S02. BID ISSUE SUBMISSION - DRAWINGS.pdf
PDF 37 MB Posted
- Solicitation number
- 36C25021B0032_1
About this file
This document outlines a federal contract opportunity for site preparation work. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 is soliciting bids to renovate and reconfigure spaces at the Louis Stokes Cleveland VA Medical Center to accommodate a new nuclear medicine SPECT/CT scanner. The project scope includes renovating and reconfiguring clinical services areas, with new mechanical, electrical, and plumbing work. The project value is between $500,000 and $1,000,000. Bids are due by May 20, 2021 and the NAICS code for this project is 236220. This opportunity is set aside for a Service-Disabled Veteran-Owned Small Business. All bidders must be verified in VETBIZ and registered in SAM to be eligible for award.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S02. Safety.docx | DOCX document | |
| S02. Site Visit Information.pdf | ||
| S02. Bid Opening Instructions.pdf | ||
| S02. Encl 1-2 ICRAMatrixofPrecautions.pdf | ||
| S02. VAMC Health Requirements.pdf | ||
| S02. Calculation of Self-Performed and Sub-Contracted Work.docx | DOCX document | |
| S02. RFI Form.pdf | ||
| S02. Solicitation 36C25021B0032_1.pdf | ||
| S02. BID ISSUE SUBMISSION - SPECIFICATIONS.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/PLUMBING
ENGINEERING:
HEAPY
1422 EUCLID AVE STE 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
C U s e rs
\r ic h \D o c u m e n ts
\V A
S P
E C
T C
T ri c h
Q X
K S
.r v t
/2
/2
:0
:2
P
M
BID ISSUE SUBMISSION
GI-1
TITLE SHEET & DRAWING INDEX PROVIDE SITE PREP FOR SPECT
CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH
541-CSI-130
4.23.21 CJK JAW
DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER - WADE PARK
PROVIDE SITE PREP FOR SPECT CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH 44106
PROJECT NO. 541-CSI-130
Cleveland Veterans Affairs Medical Center
CODE INFORMATION:
I. PROJECT LOCATION: CLEVELAND VETERANS AFFAIRS MEDICAL CENTER
10701 EAST BLVD.
CLEVELAND, OHIO
II. DESCRIPTION & USER GROUP CLASSIFICATION OF BUILDING
A. NATURE OF PROJECT: INTERIOR RENOVATIONS OF EXISTING BASEMENT LEVEL NUCLEAR
MEDICINE DEPARTMENT TO INSTALL A NEW SPECT CT SCANNER
B. DESIGN CODES: 2018 NFPA LIFE SAFETY CODE 101, IBC 2018
C. USE GROUP: I-2 HEALTH CARE - NO CHANGE PROPOSED
D. CONSTRUCTION TYPE: TYPE I-332, IB - NON-COMBUSTIBLE, PROTECTED
FIRE RATED CONSTRUCTION (LSC A.8.2.1.1)
EXTERIOR BEARING WALLS 3 HRS
INTERIOR BEARING WALLS 3 HRS
STRUCTURAL COLUMNS 3 HRS (SUPPORTING > 1 FLOOR)
2 HRS (SUPPORTING 1 FLOOR ONLY)
2 HRS (SUPPORTING ROOF ONLY)
BEAMS, GIRDERS, TRUSSES 3 HRS (SUPPORTING > 1 FLOOR, COLS., OR BEARING
WALLS)
FLOOR-CEILING ASSEMBLIES 2 HRS
ROOF-CEILING ASSEMBLIES 1-1/2 HRS
INTERIOR NON-BEARING WALLS 0 HRS
EXTERIOR NON-BEARING WALLS 0 HRS
WALL ASSEMBLIES
EXIT ACCESS CORRIDOR WALLS 0 HR SMOKE PARTITIONS
E. PROJECT AREA: BASEMENT LEVEL: 1,160 SF
FIRST FLOOR: 9 SF
TOTAL: 1,169 SF
F. PROJECT AREA OCCUPANT LOAD: BASEMENT LEVEL: 12
G. FIRE PROTECTION: EXISTING BUILDING FULLY SPRINKLED. MODIFICATIONS AS
REQUIRED PER NEW IMPROVEMENTS PROPOSED
DRAWING INDEX:
BID ISSUE SUBMISSION
4.23.21
GI-1 TITLE SHEET & DRAWING INDEX
ARCHITECTURAL
LS-0.1A PHASE I BASEMENT LEVEL LIFE SAFETY PLAN
LS-0.1B PHASE II BASEMENT LEVEL LIFE SAFETY PLAN
AS-X-0.1 BASEMENT LEVEL - EXISTING CONDITIONS PLAN
AS-XC-0.1 BASEMENT LEVEL - EXISTING CEILING PLAN
AS-D-0.1A BASEMENT LEVEL - PHASE I DEMOLITION PLAN
AS-D-0.1B BASEMENT LEVEL - PHASE II DEMOLITION PLAN
AS-DC-0.1A BASEMENT LEVEL - PHASE I CEILING DEMOLITION PLAN
AS-DC-0.1B BASEMENT LEVEL - PHASE II CEILING DEMOLITION PLAN
AS-0.1A BASEMENT LEVEL - PHASE I PROPOSED IMPROVEMENT PLAN
AS-0.1B BASEMENT LEVEL - PHASE II PROPOSED IMPROVEMENT PLAN
AS-1.0 FIRST AND SECOND FLOOR EXHAUST SHAFT/DUCT ROUTING PLANS
AS-C-0.1A BASEMENT LEVEL - PHASE I REFLECTED CEILING PLAN
AS-C-0.1B BASEMENT LEVEL - PHASE II REFLECTED CEILING PLAN
AS-300 ENLARGED PLANS AND INTERIOR ELEVATIONS
AS-600 WALL TYPES, DOOR SCHEDULE, AND MILLWORK DETAILS
AS-700 FINISH PLAN AND SCHEDULE
MECHANICAL/HVAC
M-001 LEGEND AND INDEX OF DRAWINGS
MD-10B PARTIAL BASEMENT FLOOR PLAN - DEMO
MH-10B PARTIAL SUB-BASEMENT AND BASEMENT PLANS - HVAC
MH-101 PARTIAL FIRST FLOOR AND SECOND FLOOR - NEW
M-501 DETAILS
M-502 DETAILS
M-601 SCHEDULES
M-901 CONTROLS
M-902 CONTROLS
TECHNOLOGY
T-001 TECHNOLOGY LEGEND
T-D-0.1 DEMOLITION PLAN - TECHNOLOGY
T-T-0.1 NEW WORK PLAN - TECHNOLOGY
T-500 TECHNOLOGY DETAILS
T-501 SECURITY DETAILS
T-700 ENLARGED SIGNALS CLOSET PLAN
PLUMBING
P-001 LEGEND AND INDEX OF DRAWINGS
P-D-0.1A PARTIAL SUB BASEMENT PLUMBING DEMO PLAN - PHASE I
P-D-0.2A PARTIAL BASEMENT PLUMBING DEMO PLAN - PHASE I
P-D-0.1B PARTIAL SUB BASEMENT PLUMBING DEMO PLAN - PHASE II
P-D-0.2B PARTIAL BASEMENT PLUMBING DEMO PLAN - PHASE II
P-P-0.1A PARTIAL SUB BASEMENT PLUMBING PLAN - PHASE I
P-P-0.2A PARTIAL BASEMENT PLUMBING PLAN - PHASE I
P-P-0.1B PARTIAL SUB BASEMENT PLUMBING PLAN - PHASE II
P-P-0.2B PARTIAL BASEMENT PLUMBING PLAN - PHASE II
P-600 SANITARY RISER DIAGRAM
P-700 SCHEDULES AND DETAILS
FIRE PROTECTION
FP-F-0.1 PARTIAL BASEMENT PLAN - FIRE SUPPRESSION
ELECTRICAL
E-001 LEGEND AND ABBREVIATIONS
ED-0.1A ELECTRICAL BASEMENT - DEMOLITION PLAN - PHASE I
ED-0.1B ELECTRICAL BASEMENT - DEMOLITION PLAN - PHASE 2
EL-0.1A ELECTRICAL BASEMENT - LIGHTING PLAN - PHASE I
EL-0.1B ELECTRICAL BASEMENT - LIGHTING PLAN - PHASE 2
EL-1.1B ELECTRICAL FIRST FLOOR - LIGHTING PLAN - PHASE 2
EP-0.1A ELECTRICAL BASEMENT - POWER PLAN - PHASE 1
EP-0.1B ELECTRICAL BASEMENT - POWER PLAN - PHASE 2
EP-2.1B ELECTRICAL ROOF - POWER PLAN - PHASE 2
E-501 ELECTRICAL DETAILS
E-601 PANEL SCHEDULES
SCOPE OF WORK AREA
STRUCTURAL
SS-001 GENERAL NOTES - PHASE II
SS-100 BASEMENT LEVEL - PHASE II PROPOSED STRUCTURAL IMPROVEMENT
PLAN & DETAILS
BASEMENT LEVEL
N.T.S.
REFERENCE DRAWINGS
1-Q1 SIEMENS REFERENCE DRAWING A-101 ARCHITECTURAL EQUIPMENT PLAN
1-Q2 SIEMENS REFERENCE DRAWING A-102 SAFETY/SERVICE CLEARANCE PLAN
1-Q3 SIEMENS REFERENCE DRAWING S-101 STRUCTURAL FLOOR PLAN
1-Q4 SIEMENS REFERENCE DRAWING S-501 FLOOR REQUIREMENTS
1-Q5 SIEMENS REFERENCE DRAWING E-101 ELECTRICAL RACEWAY PLAN
1-Q6 SIEMENS REFERENCE DRAWING E-102 ELECTRICAL DIMENSION PLAN
Revisions: Date:
65% CD's SUBMISSION 8.7.20
100% CD's SUBMISSION 10.13.20
FINAL CD's SUBMISSION 11.19.20
BID ISSUE SUBMISSION 4.23.21
CG-1 CG-1
CG-1CG-1
CG-1
FE
F E
FE
FE
F E
FE
F E
F E
F E
F E
FE
F E
FE
PROJECT SCOPE BOUNDARY
3' - 0"
GC ACCESS
DOOR
EXISTING EGRESS PATHS TO REMAIN
UNAFFECTED DURING CONSTRUCTION
E
Injection Room
BC461
Nuc Med
BC475
Future Thyroid Uptake
BC448
EKG
BC436Storage
BC432
EKG
BC434
OFFICE
BC446
Rad Waste
BC446A
Nuc Med
BC474
Storage
BC431
Control Room
BC475A
Corridor
B-D311
Stair 5
E03
Conference
B-D352
Corridor
BC400C
Corridor
BC1087
Storage
BB427A
E.C.
G08A
Paint Shop
G08
Stair 6
E25
Corridor
CG01
Repair Station 2
BC490M
Repair Station 1
BC490N
Repair Station 3
BC490L
Ref. & Files
BC490O
Supv Office
BC1088
Repair Station
BC490B
Repair Station
BC490C
Repair Station
BC490E
Receiving & Cleaning
BC490A Repair Station 6
BC490I
Womens Showers
BC482A
Repair Station 9
BC490F
Repair Station 8
BC490G
Repair Station 7
BC490H
Bio Med
BC1089
Repair Station 5
BC490J
Repair Station 4
BC490K
Nuc Med CT
BC1090
Reading
BC1091
Soiled
BC1092
Patient Holding
BC1093
Holter
BC1094
Toilet
BC1095
Nuc Med CT
BC1096
Electrical
BC1097
Nuc Med
BC1098
Patient Holding
BC1099
Echo Stress
BC447
Office
BB428
Office
BB426
Storage
BB418
Stair #8
BB420
Service Room
BB419
Comm
BB472
Clos
BB471
Electrical
BB473
Office
BB468
Office
BB466
Office
BB482
Office
BB467
Office
BB483
Corridor
BC400B
Clean Storage
BC425
Staff
BC1100
Diabetes Coordinator
BC424
Echo Stress
BC445
Fes. Treatment
BC420
Corridor
BC400A
Diabetes Education
BC423
Dietitian
BC422
Dietitian
BC421
Conference Room
BC410
Eng. Office
BC444
Reading Room
BC443
Cardiology Tech
BC442
Corridor
BC400
Corridor
BC440
Corridor
BC430
Staff
BC441
Echo
BC437
Echo
BC435
Echo
BC433
Reception
BC471A
Work
BC1101
Corridor
BC470A
Interview
BC1102
Toilet
BC1103
Waiting
BC1104
Biohazard Storage
E26
Mens Restroom
BC481B
Corridor
BC470B
Womens Locker Room
BC1105
Mens Locker Room
BC1106
Corridor
CE03
Service Lobby
BC404
Tech Supv
BC311
IP Chief
BC312
Alcove
BC313
Staff Entry
BC314
ELEC.
BC315
Assistant Chief
BC316
Secretary & Waiting
BC317
Chief Pharm.
BC318
Admin. Assist.
BC319
Mainstreet Corridor
BC402
Closet
BB375A
Laminating
Room
BB375
Machine Room
BB374
Cad Room
BB373
Corridor
BC401
Tech Area
BB372
Paster Room
BB376
Lobby
BD300C
Mechanical
BC310A
Elevator Lobby
BC403
Office
BB427
Control
BC1107
Corridor
CG02
Vestibule
B-D401A
Storage
B-D401B
Office
BB465
Office
BB429
Corridor
BB530
Office
BB481
Repair Station
BC490D
6'
6' - 0"
MAINTAIN 6'-0"
MIN. CLEAR IN
CORRIDORS, TYP.
GC ACCESS
DOORNORTH DOOR LEAF SHALL BE
CLOSED AND NOT IN USE.
SOUTH LEAF SHALL BE ON
HOLD-OPENS AT ALL TIMES
LIFE SAFETY LEGEND:
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR
EXISTING/NEW 2 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED SMOKE BARRIER
EXISTING/NEW O HOUR RATED SMOKE PARTITION
E EXIT
FE
FIRE EXTINGUISHER
EXIT SIGN LOCATION
LIFE SAFETY GENERAL NOTES:
1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. BUILDING IS CLASSIFIED AS AN "EXISTING
HEALTH CARE OCCUPANCY" PER NFPA 101 2018.
2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY
DRAWINGS
3. CONTRACTOR TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS WHICH, DUE TO CONSTRUCTION, TEMPORARILY DO NOT DEPICT EXIT PATHS AND/OR ARE IN THE WAY OF TEMPORARY CONSTRUCTION BARRIERS (TYP. OF ALL EXIT SIGNS IN OR BEYOND PROJECT AREA)
4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.
5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, GC SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW
PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE
COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD. GC SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS. FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, GC SHALL
PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING
6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE
FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)
PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT
ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR. GC SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH
THE OPENING SIZE AS DICTATED BY THE ASSEMBLY.
7. TEMPORARY FIRE ALARMS IN CONSTRUCTION AREAS: GC SHALL PROVIDE TEMPORARY FIRE ALARMS IN ALL CONSTRUCTION AREAS THROUGHOUT THE CONSTRUCTION DURATION UNTIL SUCH TIME THAT
NEW FIRE ALARM SYSTEM DEVICES ARE INSTALLED, TESTED, AND IN FULL OPERATION. HEAT
DETECTION DEVICES SHALL BE UTILIZED AND SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND COORDINATED THROUGH THE VA ELECTRICAL SHOP. GC SHALL COORDINATE WITH VA SAFETY DEPARTMENT FOR ALL TEMPORARY FIRE ALARM INSTALLATIONS TO ENSURE COMPLIANCE
WITH SAFETY STANDARDS.
HAZARDOUS ROOM
EXISTING/NEW 2 HOUR RATED SMOKE BARRIER
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"
TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY
BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE
APPROVED BY THE COR.
SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE
SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.
PROJECT SCOPE BOUNDARY
SOLID WHITE AREA INDICATES
CONSTRUCTION AREA WITHIN SCOPE
OF WORK
GRAY HATCHED AREA INDICATES AREA
OUTSIDE OF SCOPE OF WORK. ALL
AREAS SHALL BE CONSIDERED
OCCUPIED AND IN USE BY THE VA
PHASING DURATION & CONSTRUCTION TIMEFRAMES:
THE SCOPE OF WORK DESCRIBED IN THIS DRAWING PACKAGE REPRESENTS A MULTI-PHASED PROJECT THAT MUST BE UNDERTAKEN SIMULTANEOUSLY WITH THE FULL OCCUPANCY AND FUNCTION OF THE EXISTING
HOSPITAL. THE PROPOSED PHASING DURATING PLAN IS AS FOLLOWS:
PRECONSTRUCTION: 60 DAYS
PHASE I: 40 DAYS
VA ACTIVATION OF PHASE I: 20 DAYS
PHASE II: 90 DAYS
TOTAL TIMEFRAME: 210 DAYS
THE FOLLOWING CONSTRUCTION SCHEDULE TIMEFRAMES SHALL APPLY TO THIS PROJECT:
CONSTRUCTION ACTIVITIES ARE PERMITTED TO OCCUR DURING REGULAR SHIFT HOURS. TEMPORARY CONSTRUCTION BARRIERS MUST BE FULLY IN PLACE AND INTACT DURING CONSTRUCTION. CONTRACTORS, HOWEVER, SHALL NOT BE PERMITTED TO HAVE MATERIALS AND DELIVERIES DELIVERED OR TAKEN AWAY DURING REGULAR SHIFT HOURS, AND MUST COORDINATE SUCH ACTIVITIES WITH STAFF AND VA COR.
THE TIMEFRAMES IDENTIFIED ABOVE ARE IN REFERENCE TO NORMAL CONSTRUCTION ACTIVITIES AND, UNLESS
APPROVED BY VA COR, SHALL NOT APPLY TO WORK INCLUDING BUT NOT LIMITED TO:
• UTILITY SHUTDOWNS
• EXISTING MEP SYSTEM SHUTDOWNS
• WORK IN PUBLIC CORRIDORS/WAITING AREAS
• CUTTING OF FLOOR OPENINGS IN THE EXISTING BUILDING
• WORK OUTSIDE OF TEMPORARY CONSTRUCTION PARTITIONED AREAS, INCLUDING ACCESS OF CEILING
PLENUM SPACES IN FLOORS ABOVE OR BELOW CONSTRUCTION AREAS, AND REPLACEMENT OF
EXISTING FINISHES
• CONSTRUCTION OF TEMPORARY CONSTRUCTION BARRIERS
• ABOVE-CEILING WORK IN ROOMS OUTSIDE THE PROJECT SCOPE AREA
WORK IDENTIFIED ABOVE SHALL OCCUR EITHER IN THE EVENING SHIFT, OR IF REQUIRED BY THE VA, ON WEEKENDS. ALL CONSTRUCTION ACTIVITIES AND SCHEDULES MUST BE REVIEWED AND APPROVED BY VA COR.
REFER TO SPEC DIVISION 01 FOR GENERAL PROJECT REQUIREMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/PLUMBING
ENGINEERING:
HEAPY
1422 EUCLID AVE STE 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
C U s e rs
\r ic h \D o c u m e n ts
\V A
S P
E C
T C
T ri c h
Q X
K S
.r v t
/2
/2
:0
:3
P
M
BID ISSUE SUBMISSION
LS-0.1A
PHASE 1 BASEMENT LEVEL LIFE SAFETY
PLAN
PROVIDE SITE PREP FOR SPECT
CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH
541-CSI-130
4.23.21 CJK JAW
NORTH
SCALE: 1/8" = 1'-0"
BASEMENT LEVEL LIFE SAFETY PLAN - PHASE I
Revisions: Date:
65% CD's SUBMISSION 8.7.20
100% CD's SUBMISSION 10.13.20
C G
-1C G
-1
C G
-1 C
G -1
CG-1 CG-1
CG-1CG-1
CG-1
CG-1
Corridor
B-D311
Stair 5
E03
Conference
B-D352
Corridor
BC400C
Corridor
BC460
Storage
BB427A
E.C.
G08A
Paint Shop
G08
Stair 6
E25
Corridor
CG01
Repair Station 2
BC490M
Repair Station 1
BC490N
Repair Station 3
BC490L
Ref. & Files
BC490O
Supv Office
BC491
Repair Station
BC490B
Repair Station
BC490C
Repair Station
BC490E
Receiving & Cleaning
BC490A Repair Station 6
BC490I
Womens Showers
BC482A
Repair Station 9
BC490F
Repair Station 8
BC490G
Repair Station 7
BC490H
Bio Med
BC490
Repair Station 5
BC490J
Repair Station 4
BC490K
Nuc Med CT
BC468
Reading
BC467
Soiled
BC466
Patient Holding
BC464
Holter
BC449
Toilet
BC462
Nuc Med CT
BC453
Electrical
BC479
Nuc Med
BC452
Patient Holding
BC463
Echo Stress
BC447
Office
BB428
Office
BB426
Storage
BB418
Stair #8
BB420
Service Room
BB419
Comm
BB472
Clos
BB471
Electrical
BB473
Office
BB468
Office
BB466
Office
BB482
Office
BB467
Office
BB483
Corridor
BC400B
Clean Storage
BC425
Staff
BC451
Diabetes Coordinator
BC424
Echo Stress
BC445
Fes. Treatment
BC420
Corridor
BC400A
Diabetes Education
BC423
Dietitian
BC422
Dietitian
BC421
Conference Room
BC410
Eng. Office
BC444
Reading Room
BC443
Cardiology Tech
BC442
Corridor
BC400
Corridor
BC440
Corridor
BC430
Staff
BC441
Echo
BC437
Echo
BC435
Echo
BC433
Reception
BC471A
Work
BC471
Corridor
BC470A
Interview
BC473
Toilet
BC472
Waiting
BC470
Biohazard Storage
E26
Mens Restroom
BC481B
Corridor
BC470B
Womens Locker Room
BC482
Mens Locker Room
BC481
Corridor
CE03
Service Lobby
BC404
Tech Supv
BC311
IP Chief
BC312
Alcove
BC313
Staff Entry
BC314
ELEC.
BC315
Assistant Chief
BC316
Secretary & Waiting
BC317
Chief Pharm.
BC318
Admin. Assist.
BC319
Mainstreet Corridor
BC402
Closet
BB375A
Laminating
Room
BB375
Machine Room
BB374
Cad Room
BB373
Corridor
BC401
Tech Area
BB372
Paster Room
BB376
Lobby
BD300C
Mechanical
BC310A
Elevator Lobby
BC403
Office
BB427
Control
BC454
Corridor
CG02
Vestibule
B-D401A
Storage
B-D401B
Office
BB465
Office
BB429
Corridor
BB530
Office
BB481
Repair Station
BC490D
Nuc Med
BC475
Control Room
BC475A
Injection Room
BC461
Thyroid Uptake
BC448
OFFICE
BC446
EKG
BC436
Rad Waste
BC432A
Hot Lab
BC432
Storage
BC431
Nuc Med
BC474
FE
F E
FE
FE
F E
FE
F E
F E
F E
F E
FE
F E
FE
PROJECT SCOPE BOUNDARY
3' - 0"
CONSTRUCTION
ENTRY
Control Room
BC474A
6' - 0"
6'
EXISTING EGRESS PATHS TO REMAIN
UNAFFECTED DURING CONSTRUCTION
E
CONSTRUCTION
ENTRY
MAINTAIN 6'-0"
MIN. CLEAR IN
CORRIDORS, TYP.
4' - 9"
LIFE SAFETY LEGEND:
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR
EXISTING/NEW 2 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED FIRE BARRIER
EXISTING/NEW 1 HOUR RATED SMOKE BARRIER
EXISTING/NEW O HOUR RATED SMOKE PARTITION
E EXIT
FE
FIRE EXTINGUISHER
EXIT SIGN LOCATION
LIFE SAFETY GENERAL NOTES:
1. SEE COVER SHEET FOR APPLICABLE CODE INFORMATION. BUILDING IS CLASSIFIED AS AN "EXISTING
HEALTH CARE OCCUPANCY" PER NFPA 101 2018.
2. PROJECT SCOPE LINE IS INDICATED FOR GENERAL INTENT ONLY. CONTRACTOR WILL COMPLETE ALL WORK REGARDLESS IF IT IS LOCATED OUTSIDE OF PROJECT SCOPE AREA AS INDICATED ON ANY
DRAWINGS
3. CONTRACTOR TO COVER OR ALTER EXIT SIGNS, OR TEMPORARILY RELOCATE EXISTING EXIT SIGNS WHICH, DUE TO CONSTRUCTION, TEMPORARILY DO NOT DEPICT EXIT PATHS AND/OR ARE IN THE WAY OF TEMPORARY CONSTRUCTION BARRIERS (TYP. OF ALL EXIT SIGNS IN OR BEYOND PROJECT AREA)
4. TRAVEL DISTANCES OVER 200' WILL REQUIRE INTERIM LIFE SAFETY MEASURES. COORDINATE WITH VA.
5. EXISTING FLOOR SLABS ARE 2 HR RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, GC SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW
PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE
COMPROMISED, AND SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD. GC SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS. FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, GC SHALL
PATCH CONC. SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING
6. PROVIDE FIRESTOPPING AT ALL PENETRATIONS THROUGH NEW AND EXISTING FIRE/SMOKE RATED BARRIER WALLS AND FLOOR SLABS TO COMPLY WITH THE REQUIRED BARRIER RATINGS. PROVIDE
FIRESTOPPING AROUND TEN (10) PENETRATIONS LESS THAN 6 SQUARE INCHES AND FOUR (4)
PENETRATIONS BETWEEN 16 AND 36 SQUARE INCHES TO COMPLY WITH REQUIRED RATING NOT
ASSOCIATED WITH NEW WORK. LARGER OPENINGS SHALL BE BROUGHT TO THE ATTENTION OF THE COR. GC SHALL SUBMIT UL LISTED METHODS FOR PATCHING ALL FIRE BARRIERS THAT MEET THE MINIMUM FIRE RATING REQUIREMENTS OF THE PENETRATING BARRIER AND ARE IN COMPLIANCE WITH
THE OPENING SIZE AS DICTATED BY THE ASSEMBLY.
7. TEMPORARY FIRE ALARMS IN CONSTRUCTION AREAS: GC SHALL PROVIDE TEMPORARY FIRE ALARMS IN ALL CONSTRUCTION AREAS THROUGHOUT THE CONSTRUCTION DURATION UNTIL SUCH TIME THAT
NEW FIRE ALARM SYSTEM DEVICES ARE INSTALLED, TESTED, AND IN FULL OPERATION. HEAT
DETECTION DEVICES SHALL BE UTILIZED AND SHALL BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM AND COORDINATED THROUGH THE VA ELECTRICAL SHOP. GC SHALL COORDINATE WITH VA SAFETY DEPARTMENT FOR ALL TEMPORARY FIRE ALARM INSTALLATIONS TO ENSURE COMPLIANCE
WITH SAFETY STANDARDS.
HAZARDOUS ROOM
EXISTING/NEW 2 HOUR RATED SMOKE BARRIER
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO "TEMPORARY CONSTRUCTION BARRIER"
TYPICAL PARTITION DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY
BARRIERS SHALL BE PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE
APPROVED BY THE COR.
SEPARATE ALL OCCUPIED AREAS OF THE RENOVATION AREA BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS BUILT TO THE DECK ABOVE, AND FOR AREAS WITHOUT ACTIVE
SPRINKLER PROTECTION ON BOTH SIDES, THE PARTITION SHALL BE ONE-HOUR FIRE RATED.
PROJECT SCOPE BOUNDARY
SOLID WHITE AREA INDICATES
CONSTRUCTION AREA WITHIN SCOPE
OF WORK
GRAY HATCHED AREA INDICATES AREA
OUTSIDE OF SCOPE OF WORK. ALL
AREAS SHALL BE CONSIDERED
OCCUPIED AND IN USE BY THE VA
PHASING DURATION & CONSTRUCTION TIMEFRAMES:
THE SCOPE OF WORK DESCRIBED IN THIS DRAWING PACKAGE REPRESENTS A MULTI-PHASED PROJECT THAT MUST BE UNDERTAKEN SIMULTANEOUSLY WITH THE FULL OCCUPANCY AND FUNCTION OF THE EXISTING
HOSPITAL. THE PROPOSED PHASING DURATING PLAN IS AS FOLLOWS:
PRECONSTRUCTION: 60 DAYS
PHASE I: 40 DAYS
VA ACTIVATION OF PHASE I: 20 DAYS
PHASE II: 90 DAYS
TOTAL TIMEFRAME: 210 DAYS
THE FOLLOWING CONSTRUCTION SCHEDULE TIMEFRAMES SHALL APPLY TO THIS PROJECT:
CONSTRUCTION ACTIVITIES ARE PERMITTED TO OCCUR DURING REGULAR SHIFT HOURS. TEMPORARY CONSTRUCTION BARRIERS MUST BE FULLY IN PLACE AND INTACT DURING CONSTRUCTION. CONTRACTORS, HOWEVER, SHALL NOT BE PERMITTED TO HAVE MATERIALS AND DELIVERIES DELIVERED OR TAKEN AWAY DURING REGULAR SHIFT HOURS, AND MUST COORDINATE SUCH ACTIVITIES WITH STAFF AND VA COR.
THE TIMEFRAMES IDENTIFIED ABOVE ARE IN REFERENCE TO NORMAL CONSTRUCTION ACTIVITIES AND, UNLESS
APPROVED BY VA COR, SHALL NOT APPLY TO WORK INCLUDING BUT NOT LIMITED TO:
• UTILITY SHUTDOWNS
• EXISTING MEP SYSTEM SHUTDOWNS
• WORK IN PUBLIC CORRIDORS/WAITING AREAS
• CUTTING OF FLOOR OPENINGS IN THE EXISTING BUILDING
• WORK OUTSIDE OF TEMPORARY CONSTRUCTION PARTITIONED AREAS, INCLUDING ACCESS OF CEILING
PLENUM SPACES IN FLOORS ABOVE OR BELOW CONSTRUCTION AREAS, AND REPLACEMENT OF
EXISTING FINISHES
• CONSTRUCTION OF TEMPORARY CONSTRUCTION BARRIERS
• ABOVE-CEILING WORK IN ROOMS OUTSIDE THE PROJECT SCOPE AREA
WORK IDENTIFIED ABOVE SHALL OCCUR EITHER IN THE EVENING SHIFT, OR IF REQUIRED BY THE VA, ON WEEKENDS. ALL CONSTRUCTION ACTIVITIES AND SCHEDULES MUST BE REVIEWED AND APPROVED BY VA COR.
REFER TO SPEC DIVISION 01 FOR GENERAL PROJECT REQUIREMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/PLUMBING
ENGINEERING:
HEAPY
1422 EUCLID AVE STE 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
C U s e rs
\r ic h \D o c u m e n ts
\V A
S P
E C
T C
T ri c h
Q X
K S
.r v t
/2
/2
:0
:4
P
M
BID ISSUE SUBMISSION
LS-0.1B
PHASE 2 BASEMENT LEVEL LIFE SAFETY
PLAN
PROVIDE SITE PREP FOR SPECT
CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH
541-CSI-130
4.23.21 CJK JAW
NORTH
SCALE: 1/8" = 1'-0"
BASEMENT LEVEL LIFE SAFETY PLAN - PHASE II
Revisions: Date:
65% CD's SUBMISSION 8.7.20
100% CD's SUBMISSION 10.13.20
CG-1
25 26 27
Q
RR
TT
VV
SS
UU
R1 R1
Injection Room
BC461Nuc Med
BC475
Thyroid Uptake
BC448
Corridor
BC430
EKG
BC436
Storage
BC432
EKG
BC434
Hot Lab
BC446
Rad Waste
BC446A
Nuc Med
BC474
Injection Room
BC431
Corridor
BC470B
Control Room
BC475A
Corridor
BC440
Corridor
BC460
DASHED RECTANGLE INDICATES SEPARATE
CONSTRUCTION PROJECT AREA "VA SITE
PREP FOR INTEVO" WHICH IS CURRENTLY
UNDER CONSTRUCTION. IMPROVEMENT
PLAN FOR SEPARATE PROJECT IS SHOWN
AS EXISTING CONDITIONS FOR THE
PURPOSES OF THIS PROJECT
CV
MG
MG
MG
CV
MG
FE CR
CR
CR CR CR
CR
CR
WALL-MTD. TEST
TUBE RACK
MIRROR
ELEC. PANEL
CONDUIT
CHASE
MOBILE STORAGE
RACK
FE
CR
CT SCANNER
LEAD RADIOACTIVE
WASTE CABINETS
NOTE: ALL WALLS IN
ROOM ARE LEAD-LINED
NOTE: ALL WALLS IN
ROOM ARE LEAD-LINED
NOTE: ALL
WALLS IN ROOM
ARE LEAD-LINED
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.
ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW
TO MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS
REQUIRED.
NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED
BY THE OWNER UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY
POINTS.
CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS.
PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE.
DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"
ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.
ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.
REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS) AND PATCH ADJACENT
WALLS TO MATCH EXISTING.
ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.
DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.
ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS
OTHERWISE APPROVED BY THE COR.
EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, GC SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND GC SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD. GC SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS. FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, GC SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED INFILL FIRESTOP ASSEMBLY WHEN APPROVED
BY THE COR.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
SYMBOL LEGEND:
INDICATES EXISTING DOOR
INDICATES NEW DOOR
EXISTING WALLS TO REMAIN
NEW WALLS
WALLS TO BE REMOVED FULL HEIGHT U.N.O.
DASHED LINES INDICATE ITEMS TO BE DEMOLISHED
HATCHED AREA OUTSIDE OF PROJECT SCOPE.
ACCESS INTO CEILING SPACES MAY OCCUR, REFER
TO MEP DWGS.
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO TEMPORARY CONSTRUCTION BARRIER
DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY BARRIERS SHALL BE
PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE APPROVED BY THE COR.
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR
GENERAL CONSTRUCTION PARTITION NOTE: WHERE TEMP. CONST. PARTITIONS CONFLICT
W/EX. LIGHTS/DIFFUSER/MEP ITEM LOCATIONS (INDICATED ON CEILING DEMOLITION PLANS), GC
SHALL COORD. W/COR TO EITHER TEMPORARILY REMOVE SUCH ITEMS, OR ADJUST LOCATION
OF CONST. PARTITION ACCORDINGLY TO ALLOW ITEMS TO REMAIN IN PLACE
EXISTING RECESSED MED. GAS CONTROL VALVE BOX
EXISTING MEDICAL AIR, VACUUM, OXYGEN WALL OUTLETS
EXISTING FIRE EXTINGUISHER CABINET
FE
CV
MG
CR
CARD READER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/PLUMBING
ENGINEERING:
HEAPY
1422 EUCLID AVE STE 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
C U s e rs
\r ic h \D o c u m e n ts
\V A
S P
E C
T C
T ri c h
Q X
K S
.r v t
/2
/2
:0
:2
P
M
BID ISSUE SUBMISSION
AS-X-0.1
BASEMENT LEVEL EXISTING CONDITIONS
PLAN
PROVIDE SITE PREP FOR SPECT
CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH
541-CSI-130
4.23.21 CJK JAW
NORTH
SCALE: 1/4" = 1'-0"
BASEMENT LEVEL EXISTING CONDITIONS PLAN
Revisions: Date:
65% CD's SUBMISSION 8.7.20
100% CD's SUBMISSION 10.13.20
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
9' - 3"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
8' - 0"A.F.F.
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
ACT-1
8' - 0"A.F.F.
Injection Room
BC461
Nuc Med
BC475
Thyroid Uptake
BC448
Corridor
BC430
EKG
BC436
Storage
BC432
EKG
BC434
Hot Lab
BC446
Rad Waste
BC446A
Nuc Med
BC474
Injection Room
BC431
Corridor
BC470B
Corridor
BC440
Corridor
BC460
Control Room
BC475A
DASHED RECTANGLE INDICATES SEPARATE
CONSTRUCTION PROJECT AREA "VA SITE
PREP FOR INTEVO" WHICH IS CURRENTLY
UNDER CONSTRUCTION. IMPROVEMENT
PLAN FOR SEPARATE PROJECT IS SHOWN
AS EXISTING CONDITIONS FOR THE
PURPOSES OF THIS PROJECT
EXISTING WALL-MTD
UV LIGHT FIXTURES
(4 TOTAL)
S
S
S S
S
S
S
S
S
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.
ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW
TO MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS
REQUIRED.
NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED
BY THE OWNER UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY
POINTS.
CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS.
PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE.
DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"
ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.
ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.
REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS) AND PATCH ADJACENT
WALLS TO MATCH EXISTING.
ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.
DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.
ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS
OTHERWISE APPROVED BY THE COR.
EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, GC SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND GC SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD. GC SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS. FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, GC SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED INFILL FIRESTOP ASSEMBLY WHEN APPROVED
BY THE COR.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
CEILING SYMBOL LEGEND:
EXISTING CEILING
TILE AREAS TO
REMAIN
NEW CEILING TILE
AREAS
GYPSUM BOARD
CEILING/SOFFIT -
PAINTED FINISH
2 X 2 LIGHT FIXTURE
RECESSED CAN
LIGHT FIXTURE
RETURN AIR
DIFFUSERS
SUPPLY AIR DIFFUSERS
SECURITY CAMERA
RECESSED SPEAKER
WIRELESS ACCESS POINT
SD SMOKE DETECTOR
DOMED MIRROR
ILLUMINATED EXIT SIGNAGE
CEILING-MTD. NURSE
CALL LIGHT
GENERAL NOTE: ACCESS INTO CEILINGS OUTSIDE OF TEMPORARY CONSTRUCTION BARRIERS AS A PART OF A CONSTRUCTION PHASE MAY OCCUR. REFER TO MEP DRAWINGS FOR ABOVE-CEILING DEMOLITION THAT OCCURS OUTSIDE THE TEMPORARY CONSTRUCTION BARRIER EXTENTS. GC SHALL PROVIDE TEMPORARY PROTECTION MEASURES IN SUCH AREAS TO PROTECT EXISTING CONDITIONS. COORD. REQUIREMENTS W/VA COR
S
2 X 4 LIGHT FIXTURE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/PLUMBING
ENGINEERING:
HEAPY
1422 EUCLID AVE STE 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
C U s e rs
\r ic h \D o c u m e n ts
\V A
S P
E C
T C
T ri c h
Q X
K S
.r v t
/2
/2
:0
:2
P
M
BID ISSUE SUBMISSION
AS-XC-0.1
BASEMENT LEVEL EXISTING CEILING PLAN PROVIDE SITE PREP FOR SPECT
CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH
541-CSI-130
4.23.21 CJK JAW
NORTH
SCALE: 1/4" = 1'-0"
BASEMENT LEVEL EXISTING CEILING PLAN
Revisions: Date:
65% CD's SUBMISSION 8.7.20
100% CD's SUBMISSION 10.13.20
CG-1
3' - 0"
ALIGN
ALIGN
CV
MG
MG
CV
MG
1A
4'
4"
REMOVE MIRROR
REMOVE AND
RELOCATE WALL-MTD.
TEST TUBE RACK
5A
DOOR TO BE SEALED
DURING PHASE I
CONSTRUCTION
TEMPORARY
CONTRACTOR
ENTRY DOOR
ALIGN
COORD. LOCATION OF TEMP.
BARRIER W/ EXISTING
CONTROL ROOM EQUIPMENT
ALIGN6
5' - 2 1/2"
TEMP GC DOOR
13A
3'-10" +/-
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.
ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW
TO MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS
REQUIRED.
NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED
BY THE OWNER UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY
POINTS.
CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS.
PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE.
DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"
ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.
ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.
REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS) AND PATCH ADJACENT
WALLS TO MATCH EXISTING.
ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.
DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.
ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS
OTHERWISE APPROVED BY THE COR.
EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, GC SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND GC SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD. GC SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS. FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, GC SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED INFILL FIRESTOP ASSEMBLY WHEN APPROVED
BY THE COR.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
SYMBOL LEGEND:
INDICATES EXISTING DOOR
INDICATES NEW DOOR
EXISTING WALLS TO REMAIN
NEW WALLS
WALLS TO BE REMOVED FULL HEIGHT U.N.O.
DASHED LINES INDICATE ITEMS TO BE DEMOLISHED
HATCHED AREA OUTSIDE OF PROJECT SCOPE.
ACCESS INTO CEILING SPACES MAY OCCUR, REFER
TO MEP DWGS.
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO TEMPORARY CONSTRUCTION BARRIER
DETAIL ON SHEET AS-600. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY BARRIERS SHALL BE
PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE APPROVED BY THE COR.
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR
GENERAL CONSTRUCTION PARTITION NOTE: WHERE TEMP. CONST. PARTITIONS CONFLICT
W/EX. LIGHTS/DIFFUSER/MEP ITEM LOCATIONS (INDICATED ON CEILING DEMOLITION PLANS), GC
SHALL COORD. W/COR TO EITHER TEMPORARILY REMOVE SUCH ITEMS, OR ADJUST LOCATION
OF CONST. PARTITION ACCORDINGLY TO ALLOW ITEMS TO REMAIN IN PLACE
EXISTING RECESSED MED. GAS CONTROL VALVE BOX
EXISTING MEDICAL AIR, VACUUM, OXYGEN WALL OUTLETS
EXISTING FIRE EXTINGUISHER CABINET
FE
CV
MG
CR
CARD READER
Injection Room
BC461
Nuc Med
BC475
Thyroid Uptake
BC448
Corridor
BC430
EKG
BC436
Storage
BC432
EKG
BC434
Hot Lab
BC446Rad Waste
BC446A
Nuc Med
BC474
Injection Room
BC431
Corridor
BC470B
Control Room
BC475A
Corridor
BC440
Corridor
BC460
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
MECHANICAL/PLUMBING
ENGINEERING:
HEAPY
1422 EUCLID AVE STE 1162
CLEVELAND, OH 44115
P. 216.862.5846
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
ELECTRICAL ENGINEERING:
FFE, INC.
110 BOGGS LN, SUITE 170
SPRINGDALE, OH 45246
P. 513.522.0956
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
C U s e rs
\r ic h \D o c u m e n ts
\V A
S P
E C
T C
T ri c h
Q X
K S
.r v t
/2
/2
:0
:0
P
M
BID ISSUE SUBMISSION
AS-D-0.1A
BASEMENT LEVEL- PHASE I DEMOLITION
PLAN
PROVIDE SITE PREP FOR SPECT
CT ROOM BC-474
10701 EAST BLVD. CLEVELAND, OH
541-CSI-130
4.23.21 CJK JAW
NORTH
SCALE: 1/4" = 1'-0"
BASEMENT LEVEL DEMOLITION PLAN - PHASE I
DEMOLITION NOTES
NOTE COMMENT
1 REMOVE EXISTING DOOR, FRAME AND HARDWARE. FOR REMOVED DOORS ALONG CORRIDORS, INFILL OPENING AFTER REMOVAL OF EXISTING DOOR. ALIGN NEW WALL THICKNESS TO BE FLUSH ON BOTH SIDES OF WALL. FINISH CORRIDOR SIDE TO MATCH EXISTING FINISHES. FOR CORRIDOR-FACING DOORS THAT WILL BE REPLACED W/ LARGER OPENINGS, GC SHALL SCHEDULE FRAME REMOVAL AND REPLACEMENT TO MINIMIZE
TIME WITHOUT A DOOR IN PLACE
1A EXISTING DOOR/FRAME TO BE REMOVED AND RELOCATED, SEE IMPROVEMENT PLAN FOR NEW LOCATION
2 EXISTING WALL TO BE REMOVED, FULL HEIGHT
3 REMOVE PORTION OF EXISTING WALL REQUIRED FOR INSTALLATION OF NEW DOOR FRAME. SEE DOOR
SCHEDULE FOR FRAME SIZE
4 REMOVE EXISTING FLOORING AND WALL BASE IN ENTIRE ROOM
5 EXISTING MILLWORK TO BE REMOVED
5A EXISTING MILLWORK TO BE REMOVED AND RELOCATED. SEE IMPROVEMENT PLAN FOR NEW LOCATION
6 EXISTING PLUMBING FIXTURE TO BE REMOVED. SEE PLUMB. DWGS. FOR ANY PIPING TO BE REUSED AND/OR CAPPED & ABANDONED WHERE SINKS ARE INDICATED TO BE REMOVED, GC SHALL ALSO REMOVE EXISTING WALL-MOUNTED MIRROR, SOAP DISPENSER, & PAPER TOWEL DISPENSER, AND RE-INSTALL SAME AT NEW WALL-MTD. SINK LOCATIONS (SEE IMPROVEMENT PLANS), ALL NON-REUSED ITEMS SHALL BE RETURNED TO
THE VA
7 REMOVE EXISTING WALL-MOUNTED HANDRAIL
8 EXISTING SOLID LEAD RADIOACTIVE WASTE CABINETS TO BE REMOVED AND RELOCATED BY GC. SEE
IMPROVEMENT PLAN FOR NEW LOCATION
9 EXISTING CT SCANNER TO BE FULLY REMOVED BY CT VENDOR, RETAINED/PERFORMED BY VA
10 EXISTING MED. GAS OUTLETS TO BE REMOVED
11 DASHED LINE INDICATES EXISTING LEAD-LINED GYPSUM BOARD TO BE REMOVED ON PARTITIONS FACING
ROOM. STUDS TO REMAIN
11A DASHED LINE INDICATES EXISTING NON-LEAD-LINED GYPSUM BOARD TO BE REMOVED ON PARTITIONS FACING
ROOM. STUDS TO REMAIN
12 EXISTING FURNITURE IN ROOM TO BE FULLY REMOVED BY VA
13 REMOVE AND RELOCATE EXISTING CARD READER
13A EXISTING CARD READER TO REMAIN AND BE REWIRED TO NEW DOOR
14 CONTRACTOR SHALL BE AWARE THAT EXISTING CARPET FLOORING IN EX. CONTROL ROOM BC475A IS DISCONTINUED AND CANNOT BE REPLACED. EXISTING FLOORING MUST BE PROTECTED FROM DAMAGE AT ALL TIMES. ALL DAMAGES CAUSED SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO ADDITIONAL
COST TO THE VA
Revisions: Date:
65% CD's SUBMISSION 8.7.20
100% CD's SUBMISSION 10.13.20
CG-1
1 1
EX. DOORS SHALL BE USED AS
CONSTRUCTION ENTRY AND WILL
BE REPLACED AS A PART OF
CONSTRUCTION. COORD. PHASING
OF DOOR REPLACEMENT TO OCCUR
AT END OF CONSTRUCTION
3' - 0"
6' - 0"
6'
7 7
ALIGN
ALIGN
+/- 4' - 10"
CV
MG
MG
CV
MG
5A
ALIGN
4' - 6"
EKG ROOMS SHALL REMAIN IN
USE THROUGHOUT PHASE II
CONSTRUCTION
CONTROL AND CT ROOMS SHALL REMAIN
IN USE THROUGHOUT CONSTRUCTION 1 7
13 13
11A
8'
/2
(FINISHES REMOVED PHASE I)
(FINISHES REMOVED PHASE I)
2'
EX. DOORS SHALL BE USED AS
CONSTRUCTION ENTRY AND WILL
BE REPLACED AS A PART OF
CONSTRUCTION. COORD. PHASING
OF DOOR REPLACEMENT TO OCCUR
AT END OF CONSTRUCTION
8" +/-
4' -4
4'
11A
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.
ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW
TO MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED…