S02 - Attachment 1 - Drawings - VA San Juan Upgrade UPS Elec BID SET.pdf

PDF 2 MB Posted

Attached to
Z2DA--Upgrade UPS System at Telecommunication Room Federal contract opportunity
Solicitation number
36C24825R0084
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

These are electrical design drawings for a project to upgrade the Uninterruptible Power Supply (UPS) system at the VA Caribbean Health Care System in San Juan, Puerto Rico. The documents are 100% bid set drawings dated December 4, 2023, for Project Number 672-20-601, with sheets covering demolition plans, new power plans, electrical legends, and equipment details. The primary scope involves replacing an existing UPS with a new 40kW Schneider Electric Galaxy VS UPS system in Room A-20, which requires removing the old UPS, installing a new 80A circuit breaker in the existing Panel BHTR, adding a new 100A disconnect switch, and carefully managing the load transfer to minimize disruption to critical systems. The design includes detailed phasing instructions to ensure continuous power during the equipment replacement process.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOCATION MAP

NOT TO SCALE

AREA MAP

NOT TO SCALE

TRUE

NORTH

TRUE

NORTH

PROJECT LOCATION

PROJECT LOCATION

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

100% SUBMITTAL - BID

DOCUMENTS590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

F ile

P a th

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

COVER SHEET UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

SAN JUAN, P.R.

G-001

672-20-601

12/04/2023 F.K. E.O.

ELECTRICAL SHEET LIST

DWG NO. DRAWING TITLE

G-001 COVER SHEET

E-001 ELECTRICAL GENERAL NOTES AND ABBREVIATIONS

E-002 ELECTRICAL LEGEND

ED111 PARTIAL SUB-BASEMENT AND BASEMENT DEMOLITION PLAN

E-111 PARTIAL BASEMENT NEW POWER PLAN

E-501 ELECTRICAL DETAILS

UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

VA CARIBBEAN HEALTH CARE SYSTEM

SAN JUAN, PUERTO RICO 00921-3201

PROJECT NO. 672-20-601

100% SUBMITTAL - BID DOCUMENTS

2023-12-04

SHEET NAMING CONVENTION

E-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

ELECTRICAL GENERAL NOTES:

1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:

A. NFPA 70-2020 (NATIONAL ELECTRICAL CODE)

B. ANSI C2-2020 (NATIONAL ELECTRICAL SAFETY CODE)

C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.

2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40%

FULL.

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND

CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL

DESCRIPTIONS INDICATED.

5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.

6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.

7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE

RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.

8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE

ROUGHING-IN.

9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA

COMPENSATION WILL BE GRANTED.

10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM THE

EXISTING SHALL BE REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.

11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.

12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND

SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE

CONTRACTOR'S RESPONSIBILITY.

14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.

15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY

MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.

16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN

WITH AN INDELIBLE MARKER.

17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.

18. EMT SHALL COMPLY WITH ANSI C80.3 AND UL 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING COLORS FOR

EACH SYSTEM:

• FIRE ALARM - RED

• TELECOMMUNICATIONS - ORANGE

• 480/277V POWER - YELLOW

• 208/120V POWER - BLUE

• GENERATOR POWER - GREEN

• SECURITY - PURPLE

ELECTRICAL ABBREVIATIONS

A OR AMP

ACC

AC

AC

AF

AFF

AFG

AHU

AIC

AL

AM

ASYM

AT

ATS

AUTO

AWG

B

BC

BCW

BFF

BFG

BLDG

C

CAT

CB

CCT

CCTV

CFCI

CH

CHWCP

CHWP

CHWSP

CKT

CMH

CP

CPT

CRAC

CRI

CT

CT

CU

CWP

D

DC

DF

DH or DUH

DHWCP

DISC

DOAS

DPST

DPDT

DSCU

DSHP

DSS

DWBP

DX

EC

EF

ELEC

EMH

EMT

E or EMER

EPA

EQUIP

ERV

ERU

EXIST or EX

EUH

EXP

EWC

EWH

F

FACP

FCU

FLEX

FWE

G OR GND

GFGI

GFI

GRS

GUH

GWH

H or HT

HAC

HOA

HP

HP

HT

HVU

HWCP

HWP

AMPERE(S)

AIR COOLED CHILLER

ALTERNATING CURRENT

AIR COMPRESSOR / AIR CURTAIN

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AMMETER

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

BOILER

BRANCH CONTROLLER

BARE COPPER WIRE

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CHILLER

CHILLED WATER CIRCULATING PUMP IN A

PRIMARY-SECONDARY SYSTEM

CHILLED WATER PUMP

CHILLED WATER SUPPLY PUMP IN A PRIMARY-

SECONDARY SYSTEM

CIRCUIT

COMMUNICATIONS MANHOLE

CONDENSATE PUMP

CONTROL POWER TRANSFORMER

COMPUTER ROOM AC UNIT

COLOR RENDERING INDEX

CURRENT TRANSFORMER

COOLING TOWER

COPPER OR CONDENSING UNIT

CONDENSER WATER PUMP

DEPTH

DIRECT CURRENT

DESTRATIFICATION FAN

DUCT HEATERS

DOMESTIC HOT WATER CIRCULATING PUMP

DISCONNECT SWITCH

DEDICATED OUTSIDE AIR SYSTEM (UNIT)

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

DUCTLESS SPLIT CONDENSING UNIT (POWERS

THE DSS INDOOR UNIT)

DUCTLESS SPLIT HEAT PUMP (POWERS THE

DSS INDOOR UNIT)

DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DOMESTIC WATER BOOSTER PUMP

DIRECT EXPANSION (DX) COOLING COIL

EMPTY CONDUIT

EXHAUST FAN

ELECTRICAL

ELECTRICAL MANHOLE

ELECTRICAL METALLIC TUBING

EMERGENCY

EFFECTIVE PROJECTED AREA

EQUIPMENT

ENERGY RECOVERY VENTILATOR

ENERGY RECOVERY UNIT

EXISTING

ELECTRIC UNIT HEATER

EXPLOSION PROOF

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FUSE

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FLEXIBLE

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GROUND FAULT INTERRUPTER

GALVANIZED RIGID STEEL CONDUIT

GAS UNIT HEATER

GAS WATER HEATER

HEIGHT

HEATED AIR CURTAIN

HAND-OFF AUTOMATIC

HORSE POWER

HEAT PUMP (OUTDOOR PORTION OF SPLIT

SYSTEM HEAT PUMP, USE CU FOR

STANDARD DX OUTDOOR UNIT)

HEAT TRACKING

HEATING/VENTILATING UNIT

HEATING WATER CIRCULATING PUMP IN A

PRIMARY-SECONDARY SYSTEM

HEATING WATER SUPPLY IN A PRIMARY-ONLY

SYSTEM

HWRP

HWSP

HWUH

HZ

IDS

IMC

IRH

J OR JB

K

KAIC

KCM OR KCMIL

KEF

KH

KV

KVA

KW

KWHR

L

LA

LAN

LAV

LTG

MAU

MAX

MCA

MCB or MB

MCC

MGB

MH

MIN

MLO

MOD

MT or MTD

MRS

N

NEC

NEMA

NFPA

NC

NESC

NL

NO

NTS

P

PA

PDU

PF

PH

PIU

PMT

PNL

PTAC

PVC

RECEPT or RECP

RF

RH

RMC

RMS

RTU

RVNR

SA

SCCR

SD

SF

S/N

SP

SPD

SPDT

SPEC

SPST

SWBD

SWGR

TMGB

TOL

TP

TYP

U

UH

UG

UIO

UL

UTP

V

VA

VAV

VEF

VM

VRF

W

WC

WEF

WH

WHDM

WSHP

WP

XFMR

Z

HOT WATER RECIRCULATION PUMP

HEATING WATER SUPPLY PUMP IN A PRIMARY-

SECONDARY SYSTEM

HOT WATER UNIT HEATER

HERTZ

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

INFRARED HEATER

JUNCTION BOX

KILO

THOUSAND AMPERE INTERRUPTING CAPACITY

THOUSAND OF CIRCULAR MILS

KITCHEN EXHAUST FAN

KITCHEN HOOD

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

KILOWATT-HOUR

LENGTH

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

LAVATORY

LIGHTING

MAKE-UP AIR UNIT

MAXIMUM

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE or MOUNTING HEIGHT

MINIMUM

MAIN LUGS ONLY

MOTOR OPERATED DAMPER

MOUNT or MOUNTED

MOTOR RATED SWITCH

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NORMALLY CLOSED

NATIONAL ELECTRICAL SAFETY CODE

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE(S) or PUMP

PUBLIC ADDRESS

POWER DISTRIBUTION UNIT

POWER FACTOR

PHASE

VAV TERMINAL UNIT WITH PARALLEL OR

SERIES FAN (PRIMARY INDUCTION UNIT)

PAD MOUNTED TRANSFORMER

PANEL OR PANELBOARD

PACKAGED THRU-WALL AIR CONDITIONER

POLYVINYL CHLORIDE

RECEPTACLE

RETURN FAN

RADIANT HEATERS (ELECTRIC)

RIGID METAL CONDUIT

ROOT MEAN SQUARE

ROOF TOP UNIT

REDUCED VOLTAGE NON-REVERSING

SURGE ARRESTOR

SHORT CIRCUIT CURRENT RATING

SMOKE DAMPER

SUPPLY FAN

SOLID NEUTRAL

SUMP PUMP

SURGE PROTECTIVE DEVICE

SINGLE POLE DOUBLE THROW

SPECIFICATIONS

SINGLE POLE SINGLE THROW

SWITCHBOARD

SWITCHGEAR

TELECOMMUNICATIONS MAIN GROUNDING

BUSBAR

THERMAL OVERLOAD

TWISTED PAIR

TYPICAL

URINAL

UNIT HEATER

UNDERGROUND

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

VAV TERMINAL UNIT

VEHICLE EXHAUST FAN

VOLTMETER

VARIABLE REFRIGERANT FLOW SYSTEM

WATTS or WIRE or WIDTH

WATER CLOSET

WELDING EXHAUST FAN

WATER HEATER

WATTHOUR DEMAND METER

WATER SOURCE HEAT PUMP

WEATHERPROOF

TRANSFORMER

IMPEDANCE

NOTE:

1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS

PROJECT.

WIRE SIZE FOR ALL 277V, 20A CIRCUITS,

UIO:

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 170 FT,

PROVIDE 2#12 & 1#12G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 280 FT

AND GREATER THAN OR EQUAL TO 170 FT, PROVIDE 2#10 & 1#10G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 440 FT

AND GREATER THAN OR EQUAL TO 280 FT, PROVIDE 2#8 & 1#8G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 700 FT

AND GREATER THAN OR EQUAL TO 440 FT, PROVIDE 2#6 & 1#6G,

3/4"C.

WIRE SIZE FOR ALL 120V, 20A CIRCUITS,

UIO:

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,

PROVIDE 2#12 & 1#12G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT

AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT

AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT

AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,

3/4"C.

NOTES:

1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.

ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

100% SUBMITTAL - BID

DOCUMENTS590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

F ile

P a th

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

ELECTRICAL GENERAL NOTES AND

ABBREVIATIONS

UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

SAN JUAN, P.R.

E-001

672-20-601

12/04/2023 F.K. E.O.2023-12-04

1/2

B

W

SB

M

M

2/60/40/1

60/40/3/3R

40/3/3R

CB

T

M

EM

J J

J

G

G4

A

AE

M

X X

C

D a b

LUMINAIRES

LUMINAIRE AND OUTLET BOX. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

LUMINAIRE AND OUTLET BOX WIRED FOR

MULTILEVEL SWITCHING, LOWER CASE LETTER

INDICATES SWITCHLEG DESTINATION.

LUMINAIRE AND OUTLET BOX, WITH PROVISIONS

FOR EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LUMINAIRE SCHEDULE.

CEILING OR WALL MOUNTED EXIT SIGN AND

OUTLET BOX. PROVIDE NUMBER OF ARROWS

AND FACES INDICATED. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNT AT 96" ABOVE FINISHED FLOOR.

RECESSED OR PENDANT MOUNTED LUMINAIRE

AND OUTLET BOX. LETTER INDICATES LUMINAIRE

TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LUMINAIRE SCHEDULE.

CEILING OR WALL MOUNTED LUMINAIRE AND

OUTLET BOX WITH PROVISIONS FOR

EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

EMERGENCY LIGHT UNIT. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

REMOTE HEAD OR FLOOD LUMINAIRE. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

WALL WASH DOWNLIGHT. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

POLE MOUNTED LUMINAIRE. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

POST-TOP OR BOLLARD LUMINAIRE. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

EQUIPMENT

MOTOR, HORSEPOWER AS INDICATED

MOTORIZED DAMPER

3-POLE COMBINATION MAGNETIC MOTOR

STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/

NEMA ENCLOSURE) NF = NONFUSED

DISCONNECT SWITCH, (SWITCH AMPS/ FUSE

SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-

FUSED

INDIVIDUALLY MOUNTED CIRCUIT BREAKER,

(CIRCUIT BREAKER SIZE/ POLES/ NEMA

ENCLOSURE)

DRY TYPE TRANSFORMER, KVA AS INDICATED

METER

ELECTRONIC METER

PANELBOARD, SEE SCHEDULES

DISTRIBUTION PANELBOARD, SEE SCHEDULES

EQUIPMENT AS INDICATED

CEILING OR WALL MOUNTED JUNCTION BOX

PULL OR JUNCTION BOX

CEILING MOUNTED BLUE LIGHT SYSTEM

ROTATING BEACON

WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE

DROP CEILING

BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT

48" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

WHITE NOISE ROTARY VOLUME CONTROL;

MOUNT 48" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE.

CR

ST

TR

M

R

LA-1,3,5

WIRING DEVICES

LOW VOLTAGE ON/OFF WALL SWITCH, WALL

MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE

DIMMER CONTROL WITH DIMMABLE FIXTURES

INTEGRAL WITH SWITCH.

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

CEILING MOUNTED DUAL TECHNOLOGY

VACANCY SENSOR

CEILING MOUNTED DAYLIGHT SENSOR

PHOTOELECTRIC CELL

WIRING

CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5

ADJACENT TO ARROW INDICATES HOMERUN OF

CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS

RACEWAY INDICATE THE NUMBER OF PHASE

CONDUCTORS AND NEUTRAL IN RACEWAY.

GROUND CONDUCTORS ARE INDICATED BY

LONGER HASHMARKS. NO MARKS ACROSS

RACEWAY INDICATES 2#12 CONDUCTORS AND 1

#12 GROUND CONDUCTOR. CONDUCTOR SIZE #

12 UNLESS INDICATED OTHERWISE. MINIMUM

RACEWAY SIZE SHALL BE 3/4"

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR

ABOVE FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW

GRADE OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

PLUG-IN BUSWAY, UNLESS INDICATED

OTHERWISE

SURFACE METAL RACEWAY OR MULTIOUTLET

ASSEMBLY AS INDICATED

LADDER TYPE CABLE TRAY (SIZE AS INDICATED

ON PLAN)

DUCTBANK, TEXT INDICATES QUANTITY AND

SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)

LIGHTNING PROTECTION

3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG

GROUND ROD TEST WELL

BARE COPPER GROUND CONDUCTOR, 1/0

UNLESS INDICATED OTHERWISE.

4/0 BARE COPPER GROUND CONDUCTOR

LIGHTNING PROTECTION SYSTEM AIR TERMINAL

LIGHTNING PROTECTION ROOF CONDUCTOR

ELECTRICAL CONNECTION

SITE

ELECTRICAL MANHOLE

ELECTRICAL HANDHOLE

PAD MOUNTED TRANSFORMER

POWER POLE

DOWN GUY AND ANCHOR (QUANTITY AS

INDICATED)

2W4"

WIRING DEVICES

SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"

ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE.

DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"

ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"

ABOVE FINISHED FLOOR OR ABOVE COUNTER

TOP/BACKSPLASH

DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT

18" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT

48" ABOVE FINISHED FLOOR OR ABOVE

COUNTER TOP/BACKSPLASH

DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 18" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE

SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 18" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE

SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 48" ABOVE FINISHED FLOOR OR ABOVE

COUNTER TOP/BACKSPLASH

SWITCHED DUPLEX GFI RECEPTACLE NEMA

5-20R, MOUNT 18" ABOVE FINISHED FLOOR,

UNLESS INDICATED OTHERWISE

SWITCHED DUPLEX GFI RECEPTACLE NEMA

5-20R, MOUNT 48" ABOVE FINISHED FLOOR OR

ABOVE COUNTER TOP/BACKSPLASH

DOUBLE-DUPLEX GFI RECEPTACLE, NEMA

5-20R, MOUNTED CONCEALED BEHIND ELECTRIC

WATER COOLER

FLOOR BOX WITH DUPLEX RECEPTACLE NEMA

5-20R. PROVIDE FIRE RATED POKE THRU

DEVICES ON ALL FLOORS ABOVE GROUND

LEVEL.

SPECIAL RECEPTACLE, NEMA TYPE AS

INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,

UNLESS INDICATED OTHERWISE

CEILING BOX WITH DUPLEX RECEPTACLE, NEMA

5-20R

RECEPTACLE WP = IN-USE WEATHER PROOF

SUBSCRIPTS TR = TAMPER RESISTANT

TV = TELEVISION, MOUNT AT 60" ABOVE

FINISHED FLOOR

AFCI = ARC FAULT CIRCUIT INTERRUPTER

FLOOR BOX SUITABLE FOR CONCRETE FLOOR

POUR; TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE

WITH HINGED ACCESS TO RECEPTACLES AND

JACKS RECESSED BELOW COVER IN FLOOR

BOX. PROVIDE 8" FIRE RATED POKE THRU

ABOVE GROUND FLOOR.

WALL SWITCH, AC TYPE, SPST, MOUNT 48"

ABOVE FINISHED FLOOR

WALL SWITCH, AC TYPE, DPDT, MOUNT 48"

ABOVE FINISHED FLOOR

3-WAY WALL SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

4-WAY WALL SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

SLIDE DIMMER, MOUNT 48" ABOVE FINISHED

FLOOR

MOTOR RATED DISCONNECT SWITCH WITH

THERMAL OVERLOADS, SINGLE POLE SINGLE

THROW, MOUNT ON UNIT, UNLESS INDICATED

OTHERWISE.

WALL MOUNTED, DUAL TECHNOLOGY VACANCY

SWITCH, MOUNT 48" ABOVE FINISHED FLOOR

WALL MOUNTED, DUAL TECHNOLOGY

OCCUPANCY SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

ELECTRICAL LEGEND

D

M

V

O

LV

OS

DS

PE

5-30R

EWC

ONE-LINE

TRANSFORMER

CURRENT TRANSFORMER

FUSE

ELECTRICAL CONNECTION

CIRCUIT BREAKER

SWITCH

SURGE ARRESTORS

SEPARABLE CONNECTION

DRY TYPE TRANSFORMER, K-4 RATED, KVA AS

INDICATED

GROUND

SCHEMATIC

PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)

CONTROL RELAY COIL

SHUNT TRIP COIL

TIME DELAY RELAY COIL

MOTOR STARTER COIL

SW

S

S

S

S

S

S

S

S

S

VS

D

F

G

H

P

J

LP

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

100% SUBMITTAL - BID

DOCUMENTS590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

F ile

P a th

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

ELECTRICAL LEGEND UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

SAN JUAN, P.R.

E-002

672-20-601

12/04/2023 F.K. E.O.

NOTE:

1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.

MACHINE

VENDING

DELI

EQUIPMENT

EQUIPMENT

PREPARATION

CORRIDOR

GAMMA

ROOM

GAMMA

RM.

CB-2

CB-3

RADIO

PHARM

OUTPATIENT

RECEPTIONIST

WAITING

TELEPHONE

D-26

A-19

A-20

A-18

A-11

A-16

A-12

A-17

A-17b

STO.

CORRIDOR

TELEPHONE

C O R R

ID

O R

REFRIG.

RECOVERY

A-10

PET/CT

A-7&8

RECOVERY

RESEARCH

HEMA/ONCO

A-21

G

H

I

J

1 2 31.3 2.3 3.4

K

EXISTING

UPS 1

G

H

I

J

1 2 31.3 2.3 3.4

K

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

100% SUBMITTAL - BID

DOCUMENTS590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

F ile

P a th

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

PARTIAL SUB-BASEMENT AND

BASEMENT DEMOLITION PLAN

UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

SAN JUAN, P.R.

ED111

672-20-601

12/04/2023 F.K. E.O.

SCALE: 1/8" = 1'-0"1

PARTIAL SUB-BASMEMENT DEMOLITION PLAN

SCALE: 1/8" = 1'-0"2

PARTIAL BASMEMENT DEMOLITION PLAN

SHEET NOTES:

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

2. REFER TO ELECTRICAL DEMOLITION DRAWINGS FOR

ADDITIONAL EQUIPMENT TO BE DEMOLISHED.

3. FOR ALL DEMOLISHED EQUIPMENT AND DEVICES, REMOVE

ALL ASSOCIATED ACCESSORIES, BRANCH CIRCUIT WIRING

AND CONDUIT, J-BOXES, AND CONDUIT SUPPORTING

MEMBERS NOT TO BE REUSED SHALL BE BACK TO THE

SOURCE OF SUPPLY.

4. COORDINATE WITH THE COR TO VERIFY THE DEMOLISHED

EQUIPMENT AND DEVICES WHICH ARE TO BE RETURNED TO

THE VA FOR STORAGE.

5. ALL EXISTING DEVICES TO REMAIN SHALL BE PROTECTED

FROM DAMAGE THROUGHOUT THE CONSTRUCTION PROCESS.

6. THE CONTINUITY OF EXISTING CIRCUITS SERVING EXISTING

DEVICES AND EQUIPMENT TO REMAIN SHALL BE MAINTAINED.

7. UNLESS OTHERWISE NOTED, IN THE SCOPE OF WORK AREA,

ALL ELECTRICAL DEVICES SHOWN WITH A DASHED LINE

INDICATE EXISTING EQUIPMENT TO BE DEMOLISHED. DEVICES

SHOWN WITH A CONTINUOUS LINE INDICATE EXISTING

EQUIPMENT TO REMAIN.

8. PROVIDE FIRESTOPPING MATERIALS TO MAINTAIN THE

INTEGRITY OF THE FIRE RATED CONSTRUCTION WHERE

CONDUITS PASS THROUGH WALLS AND FLOORS. SEAL ALL

CONDUITS ABANDONED IN WALLS OR SLABS.

KEYNOTES:

1. EXISTING UPS AND ALL ASSOCIATED BRANCH WIRING,

CONTROLS, FEEDERS, J-BOXES, AND CONDUIT SUPPORTING

MEMBERS NOT TO BE REUSED SHALL BE DEMOLISHED.

ABANDON ALL CONDUITS CONCEALED IN CONCRETE WALLS

OR SLABS. REMOVE ALL WIRING FROM ABANDONED

CONDUITS BACK TO THE SOURCE OF SUPPLY. COORDINATE

DEMOLITION OF OLD UPS WITH THE COR PRIOR TO

DEMOLITION TO DETERMINE IF OLD UPS SHALL BE STORED

OR DISCARDED.

2. EXISTING DECOMISSIONED TELECOMMUNICATION EQUIPMENT

AND ALL ASSOCIATED BRANCH WIRING, CONTROLS, FEEDERS,

J-BOXES, AND CONDUIT SUPPORTING MEMBERS NOT TO BE

REUSED SHALL BE DEMOLISHED. ABANDON ALL CONDUITS

CONCEALED IN CONCRETE WALLS OR SLABS. REMOVE ALL

WIRING FROM ABANDONED CONDUITS BACK TO THE SOURCE

OF SUPPLY. EXISTING FURNITURE IN THIS ROOM SHALL BE

MOVED TO A NEW LOCATION TO BE DETERMINED BY COR.

COORDINATE DEMOLITION OF DECOMISSION

TELECOMMUNICATION EQUIPMENT WITH THE COR PRIOR TO

DEMOLITION TO DETERMINE IF EQUIPMENT SHALL BE STORED

OR DISCARDED.

MACHINE

VENDING

DELI

EQUIPMENT

EQUIPMENT

PREPARATION

CORRIDOR

GAMMA

ROOM

GAMMA

RM.

CB-2

CB-3

RADIO

PHARM

OUTPATIENT

RECEPTIONIST

WAITING

TELEPHONE

D-26

A-19

A-20

A-18

A-11

A-16

A-12

A-17

A-17b

STO.

CORRIDOR

TELEPHONE

C O R R

ID

O R

REFRIG.

RECOVERY

A-10

PET/CT

A-7&8

RECOVERY

RESEARCH

HEMA/ONCO

A-21

G

H

I

J

1 2 31.3 2.3 3.4

K

40KW UPS

(TYP.)

BHTR (E)

BLXR (E)

BLTR (E)

2LA (E)BLXTR (E)

100AF

80AT

BHTR

(E)-13,15,17

EXISTING MAIN SWITCHGEAR,

XXXXA, 480VAC, 3PH, 4W

A

/3 P

100AF

80AT

DISC. SWITCH

FOR 40kW UPS

80CU

PANEL

BHTR

EXISTING

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

100% SUBMITTAL - BID

DOCUMENTS590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

F ile

P a th

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

PARTIAL BASEMENT NEW POWER

PLAN

UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

SAN JUAN, P.R.

E-111

672-20-601

12/04/2023 F.K. E.O.

SHEET NOTES:

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

2. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER

DISCIPLINES AND TRADES FOR EXACT LOCATION OF

ASSOCIATED EQUIPMENT.

3. THE CONTINUITY OF EXISTING CIRCUITS SERVING EXISTING

DEVICES AND EQUIPMENT TO REMAIN SHALL BE MAINTAINED.

4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED

WITH CONCEALED CONDUITS. ANY SURFACE MOUNTED

OUTLETS, DEVICES AND CONDUITS IN THE SCOPE OF WORK

AREA MUST BE APPROVED BY THE ARCHITECT PRIOR TO

INSTALLATION.

5. FIELD VERIFY EXACT LOCATION OF ALL DEVICES AND

EQUIPMENT PRIOR TO ROUGH IN.

6. ALL WIRING SHALL BE DONE WITH COPPER WIRE UNLESS

OTHERWISE NOTED.

7. ELECTRICAL CONTRACTOR SHALL PROVIDE TYPED UPDATED

PANEL SCHEDULE FOR ALL PANELS AFFECTED DURING

CONSTRUCTION.

8. ALL REUSED CIRCUIT NUMBERS INDICATED ON THE PLAN ARE

BASED ON EXISTING DOCUMENTS AND MAY NOT MATCH THE

AS-BUILT CONDITION OF THE EXISTING CIRCUITS SERVING

THE AREA. CONTRACTOR TO VERIFY AND UPDATE THE

CIRCUIT NUMBERS UTILIZED DURING CONSTRUCTION.

9. UNLESS OTHERWISE NOTED, IN THE SCOPE OF WORK AREA,

ALL ELECTRICAL OUTLETS AND DEVICES SHOWN WITH A

SUBSCRIPT “N” OR WITHOUT ANY SUBSCRIPT ARE NEW TO BE

PROVIDED. DEVICES SHOWN WITH SUBSCRIPT “E” INDICATE

EXISTING EQUIPMENT TO REMAIN.

KEYNOTES:

1. PROVIDE POWER CONNECTION FOR 40KW UPS WITH

MAINTENANCE BYPASS CABINET (MBC). UPS AND MBC

INTERCONNECTS ARE FACTORY PROVIDED. PROVIDE ALL

CONDUITS, WIRES, AND APPURTENANCES NEEDED FOR

COMPLETE INSTALLATION.

2. PROVIDE A NEW 80A CIRCUIT BREAKER IN EXISTING PANEL

BHTR FOR NEW 40KW UPS. PROVIDE ALL CONDUITS AND

WIRING NEEDED FOR COMPLETE INSTALLATION.

UPS BASIS OF DESIGN: SCHNEIDER ELECTRIC GALAXY VS UPS.

PART NUMBER GVSUPS40K0B5FS/ GVSBP100T

3. PROVIDE A NEW 100A DISCONNECT SWITCH FOR NEW 40KW

UPS. PROVIDE ALL CONDUITS AND WIRING NEEDED FOR

COMPLETE INSTALLATION. COORDINATE FINAL LOCATION WITH

COR PRIOR TO INSTALLATION.

4. ELECTRICAL BRANCH CIRCUIT PANELBOARD IS EXISTING TO

REMAIN AND SHALL BE PROTECTED THROUGHOUT

CONSTRUCTION. SHOWN FOR REFERENCE ONLY.

SCALE: 1/8" = 1'-0"1

PARTIAL BASMEMENT NEW PLAN

SCALE: 12" = 1'-0"2

PARTIAL ONE LINE DIAGRAM

FEEDER SCHEDULE

FEEDER

TAG COPPER FEEDER

FEEDER

TAG ALUMINUM FEEDER

20CU 4#12 & 1#12G, 1/2"C. 20AL N.A.

25CU 4#10 & 1#10G, 3/4"C. 25AL N.A.

30CU 4#10 & 1#10G, 3/4"C. 30AL N.A.

35CU 4#8 & 1#10G, 1"C. 35AL N.A.

40CU 4#8 & 1#10G, 1"C. 40AL N.A.

45CU 4#6 & 1#10G, 1"C. 45AL N.A.

50CU 4#6 & 1#10G, 1"C. 50AL N.A.

60CU 4#4 & 1#10G, 1-1/4"C. 60AL 4#2 & 1#6G, 1-1/4"C.

70CU 4#4 & 1#8G, 1-1/4"C. 70AL 4#2 & 1#6G, 1-1/4"C.

80CU 4#2 & 1#8G, 1-1/2"C. 80AL 4#1 & 1#6G, 1-1/4"C.

90CU 4#2 & 1#8G, 1-1/2"C. 90AL 4-1/0 & 1#6G, 1-1/2"C.

100CU 4#1 & 1#8G, 2"C. 100AL 4-1/0 & 1#6G, 1-1/2"C.

110CU 4#1 & 1#6G, 2"C. 110AL 4-2/0 & 1#4G, 2"C.

125CU 4#1 & 1#6G, 2"C. 125AL 4-3/0 & 1#4G, 2"C.

150CU 4-1/0 & 1#6G, 2"C. 150AL 4-3/0 & 1#4G, 2"C.

175CU 4-2/0 & 1#6G, 2"C. 175AL 4-4/0 & 1#4G, 2"C.

200CU 4-3/0 & 1#6G, 2-1/2"C. 200AL 4-250 KCMIL & 1#4G, 2-1/2"C.

225CU 4-4/0 & 1#4G, 2-1/2"C. 225AL 4-300 KCMIL & 1#2G, 2-1/2"C.

250CU 4-250 KCMIL & 1#4G, 3"C. 250AL 4-350 KCMIL & 1#2G, 3"C.

300CU 4-350 KCMIL & 1#4G, 3"C. 300AL 4-500 KCMIL & 1#2G, 3"C.

350CU 4-500 KCMIL & 1#2G, 4"C. 350AL 4-750 KCMIL & 1#1G, 4"C.

400CU 4-500 KCMIL & 1#2G, 4"C. 400AL 4-750 KCMIL & 1#1G, 4"C.

450CU TWO 2-1/2-INCH CONDUITS, EACH WITH

FOUR 4/0 AND ONE #2G

450AL TWO 2-1/2-INCH CONDUITS, EACH WITH

FOUR 300 KCMIL AND ONE 1/0G

500CU TWO 3-INCH CONDUITS, EACH WITH

FOUR 250 KCMIL AND ONE #2G

500AL TWO 3-INCH CONDUITS, EACH WITH

FOUR 350 KCMIL AND ONE 1/0G

600CU TWO 3-INCH CONDUITS, EACH WITH

FOUR 350 KCMIL AND ONE #1G

600AL TWO 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 2/0G

700CU TWO 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 1/0G

700AL TWO 4-INCH CONDUITS, EACH WITH

FOUR 750 KCMIL AND ONE 3/0G

800CU TWO 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 1/0G

800AL TWO 4-INCH CONDUITS, EACH WITH

FOUR 750 KCMIL AND ONE 3/0G

1000CU THREE 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 2/0G

1000AL THREE 4-INCH CONDUITS, EACH WITH

FOUR 750 KCMIL AND ONE 4/0G

1200CU FOUR 3-INCH CONDUITS, EACH WITH

FOUR 350 KCMIL AND ONE 3/0G

1200AL FOUR 3-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 250 KCMIL G

1600CU FIVE 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 4/0G

1600AL FIVE 4-INCH CONDUITS, EACH WITH

FOUR 750 KCMIL AND ONE 350KCMIL G

2000CU SIX 4-INCH CONDUITS, EACH WITH

FOUR 500 KCMIL AND ONE 250KCMIL G

2000AL SIX 4-CONDUITS, EACH WITH FOUR 750

KCMIL AND ONE 500 KCMIL G

EPO 2#12 & 1#12G, 1/2"C. EPO N.A.

FP (SIZE IS JOB SPECIFIC) FP NOT PERMITTED FOR FIRE PUMPS

MTR1 (SIZE IS JOB SPECIFIC) MTR1 N.A.

MTR2 (SIZE IS JOB SPECIFIC) MTR2 N.A.

SE (SIZE IS JOB SPECIFIC) SE (SIZE IS JOB SPECIFIC)

NOTES:

1. FEEDER TAGS WITH A " * " IN THE TAG HAVE BEEN INCREASED IN SIZE TO ACCOUNT FOR VOLTAGE DROP.

2. COORDINATE PANEL LUG SIZE AND QUANTITIES WITH THE SPECIFIED CONDUCTOR SIZES AND NUMBER OF PARALLEL RUNS AS APPLICABLE. LUG SIZES AND QUANTITIES MUST ACCOUNT FOR CONDUCTORS THAT

WERE INCREASED IN SIZE AND/OR PARALLEL RUNS ADDED TO ACCOUNT FOR VOLTAGE DROP.

3. ALUMINUM CONDUCTORS ARE NOT PERMITTED TO BE SUBSTITUTED FOR COPPER CONDUCTORS SIZED #4 CU

AWG OR SMALLER.

Total Est. Design Current: 48 A

Total Est. Demand Current: 48 A

Total Conn. Current: 48 A

Total Est. Demand Load: 40.00 kVA

Power 40.00 kVA 40.00 kVA Total Conn. Load: 40.00 kVA

Load Classification Connected Load Estimated Demand Panel Totals

NOTES:

TOTAL LOAD: 13.33 13.33 13.33

-- 17 -- -- -- 13.33 -- -- -- -- 18 --

-- 15 -- -- -- 13.33 -- -- -- -- 16 --

13 40KW UPS 80 A 3 13.33 -- 3 -- SPACE 14

-- 11 -- -- -- 0.00 0.00 -- -- -- 12 --

-- 9 -- -- -- 0.00 0.00 -- -- -- 10 --

7 EXISTING LOAD 40 A 3 0.00 0.00 3 70 A EXISTING LOAD 8

-- 5 -- -- -- 0.00 0.00 -- -- -- 6 --

-- 3 -- -- -- 0.00 0.00 -- -- -- 4 --

1 EXISTING LOAD 60 A 3 0.00 0.00 3 70 A EXISTING LOAD 2

CKT CIRCUIT DESCRIPTION TRIP POLE A B C POLE TRIP CIRCUIT DESCRIPTION CKT

CONNECTED LOAD KVA

ENCLOSURE: NEMA 1 WIRES: 4

MOUNTING: SURFACE PHASES: 3

SUPPLY FROM: VOLTAGE: 480Y/277

LOCATION: MAINS RATING: 225A MCB MINIMUM BREAKER SCCR: 18,000

PANELBOARD SCHEDULE: BHTR (E)

PHASING NARRATIVE

THE SCHEMATIC APPROACH BELOW COVERS THE

MOST IMPORTANT ITEMS OF THE PROCESS TO

PREPARE AND PROVIDE THE NECESSARY

PROVISIONS TO MAINTAIN THE ESSENTIAL POWER

SYSTEM FUNCTIONAL WHILE WORK IS

BEING PERFORMED. IT IS EXPECTED THAT THE

CONTRACTOR CAREFULLY REVIEWS THE NARRATIVE,

AND MAKES THE REQUIRED ADJUSTMENTS TO FIT

THE CURRENT SITE CONDITIONS. THE REVIEW AND

ADJUSTMENT OF THIS

SEQUENCE SHALL BE PERFORMED PRIOR TO BID

ISSUANCE. ADJUSTMENTS PERFORMED AFTER BID

ISSUANCE THAT INCUR AN ADDITIONAL COST SHALL

BE COVERED SOLELY BY CONTRACTOR.

CONTRACTOR SHALL REQUEST A SITE

VISIT AND COORDINATE ALL SITE CONDITIONS PRIOR

TO BID SUBMITTAL. ALL DRAWINGS AND

SPECIFICATIONS SHALL BE REVIEWED ALONG WITH

THIS SCHEMATIC APPROACH. IF ANY CONFLICTS ARE

DISCOVERED, THE EOR SHALL BE NOTIFIED IN

WRITING PRIOR TO BID ISSUANCE. IN ANY CASE

WHERE THERE IS CONFLICTING INFORMATION, THE

MOST STRINGENT OPTION SHALL BE THE BASIS OF

DESIGN.

• THE OLD UPS IN THE SUBBASEMENT SHALL BE

OPERATIONAL AND ACTIVE UNTIL THE NEW UPS IS

INSTALLED AND READY TO TAKE OVER THE LOADS

FROM THE OLD UPS

• THE SPACE IN ROOM A-20 WHICH WILL HOUSE THE

NEW UPS SHALL BE CLEARED. THE OLD DEFUNCT

TELEPHONE RACK CURRENTLY IN THE ROOM

SHALL BE REMOVED. CONTRACTOR SHALL

COORDINATE THE REMOVAL OF THE RACK WITH

THE COR AND DETERMINE IF THE VA WANTS TO

SALVAGE THE RACK OR REMOVE AND DISCARD IT.

• THE NEW BREAKER AND FEEDERS TO THE NEW

40KW UPS SHALL BE INSTALLED IN PANEL BHTR

WHILE THE OLD UPS STILL REMAINS ONLINE. THE

FEEDERS AND CONDUIT SHALL BE ROUTED TO THE

LOCATION OF THE DISCONNECT FOR THE NEW

40KW UPS.

• CONDUIT ROUTING SHALL BE IN SUCH A MANNER

THAT IT DOES NOT INTERFERE WITH ANY OTHER

SYSTEMS OR ELECTRICAL GEAR.

• THE OLD UPS SHALL REMAIN OPERATIONAL WHILE

THE NEW UPS IS BEING INSTALLED IN ROOM A-20.

• AFTER THE INSTALLATION OF THE NEW 40KW UPS,

THE CONTRACTOR SHALL TEST THE NEW UPS TO

MAKE SURE IT IS READY TO TAKE ON LOAD.

• WHEN THE TEST IS COMPLETE, THE CONTRACTOR

SHALL START TRANSFERRING THE LOAD

CURRENTLY PROTECTED BY THE OLD UPS TO THE

NEW UPS. THE CONTRACTOR SHALL COORDINATE

THIS LOAD TRANSFER WITH THE COR TO MAKE

SURE THAT IF ANY CRITICAL LOAD IS IMPACTED

THAT A SCHEDULE IS PROVIDED THAT WORKS FOR

THE COR AND END USERS.

• AFTER THE LOADS ARE TRANSFERRED TO THE

NEW 40KW UPS, THE DEMOLITION OF THE OLD UPS

SHALL COMMENCE. THE CONTRACTOR SHALL

CONFIRM WITH THE COR IF THE COMPONENTS OF

THE OLD UPS IS TO BE STORED BY THE VA OR

REMOVED AND DISCARDED BY THE CONTRACTOR.

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

100% SUBMITTAL - BID

DOCUMENTS590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

F ile

P a th

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

ELECTRICAL DETAILS UPGRADE UPS SYSTEM AT

TELECOMMUNICATION ROOM

SAN JUAN, P.R.

E-501

672-20-601

12/04/2023 F.K. E.O.

SCHNEIDER ELECTRIC GALAXY VS UPS SHOP DRAWINGS

Sheets
E-001 - ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
E-002 - ELECTRICAL LEGEND
E-111 - PARTIAL BASEMENT NEW POWER PLAN
E-501 - ELECTRICAL DETAILS
ED111 - PARTIAL SUB-BASEMENT AND BASEMENT DEMOLITION PLAN
G-001 - COVER SHEET

File details come from the government source that posted it. Updated .