S02_Attachment 3_Plans_889CM3005_Part2.pdf
PDF 10 MB Posted
- Solicitation number
- 36C78622B0008
About this file
This federal contract opportunity is for construction services to build a new restroom at Fort Lyon in Colorado. The solicitation number is 36C78622B0008 and is being issued by the Department of Veterans Affairs National Cemetery Administration. The contractor will be required to construct a new restroom facility according to the statement of work and plans attached in the file S02_Attachment 3_Plans_889CM3005_Part2.pdf. The response due date is not specified, nor are any pricing or award date details provided in this document. The contract will be set aside for small businesses.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78622B0008 0002.docx | DOCX document | |
| MS02_Attachment 1_Plans_889CM3005_Part1R.pdf | ||
| 36C78622B0008 0001.docx | DOCX document | |
| MS02_Attachment 2_01 45 00 Quality ControlR1.pdf | ||
| S02_Attachment 4_Specifications_889CM3005.pdf | ||
| S02_Attachment 1_SOW_889CM3005.pdf | ||
| S02_Attachment 2_Plans_889CM3005_Part1.pdf | ||
| S02_Attachment 5_IFB Contractor Cost Estimate Worksheet.xlsx | XLSX spreadsheet | |
| S02_Attachment 6_WD_CO20220001.pdf | ||
| 36C78622B0008_2.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
04 22 00 CONCRETE UNIT MASONRY
A. MATERIALS:
1. MASONRY BLOCK UNITS SHALL CONFORM TO ASTM C90
MINIMUM COMPRESSIVE STRENGTH BASED ON GROSS AREA f'm = 2,000 psi
BLOCK UNITS BELOW GRADE AND ALL EXTERIOR BLOCK GRADE N-1
INTERIOR BLOCK, NOT EXPOSED TO WEATHER OR EARTH GRADE N-1 OR S-1
2. MORTAR CONFORMING TO ASTM C270 TYPE S
3. GROUT CONFORMING TO ASTM C476 2,000 psi
4. REINFORCING BAR CONFORMING TO ASTM A615 GRADE 60
C. EXECUTION:
1. VOIDS CONTAINING REINFORCING BARS SHALL BE GROUTED SOLID
2. GROUT ALL CELLS FOR A DISTANCE OF 24" BELOW AND 12" EACH SIDE OF ALL CONCENTRATED LOADS, UNLESS NOTED OTHERWISE
3. GROUT SHALL BE PLACED IN MAXIMUM LIFTS OF 4'-0" UNLESS CLEAN-OUT AND INSPECTION HOLE IS
PROVIDED AT BOTTOM OF VOID
4. CMU BELOW GRADE SHALL BE TREATED WITH BITUMINOUS WATER PROOFING AND GROUTED SOLID
5. LAP BARS A MINIMUM OF 24" OR 36 BAR DIAMETERS AT ALL SPLICES.
6. PROVIDE EXPANSION JOINTS @ A MAXIMUM SPACING OF 25'-0" OC.
7. PROVIDE HORIZONTAL BOND BEAMS W/ (2) #5 BARS CONTINUOUS AT 4'-0" O.C. TYP, TOP OF ALL WALLS
AND AT FLOOR AND ROOF LEVELS.
8. VERTICAL REINFORCEMENT SHALL BE #5 AT 32" O.C. U.N.O. AND EXTEND FOR THE FULL HEIGHT OF THE
WALL.
9. LAP ALL BOND BEAMS FOR A DISTANCE OF 4'-0" AT VERTICAL STEPS IN BOND BEAM COURSES.
10.PROVIDE DOWELS FROM THE FOUNDATION TO MATCH VERTICAL WALL REINFORCING.
11.LAP ALL SPLICES IN REINFORCING A MINIMUM OF 2'-0".
12.PROVIDE HORIZONTAL WALL REINFORCING AT 16" OC. USE PREFABRICATED CORNERS AT WALL
CORNERS AND PREFABRICATED TEES AT INTERSECTIONS. REINFORCING TO BE DUR-O-WALL (OR
EQUAL).
C. EXECUTION:
1. PROTECT LUMBER PRODUCTS FROM DAMAGE BY EXPOSURE TO WEATHER BOTH BEFORE AND
DURING CONSTRUCTION
2. INSTALL ROUGH CARPENTRY INCLUDING CANTS, PLATES, BLOCKING, FURRING, NAILERS AS
INDICATED.
3. PROVIDE SOLID BLOCKING BETWEEN JOISTS AND RAFTERS AT ALL POINTS OF SUPPORT.
PROVIDE APPROVED CROSS-BRIDGING BETWEEN FLOOR JOISTS AT 8'-0" O.C. (MAX.), AND
BETWEEN RAFTERS AT 10'-0" O.C. (MIN.)
4. DO NOT NOTCH, DAP, OR OTHERWISE CUT OR REDUCE FRAMING MEMBERS IN SIZE UNLESS
SPECIFICALLY DETAILED OR APPROVED.
5. PROVIDE TWO (2) STUDS MINIMUM FOR POSTS SUPPORTING BEAMS AND HEADERS
6. STUD POSTS NOTED ON PLANS ARE FOR BEARING ONLY. PROVIDE ADDITIONAL "KING STUD" AS
REQUIRED
7. POSTS AND MULTIPLE STUDS AT UPPER LEVELS SHALL HAVE MATCHING AND ALIGNED POSTS
AND MULTIPLE STUDS AT LOWER LEVELS UNLESS OTHERWISE NOTED. TIGHT FITTING, SOLID
BLOCKING SHALL BE PROVIDED BETWEEN LEVELS UNDER ALL SUCH POSTS AND MULTIPLE
STUDS. BLOCKING SHALL EQUAL AREA OF POST ABOVE AND BELOW AND ALIGNED VERTICALLY
8. CROSS BRACING REQUIRED AT MID SPAN OF JOISTS IF CEILING DRYWALL IS NOT DIRECTLY
APPLIED TO UNDERSIDE OF JOISTS
9. DETAIL AND INSTALL ENGINEERED LUMBER PRODUCTS (I-JOISTS, LVL, LSL, PSL, ETC.) PER
MANUFACTURER SPECIFICATIONS
10. REFER TO MANUFACTURER'S SPECIFICATIONS FOR BRIDGING AND BLOCKING REQUIREMENTS IF
CEILING DRYWALL IS NOT DIRECTLY APPLIED TO UNDERSIDE OF ENGINEERED JOISTS
11. TRUSS DETAILS AND CONNECTIONS SHALL BE PER THE TRUSS MANUFACTURER'S DRAWINGS.
AES GROUP, INC. MUST REVIEW ALL TRUSS LAYOUTS AND PROFILES AND BE ADVISED OF ANY
CHANGES MADE BY THE MANUFACTURER.
12. PROVIDE MINIMUM NAILING AS SPECIFIED BY IBC TABLE 2304.9.1 UNLESS NOTED OTHERWISE ON
PLANS OR DETAILS.
13. PRE-DRILL HOLES FOR NAILS LARGER THAN 16d OR WHERE DRIVING CAUSES SPLITTING.
14. BOLT HOLES IN WOOD SHALL BE 1/16-INCH MAXIMUM LARGER THAN THE BOLT SIZE. PLACE
WASHERS UNDER ALL NUTS, BOLT HEADS AND LAG SCREWS
15. INSTALL METAL CONNECTOR PER MANUFACTURER'S RECOMMENDATIONS
16. ROOF CONSTRUCTION (UNLESS NOTED OTHERWISE):
· SHEATH ROOFS 1/2" APA RATED SHEATHING 32/16 RATING, EXPOSURE
· PLACE ALL SHEATHING WITH LONG EDGE PERPENDICULAR TO RAFTERS AND STAGGER END
JOINTS.
· JOINTS IN LUMBER SHEATHING SHALL OCCUR OVER SUPPORTS UNLESS APPROVED
· NAIL SHEATHING WITH 8d NAILS @ 6"OC AT PANEL PERIMETER AND 12" OC IN FIELD. STAGGER
FASTENERS AT ADJOINING EDGES.
· PLACE SOLID BLOCKING BETWEEN RAFTERS AND LOOKOUTS AT ALL BEARING LOCATIONS.
· PLACE WIND ANCHORS AT ALL RAFTER TO STUD WALL CONNECTIONS.
06 10 00 ROUGH CARPENTRY
A. REFERENCED STANDARDS:
1. AMERICAN WOOD COUNCIL - NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION - 2009 EDITION
(NDS).
2. AMERICAN PLYWOOD ASSOCIATION
3. AITC PRODUCT STANDARD PS 66-82
4. ASTM D3737, STRESSES FOR STRUCTURAL GLUE LAMINATED TIMBER
5. ASTM D1760, PRESSURE TREATED TIMBER
6. AMERICAN SOFTWOOD LUMBER VOLUNTARY STANDARD PS 20-10
7. APA PS1, CONSTRUCTION AND INDUSTRIAL PLYWOOD
8. APA PS2, PERFORMANCE STANDARD FOR WOOD BASED STRUCTURAL PANEL
B. MATERIALS:
1. 2"-4" NOMINAL WIDTH DIMENSIONAL LUMBER HEM FIR #2 Fb = 850 PSI
2. 5" NOMINAL AND WIDER TIMBERS DOUG FIR #1 Fb = 1,200 PSI
3. LAMINATED VENEER LUMBER (ASTM D2559) Fb = 2600 PSI
Fv = 285 PSI
E = 1,900,000 PSI
4. NAILS ASTM F1667
5. BOLTS AND SCREWS ANSI/B 18
6. BOLTS ASTM A307 - BOLTS
7. LUMBER SHALL CONFORM TO PS 20-10 WITH MOISTURE CONTENT LESS THAN 19% WHEN DELIVERED TO JOB
8. LUMBER IN DIRECT CONTACT WITH CONCRETE, ROOF OR SUBJECT TO MOISTURE SHALL BE PRESSURE
TREATED PER AWPA STANDARD.
9. PLYWOOD OR O.S.B. EQUIVALENT SHALL CONFORM TO THE CURRENT APA PRODUCT STANDARD BE; 5-PLY, STRUCTURAL II, CD, CC, OR OSB AND SHALL BE GRADE MARKED.
10. WOOD STRUCTURAL PANEL SHALL BE IDENTIFIED BY A REGISTERED STAMP OF THE AMERICAN PLYWOOD ASSOCIATION, AND INCLUDES VENEER PLYWOOD, AND MATFORMED PANELS SUCH AS ORIENTED STRAND BOARD
(OSB) AND WAFERBOARD.
11. NAILS SHALL BE COMMON NAILS. OTHER NAIL TYPES MAY BE USED ONLY AFTER CONTACTING THIS OFFICE
FOR SIZES AND SPACING
12. PROVIDE SIMPSON STRONG-TIE (GALVANIZED) OR EQUAL FOR ALL INDICATED METAL CONNECTORS
CONCRETE
STRENGTH 4000 PSI
SPLICE
CLASS
BAR
SIZE
TOP
BARS
OTHER
BARS
A B
#3
A B
#4
A B
#5
A B
#6
A B
#7
A B
#8
A B
#9
A B
#10
A B
#11
NOTES:
1. UNLESS NOTED OTHERWISE ON THE
CONTRACT DRAWINGS, USE THE MINIMUM
LENGTH FOR A CLASS B LAP SPLICE OR THE
MINIMUM DEVELOPMENT LENGTH INDICATED IN
THE TABLES ABOVE MULTIPLIED BY THE
APPLICABLE FACTORS.
2. STAGGER SPLICES A MINIMUM OF 36 INCHES.
3. WHERE LIGHTWEIGHT CONCRETE IS USED,
MULTIPLY TABULATED VALUES BY 1.3.
4. CLEAR SPACING OF BARS OR WIRES BEING
SPLICED SHALL NOT BE LESS THAN 2 TIMES THE
BAR DIAMETER AND CLEAR COVER SHALL NOT BE
LESS THAN ONE BAR DIAMETER. WHERE MINIMUM
COVER OR SPACING IS NOT PROVIDED, THE
TABULATED VALUES SHALL BE MULTIPLIED BY 1.5.
5. TOP BARS ARE HORIZONTAL BARS WITH MORE
THAN 12 INCHES OF COVER BELOW THE BOTTOM
OF THE BAR.
MASONRY LAP SPLICE
SCHEDULE
BAR
SIZE LAP LENGTH
#3
#4
#5
#6
#7
NOTES:
1. VALUES APPLY TO MASONRY STRENGTH OF 2000 PSI
2. LAP LENGTHS GIVEN ARE IN INCHES
3. REFER TO ACI 530 FOR ADDITIONAL REQUIREMENTS
#8
#9
CAST IN PLACE CONCRETE
LAP SPLICE SCHEDULE
CAST-IN-PLACE CONCRETE:
A. REFERENCED STANDARDS:
1. ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
B. MATERIALS:
1. CONCRETE 28-DAY MINIMUM COMPRESSIVE STRENGTH:
PIER CAPS, FOUNDATION WALLS & GRADE BEAMS 4000 PSI
2. STEEL REINFORCING BARS ASTM A615, GRADE 60
3. GROUT, HIGH STRENGTH/LOW SHRINK DRY-PACK
MINIMUM COMPRESSIVE STRENGTH 5,000 PSI
C. EXECUTION:
1. CONCRETE SHALL BE NORMAL WEIGHT (UNLESS NOTED OTHERWISE)
2. CONCRETE EXPOSED TO WEATHER SHALL BE AIR ENTRAINED
3. CONCRETE SHALL BE PROPORTIONED, MIXED AND PLACED UNDER THE
SUPERVISION OF QUALIFIED PERSONNEL
4. ADMIXTURES CONTAINING CHLORIDE SALTS SHALL NOT BE USED
5. DETAIL REINFORCING BARS IN ACCORDANCE WITH ACI DETAILING MANUAL AND
ACI BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE
6. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORCING AT
POSITIONS SHOWN ON THE PLANS
7. MAKE ALL BARS CONTINUOUS AROUND CORNERS AND ACROSS STEP-DOWNS. LAP
BARS A MINIMUM OF 18" AT ALL SPLICES.
8. CONTINUOUS BARS IN WALLS, BEAMS AND GRADE BEAMS SHALL BE SPLICED AS
FOLLOWS:
· TOP BARS - AT MID-SPAN
· BOTTOM BARS - OVER SUPPORT
10. COLD WEATHER PROCEDURES FOR CONCRETE SHALL BE PROVIDED AS
RECOMMENDED IN THE ACI MANUAL OF CONCRETE PRACTICE.
11. CONCRETE COVERAGE FOR REINFORCING STEEL SHALL BE AS FOLLOWS:
· CONCRETE CAST AGAINST & PERMANENTLY EXPOSED TO EARTH - 3"
· CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 BAR & SMALLER - 1 1/2"
#6 BAR & BIGGER - 2"
13. EXPANSION BOLTS SHALL BE LOCATED AT A MINIMUM OF 6 BOLT DIAMETERS
FROM CONCRETE EDGE AND SPACED AT A MINIMUM OF 10 BOLT DIAMETERS
UNLESS NOTED OTHERWISE.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
SI
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
GENERAL NOTES
(AS APPLICABLE TO EACH PHASE OF CONSTRUCTION, UNLESS
NOTED OTHERWISE ON PLANS)
A. VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. DO NOT SCALE DRAWINGS.
B. DO NOT REPRODUCE CONTRACT DOCUMENTS OR COPY STANDARD PRINTED
INFORMATION AS BASIS OF SHOP DRAWINGS
C. CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION PRACTICES INCLUDING
TECHNIQUES, PROCEDURES, AND THE SEQUENCE OF CONSTRUCTION. CONTRACTOR
SHALL NOTIFY COR IF A CONFLICT ARISES DUE TO VARIATIONS OR OTHER PROBLEMS
WITH THE CONSTRUCTION DOCUMENTS
D. OBSERVATIONS OF JOBSITE OTHER THAN REQUIRED INSPECTIONS BY ENGINEER ARE
NOT CONSTRUCTION APPROVALS
E. STRUCTURAL ENGINEER MUST BE NOTIFIED AT LEAST 72 HOURS PRIOR TO ANY
REQUIRED CONSTRUCTION OBSERVATION.
DESIGN CRITERIA
A. SCOPE: THIS SPECIFICATION OUTLINES THE STRUCTURAL DESIGN CRITERIA FOR THE
INSTALLATION OF THE RESTROOM BUILDING FOR FORT LYONS NATIONAL CEMETERY.
WHEN A DIFFERENCE EXISTS BETWEEN THIS SPECIFICATION AND ANY OTHER
GOVERNING CODE, THE MORE STRINGENT SHALL CONTROL. ANY OTHER ITEMS NOT
COVERED THEREIN SHALL BE COMMENSURATE WITH GOOD ENGINEERING PRACTICE.
B. APPLICABLE CODES AND STANDARDS:
1. INTERNATIONAL BUILDING CODE - 2018 EDITION
2. AMERICAN SOCIETY OF CIVIL ENGINEERS - ASCE 7-16
3. AMERICAN INSTITUTE OF STEEL CONSTRUCTION MANUAL OF STEEL
CONSTRUCTION - 15TH EDITION
4. AMERICAN CONCRETE INSTITUTE BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE - ACI 318-19
5. NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION - 2018 EDITION
C. BUILDING RISK CATEGORY: II
D. DESIGN LOADS:
1. DEAD LOADS
a. NORMAL WEIGHT CONCRETE: 150 PCF
2. ROOF LIVE LOAD
a. LIGHT DUTY CONSTRUCTION 25 PSF
3. SNOW LOADS: 30 PSF
4. WIND LOADS: 110 MPH
5. SEISMIC DESIGN CRITERIA:
a. SOIL CLASSIFICATION: D (ASSUMED)
b. SEISMIC USE CATEGORY I
c. SEISMIC IMPORTANCE FACTOR Ie 1.00
d. MAPPED SEISMIC RESPONSE ACCELERATIONS
Ss .141 S1 .049
e. SPECTRAL RESPONSE COEFFICIENTS Sds .15 Sd1 .079
f. SEISMIC DESIGN CATEGORY: B
g. MAXIMUM STORY DRIFT: .84"
STRUCTURAL ABBREVIATIONS
ARCH ARCHITECTURE / ARCHITECTURAL
B.O. BOTTOM OF
CLR CLEAR SPACING
CMU CONCRETE MASONRY UNIT
COR CONTRACTING OFFICER'S REPRESENTATIVE
(E) EXISTING
FT FEET
HSS HOLLOW STEEL SECTION
IN INCH
LBS POUNDS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LVL LAMINATED VENEER LUMBER
MAX MAXIMUM
MIN MINIMUM
MPH MILES PER HOUR
(N) NEW
NTS NOT TO SCALE
O.C. ON CENTER
PCF POUNDS PER CUBIC FOOT
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
T.O. TOP OF
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VA US DEPARTMENT OF VETERANS AFFAIRS
STRUCTURAL GENERAL NOTES,
SYMBOLS, AND ABBREVIATIONS
SI001
MLRID12/29/21
ndas Nan_PE signed
1 2 3 4
C
B
A 3/
8"
'-8
/8
8"
8" 23'-8 3/8" 8"
#3 - 18" O.C. BOTH WAYS,
CENTERED IN SLAB
SE
25'-0 3/8"
3/
3/16" 3/16"
'-0
/8
3'-6 7/8"
10'-5 1/2"
3'-2 5/8"
4' -7
/2
2' -1
4' -7
/8
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
SE
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
FOUNDATION PLAN
SE101
MLRID
SCALE:1 FOUNDATION PLAN
1/2" = 1'-0"
SYMBOLS:
FLOOR DRAIN
SHEET NOTES:
1. SLOPE SLAB .25" PER 1' TOWARD FLOOR DRAINS,
DEPRESS SLAB 1/2" AT FLOOR DRAINS
2. SAW CUT 1/4" CONTROL JOINTS 10' O.C. MAX
12/29/21
B
A
SE501
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
SE
2.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
SHEET NOTES:
1. ROOF DECK IS 3/4" PLYWOOD
2. EAVES ARE DECKED WITH CONTINUOUS NOMINAL 1"
TONGUE AND GROOVE PLANKS
KEY NOTES:
1. PRE-ENGINEERED ROOF TRUSSES 24" O.C. MAX
2. ROUGH SAWN LUMBER WITH 2" WIDTH AND DEPTH
TO MATCH ROOF TRUSS MEMBERS
FRAMING PLAN
SE102
MLRID
SCALE:1 FRAMING PLAN
1/2" = 1'-0"
2 2
12/29/21
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
OH
E
BARN BUILDING
OVERHEAD
ELECTRIC
BARN BUILDING
SE501
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
SE
3.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
POLE BARN SLAB
SE103
MLRID
SCALE:1 POLE BARN SLAB
1" = 50'-0"
SHEET NOTES:
1. CONTRACTION JOINTS PLACED 15' O.C. USE DETAIL
9/SE501.
2. COORDINATE FINISH FLOOR ELEVATION WITH DOORS TO
MAINTAIN ACCESSIBILITY AS DETERMINED BY COR.
N 0' 100'50'
SCALE: 1" = 50'
12/29/21
NATURAL SOILS OR NEWLY PLACED FILL COMPACTED
TO AT LEAST 95% MAXIMUM DRY DENSITY AS OBTAINED
BY THE STANDARD PROCTOR METHOD (ASTM D-698)
1/2" EXP. JOINT MATERIAL @ SLAB EDGES
15 MIL POLY VAPOR BARRIER
4" CONC. SLAB
#3 SPACED 18" O.C. EACH WAY
CENTERED IN SLAB
4" OF 3/4" TO 1" WASHED AND SCREENED GRAVEL
1/2" DIA HILTI HIT-Z OR
APPROVED EQUAL, MIN
3" EMBED. 12" O.C.
1'-6"
(2) #5 GRD 60
CONT. IN FOOTING
#5 GRD 60 CROSSBARS
AT 12" O.C.
#5 GRD60
AT 18" O.C.,
1/2" EXPANSION
JOINT MATERIAL
CONCRETE SLAB
RE: PLAN
#5 GRD 60
CONT. 18" O.C.
EQ.EQ.
3' -0
M
IN
8"
#5 DOWEL 4'-0" O.C.
CONTROL JOINT,
SEE ARCH.
NOTE #2, TYP.
NOTE #5
(2) VERT. BARS AT
CONTROL JOINT. MATCH
SIZE OF TYP. VERT.
TYP. FULL HEIGHT BARS
FOR HIGH LIFT GROUTING
OPTION.
TYP. FULL HEIGHT BARS
TO MATCH JAMB BARS
(2) ADD'L MATCHING
TYP.
VERT.
BOND BEAM WITH
(2) #5 BARS
EXTEND VERT. REINF.
TO TOP OF WALL,
TYP.
DOWEL OPTIONS
NOTE #4
TYPICAL LAP SPLICE FOR
LOW
LIFT GROUT OPTION.
ADEQUATELY TIE ALL
SPLICES
PRIOR TO GROUTING
MIN. 24", TYP.
LA
P
SP
LI
C E, SE
E
SC
H
ED
U
LE
NOTE 3
TOP OF CONCRETE
TOP OF FOOTING
TOP OF WALL
OPENING
STONE VENEER , SEE ARCH
CMU WALL, SEE PLAN
WINDOW/DOOR, SEE ARCH
(2) COURSE SOLID
GROUTED BOND BEAM WITH
(2) #5, CONT. EACH.
8x2x3/8 BP HEADER WITH 3/4" DIA
(A36) RODS AT 12" O.C. AT STONE
VENEER
1/
2"
LADDER JOINT REINF.
(TERMINATE REINFORCING
2" FROM CONTROL JOINT)
PREFORMED
CONTROL JOINT
FOAM BACKER
ROD AND SEALANT
NOTE:
1. COORDINATE LOCATION OF JOINTS WITH ARCHITECT.
2. MAXIMUM JOINT SPACING IS 20-FEET.
3. DEPTH OF CAULKING =1/2 THE WIDTH OF THE HEAD JOINT.
SOLID GROUTED CELL W/
#5 VERT EACH SIDE
OF CONTROL JOINT
GROUT SOLID W/
#5 VERT BARS
AS SHOWN
NOTES:
1. VERTICAL WALL REINFORCEMENT SHALL ALIGN WITH VERTICAL FOUNDATION DOWELS. DOWELS SHALL BE PLACED IN CENTER OF CMU WALL WITH ACI STANDARD HOOK. PLACE HOOKS DIRECTLY ON TOP OF BOTTOM
LAYER OF WALL REINFORCING.
2. TYPICAL WALL REINFORCEMENT TO BE PLACED IN CENTER OF WALL. GROUT FULLY ALL CELLS
CONTAINING REINFORCEMENT. PROVIDE REINFORCEMENT POSITIONERS, TYP.
3. SPLICES IN ADJACENT BARS SHALL BE STAGGERED AND ARRANGED SO THAT NOT MORE THAN 25% OF THE
TOTAL NUMBER OF BARS ARE SPLICED AT ANY ONE HEIGHT.
4. PROVIDE (2) #5 BARS IN BOND BEAM AT ROOF LINE AND 10' O.C. MAX.
5. EITHER HIGH LIFT OR LOW LIFT GROUTING TECHNIQUES MAY BE USED AT CONTRACTOR'S OPTION.
6. LAP REINFORCEMENT IN BOND BEAMS 24" MIN. DISCONTINUE BOND BEAMS AT CONTROL JOINTS.
7. FOR HIGH LIFT GROUTING, CLEANOUTS SHALL BE FREE OF ALL DELETERIOUS AND FOREIGN MATTER.
8. ALL MASONRY SHALL BE LAID IN RUNNING BOND, UNLESS NOTED OTHERWISE.
9. CONTRACTOR SHALL PROVIDE TEMPORARY SHORING OF ALL WALLS UNTIL WALLS ARE MADE STABLE BY
THE FRAMING AND DIAPHRAGM SYSTEMS.
8" 3'-10" 8"1'-6"
ROUGH SAWN 2x WITH
DEPTH TO MATCH
TRUSS TOP CHORD.
6'-8"
1" NOMINAL TONGUE
AND GROOVE PLANKS
3/4" PLYWOOD ROOF
SHEATHING
TRUSS TOP CHORD
NOMINAL 2x8 MIN.
TRUSS 2x BLOCKING
TRUSS HEEL
1" BOLT ASSEMBLY
CENTERED IN MEMBER
DEPTH
1" BOLT ASSEMBLY
CENTERED IN MEMBER
DEPTH
SCALE:1 FOUNDATION WALL SECTION
1" = 1'-0"
SCALE:3 BATHROOM BUILDING SLAB DETAIL
1" = 1'-0" SCALE:4 CMU LINTEL DETAIL
1" = 1'-0"
SCALE:7 CMU CONTROL JOINT
1" = 1'-0"
SCALE:5 CMU TYPICAL CORNER
1" = 1'-0"
SCALE:8 EAVE RAFTER CONNECTION
1" = 1'-0"SCALE:6 CMU WALL ELEVATION
1" = 1'-0"
PIPING THROUGH
FOUNDATION WALL,
RE: MECHANICAL
PIPE SLEEVE WITH DIA 2"
GREATER THAN PIPE, FULLY
GROUT ANNULAR SPACE
SCALE:2 PIPE PENETRATION
1" = 1'-0"
SOIL COMPACTED TO 95% MAXIMUM
DRY DENSITY BY STANDARD PROCTOR
6" OF 3/4" TO 1" WASHED
AND SCREEND GRAVEL
SCALE:11 POLE BARN THICKENED SLAB EDGE
1" = 1'-0"
2x8 FASCIA BOARD
2x8 SILL PLATE WITH 3/8" DIA
ANCHOR BOLT EMBEDDED 3",
SPACED 24" O.C.
L4x2x3/8" LEDGER
6"
BEND #3 SLAB REINFORCING
INTO THICKENED EDGE
1'-0"
BEND #3 SLAB REINFORCING
INTO THICKENED EDGE
6" CONCRETE SLAB
2" C
LR
1' -6
SCALE:10 EXISTING TO NEW SLAB CONNECTION
1" = 1'-0"
DRILL AND EPOXY #4 DOWEL
INTO EXISTING SLAB
6" CONCRETE SLAB
2" C
LR
4" 4"
8"
#3 SPACED 18" O.C., EACH WAY
ASSUMED CONDITION AT
END OF EXISTING SLAB,
VERIFY IN FIELD
SLAB EDGE SHALL ABUT EXISTING
STRUCTURE., PROTECT EXISTING STRUCTURE
WITH 1/2" EXPANSION JOINT MATERIAL
3/4"x16" SMOOTH STEEL DOWEL 12"
O.C., ONE SIDE GREASED
6" CONCRETE SLAB
1" C
LR
3" MAX1/8" WIDE BY 1" DEEP SAWCUT
SCALE:9 POLE BARN SLAB CONTRACTION JOINT
1" = 1'-0"
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
SE
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
STRUCTURAL DETAILS
SE501
MLRID12/29/21
ABBREVIATIONS
AHU AIR-HANDLING UNIT
APD AIR PRESSURE DROP
ASHP AIR SOURCE HEAT PUMP
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BOD BASIS OF DESIGN
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELSIUS)
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CH CHILLER
CM CARBON MONOXIDE
CO CLEAN OUT
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CR CEILING REGISTER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
DB DECIBELS
Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
DT DUCT TEMPERATURE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FD FLOOR DRAIN
FPM FEET PER MINUTE
FPS FEET PER SECOND
FSTAT FREEZESTAT
FT FEET
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HP HEAT PUMP
HSTAT HUMIDISTAT
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/h LITERS PER HOUR L/m LITERS PER MINUTE L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LPG LIQUID PROPANE GAS
LSD LINEAR SLOT DIFFUSER
LVR LOUVER
M METER, SI UNIT
M/s METERS PER SECOND
MAU MAKE-UP AIR UNIT
MBH 1000 BTUH
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MM MILLIMETER
MS JANITORIAL MOP SINK
MVD MANUAL VOLUME DAMPER
NA NOT APPLICABLE
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
PSI POUNDS PER SQUARE INCH
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
REA RELIEF AIR
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID LINE
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION LINE
SA SUPPLY AIR
SAT SUPPLY AIR TEMPERATURE
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SG SUPPLY AIR GRILLE
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPS STATIC PRESSURE SENSOR
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SU SPLIT UNIT
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TDH TOTAL DYNAMIC HEAD
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
UC UNIT COOLER
UH UNIT HEATER
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY DRIVE
W WATTS
Wb WET-BULB (TEMPERATURE)
WFM WATER FLOWMETER
YR YEAR
DRAWING SYMBOLS
SF-3 SUPPLY FAN NO. 3
EQUIPMENT ABBREVIATION (SUPPLY FAN)
DUCTWORK SYMBOLS
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
DNUP RETURN DUCT (UP & DOWN)
LINEAR SLOT DIFFUSER
10x8
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
FIRE DAMPER
FD
VD
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
BACK DRAFT DAMPER
BDD
SECTION.)
PIPING SYMBOLS
VENT LINE
REFRIGERANT LIQUID
DRAIN LINE
DESIGN CONDITIONS
ROOM DESCRIPTION
INDOOR OUTDOOR
OCCUPIED HOURS
SUMMER WINTER DEHUMIDIFICATION
SUMMER WINTER
°F Db % RH °F Db 0.4% °F Db 0.4% °F Wb 99.6% °F Db 0.4% MCDB 0.4% DP
TOILET ROOMS / JANITOR CLOSET 75 +/- 2 20-60 70 +/- 2 100.2 68.5 -5.2 71.2 64.1
1. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR
OPERATING, CLEANING, SERVICING, MAINTENANCE,
AND CALIBRATION, SHALL BE EASILY AND SAFELY
ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL,
OR STANDING ON PERMANENT PLATFORMS, WITHOUT
THE USE OF PORTABLE LADDERS. EXAMPLES OF
THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL
TYPES OF VALVES, FILTERS AND STRAINERS,
TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO
COMMENCING INSTALLATION WORK, REFER CONFLICTS
BETWEEN THIS REQUIREMENT AND CONTRACT
DOCUMENTS TO COR FOR RESOLUTIONS.
2. CONSTRUCTION WORK SHALL NOT START ON ANY
SYSTEM UNTIL THE LAYOUT DRAWINGS HAVE BEEN
APPROVED BY VA.
3. DEMOLITION IN EXISTING TOOL BUILDING WILL CONSIST
OF DEMOLISHING ALL EXISTING HVAC EQUIPMENT
INCLUDING WALL HEATER, UNIT HEATER AND EXHAUST
FAN. REPAIR ANY NEW OPENING IN THE WALL, FLOOR
OR CEILING TO MATCH EXISTING.
4. CONTRACTOR SHALL LOCATE SEPTIC DRAIN FIELD
AND LINES. THESE AREAS SHALL BE PROTECTED
DURING CONSTRUCTION.
5. TRAILER AND TOOL BUILDING ARE CONNECTED TO
BOTH WATER AND SANITARY SEWER/SEPTIC LINES.
THESE LINES ARE TO BE LOCATED PRIOR TO
DEMOLITION AND WILL BE UTILIZED BY THE PROPOSED
RESTROOM. CONTRACTOR IS RESPONSIBLE FOR THE
REPLACEMENT OF WATER AND SEWER LINES
DAMAGED DURING CONSTRUCTION.
GENERAL NOTES
REFRIGERANT SUCTION
MAINTENANCE CLEARANCE
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
DUCT MOUNTED COIL (ELECTRIC)
DIRECTION OF AIRFLOW
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
MI
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
MECAHANICAL ABBREVIATIONS
AND SYMBOLS
MI001
LLSCDL
Jeremy Landrith Stamp
Jeremy Landrith Text Box 12/23/21
B
A
EF-3
MS-1
SU-1
UH-1
WH-1
PT-1
MS-1
EF-1 EF-2
6"
6"
6"
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
MH
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
MECHANICAL HVAC PLAN
MH101
LLSCDL
SHEET NOTES:
1. CONTRACTOR TO COORDINATE EQUIPMENT MOUNTING
LOCATION WITH ARCHITECTURE AND OTHER BUILDING
SYSTEMS. NOTIFY COR SHOULD CONDITIONS BE FOUND
TO DIFFER SIGNIFICANTLY FROM CONSTRUCTION
DOCUMENTS.
2. PROVIDE SINGLE SPLIT INSIDE UNIT FOR EACH TOILET
ROOM TO COMBINE INTO SINGLE OUTDOOR UNIT.
3. COORDINATE ALL PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
4. DEMOLITION IN EXISTING TOOL BUILDING WILL CONSIST
OF DEMOLISHING ALL EXISTING HVAC EQUIPMENT
INCLUDING WALL HEATER, UNIT HEATER AND EXHAUST
FAN. REPAIR ANY NEW OPENING IN THE WALL, FLOOR OR
CEILING TO MATCH EXISTING.
KEY NOTES:
1. INTERLOCK FAN WITH LIGHT SWITCH.
2. MOUNT WATER HEATER ON WALL AT 48" AFF.
3. MOUNT UNIT HEATER JUST BELOW CEILING HEIGHT
ALLOWING FOR CLEARANCES FOR SELECTED UNIT.
0'
SCALE: 1/2" = 1'-0"
4'2'1'
EXHAUST FAN SCHEDULE
FIXTURE
TAG
NAME
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
DESCRIPTION
FAN ELECTRICAL
NOTES
CFM
ESP
(WG)
AMPS RPM VOLT PHASE HZ
EF-1 EXHAUST FAN PANASONIC WHISPERFIT DC TOILET ROOM #1 EXHAUST FAN 70 0.375 .29 1.5 120 1 60
INTERLOCK FAN WITH OCCUPANCY
SENSOR ON LIGHT SWITCH
EF-2 EXHAUST FAN PANASONIC WHISPERFIT DC TOILET ROOM #2 EXHAUST FAN 70 0.375 .29 1.5 120 1 60
INTERLOCK FAN WITH OCCUPANCY
SENSOR ON LIGHT SWITCH
EF-3 EXHAUST FAN PANASONIC WHISPERFIT DC JANITOR CLOSET EXHAUST FAN 70 0.375 .29 1.5 120 1 60
INTERLOCK FAN WITH OCCUPANCY
SENSOR ON LIGHT SWITCH
SPLIT SYSTEM SCHEDULE
FIXTURE
TAG
NAME
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
DESCRIPTION
NOMINAL
TON
EVAPORATOR COIL ELECTRICAL
DIMENSIONS
L" X W" X H"
WEIGHT
(LBS)
NOTES
CFM
TOTAL
(MBH)
SENSIBLE
(MBH)
EAT LAT
EER
COP
VOLT PHASE HZ MCA MOCP
SU-1
MS-1
HVAC SPLIT UNIT MITSUBISHI
MR SLIM -
MXZ-3C24NA2
MSZ-GL06NA
TOILET ROOM #1 1 94 8.5 3.4 60 110 12.7 240 1 60 17.2 20
SU-1 38" X 13" X 32"
MS-1 12" X 32" X 9"
INCLUDE LOW AMBIENT TEMP
HEATING OPTION
MS-2 HVAC SPLIT UNIT MITSUBISHI
MR SLIM -
MSZ-GL06NA
TOILET ROOM #2 1 94 8.5 3.4 60 110 12.7 240 1 60 17.2 20 MS-2 12" X 32" X 9" 22
INCLUDE LOW AMBIENT TEMP
HEATING OPTION
UNIT HEATER SCHEDULE
FIXTURE
TAG
NAME
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
DESCRIPTION
HEATING CAPACITY AIR DATA ELECTRICAL DATA
DIMENSIONS
L" X W" X H"
WEIGHT
(LBS)
NOTES
KW MBH
AIRFLOW
(CFM)
TEMP
RISE
(DEG F)
VOLT PHASE HZ
UH-1 UNIT HEATER MODINE HER JANITOR CLOSET WALL MOUNTED UNIT HEATER 3 10.2 43 10 230 1 60 17" X 21" X 21" 67
N
LINE TYPE:
MAINTENANCE CLEARANCE
Jeremy Landrith Text Box 12/23/21
Jeremy Landrith Stamp
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1
- SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
BAND
1-5/8" 12 GAUGE
CHANNEL OR 2"x2"x1/4"
ANGLE
1/2" DIA. HANGER RODS WITH
36" MAX. SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
1" M
A X
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOM. SIZE IN.
mm
THRU 3/4
THRU 20
1 1/4
1 1/2
2 1/2
PIPE IN. 7 7 7 9 10 11 12 14 16 17 19
TUBING IN. 5 FT 6 7 8 8 9 10 12 13 14 16
NOTE: FOR TRAPEZE HANGER, TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
SEE MANUFACTURER
INSTALLATION FOR
MOUNTING REQUIREMENTS
TO CEILING OR WALL
UNIT HEATER
UNIT HEATER WILL
BE SECURED
WITH A MINIMUM OF
TWO BRACKETS
MOTOR HOUSING
EXHAUST
PLAN VIEW
AIR
FLOW
W
BRANCH DUCT
1/4W OR 4" MIN
EXHAUST FAN
BIRD
SCREEN
SCALE:
UNIT HEATER
N.T.S.
SCALE:
EXHAUST DUCTWORK
N.T.S.
SCALE:
PIPE HANGERS
N.T.S.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
MH
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
MECHANICAL DETAILS
MH501
LLSCDL
Jeremy Landrith Text Box 12/23/21
PLUMBING VALVE SYMBOLS
BALL VALVE
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
GLOBE VALVE
PRESSURE REGULATING VALVE
THREE-WAY TWO POSITION CONTROL VALVE
AUTOMATIC AIR VENT
FE
GENERAL PLUMBING SYMBOLS
LIMIT OF DEMOLITION
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
AND EXISTING WORK
POINT OF CONNECTION BETWEEN NEW
PRESSURE GAGE
THERMOMETER
STRAINER
FLOW ELEMENT
PIPE UP
PIPE DOWN
CO CLEAN OUT
HOSE BIB
PUMP
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAUGE
PTRV PRESSURE TEMPERATURE RELIEF
VALVE
PT WELL PRESSURE TANK
PW POTABLE WATER
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RP RECIRCULATION PUMP
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SCFM STANDARD CUBIC FOOT/MINUTE
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SP SUMP PUMP
SQFT SQUARE FEET
SS SANITARY SEWER
SS STAINLESS STEEL
ST STORAGE TANK
SW STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
V VENT
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VP VACUUM PUMP
VS VENT STACK
VSD VARIABLE SPEED DRIVE
VSMC VARIABLE SPEED MOTOR CONTROLLER
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
YCO YARD CLEANOUT
YH YARD HYDRANT
L/S LITER PER SECOND
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LNG LIQUID NATURAL GAS
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTADING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N2 NITROGEN
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
O2 OXYGEN
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OR OPERATING ROOM
ORD OVERFLOW ROOF DRAIN
OSD OVERFLOW STORM DRAIN
OVFL OVERFLOW
KW KILOWATT
KWHR KILOWATT-HOUR
ID INSIDE DIAMETER
IE INVERT ELEVATION
ICW INDUSTRIAL COLD WATER
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IPS IRON PIPE SIZE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
HW/CW HOT AND COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HW HOT WATER
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HWR HOT WATER RETURN
HYD HYDRANT
GAL GALLON
GCO GRADE CLEANOUTS
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GRS GAS REGULATOR STATION
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED WATER HEATER
PLUMBING ABBREVIATIONS
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FD-C FLOOR DRAIN - TYPE C
FM FLOW METER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FS FLOOR SINK
FU FIXTURE UNITS
EL ELEVATION
EPA ENVIROMENTAL PROTECTION AGENCY
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING
DCW DOMESTIC COLD WATER
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DI DEIONIZED WATER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
C CELSIUS
CA COMPRESSED AIR
CGA COMPRESSED GAS ASSOCIATION
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CO CLEANOUT
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CV CONTROL VALVE
CW COLD WATER
BFP REDUCED PRESSURE BACKFLOW
PREVENTER
BHP BREAK HORSEPOWER
BSP BLACK STEEL PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
A/E ARCHITECT / ENGINEER
AD AREA DRAIN
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY HEATING,
REFRIGERATION, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY PLUMBING
ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
P-3 PUMP NO. 3
EQUIPMENT ABBREVIATION (PUMP)
CIRCUIT SETTER (BALANCING VALVE)
WATER HAMMER ARRESTOR
GATE VALVE
FLOOR DRAIN (FD-1)
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
FIXTURES LEGEND
ICE
SINK
DOUBLE SINK / KITCHEN SINK
FLOOR DRAIN
FLOOR SINK
MOP SINK
DRINKING FOUNTAIN
EYE WASH WITH SHOWER
SHOWER
ICE MAKER
TOILET
URINAL
EQUIPMENT
TRAP PRIMER
PLUMBING PIPING SYMBOLS
DOMESTIC HOT WATER, HOT WATER
DOMESTIC COLD WATER, COLD WATER
MAINTENANCE CLEARANCE
SANITARY VENT
SANITARY SEWER
CONDENSATE DRAINCD
SS
GENERAL NOTES
1. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR
OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE
EASILY AND SAFELY ACCESSIBLE BY PERSONS
STANDING AT FLOOR LEVEL, OR STANDING ON
PERMANENT PLATFORMS, WITHOUT THE USE OF
PORTABLE LADDERS. EXAMPLES OF THESE ITEMS
INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS AND STRAINERS,
TRANSMITTERS, AND CONTROL DEVICES. PRIOR
TO COMMENCING INSTALLATION WORK, REFER
CONFLICTS BETWEEN THIS REQUIREMENT AND
CONTRACT DOCUMENTS TO COR FOR
RESOLUTIONS.
2. CONSTRUCTION WORK SHALL NOT START ON ANY
SYSTEM UNTIL THE LAYOUT DRAWINGS HAVE
BEEN APPROVED BY VA.
3. DEMOLITION IN EXISTING TOOL BUILDING WILL
CONSIST OF DEMOLISHING ALL EXISTING
PLUMBING EQUIPMENT INCLUDING SINK, TOILET,
WELL PRESSURE TANK, METER AND ASSOCIATED
WATER AND SANITARY WASTE AND VENT PIPING.
CUT AND CAP ALL SANITARY SEWER LINES BELOW
DIRT UNDER THE CONCRETE SLAB. REMOVE ALL
WATER LINES FROM EXISTING WALL AND
PRESSURE TANK, AND CAP AT BUILDING ENTRY
POINT. CAP SUPPLY PIPING AT THE LOCATION
WHERE THE LINE SPLITS FROM THE EXISTING
WELL PUMP TO THE NEW BUILDING CONNECTION
POINT. IF PIPING IS UNDERGROUND ABANDON IN
PLACE. REPAIR ANY NEW OPENING IN WALL,
FLOOR OR CEILING TO MATCH EXISTING.
4. CONTRACTOR SHALL LOCATE SEPTIC DRAIN
FIELD AND LINES. THESE AREAS SHALL BE
PROTECTED DURING CONSTRUCTION.
5. TRAILER AND TOOL BUILDING ARE CONNECTED
TO BOTH WATER AND SANITARY SEWER/SEPTIC
LINES. THESE LINES ARE TO BE LOCATED PRIOR
TO DEMOLITION AND WILL BE UTILIZED BY THE
PROPOSED RESTROOM. CONTRACTOR IS
RESPONSIBLE FOR THE REPLACEMENT OF
WATER AND SEWER LINES DAMAGED DURING
CONSTRUCTION.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
PI
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
PLUMBING ABBREVIATIONS
AND SYMBOLS
PI001
LLSCDL
AutoCAD SHX Text
AV
Jeremy Landrith Text Box 12/23/21
B
A
P-114
P-401
FD-2
SS SS SS SS
S S
S S
FD-1
P-114
WCO
WCO
FD-3
WH-1
PT-1
P-401
2" 1-1/2"
1-1/2"
2"
4"
2"
2"
1-1/2"
1-1/2"
2"
1-1/2"
2"
1-1/2"
2"
4"
4"
4"4"
P-502
4"
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
PL
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
SANITARY PLAN
PL101
LLSCDL
SHEET NOTES:
1. CONTRACTOR TO COORDINATE EQUIPMENT MOUNTING
LOCATION WITH ARCHITECTURE AND OTHER BUILDING
SYSTEMS. NOTIFY COR SHOULD CONDITIONS BE FOUND
TO DIFFER SIGNIFICANTLY FROM CONSTRUCTION
DOCUMENTS.
2. COORDINATE ALL PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
3. DEMOLITION IN EXISTING TOOL BUILDING WILL CONSIST
OF DEMOLISHING ALL EXISTING PLUMBING EQUIPMENT
INCLUDING SINK, TOILET, WELL PRESSURE TANK, METER
AND ASSOCIATED WATER AND SANITARY WASTE AND
VENT PIPING. CUT AND CAP ALL SANITARY SEWER LINES
BELOW DIRT UNDER THE CONCRETE SLAB. REMOVE ALL
WATER LINES FROM EXISTING WALL AND PRESSURE
TANK, AND CAP AT BUILDING ENTRY POINT. CAP SUPPLY
PIPING AT THE LOCATION WHERE THE LINE SPLITS FROM
THE EXISTING WELL PUMP TO THE NEW BUILDING
CONNECTION POINT. IF PIPING IS UNDERGROUND
ABANDON IN PLACE. REPAIR ANY NEW OPENING IN WALL,
FLOOR OR CEILING TO MATCH EXISTING.
KEY NOTES:
1. VENT THROUGH ROOF.
2. CONNECT TO EXISTING SEPTIC SYSTEM.
COORDINATE EXACT CONNECTION POINT WITH SEE
CIVIL. MATCH SANITARY MAIN TO EXISTING PIPE
SIZE. IF EXISTING PIPE TO REMAIN TO SEPTIC
SYSTEM AT POINT OF CONNECTION IS 3", THEN
CHANGE ALL 4" PIPE TO 3".
0'
SCALE: 1/2" = 1'-0"
4'2'1'
N
Jeremy Landrith Text Box 12/23/21
B
A
FD-3
P-114
P-502
P-401
TMV-1
FD-2
FD-1
P-114
P-401
TMV-1
WH-1
PT-1
1/2"
1/2"
1/2"
1"
3/4"
3/4"
1/2"
1/2"
3/4" CW
1/2" HW
3/4" CW
1/2" HW
1/2"
P-801
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
PP
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
WATER SUPPLY PLUMBING PLAN
PP101
LLSCDL
SHEET NOTES:
1. CONTRACTOR TO COORDINATE EQUIPMENT MOUNTING
LOCATION WITH ARCHITECTURE AND OTHER BUILDING
SYSTEMS. NOTIFY COR SHOULD CONDITIONS BE FOUND
TO DIFFER SIGNIFICANTLY FROM CONSTRUCTION
DOCUMENTS.
2. COORDINATE ALL PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
3. DEMOLITION IN EXISTING TOOL BUILDING WILL CONSIST
OF DEMOLISHING ALL EXISTING PLUMBING EQUIPMENT
INCLUDING SINK, TOILET, WELL PRESSURE TANK, METER
AND ASSOCIATED WATER AND SANITARY WASTE AND
VENT PIPING. CUT AND CAP ALL SANITARY SEWER LINES
BELOW THE DIRT UNDER CONCRETE SLAB. REMOVE ALL
WATER LINES FROM EXISTING WALL AND PRESSURE
TANK, AND CAP AT BUILDING ENTRY POINT. CAP SUPPLY
PIPING AT THE LOCATION WHERE THE LINE SPLITS FROM
THE EXISTING WELL PUMP TO THE NEW BUILDING
CONNECTION POINT. IF PIPING IS UNDERGROUND
ABANDON IN PLACE. REPAIR ANY NEW OPENING IN WALL,
FLOOR OR CEILING TO MATCH EXISTING.
KEY NOTES:
1 CONNECT COLD WATER ENTRY FROM EXISTING
WELL TO PRESSURE TANK ENTRY CONNECTION.
WIRE EXISTING PUMP TO PRESSURE SWITCH.
COORDINATE EXACT ENTRY LOCATION WITH CIVIL.
2. INSTALL FREEZE PROOF KEYED WALL HYDRANT.
3. INSTALL TRAP PRIMER.
4. INSTALL RIGHT HAND HANDLE WATER CLOSET.
5. INSTALL LEFT HAND HANDLE WATER CLOSET.
6. INSTALL REDUCED PRESSURE BACKFLOW
PREVENTER.
0'
SCALE: 1/2" = 1'-0"
4'2'1'
PLUMBING FIXTURE SCHEDULE
FIXTURE
TAG
NAME BASIS OF DESIGN DESCRIPTION ADA
FLOW
RATE
CW HW SAN VENT
P-401 LAVATORY
BASIN MFR: KOHLER
MODEL: KINGSTON K-2007
FAUCET MFR: ZURN - Z86500-XL
VALVE MFG: AMERICAN STANDARD
VALVE MODEL: SELECTRONIC 605XTMV1070
21" X 18" KINGSTON WHITE WALL MOUNT VITREOUS CHINA WITH
4" CENTER FAUCET HOLES AND REAR CENTER DRAIN.
METERED PUSH BUTTON FAUCET, VANDAL-RESISTANT, 3.75"
POLISHED CHROME SPOUT, BRASS.
YES 0.5 GPM 1/2" 1/2" 2" 1-1/2"
TMV-1
THERMOSTATIC
MIXING VALVE
MFR: AMERICAN STANDARD
MODEL: SELECTRONIC 605XTMV1070
LEAD FREE CAST COPPER. ANTI-SCALD PROTECTION -- 1/2" 1/2" 1/2" -- --
P-114 WATER CLOSET
MFR: KOHLER
MODEL: K-25087-T
VALVE: CLASS FIVE CANISTER
VITREOUS CHINA, FLOOR MOUNT, ADA WATER CLOSET
WITH LID LOCKS
YES 1.28 GPF 3/4" -- 4" 1-1/2"
P-502 SERVICE SINK
MFR: FIAT
MODEL: TSBCR1000 SERIES
FAUCET MFG: CHICAGO FAUCETS
VALVE MODEL: 540-LD897SCP
TERRAZZO CORNER FLOOR MOUNTED MOP SINK 24" X 24" X 12"
WITH 6" DROP FRONT
P-801 WALL HYDRANT
MFR: ZURN
MODEL: Z1320
NON-FREEZE KEYED WALL HYDRANT WITH RECESSED BOX -- -- -- -- -- --
WATER HEATER SCHEDULE
FIXTURE
TAG
NAME
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
DESCRIPTION
RECOVERY
RATE
TANK
CAPACITY
HEATING
ELEMENT
VOLTS/
PHASE
TEMP
RISE
SET
PRESS
NOTES
WH-1
ELECTRIC WATER
HEATER
AMERICAN
STANDARD
CE-12-AS
DOMESTIC WALL MOUNTABLE WATER HEATER WITH STAINLESS
STEEL DRIP PAN. DRAIN PIPING TO JANITOR'S CLOSET FLOOR DRAIN.
10 gal
1.5 kW 120V / 1
WALL
MOUNTED
WELL PRESSURE TANK SCHEDULE
FIXTURE
TAG
NAME
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
DESCRIPTION
DRAW
DOWN
TANK
CAPACITY
SET
PRESS
DIAMETER HEIGHT
SET
PRESS
CONNECTION NOTES
PT-1 WELL PRESSURE TANK PENTAIR
PRO-SOURCE PLUS
PREMIUM STEEL TANK
DIAPHRAGM TYPE WELL PRESSURE TANK.
CONTROLLER, PRESSURE SWITCH, RELIEF
VALVE.
5 GAL
20 gal
40-60
PSI
20 IN 21.5 IN
40-60
PSI
1 IN NPT
1 FOOT MAINTENANCE
ENVELOP AROUND TANK
N
Jeremy Landrith Text Box 12/23/21
STRAINER
CW
SEE PLAN FOR SIZE
REDUCED PRESSURE PRINCIPLE
B.F. PREVENTER
AIR GAUGE
PIPE TO FLOOR
DRAIN
MINIMUM 1/4" CLEARANCE
ALL AROUND PROVIDE 2"
CLEARANCE ALL AROUND
FOR SPRINKLER PIPE.
EXTERIOR
BLOCK
WALL
STEEL PIPE
SEAL WITH
WATERPROOF
SEALANT
SEALANT
BACKING
MATERIAL
FILL WITH
NON-SHRINK
GROUT
STEEL
PIPE
SLEEVE
1/2" TRAP PRIMER SUPPLY
DOMESTIC WATER LINE
TRAP PRIMER VALVE
DISTRIBUTION UNIT, FOR
5 LINES
1/2" TRAP PRIMER LINE
SLEEVE THRU
SLAB
FLOOR SLAB
FLOOR DRAIN
ALL-THREAD ROD SECURED TO
STRUCTURE WITH CLAMPS,
FASTENERS, AND HARDWARE
WH-1
NOTE: EXTERNAL
GAUGE TAPS ON PIPES
SHALL NOT BE
REQUIRED WHEN
PUMP IS PROVIDED
WITH FLANGE GAUGE
H C
DRAIN
FINISHED
FLOOR
IPS
SUPPLY
NOTE: WALL MOUNTED PER
MANUFACTURER'S SPECIFICATIONS.
INSIDE (BACK) OF WALL
INLET
CONNECTION
FINISHED
WALL
WALL BOX
FLANGE
WALL CLAMP
NON-FREEZE HYDRANT
WITH INTEGRAL VACUUM
BREAKER ASSEMBLY
T&P RELIEF VALVE AND
DISCHARGE PIPING INTO
FLOOR DRAIN
WALL
WALL
MOUNTING
BRACKET
GABLE ROOF WITH ASPHALT
SHINGLES SEE
ARCHITECTURE DRAWINGS
SEAL ENDS OF INSULATION
WITH PLASTIC CEMENT
PIPING THROUGH ROOF
WITH INSULATION AND
ALUMINUM JACKET
DRAW BAND
ROUND COPPER WEATHER CAP,
CAULK THE SEAM BETWEEN THE
CAP AND ALUMINUM JACKET
SQUARE SHAPED COPPER
FLASHING
WITH FLANGE BASE
SECURE FLASHING IN PLACE
WITH 8 EVENLY SPACED
ROOFING NAILS
TWO LAYERS 15 LB. FELT,
SET IN BEDS OF PLASTIC
CEMENTS AND EXTENDED
MIN. 3" AND 6" BEYOND EDGE
OF FLASHING ON EACH SIDE
AND MOP INTO ROOFING
ASPHALT SHINGLES
PRESSURE SWITCH
PRESSURE GAUGE
1/4" X 3" NIPPLE
VALVE
1/4" PLUG
OPTIONAL
GATE
VALVE
PRESSURE GAUGE
TO WELL
MALE PVC
ADAPTER
TO SYSTEM
PRESSURE RELIEF
VALVE/ DRAIN
SCALE:
PRESSURE TANK
N.T.S
SCALE:
WATER HEATER
N.T.S SCALE:
LAVATORY P-401
N.T.S SCALE:
MOP SINK
N.T.S
SCALE:
TRAP SEAL PRIMER
N.T.S
SCALE:
REDUCED PRESSURE
BACKFLOW PREVENTER
N.T.S
SCALE:
PIPE SLEEVE THROUGH EXTERIOR WALL
N.T.S
SCALE:
PIPING THROUGH ROOF
N.T.S SCALE:
FREEZE PROOF KEYED WALL HYDRANT
N.T.S
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
PI
1.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
PLUMBING DETAILS
PI501
LLSCDL
Jeremy Landrith Text Box 12/23/21
WATERPROOF
MEMBRANE
CLAMP WATERPROOF
MEMBRANE INSIDE OF
DRAIN BODY TO DRAIN
TO WEEP HOLES
NICKLE
BRONZE
ADJUSTABLE
STRAINER
(FLUSH
WITH
FINISHED
FLOOR)
LOOSE GRAVEL
AT WEEP HOLES
THIN SET
MORTAR BED SETTING
FLASHING
CLAMP WITH
WEEP HOLES
STRUCTURAL SLAB
THREADED, CAULKED OR
NO-HUB CONNECTION
PROVIDE A METAL
SUPPORT PLATE WHEN
DRAIN IS INSTALLED IN
AN EXISTING FLOOR -
CAULK AROUND DRAIN
PRIOR TO RE-GROUTING
SOIL PIPE
FINISHED FLOOR
STOP VALVE
CW PIPE
VENT PIPE
WALL
SCALE:
WATER CLOSET WITH FLUSH TANK
N.T.S
SCALE:
FLOOR DRAIN (FD) TYPE C
N.T.S
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
FORT LYON, COLORADO
889CM3005
DECEMBER 23, 2021 Dwg. of
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Drawing Title
Approved: Project Director
Phase
Building Number
BID DOCUMENTS SUBMISSION
BID DOCUMENTS
VA FORM 08 - 6231
321 4 5 6 7 8 9
FORT LYON NATIONAL CEMETERY
NEW RESTROOMCB Design Group
(888) 585-2234
OCMI
(202) 607-7575 Clark Land Surveying
(719) 766-9076
Fil e P ath : P
:\G
OR
D1 -2
1 F
OR
T
LY
ON
N
AT
L C
EM
ET
ER
Y\
DR
AW
IN
GS
\S
HE
ET
S\
PI
2.D
W G
BID DOCUMENTS SUBMISSION
GORDON
148 S. Queen Street, Suite 201 Martinsburg, WV 25401
(304) 725-8456
AES Group
(303) 841-3922
CRA
(859) 252-4737
Mabbett & Associates
(781) 275-6050
PLUMBING DETAILS
PI502
LLSCDL
Jeremy Landrith Text Box 12/23/21
1. CONTRACTOR SHALL COMPLY WITH ALL CURRENT APPLICABLE
CODES AND STANDARDS. ALL ELECTRICAL WORK SHALL BE IN
STRICT COMPLIANCE WITH THE CURRENT EDITION OF THE NEC.
ELECTRICAL WORK SHALL ALSO COMPLY WITH ANY APPLICABLE
FEDERAL AND STATE REGULATIONS. PROVIDE AND MAINTAIN
ELECTRICAL SAFETY AND WORKING CLEARANCES IN FRONT OF
AND AROUND ALL ELECTRICAL PANELS AND DISTRIBUTION
EQUIPMENT IN ACCORDANCE WITH NEC.
2. ALL MATERIAL SHALL CONFORM TO NEMA, ANSI AND U.S.
STANDARDS, WHICHEVER APPLIES AND SHALL BEAR THE
INSPECTION LABEL OF UNDERWRITER LABORATORIES, INC.
3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
ABOUT QUALITY AND GENERAL INSTALLATION REQUIREMENTS
OF ELECTRICAL CONSTRUCTION MATERIALS, ITEMS, AND
DEVICES.
4. FOR QUALITY ASSURANCE, ALL EQUIPMENT SHALL BE UL LISTED
AND APPROVED. ALSO, PERFORM WORK IN ACCORDANCE WITH
THE NATIONAL ELECTRICAL CONTRACTOR ASSOCIATION (NECA)
"STANDARD OF INSTALLATION."
5. CONTRACTOR TO PATCH AND REPAIR ALL SURFACES TO A "LIKE
NEW" FINISH. IF ANY ADJACENT FINISH SURFACES ARE
AFFECTED, PROVIDE A SEAMLESS TRANSITION AND FINISH
LEVEL.
6. PROVIDE SEALANT AROUND ALL ELECTRICAL OUTLETS,
PLUMBING FIXTURES, PIPING, AND EQUIPMENT ABUTTING OR
PENETRATING A WALL OR PARTITION INCLUDING FIRESTOPPING
AT FIRE RATED ASSEMBLES. PROVIDE FIRESTOPPING AROUND
ALL PENETRATIONS OCCURRING THROUGH FLOORS, WALLS,
AND CEILINGS AT FIRE-RATED ASSEMBLIES.
7. CLEAN ALL AREAS OF WORK UPON COMPLETION, INCLUDING BUT
NOT LIMITED TO: ALL EXISTING EQUIPMENT, FIXTURES,…