4,160 V 480 V 8 T/125 300 4,160 V 208 V 8
T/128/129 300 4,160 V 208 V 2 T/130 150 4,160 V 208 V 2
T/131 150 4,160 V 208 V 2 T/132/133 750 4,160 V 208 V 2
T/140 500 4160 V 208 V 9
3) Switches, Bolted-Pressure, Low-Voltage.
Location Device ID Ampacity
B14 Main 1200
4) Switches, Air, Medium-Voltage, Metal-Enclosed.
Switch Circuit
SW-MH46 2
S&C PMH-9 2
SW-MH26-A 3
SW-MH26-B 4
SW-MH28-A 3
SW-MH28-B 4
SW-MH49-A 3
SW-MH49-B 4
SW-MH34A 8
SW-MH22-A 9
SW-MH43 9
SW-MH25 9
SW-MH48 9
SW-MH54 2
5) Circuit Breakers, Air, Insulated-Case/ Molded-Case.
Location Device ID Trip Rating
B14 Chiller 400 B14 Generator 350 B14 Transfer Switch 400 B19 Main 400 B26 Main 400 B30 Main 400 B58 Generator 800 B60 Main 600
B64/72 Generator 150 B64/72 Main 600
B98 Generator 800
B125 Main 800 B128/129 Generator 800 B128/129 Main 800 B128/129 North 400 B128/129 South 400 B128/129 Spare 400
B130 Main 400 B130 Generator 250 B131 Main 400 B131 Generator 250
B132/133 Generator 600 B140 Generator 400 B140 Generator 100 B140 Generator 100 B140 Main 400 B140 Main 100 B140 Main 100 B140 Panel 1N1 200 B140 Panel 1N2 100 B140 Panel 1N3 100 B140 Panel 1N4 100 B140 Panel 2N1 200 B140 Panel 1ER1 400 B140 Panel 1CR1 100 B140 Panel 1LS1 100 B140 Panel SPD 60
6) Circuit Breakers, Draw-Out Air, Low-Voltage Power.
Location Device ID Frame Size
B58 58/DP1 800
B58 Alt Source 3200 B58 Bus Duct 800 B58 Chiller CK-1 800 B58 Chiller CK-2 800
B58 58/DP2 800
B58 58/K1 800 B58 Main 3200
B58 MCC-P1 800
B58 MCC-P2 800
B58 58/MSR 800
B58 58/NDP 800
B98 DP-A 600
B98 DP-B 600
B98 DP-C 600
B98 B-PH 600
B98 DSB 1600
B98 Main 3000
B98 MCC 225
B98 MCC 2 800
B98 New Main 2000 B98 Trane Ckt #1 600 B98 Trane Ckt #2 600A
B98 ATS 1 600
B98 ATS 2 600
B101 ATS 101 600
B101 DS-206 800
B101 Main 1600
B101 MCC 600
B101 MDP 600
B101 Spare 600 B101 T-1 600 B101 T-2 600 B101 T-3 600 B101 T-4 600 B101 T-5 600 B101 T-6 600 B102 Chiller 800 B102 Main 1600
B102 MCC 600
B102 PA 6 600
B102 PB 600
B102 Spare 600
B102 MCC 600
B103 PE 600
B103 EMN 800
B103 Main 1600
B103 PF 600
B103 Spare 600 B104 Alt Source 3200 B104 FDR Trane Chiller 600
B104 EM #1 B102 600
B104 EM #2 B103 600
B104 EM #3 B101 600
B104 EM #4 B104 600
B104 FDR EMN 600
B104 EP B125 800
B104 FDR 1 600
B104 FDR 2 600
B104 FDR 3 600
B104 FDR 4 600
B104 FDR 5 600
B104 FDR 6 600
B104 Generator 1400 B104 New Main 3200 B104 Old Main 1600 B104 Panel NX 800
7) Circuit Breakers, Medium-Voltage Power
Location Device ID Trip Rating
B99 Circuit 1 1200 B99 Circuit 2 1200 B99 Circuit 3 1200 B99 Circuit 4 1200 B99 Circuit 5 1200 B99 Circuit 6 1200 B99 Circuit 7 1200 B99 Circuit 8 1200 B99 Circuit 9 1200 B99 Spare 1200 B99 Spare 1200
8) Protective Relays, Electronic, Medium-Voltage.
Location Device ID Description
B99 RLY-102A GE MULTILIN 350
B99 RLY-104B GE MULTILIN 350
B99 RLY-109A GE MULTILIN 350
B99 RLY-F1 GE MULTILIN 350
B99 RLY-F2 GE MULTILIN 350
B99 RLY-F3 GE MULTILIN 350
B99 RLY-F4 GE MULTILIN 350
B99 RLY-F5 GE MULTILIN 350
B99 RLY-F6 GE MULTILIN 350
B99 RLY-F7 GE MULTILIN 350
B99 RLY-F8 GE MULTILIN 350
B99 RLY-F9 GE MULTILIN 350
B99 RLY-MAIN-1 GE MULTILIN 750
B99 RLY-MAIN-2 GE MULTILIN 750
B99 RLY-TIE GE MULTILIN 750
B99 RLY-UTILITY BASLER BE1-50/51B, Series 100
9) Facility Grounding Systems.
Buildings 14, 19, 22/69, 25, 49, 58, 60, 64/72, 93, 98, 99, 101, 102, 103, 104, 125, 128, 129, 130, 131, 132, 133, 140, 211, 212, 214, & 216.
10) Medium-Voltage Cables
Cable From To Size Circuit #2 B99 Main Sub T/14, T/48, T/60, T/93, T/128/129, T/130/131, T/132/133
4/0
Circuit #3 B99 Main Sub T/58A 500 MCM Circuit #4 B99 Main Sub T/98 500 MCM Circuit #5 B99 Main Sub T/102 4/0
T/103 – T/102 T/103 T/102 4/0 Circuit #6 B99 Main Sub T/101 4/0
T/101 – T/104 T/101 T/104 4/0 Circuit #7 B99 Main Sub T/103 4/0 Circuit #8 B99 Main Sub T/104 4/0 Circuit #9 B99 Main Sub T/26 4/0
T/64/72 – T/26 T/64/72 T/26 4/0 T/19 – T/68 T/19 T/68 4/0
T/30 – T/39/40 T/30 T/39/40 4/0 T/49 – T/33A T/49 T/33A 4/0
SW-MH22A –
T/140
SW-MH22A T/140 4/0
T/58B – T/30 T/58B T/30 4/0 T/64/72 –
T/58B T/64/72 T/58B 4/0
T/64/72 – T/49 T/64/72 T/49 4/0 *T/99 – B99
Main Sub T/99 B99 Main Sub *
* T/99 (69 kV / 4.16 kV) and cables to B99 Main Substation busway is owned by Ameren Illinois. Contractor shall coordinate with Ameren.
11) Panelboards & Disconnects (Inspection Only).
Building Equipment ID Volts Size
B14 14/EM 208/120 400
B14 14/MDP 208/120 1200
B14 ATS 208/120 400
B14 T/14 Chiller Disconnect 600 400 B19 T/19 Main Disconnect 600 400
B19 19/MDP1 208/120 400
B19 19/MDP2 208/120 225
B19 19/MDP3 208/120 400
B22 22/MDP-1 (Left) 480 400 B22 22/MDP-2 (Right) 480 400
B25 25/MDP 208/120 400
B33 33/DP-1 208/120 600
B33 33/DP-2 208/120 400
B49 49/MDP 208/120 400
B58 58/MDP 480/277 600
B58 58/H 480/277 400
B58 58/DP2 480/277 250
B58 58/DP1 480/277 600
B58 Chiller Compressor 1&2 480 400 B58 Chiller Compressor 3&4 480 600
B58 58/NE 240/120 400
B58 58/EP4 480/277 250
B60 60/MDP1 208/120 400
B60 60/MDP2 208/120 225
B64 64/MDP 208/120 600
B68 68/MDP1 208/120 200
B93 93/MDP 208/120 400
B93 T1 Primary Disconnect 600 200 B93 T1 Secondary Disconnect 240 60 B98 Main Switchgear 480/277 3000
B98 98/DP-C 480/277 400
B98 98/EDP1 480/277 400
B98 98/EDP2 480/277 400
B98 98/ATS-1 480 400
B98 98/ATS-2 480 400
B98 98/ATS-3 480 400
B98 98/EMCC1 480 600
B98 98/EMCC2 480 600
B98 98/MCC1 480 600
B98 98/MCC2 480 600
B98 98/BPH 480/277 400
B98 98/2DP-A 480/277 400
B98 98/2DP-B 480/277 400
B98 98/DSB 480/277 1200
B98 98/2RP-A1 208/120 250
B98 98/2RP-A2 208/120 250
B98 98/2RP-A3 208/120 250
B98 98/2RP-B1 208/120 250
B98 98/2RP-B2 208/120 250
B98 98/2RP-B3 208/120 250
B98 2DP-A T1 Sec Disconnect 240 400 B98 2DP-B T2 Sec Disconnect 240 400 B98 Trane Ckt #1 Disconnect 480 800 B98 Trane Ckt #2 Disconnect 480 400
B101 101/EMCCA 480 N/L
B101 101/EMCCB 480 N/L
B101 101/MCC 480 N/L
B101 101/MDP-1 480/277 600
B101 101-1 480/277 800 B101 Main Switchgear 480/277 2000 B101 101/A1-A 208/120 250 B101 101/B1-A 208/120 250 B101 101/C1-A 208/120 250 B101 101/F1 480 800 B101 T1 Primary Disconnect 480 200 B101 T1 Sec Disconnect 240 100 B101 T2 Primary Disconnect 480 200 B101 T2 Sec Disconnect 240 100 B101 T3 Primary Disconnect 480 200 B101 T3 Sec Disconnect 240 100 B101 T4 Primary Disconnect 480 200 B101 T4 Sec Disconnect 240 100 B101 T5 Disconnect 480 200 B101 T6 Disconnect 480 200 B102 Main Switchboard 480/277 2000
B102 102/PA 480/277 600
B102 102/PAA 480/277 400
B102 Panel PB 480/277 600 B102 102/J5 208/120 250 B102 102/J6 208/120 250 B102 102/J7 208/120 250
B102 102/SK3 208/120 400
B102 102/EMA2 480 400
B102 102/PP1 480/277 400
B102 102/PP2 480/277 400
B102 102/PP3 480/277 400
B102 102/PP4 480/277 400
B102 102/A 208/120 250 B102 102/B 208/120 250
B102 102/AB 208/120 250
B102 102/C 208/120 250
B102 102/CD 208/120 250
B102 102/E 208/120 250 B102 102/F 208/120 250
B102 102/EF 208/120 250
B102 102/G 208/120 250 B102 102/H 208/120 250
B102 102/GH 208/120 250
B102 102/EAMLS 480/277 250
B102 102/EMACE 480/277 250
B102 102/EMBLS 480/277 250
B102 102/EMBCE 480/277 250
B102 102/MCC 480 N/L
B102 102/EMCC 480 N/L
B102 102/MDP1 480/277 800
B102 102/EDP 480 N/L
B103 Main Switchboard 480/277 1600
B103 103/PF 480/277 600
B103 103/MDP1 480/277 N/L
B103 103/EMCC 480/277 N/L
B103 103/MCC 480/277 600
B104 Main Switchboard 480/277 3200 B104 104/P2 480/277 600
B104 104/EMDP-2 480/277 400
B104 104/EMDP3 208/120 350
B125 125/MDP 208/120 800
B128/129 MDP1 208/120 800
B128/129 EMDP 208/120 400
B128 Panel A-1 208/120 400 B128 Panel A-2 208/120 400 B128 Panel EM-1 208/120 250 B128 Panel EM-2 208/120 250 B129 Panel A-1 208/120 400
B129 Panel A-2 208/120 400 B129 Panel EM-1 208/120 250 B129 Panel EM-2 208/120 250 B130 Panel EDP 208/120 250 B130 Panel NRP1 208/120 150 B130 Panel NRP2 208/120 150 B130 Panel NRP3 208/120 150 B130 Panel ELRP 208/120 150 B130 Panel EPP1 208/120 100 B130 Panel EPP2 208/120 150 B131 Panel EDP 208/120 250 B131 Panel NRP1 208/120 150 B131 Panel NRP2 208/120 150 B131 Panel NRP3 208/120 150 B131 Panel ELRP 208/120 150 B131 Panel EPP1 208/120 100 B131 Panel EPP2 208/120 150
B132 MDP 208/120 600
B133 MDP 208/120 600
B211 211-BP0 480/277 200
B211 211-BP1 208/120 110
B212 212-BP0 480/277 200
B212 212-BP1 208/120 110
B214 214-BP0 480/277 150
B214 214-BP1 208/120 110
B216 216-BP0 480/277 150
B216 216-BP1 208/120 110
B140 AHU-1 208 100
B140 AHU-2 208 60
B140 CU-1A 208 100
B140 CU-1B 208 100
B140 CU-2 208 100
B140 BPP-1 208 100
B140 HU-1A 208 100
B140 HU-1B 208 100
End of Attachment 1