This document provides details for a federal contract opportunity to provide construction services at the C.W. Bill Young VA Medical Center in Bay Pines, Florida. The solicitation number is 36C24823R0091 and seeks to resolve statement of conditions deficiencies through a bid build project with a magnitude between $500,000 and $1,000,000. This opportunity is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The NAICS code is 236220 with a small business size standard of $39.5 million. Interested vendors must be verified by the VA's Center for Verification and Evaluation prior to contract award. The point of contact is Joseph Wingfield, who can be reached at 307-712-5769 or amber.milton@va.gov. The response deadline is not provided.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CO2

CO

H

HS

NO2

S

TH

TS

T

MS

CWS

CD

CDR

CR

CS

HWR

HWS

G

STM

CWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSATE DRAINAGE

CONDENSATE RETURN

CONDENSER WATER

RETURN

CONDENSER WATER

SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

NATURAL GAS

STEAM

REF-L

REF-S

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION

2"

4"

4"

REF-HG REFRIGERANT-HOT GAS

PIPING SYMBOLS

PIPE RISE

PIPE DROP

PIPE TEE

REDUCING 45

DEGREE TEE

45 DEGREE TEE

* NOTE *

ALL OF NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN

THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR

MAY NOT BE USED IN THIS SET OF DRAWINGS.

PG PROPANE GAS

16"x8"

16"/8"

FD

SD

M

B

D

C

16"Ø

EXHAUST AIR

OUTSIDE AIR

RELIEF AIR

RETURN AIR

SUPPLY AIR

TRANSFER AIR

GRILLES, REGISTERS & DIFFUSERS TAG

CFM

THROW-150FPM/ 100FPM/ 50FPM

NECK SIZE / MODULE SIZE

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT TAGS

ROUND DUCT SIZE TAG (DIAMETER)

LINEAR DIFFUSER TAG

CFM

TYPE (SEE SCHEDULE) NUMBER OF SLOTS /

ACTIVE SLOT LENGTH (PLENUM LENGTH) /

NECK SIZE

DUCT BEING DEMOLISHED

ELEVATION (CENTER OF FACE)

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

GREASE EXHAUST AIR

SMOKE EXHAUST AIR

EXHAUST GAS FLUE

COMBUSTION AIR

CONDITIONED OUTSIDE AIR

VAV-XX

10' - 0"

48"x2 1/2"

SLB3 400

10" / 24x24

SD3 300

12" / ---

SD9 400

LINEAR BAR GRILLE

LINEAR SLOT

DIFFUSER

PERFORATED

DIFFUSER WITH

DEFLECTORS

ROUND DIFFUSER

WITH ADJUSTABLE

PATTERNS

LOUVERED DOUBLE

DEFLECTION GRILLE

12"x10"

SG5 500

TYPE (SEE SCHEDULE)

10" / 24x24 H-5/7/1422

SD1 400

3-CONE DIFFUSER

THROW PATTERN

MAX NC RATING

1 / 4' - 0" / 8"

LSD1 200

8' - 0"AFF

1 / 4' - 0" / 8"

LSD1 200

6' - 0" 1 / 4' - 0" / 8"

LSD1 200

SECTION TOTAL TRACK LENGTH

12"x10" / 24x12

RG11 500

LOUVERED GRILLE

12"x10" / 24x24

RG2 500

EGGCRATE RETURN

GRILLE

BOTTOM OF EQUIPMENT

ELEVATION

590 lb

RTU-XX

4.0 ton

RTU-XX

115000 Btu/h

115 CFH

RTU-XX

Htg: 3.7 GPM

VAV-XX

HEATING

COIL

FLOW

OPERATING WEIGHT

NOT INCLUDING CURB

FUEL INPUT

GAS PIPE FLOW

NOMINAL COOLING

CAPACITY

VAV BOX

ROOFTOP UNIT

2" DOM. WM

PIPE ACCESSORY TAGS

DOMESTIC WATER METER

BALANCING VALVE

1/4 TURN BALL VALVE

CHECK VALVE

3-WAY MIXING VALVE

MOTORIZED CONTROL VALVE

3 WAY MOTORIZED CONTROL

VALVE

PRESSURE REDUCING VALVE

REFRIGERANT SOLENOID VALVE

BUTTERFLY VALVE

2" BALANCING

2" SHUTOFF

2" CHECK

2" TMV

2" M-CNTRL

2" 3-WAY CNTRL

2" PRV

3/8" SOLENOID

2" BUTTERFLY

DATA DEVICE TAGS

DAMPER TAGS

EQUIPMENT ID

SYMBOL

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKE

DAMPER

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

CAP

PLUG

GWR

GWS

GEOTHERMAL WATER

RETURN

GEOTHERMAL WATER

SUPPLY

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

LIMIT OF DEMOLITION

ITEM TO BE DEMOLISHED

TYP.

Room

(E)

2"

1/8" / 12" SLOPE

PIPE SIZE TAG (DIAMETER)

ABOVE GROUND PIPING

BELOW GROUND PIPING

EXISTING PIPE TAG

PIPING BEING DEMOLISHED

INVERT: -105' - 1" PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

NEW WORK NOTES

DEMOLISHED WORK NOTES

(E)

CONNECT NEW DUCT TO EXISTING DUCT

AREA NOT IN CONTRACT

KG KILOGRAM

KG/HR KILOGRAM PER HOUR

kPa KILOPASCAL

KW KILOWATT

KWH KILOWATT HOUR

L LITER

L/h LITERS PER HOUR (or LITERS/HOUR) L/m LITERS PER MINUTE (or LITERS/MINUTE) L/s LITERS PER SECOND (or LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUEFIED PETROLEUM GAS

LPR LOW PRESSURE RETURN (STEAM

CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN

(CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER, SI UNIT

M/S METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1,000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING

VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN

(STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

Nm NEWTON METER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC &

ATMOSPHERIC ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NPSHA NET POSITIVE SUCTION HEAD

AVAILABLE

NPSHR NET POSITIVE SUCTION HEAD

REQUIRED

NTS NOT TO SCALE

OA OUTSIDE AIR

OAD OUTDOOR AIR DAMPER

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OR OPERATING ROOM

P PUMP

Pa PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PEF PROPELLER (TYPE) EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER

(SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE)

STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH –

ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR

CONDITIONER

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD RETURN AIR DAMPER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RELAD RELIEF AIR DAMPER

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCI SPINAL CODE INJURY

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN (SUBMISSION1)

SD-2 SCHEMATIC DESIGN (SUBMISSION2)

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND

DISTRIBUTION

SPRV STEAM PRESSURE REDUCING

VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT

EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SV STEAM PRESSURE REDUCING

VALVE

SVS STEAM VENT SILENCER

SW SOFTWATER

SWHX STEAM TO WATER HEAT

EXCHANGER

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

UC UNDER CUT

UC UNIT COOLER

UH UNIT HEATER

U UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL

OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH

ADMINISTRATION

VI VIBRATION ISOLATOR

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE)

RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

W WATTS

WAG WASTE ANETHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WEF WALL EXHAUST FAN

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

YR YEAR

ABBREVIATIONS

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT

EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT WC FEET OF WATER COLUMN

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

H HUMIDIFER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN

(STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING HOT WATER PUMP

HWR HEATING HOT WATER RETURN

HWS HEATING HOT WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HVD HOISTWAY VENT DAMPER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTERGRATED PART LOAD VALUE

IRH INTRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

J INTENTIALLY LEFT BLANK

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AAV AUTOMATIC AIR VENT

AB AIR BLENDER

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR COOLED CONDENSING UNIT

ACD AUTOMATIC CONTROL DAMPER,

MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER,

TWO POSITION

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMS AIR FLOW MEASURING STATION

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

AQST AQUASTAT

ARI AIR CONDITIONING AND

REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING

REFRIGERATION AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BMT BONE MARROW TRANSPLANT

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C CENTIGRADE (CELSIUS)

CAV CONSTANT AIR VOLUME

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS

(SUBMISSION1)

CD-2 CONSTRUCTION DOCUMENTS

(SUBMISSION2)

CENT CENTRIFICAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CLEAN OUT

CO2 CARBON DIOXODE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO

COOLING TOWER)

CWS CONDENSER WATER SUPPLY (FROM

COOLING TOWER)

D DAMPER - AUTOMATIC

Db DRY-BULB TEMPERATURE

DB DECIBELS

DCW DOMESTIC COLD WATER

DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)

DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

ACCESS DOOR ON TOP OF DUCT

ACCESS DOOR ON SIDE OF DUCT

ACCESS DOOR ON BOTTOM OF DUCT

SHEET NOMENCLATURE

M P # # #

SERIES

MECHANICAL

(H) HVAC

(P) PIPING

(D) DEMO

(Z) ZONE

SERIES

0 - SYMBOLS AND NOTES

1 - PLAN VIEWS

3 - ELEVATIONS AND SECTIONS

4 - LARGE SCALE - PLANS AND SECTIONS

5 - SCHEMATICS AND DETAILS

6 - SCHEDULES

8 - CONTROLS

AD

CARBON DIOXIDE SENSOR

NITROGEN DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

HUMIDITY SENSOR

HUMIDISTAT SENSOR

MANUAL SWITCH

TEMPERATURE SENSOR

THERMOSTAT

TEMPERATURE & HUMIDITY SENSORRTU-XX

VAV-XX

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

LEGENDS, ABBREVIATIONS, AND

NOTES

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

M001

516-19-111

JMK JSW06/25/2021

MECHANICAL SHEET INDEX

M001 LEGENDS, ABBREVIATIONS, AND NOTES

MD101 FIRST FLOOR INTERSTITIAL HVAC DEMOLITION FLOOR PLAN

MD102 SECOND FLOOR INTERSTITIAL HVAC DEMOLITION FLOOR PLAN

MD103 FOURTH INTERSTITIAL HVAC DEMOLITION FLOOR PLAN

M101 FIRST FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN

M102 SECOND FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN

M103 FOURTH FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN

M104 FIFTH FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN

M501 DUCTWORK AND PIPING DETAILS

GENERAL MECHANICAL NOTES

DEMOLITION MECHANICAL NOTES

PHASING MECHANICAL NOTES

A. THE TEST AND BALANCE CONTRACTOR SHALL BE A SUBCONTRACTOR TO THE

PRIME CONTRACTOR AND NOT A SUBCONTRACTOR TO THE MECHANICAL OR

ANY OTHER SUBCONTRACTOR.

B. PRE-TAB REPORT: TO ESTABLISH BASELINE PERFORMANCE BEFORE

COMMENCING WORK, THE CONTRACTOR SHALL PROVIDE A PRE-TAB REPORT

ON ALL AIR HANDLING UNITS MODIFIED IN THIS PROJECT. THE REPORT SHALL

AT A MINIMUM, PROVIDE SUPPLY AND RETURN FLOWS, PRESSURE PROFILES,

MOTOR CHARACTERISTICS, AND ANY OTHER PERFORMANCE DATA REQUIRED

TO ESTABLISH BASELINE PERFORMANCE OF EXISTING EQUIPMENT TO REMAIN.

SUBMIT REPORT TO COR FOR APPROVAL.

TEST AND BALANCE MECHANICAL NOTES

A. THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS, BOTH

EXISTING AND THOSE ILLUSTRATED BY THESE DOCUMENTS, AS WELL AS

THOSE WHICH CAN BE REASONABLY ANTICIPATED INCLUDING, BUT NOT

LIMITED TO ARCHITECTURAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AND

OTHER SYSTEMS INVOLVED ON THIS PROJECT.

B. FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM AND

SHALL CONFORM TO ALL CURRENT REQUIREMENTS FOUND IN THE UNITED

STATES DEPARTMENT OF VETERANS AFFAIRS TECHNICAL INFORMATION

LIBRARY, INCLUDING BUT NOT LIMITED TO THE PHYSICAL SECURITY MANUAL,

HVAC DESIGN MANUAL, AND STEAM, HEATING HOT WATER, AND OUTSIDE

DISTRIBUTION SYSTEM DESIGN MANUAL. ALL WORK SHALL ALSO CONFORM

TO ALL FEDERAL, STATE, AND LOCAL CODES, INCLUDING BUT NOT LIMITED TO

THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL

CODE.

C. INSTALL ALL EQUIPMENT AND DEVICES IN ACCORDANCE WITH THEIR

RESPECTIVE MANUFACTURER’S INSTALLATION INSTRUCTIONS AT A LEVEL OF

QUALITY AND WORKMANSHIP CONSISTENT WITH THESE DOCUMENTS. ANY

DEVIATIONS BETWEEN THE INSTALLATION INSTRUCTIONS AND THESE

DOCUMENTS WILL BE BROUGHT TO THE ATTENTION TO THE COR BEFORE ANY

COURSE OF ACTION BY THE CONTRACTOR IS INITIATED, INCLUDING

PURCHASE OF EQUIPMENT.

D. CONTRACTOR SHALL COORDINATE ALL WORK DESCRIBED AND ILLUSTRATED

IN THESE DRAWINGS. LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS

INDICATED ON THESE DRAWINGS ARE APPROXIMATE AND SUBJECT TO

ADJUSTMENTS IN THE FIELD. OFFSET DUCTS, PIPING, AND SHIFT EQUIPMENT

AS REQUIRED TO AVOID INTERFERENCE AND CONFLICTS IN THE FIELD.

COORDINATE DUCT AND PIPE ROUTING AND EQUIPMENT LOCATIONS WITH

PLUMBING AND ELECTRICAL INSTALLATIONS AND WITH BUILDING

STRUCTURAL MEMBERS.

E. THESE MECHANICAL DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE NOT TO

BE SCALED. BEFORE BEGINNING WORK, THE CONTRACTOR SHALL VISIT THE

SITE AND COMPLETE MEASURED SURVEY AND CREATE LAYOUT DRAWINGS AS

REQUIRED BY THE SPECIFICATIONS. WORK SHALL NOT BEGIN UNTIL ALL

LAYOUT DRAWINGS ARE APPROVED BY THE COR.

F. COORDINATE LOCATIONS OF CEILING REGISTERS AND DIFFUSERS WITH

LIGHTING LAYOUT AND ARCHITECTURAL REFLECTED CEILING PLAN.

G. DUCT SIZES INDICATED ARE MINIMUM CLEAR INSIDE DIMENSIONS. WHERE

DUCT LINER OCCURS, INCREASE SHEET METAL DUCT SIZES TO

ACCOMMODATE LINER.

H. DUCT AND PIPE SUPPORTS ARE NOT SHOWN ON DRAWINGS.

I. SUPPORT ALL DUCTS, PIPING, AND EQUIPMENT FROM PRIMARY BUILDING

STRUCTURAL MEMBERS. PROVIDE ADDITIONAL STRUCTURAL MEMBERS

WHERE NECESSARY TO ACCOMPLISH THIS REQUIREMENT.

J. NEW AND EXISTING SUPPORT, RODS, AND ASSOCIATED APPURTENANCES

SHALL NOT RESTRICT EQUIPMENT SERVICE AND MAINTENANCE ACCESS.

EXISTING SUPPORTS SHALL BE MODIFIED TO PROVIDE FOR EQUIPMENT

SERVICE AND MAINTENANCE ACCESS.

K. DUCT HANGERS SHALL BE IN STRICT ACCORDANCE WITH FIG 4-4 OF SMACNA

HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - SECOND

EDITION EXCEPT THAT HANGER WIRE SHALL NOT BE USED TO SUPPORT

DUCTS OR EQUIPMENT, AND HANGERS THAT REQUIRE PENETRATION OF DUCT

WITH BOLTS, RIVETS, SCREWS, WIRES OR ANY OTHER FASTENER SHALL NOT

BE USED.

L. CONTRACTOR SHALL REWORK EXISTING HANGERS AND OTHER SUPPORT FOR

DUCT AND PIPING TO COORDINATE WITH NEW EQUIPMENT AND WALL

LOCATIONS. ADD SUPPORT (TRAPEZE, CLEVIS, ETC) AT EQUIPMENT AND ON

EACH SIDE OF NEW WALLS SO FULL WEIGHT OF DUCT AND PIPING IS

SUPPORTED FROM STRUCTURE AND EQUIPMENT AND NEW WALLS BEAR NO

WEIGHT.

M. CONTRACTOR SHALL PROVIDE A LIST OF ALL MECHANICAL EQUIPMENT,

DEVICES, AND ALL APPURTENANCES REQUIRING POWER TO THE COR FOR

REVIEW AND APPROVAL AS PART OF COORDINATION FOR THIS PROJECT. LIST

ALL ELECTRICAL REQUIREMENT CHARACTERISTICS, INCLUDING BUT NOT

LIMITED TO VOLTAGE, AMPERAGE, PHASE, DISCONNECTING MEANS, OVER

CURRENT PROTECTION AND ALL CHARACTERISTICS FOR A FULLY

FUNCTIONAL AND COORDINATED SYSTEM. REFER TO ELECTRICAL DRAWINGS

FOR VOLTAGE REQUIREMENTS OF ALL EQUIPMENT.

N. DO NOT USE SCHEDULED EQUIPMENT IDENTIFICATION NUMBERS SHOWN ON

DRAWINGS FOR FINAL EQUIPMENT SIGNS AND FOR CONTROL SYSTEM

SCHEMATICS. CONTACT COR AND OBTAIN FROM REFRIGERATION AND HVAC

MAINTENANCE SUPERVISOR THE CORRECT NOMENCLATURE AND EQUIPMENT

NUMBERS FOR INCLUSION IN SIGNAGE, CONTROL SCHEMATICS, AND AS-BUILT

DRAWINGS.

O. CONTROL DEVICES ASSOCIATED WITH THE WORK OF THIS PROJECT SHALL BE

RELOCATED AS NECESSARY SO THAT THE FINAL PRODUCT RESULTS IN A

FULLY FUNCTIONAL AND FULLY ACCESSIBLE SYSTEM. CONTRACTOR SHALL

RELOCATE ALL EXISTING CONTROLS, SENSORS, PROBES, OR OTHER DEVICES

AND PROVIDE NEW WIRING, CONDUIT, AND/OR TUBING TO EXTEND SUCH

DEVICES AS NECESSARY TO PRODUCE A FULLY FUNCTIONAL SYSTEM EQUAL

OR BETTER THAN EXISTING. PROTECT AND STORE ALL SUCH RELOCATED

DEVICES.

A. EQUIPMENT INDICATED TO BE REMOVED SHALL BE REMOVED FROM THE

PROJECT SITE IN ITS ENTIRETY INCLUDING ALL HANGERS, ELECTRICAL

CONDUIT, WIRING, JUNCTION BOXES, PIPING, CONTROLS, ACCESSORIES AND

ALL APPURTENANCES THAT ARE RENDERED USELESS OR ABANDONED BY

THE REMOVAL OF THE INDICATED EQUIPMENT.

B. WHERE THESE DOCUMENTS REQUIRE REMOVAL OF DUCTWORK, PIPING,

EQUIPMENT OR ASSOCIATED APPURTENANCES, CONTRACTOR SHALL

PROTECT ALL EXISTING-TO-REMAIN COMPONENTS FROM DAMAGE.

CONTRACTOR SHALL COVER ALL OPENINGS IN DUCT, PIPING, EQUIPMENT,

AND ANY OTHER DEVICE FROM CONSTRUCTION DUST AND DEBRIS.

C. WHERE EQUIPMENT, DUCTWORK, OR PIPING IS TO BE REMOVED THAT IS IN-

SERVICE, CONTRACTOR SHALL GIVE NOTICE TO THE COR OF ANY

INTERRUPTIONS ANTICIPATED. IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO COORDINATE ALL SHUTDOWNS OR INTERRUPTIONS TO THE

SATISFACTION OF THE COR AND HOSPITAL STAFF.

A. CONTRACTOR SHALL PHASE ALL WORK AS REQUIRED TO MAINTAIN

CONTINUOUS OPERATION OF THE HOSPITAL.

B. HOSPITAL OPERATIONS SHALL NOT BE INTERRUPTED DUE TO THE WORK OF

THIS PROJECT EXCEPT FOR SCHEDULED SHUTDOWNS OF NO LONGER THAN

ONE HOUR. CONTRACTOR SHALL GIVE REASONABLE NOTICE TO COR BEFORE

ANY SUCH SHUTDOWN OR INTERRUPTION.

C. WHERE LONGER SHUTDOWNS ARE REQUIRED TO COMPLETE THE WORK

DESCRIBED IN THIS DOCUMENT, THE CONTRACTOR SHALL SCHEDULE THE

EVENT A MINIMUM OF 3 WEEKS PRIOR TO COMMENCING WORK. ALL SUCH

SHUTDOWNS AND INTERRUPTIONS SHALL BE MINIMIZED AND SHALL UTILIZE

WEEKENDS, FEDERAL HOLIDAYS, NIGHTS, AND OTHER TIMES WHEN HOSPITAL

OPERATIONS ARE MINIMIZED AND OTHER SUCH TIMES AGREEABLE TO THE

COR.

D. WHERE NECESSARY TO INTERRUPT CONTINUOUS OPERATION OF THE

HOSPITAL, THE CONTRACTOR SHALL DIVIDE WORK INTO PHASED

CONSTRUCTION THAT IS NOT NECESSARILY SHOWN ON THESE DOCUMENTS.

AS PART OF SCHEDULING AN INTERRUPTION OR SHUTDOWN, THE

CONTRACTOR SHALL PROVIDE THE COR WITH A DETAILED SHUTDOWN PLAN

INDICATING THE SYSTEMS AFFECTED, INCLUDING BUT NOT LIMITED TO

ARCHITECTURAL, ELECTRICAL, MECHANICAL, PLUMBING, FIRE PROTECTION,

AND OTHER SYSTEMS INVOLVED. THE PLAN SHALL INCLUDE THE WORK TO BE

PERFORMED, THE LENGTH OF INTERRUPTION, AND A DETAILED PHASING AND

MANNING DESCRIPTION. THE PLAN SHALL INCLUDE AND ADDRESS

CONTINGENCY FOR MITIGATING ANY DELAYS THAT MAY OCCUR IN THE

PLANNED WORK. PROVIDE THIS PLAN TO THE COR 5 WEEKS BEFORE THE

EVENT FOR APPROVAL.

KEY PLAN B100

E L E V .

P - 1 P - 2

E L E V .

P - 3

E L E V .

E L E V .

S - 6S - 5

E L E V .E L E V .

S - 4

E L E V

S - 7

E L E V

S - 8

E L E V

S - 9

E L E V

S - 1 1

E L E V

S - 1 2

E L E V

S - 1 0

AD

B C

MD101

(E)22"Ø R/A

(E)32"Ø R/A

(E)28"Ø R/A

(E )1 6" Ø R /A

(E )1 2" Ø R /A

(E)28"Ø S/A

(E )1 6" Ø S /A

(E)18"Ø S/A

(E )1 2" Ø S /A

(E)24"Ø S/A

(E )2 5" /1 2" S /A

(E)1H-70

(E )8 "Ø

S /A

(E )1 4" Ø S /A

(E)1H69

(E)10"x12" S/A

(E )8 "x 8" S /A

(E)8"Ø S/A

(E)5"Ø S/A

(E)5"Ø S/A

(E )1 0" x8 S /A

(E )2 5" /1 2" R /A

(E )1 2" Ø R /A(E)10"Ø R/A

(E)6"Ø R/A

(E)10"Ø R/A

(E )1 4" Ø R /A

(E)6"Ø R/A

(E )1 8" Ø R /A

(E)8"Ø R/A

(E )1 6" Ø S /A

(E)8"Ø S/A

(E)1H-82

(E)16"x8" S/A

(E )8 "x 8" S /A

(E )8 "Ø

S /A

(E)1H-82A

(E)8"x8" R/A

(E)6"Ø

(E)10"x4" R/A

(E)6"Ø R/A

(E )1 0" Ø R /A

(E)1H-85

(E )1 0" Ø S /A

(E)1H-86

(E)1H-87

(E)10"Ø S/A

(E)1H-88

(E )1 0" Ø S /A

(E)10"Ø R/A

(E )1 8" Ø R /A

(E )1 0" Ø S /A

(E )1 2" Ø R /A

(E )1 0" Ø R /A

(E )1 2" Ø S /A

(E)6"Ø S/A

(E)6"Ø S/A

(E)18"Ø S/A

(E )1 8" Ø R /A

(E )2 5" /1 2" R /A

(E)28"Ø R/A

(E )1 2" Ø S /A

(E )1 2" Ø R /A

(E)8"x8" S/A

(E)AHU-34

(E)40"x26"

(E )3 0" x2 0"

(E )3 0" x1 2" S /A

(E )3 0" x2 0" R /A

(E )1 2" Ø S /A

(E )1 2" Ø R /A

(E )6 "Ø

S /A

(E)6"Ø S/A

(E)1H-82A

(E )6 "Ø

S /A

(E) 2" CWR

(E) 2" CWS

G.8 G.8

G G

F.6 F.6

F.2 F.2

F.1 F.1

MD101

MD101

MD101

1 Interstitial -

Mechanical

14' - 0"

Level 2

22' - 10"

(E )2 6" x4 0"

(E)20"x30"

(E)AHU-34

REMOVE AUX DRAIN PAN

EXISTING MECHANICAL AND

ELECTRICAL TO REMAIN ACTIVE

(E)12"x30" S/A

(E)20"x30" R/A

(E)12"x30"

2" CWS/R TO

REMAIN

G

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

FIRST FLOOR INTERSTITIAL HVAC

DEMOLITION FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

MD101

516-19-111

JMK JSW06/25/2021

0 4' 8'2'

1/4" = 1'-0"MD101

1 FIRST FLOOR INTERSTITIAL HVAC DEMOLITION PLAN

MD101 DEMOLITION NOTES

NOTE

NUMBER NOTE TEXT

1 REMOVE 30"x20" RETURN DUCT FROM BLOWER COIL UNIT TO

APPROXIMATE LOCATION AS INDICATED. PREPARE DUCT FOR NEW. SEE

SHEET M101.

2 REMOVE 8" DIA RETURN DUCT FROM FLOOR PENETRATION TO 30"x20"

RETURN DUCT. PREPARE FOR NEW WORK. SEE SHEET M101.

3 REMOVE 6" DIA RETURN DUCT FROM MAKE-UP AIR VAV TERMINAL TO

30"x20" RETURN DUCT. PREPARE FOR NEW WORK. SEE SHEET M101.

4 REMOVE 30"x20" SUPPLY DUCT FROM BLOWER COIL UNIT TO

APPROXIMATE LOCATION OF SCOPE OF WORK. PREPARE DUCT FOR

NEW. SEE SHEET M101.

5 REMOVE 6" DIA RETURN DUCT FROM FLOOR PENETRATION TO 12" DIA

RETURN DUCT.

6 REMOVE A PORTION OF THE 12" DIA RETURN DUCT APPROXIMATLY 16'-0"

FROM FACE OF WALL AND END CAP DUCT. PREPARE FOR NEW WORK.

SEE SHEET M101.

7 AHU-34 WILL REMAIN IN PLACE.

8 REMOVE APPROXIMATE 42" OF 6" DIA SUPPLY DUCT. COORDINATE WITH

NEW 30"x20" RETURN AIR DUCT. SEE NEW WORK SHEET M101.

0 4' 8'2'

1/4" = 1'-0"MD101

2 FIRST FLOOR DEMOLITION WORK INTERSTITIAL MECHANICAL - SECTION

TRUE

NORTH

PLAN

NORTH

REMOVE AUX

DRAIN PAN

NOT TO SCALEMD101

3 AHU-34 ELEVATION VIEW 1

NOT TO SCALEMD101

5 AHU-34 ELEVATION VIEW 3

NOT TO SCALEMD101

4 AHU-34 ELEVATION VIEW 2

G

F. 5

F. 2

F

E. 6

H

G. 7

G. 5

252423222120

J

D

E

15 16 17 18 19

D. 4

ROOF

ROOF

KEY PLAN B100

AD

B C

MD102

MD102

(E )1 6" x1 2" R /A

(E )1 4" Ø R /A

(E)12"x10" S/A

(E )1 6" x1 2" S /A

(E)AHU-36

(E)8"Ø S/A

(E)8"Ø S/A

(E)16"x16" R/A

(E )1 6" x1 6" R /A

(E)2E-1A

MAKE-UP

AIR

(E)40"x24" R/A

(E)8"Ø S/A

(E)8"Ø S/A

(E)A36-1

(E)A36-2

(E)8"Ø

(E)12"Ø S/A

(E)5"Ø S/A

(E)6"x6" S/A (E)6"x6" S/A

(E)10"Ø S/A

(E)2E-10

(E)2E-11

(E )1 2" Ø S /A

(E)6"x6" S/A

(E)34"Ø S/A (E)14"Ø S/A

(E)30"Ø R/A (E)32"Ø R/A

(E )1 2" Ø S /A

(E)2E-9

(E)2E-8

(E )8 "x 4" S /A

(E)8"x4" S/A

(E )5 "Ø

S /A

(E )5 "Ø

S /A

(E )8 "Ø

S /A

(E )2 1" /1 2" S /A

(E )8 "x 4" S /A

(E)10"Ø R/A (E)12"x10" S/A

(E )1 2" x1 0" S /A

(E )8 "Ø

S /A

(E)2E-7

(E)2E-6

(E )8 "Ø

S /A

(E)10"x8" S/A

(E)12"Ø R/A

(E )1 4" Ø R /A

(E)5"Ø S/A

(E)2E-5

(E )1 2" Ø S /A

(E)12"Ø R/A

(E )5 "Ø

S /A

(E )1 5" /1 2" S /A

(E )1 2" Ø R /A

(E)34"Ø S/A

(E)40"Ø R/A

(E)10"Ø S/A

(E)A36-4

(E)8"Ø S/A

(E)12"Ø R/A

(E)8"Ø S/A

(E)5"Ø S/A

(E)2E-4

(E)16"x4" S/A

(E)8"x4" S/A

(E)6"Ø R/A

(E)8"x6" S/A

(E )1 2" Ø R /A

(E)12"Ø R/A (E )1 0" Ø S /A

(E)8"Ø S/A

(E)A36-3

(E)8"Ø S/A

EXISTING

DRAIN PAN TO

REMAIN

2" CWS/R TO

REMAIN

1" DHW/R TO

REMAIN

(E)6"Ø

(E )8 "Ø

S /A

MD102

MD102

MD102

K K

J J

(E )1 0" Ø R /A

2 Interstitial -

Mechanical

42' - 0"

Level 3

50' - 10"

(E)2E-1A

MAKE-UP

AIR

(E)6"Ø

(E)16"x16" R/A

EXISTING MECHANICAL AND

ELECTRICAL TO REMAIN ACTIVE

(E)AHU-36

(E)8"Ø S/A

(E )8 "Ø

S /A

2" CWS/R TO

REMAIN

(E)A36-1

EXISTING

DRAIN PAN

1" DHW/R

TO REMAIN

(E)8"Ø S/A

(E)8"Ø S/A(E)8"Ø S/A

2 Interstitial -

Mechanical

42' - 0"

Level 3

50' - 10"

(E)8"Ø S/A

(E)A36-1

(E)12"Ø S/A

(E)AHU-36(E)16"x16" S/A

(E)8"Ø S/A

(E)8"Ø

(E)A36-2

(E)12"Ø S/A

EXISTING DRAIN

PAN TO REMAIN

(E)12"x16" S/A

2" CWS/R TO

REMAIN

EXISTING MECHANICAL AND

ELECTRICAL TO REMAIN ACTIVE

(E)24"x40" R/A

1" DHW/R

TO REMAIN

(E)10"Ø R/A(E)14"Ø R/A

(E)8"Ø S/A (E)8"Ø S/A

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

SECOND FLOOR INTERSTITIAL HVAC

DEMOLITION FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

MD102

516-19-111

JMK JSW06/25/2021

PLAN

NORTH

TRUE

NORTH

0 4' 8'2'

1/4" = 1'-0"MD102

1 SECOND FLOOR INTERSTITIAL HVAC DEMOLITION PLAN

0 4' 8'2'

1/4" = 1'-0"MD102

2 SECOND FLOOR INTERSTITIAL HVAC DEMOLITION PLAN

0 4' 8'2'

1/4" = 1'-0"MD102

3 SECOND FLOOR INTERSTITIAL HVAC DEMOLITIO PLAN

MD102 DEMOLITION NOTES

NOTE

NUMBER NOTE TEXT

1 REMOVE RUNOUT FROM BRANCH TO TU A36-2. PATCH AND REPAIR

BRANCH DUCT.

2 REMOVE EXISTING RUNOUT AT TU 2E-1A TO THE EXTENT INDICATED FOR

REROUTING IN NEW WORK PHASE.

3 REMOVE EXISTING DUCT TO THE APPROXIMATE EXTENT INDICATED TO

INSTALL NEW FIRE DAMPER.

3 3 3

NOT TO SCALEMD102

4 AHU-36 ELEVATION VIEW 1

NOT TO SCALEMD102

5 AHU-36 ELEVATION VIEW 2

NOT TO SCALEMD102

6 AHU-36 ELEVATION VIEW 3

G . 5

2 72 6

2 52 42 32 22 12 0

F . 5

E . 6

F . 3

F

E

D . 4

D

1 91 81 71 61 5

1 41 3

H

J

K

G. 7

2 72 61 41 3

H

DN

(E)40"/36" S/A(E)36"Ø S/A(E)34"Ø S/A

(E)52"/40" R/A(E)44"/40" R/A(E)42"/40" R/A

(E )2 1" /2 2" S /A

(E )1 6" /2 2" S /A

(E )8 "Ø

S /A(E)4B-4

(E)10"x8" S/A

(E)10"x8" S/A

(E)8"Ø S/A

(E)8"Ø S/A(E)4B-5

(E)8"x8" S/A

(E )2 2" /1 6" R /A

(E)22"/16" R/A

(E)8"x8" R/A

(E )8 "Ø

R /A

(E )8 "x 8" R /A

(E)10"x8" R/A

(E)6"Ø R/A

(E)6"Ø R/A

(E )2 2" /1 6" S /A

(E )2 2" /1 6" R /A

(E)8"Ø S/A

(E)4B-6

(E)10"x8" S/A

(E)8"x4" S/A

(E )8 "x 4" S /A

(E )5 "Ø

S /A

(E)6"x6" S/A

(E )6 "x 6" S /A

(E )5 "Ø

S /A

(E)5"Ø S/A

(E)10"x8" S/A

(E)8"Ø S/A

(E)4B-7

(E)10"x8" S/A

(E)10"x8" S/A

(E )8 "Ø

S /A

(E )8 "Ø

S /A

(E)4B-9

(E)14"Ø S/A

(E)4B-10

(E )1 6" Ø R /A

(E )1 2" Ø R /A

(E)8"x8" R/A

(E )6 "Ø

R /A

(E )8 "Ø

R /A

(E)16"x8" R/A(E)8"Ø R/A

(E )6 "Ø

R /A

(E)12"x10" R/A

(E )1 2" x1 0" R /A

(E )6 "Ø

R /A

(E )1 0" Ø R /A

(E)6"Ø R/A

(E )1 4" Ø S /A

(E)6"Ø S/A

(E)4B-13

(E)10"x6" S/A

(E )1 0" x6 S /A

(E)8"Ø S/A

(E)6"Ø S/A (E)4B-14

(E)8"x8" S/A

(E )8 "Ø

S /A

(E )5 "Ø

S /A

(E)8"Ø S/A

(E)4B-15

(E)10"x14" S/A

(E )1 0" x1 4" S /A

(E)10"x14" S/A

(E)12"Ø S/A

(E )8 "Ø

S /A

(E )1 2" Ø S /A

(E)6"Ø S/A

(E)4B-16

(E )1 2" x6 S /A

(E )8 "Ø

S /A

(E)8"Ø S/A

(E)8"x8" R/A

(E )6 "Ø

R /A

(E)12"x10" R/A

(E )1 2" x1 0" R /A

(E )1 0" x1 0" R /A

(E)10"Ø R/A

(E)6"Ø R/A

(E)8"Ø R/A

(E)AHU-40

(E )1 2" Ø S /A

(E )1 4" Ø S /A

(E )1 0" Ø R /A

(E )1 2" x1 0" R /A

(E)4B-9

(E)22"Ø S/A

(E )2 2" Ø S /A

(E )2 2" Ø R /A

(E)10"Ø S/A

(E)10"Ø S/A

(E)10"Ø S/A(E)12"Ø S/A

(E )1 2" Ø S /A

(E )1 2" Ø S /A

(E)10"Ø R/A

(E )1 4" Ø S /A

(E )2 2" /1 6" S /A

(E)6"Ø S/A

(E )1 0" Ø R /A

MD103

MD103

J J

H H

MD103

MD103

MD103(E) 1 1/4" CD

Level 5

106' - 10"

4 Interstitial -

Mechanical

98' - 0"

(E)AHU-40

(E)10"Ø R/A (E)10"Ø

(E)22"Ø (E)22"Ø S/A

(E) 1" HW

EXISTING MECHANICAL AND

ELECTRICAL TO REMAIN ACTIVE

(E) 1" HW

(E) 1 1/4" CD

(E)10"x12" R/A

10"Ø R/A

8"x4" R/A 6"Ø R/A

Level 5

106' - 10"

4 Interstitial -

Mechanical

98' - 0"

(E) 1" HW

(E)AHU-40

(E)22"Ø R/A

(E)10"Ø S/A

EXISTING MECHANICAL AND

ELECTRICAL TO REMAIN ACTIVE

(E) 1" HW

(E) 1 1/4" CD

(E)12"Ø S/A

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

FOURTH INTERSTITIAL HVAC

DEMOLITION FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

MD103

516-19-111

JMK JSW06/25/2021

TRUE

NORTH

PLAN

NORTH

0 4' 8'2'

1/4" = 1'-0"MD103

1 FOURTH FLOOR INTERSTITIAL HVAC DEMOLITION PLAN

MD103 DEMOLITION NOTES

NOTE

NUMBER NOTE TEXT

1 REMOVE 1" COPPER BALL VALVE AND INSTALL NEW COPPER PIPING AND

RE-INSULATE.

2 REMOVE EXISTING RETURN AIR DUCT FROM AIR HANDLING UNIT TO THE

EXTENT INDICATED.

3 REMOVE EXISTING SUPPLY AIR DUCT FROM AIR HANDLING UNIT TO THE

EXTENT INDICATED.

4 AHU-40 WILL REMAIN IN PLACE.

5 REMOVE APPROXIMATLY 2'-0" OF 1" COPPER PIPE TO PREPARE TO

INSTALL RELOCATED BALL VALVE.

6 REMOVE CONDENSATE PIPING TO EXTENT INDICATED.

0 4' 8'2'

1/4" = 1'-0"MD103

2 FOURTH FLOOR INTERSTITIAL HVAC DEMOTION PLAN

0 4' 8'2'

1/4" = 1'-0"MD103

3 FOURTH FLOOR INTERSTITIAL HVAC DEMOLITION PLAN

NOT TO SCALEMD103

6 AHU-40 ELEVATION VIEW 3

NOT TO SCALEMD103

4 AHU-40 ELEVATION VIEW 1

NOT TO SCALEMD103

5 AHU-40 ELEVATION VIEW 2

KEY PLAN B100

E L E V .

P - 1 P - 2

E L E V .

P - 3

E L E V .

E L E V .

S - 6S - 5

E L E V .E L E V .

S - 4

E L E V

S - 7

E L E V

S - 8

E L E V

S - 9

E L E V

S - 1 1

E L E V

S - 1 2

E L E V

S - 1 0

AD

B C

1 Interstitial -

Mechanical

14' - 0"

Level 2

22' - 10"

(E)AHU-34

12"x30" S/A

20"x30" R/A

"x R /A

MINIMUM 2" AFF

PROVIDE SUPPORT

RETURN AIR

PLENUM

NEW AUX

DRAIN PAN

NEW RATED

WALL

FD

10"x10" ACCESS DOOR

ON SIDE OF DUCT

16"x16" ACCESS DOOR ON SIDE OF

DUCT. TYPICAL OF BOTH SIDES OF

RETURN DUCT.

2" CWS/R TO

REMAIN

FD

20"x30" R/A

G

30"x20" FLEXIBLE

CONNECTOR

26"x40" R/A

APPROX

1' - 0"

HORIZONTAL OFFSET IN WALL;

CORDINATE EXACT LOCATION

WITH DUCT AND PIPING.

AD

AD

(E)22"Ø R/A

(E)32"Ø R/A

(E)28"Ø R/A

(E )1 6" Ø R /A

(E )1 2" Ø R /A

(E)28"Ø S/A

(E )1 6" Ø S /A

(E)18"Ø S/A

(E )1 2" Ø S /A

(E)24"Ø S/A

(E )2 5" /1 2" S /A

(E)1H-70

(E )8 "Ø

S /A

(E )1 4" Ø S /A

(E)1H69

(E)10"x12" S/A

(E )8 "x 8" S /A

(E)8"Ø S/A

(E)5"Ø S/A

(E)5"Ø S/A

(E )1 0" x8 S /A

(E )2 5" /1 2" R /A

(E )1 2" Ø R /A(E)10"Ø R/A

(E)6"Ø R/A

(E)10"Ø R/A

(E )1 4" Ø R /A

(E)6"Ø R/A

(E )1 8" Ø R /A

(E)8"Ø R/A

(E )1 6" Ø S /A

(E)8"Ø S/A

(E)1H-82

(E)16"x8" S/A

(E )8 "x 8" S /A

(E )8 "Ø

S /A

(E)1H-82A

(E)8"x8" R/A

(E)10"x4" R/A

(E)6"Ø R/A

(E )1 0" Ø R /A

(E)1H-85

(E )1 0" Ø S /A

(E)1H-86

(E)1H-87

(E)10"Ø S/A

(E)1H-88

(E )1 0" Ø S /A

(E)10"Ø R/A

(E )1 8" Ø R /A

(E )1 0" Ø S /A

(E )1 0" Ø R /A

(E )1 2" Ø S /A

(E)6"Ø S/A

(E)6"Ø S/A

(E)18"Ø S/A

(E )1 8" Ø R /A

(E )2 5" /1 2" R /A

(E)28"Ø R/A

(E )1 2" Ø S /A

(E )1 2" Ø R /A

(E)8"x8" S/A

(E)AHU-34

(E )3 0" x1 2" S /A

(E )3 0" x2 0" R /A

M101

T .O .D (7 6"

B .O .D 7' 0"

6" Ø R /A

60"x14"

(E )1 2" Ø S /A

(E )1 2" Ø R /A

(E )6 "Ø

S /A

(E)6"Ø S/A

(E)1H-82A

6"Ø S/A

8" Ø R /A

RETURN AIR

PLENUM

NEW AUX

DRAIN PAN

R

IS

E

R

IS

E

(E) 2" CWR

(E) 2" CWS

SEAL AND FIRE

CAULK PIPING

"x R /A

FD

FD

AD

G.8 G.8

G G

F.6 F.6

F.2 F.2

F.1 F.1

16"x16" ACCESS DOOR

ON BOTH SIDES OF

RETURN DUCT

SERVICE

ISLE

SERVICE

ISLE

(E)6"Ø S/A

FD

AD

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

FIRST FLOOR INTERSTITIAL HVAC NEW

WORK FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

M101

516-19-111

JMK JSW06/25/2021

0 4' 8'2' 1/4" = 1'-0"M101

2 FIRST FLOOR NEW WORK INTERSTITIAL MECHANICAL - SECTION

0 4' 8'2' 1/4" = 1'-0"M101

1 FIRST FLOOR INTERSTITIAL NEW HVAC PLAN

M101 NEW WORK NOTES

NOTE

NUMBER NOTE TEXT

1 CONTRACTOR SHALL PROVIDE NEW CONNECTION TO AHU-34. PROVIDE

FLEXIBLE CONNECTOR AT UNIT CONNECTION AND RE-WORK DUCTWORK

AND TRANSITION TO MAKE CONNECTION WITH EXISTING SUPPLY AIR

DUCT.

2 CONTRACTOR SHALL CONNECT RETURN AIR PLENUM AND AHU-34 WITH

BELLMOUNTH CONNECTION. ROUTE AND CONNECT RETURN AIR DUCT

UNDER UNIT TO CREATE SERVICE AISLE AS INDICATED. PROVIDE 45

DEGREE CONNECTION AT PLENUM CONNECTION AND RELOCATE ALL

HANGERS AND SUPPORTS REQUIRED. PROVIDE FLEXIBLE CONNECTOR

IN RETURN DUCT AS INDICATED.

3 RECONNECT EXISTING RETURN AIR DUCT FROM BELOW TO NEW

RETURN AIR DUCT, FULL SIZE. (SIZE INDICATED IS APPROXIMATE.)

4 RECONNECT EXISTING TU-1H-82A TO RETURN AIR DUCT TO PROVIDE

VENTILATION AIR TO AHU-34 AS INDICATED. CONTRACTOR TO PROVIDE

FULL SIZE AS EXISTING. (SIZE INDICATED IS APPROXIMATE.)

5 REMOVE AND CAP EXISTING RETURN AIR DUCT TO CREATE A SERVICE

CLEARANCE AISLE. REMOVE ANY HANGERS AND SUPPORTS REQUIRED.

6 ROUTE NEW RETURN AIR DUCT HIGH (MIN 7’-0” A.F.F.) FROM EXISTING

RETURN AIR DUCT TO EXISTING FLOOR PENETRATION OF FLOOR

BELOW. REMOVE ANY HANGERS AND SUPPORTS REQUIRED. SUPPORT

DUCT FROM ABOVE.

7 OFF-SET SUPPLY AIR DUCT AROUND STRUCTURE TO COORDINATE WITH

NEW RETURN DUCT ROUTING.

8 PROVIDE NEW SUPPLY CONNECTION, FULL SIZE OF UNIT CONNECTION,

THROUGH WALL WITH FIRE DAMPER. TRANSITION TO 30”X12” DUCT, FULL

SIZE. (SIZE INDICATED IS APPROXIMATE)

9 ALL UTILITIES AROUND AND ABOVE UNIT TO REMAIN ACTIVE AND IN

OPERATION. SEAL AROUND ALL MECHANICAL PENETRATIONS.

TRUE

NORTH

PLAN

NORTH

F. 5

F. 2

F

E. 6

H

G. 7

G. 5

252423222120

J

D

E

15 16 17 18 19

D. 4

ROOF

ROOF

KEY PLAN B100

AD

B C

(E)34"Ø S/A

(E)40"Ø R/A

(E)34"Ø S/A

(E)32"Ø R/A

(E)14"Ø S/A

(E)30"Ø R/A

(E)5"Ø S/A

(E)2E-11

(E)6"x6" S/A

(E)6"Ø S/A

(E)10"Ø S/A

(E)2E-10

(E )1 2" Ø S /A

(E )1 2" Ø R /A

(E)6"x6" S/A

(E )1 2" Ø S /A

(E)2E-9

(E)8"Ø S/A

(E )1 4" Ø R /A

(E )2 1" /1 2" S /A

(E )8 "x 4" S /A

(E )1 5" /1 2" S /A

(E)2E-8

(E )5 "Ø

S /A

(E )8 "x 4" S /A

(E)8"x4" S/A

(E )5 "Ø

S /A

(E)10"Ø R/A

(E)2E-7

(E )8 "Ø

S /A

(E )1 4" Ø R /A

(E )1 5" /1 2" S /A

(E )1 2" x1 0" S /A

(E)2E-6

(E)2E-5

(E)5"Ø S/A

(E )8 "Ø

S /A

(E)12"Ø R/A

(E)10"x8" S/A

(E )1 2" Ø S /A

(E)32"Ø R/A

(E)6"Ø R/A

(E)8"x6" S/A

(E)16"x4" S/A

(E)2E-4 (E)5"Ø S/A

(E )1 2" Ø R /A(E

)8 "Ø

S /A

(E )8 "x 4" S /A

(E)10"Ø R/A

(E )1 4" Ø R /A

(E )1 4" Ø R /A

(E )1 0" Ø R /A

(E )1 6" x1 2" S /A

(E)16"x16" R/A

(E )1 6" x1 6" R /A

(E)AHU-36

(E)A36-2

(E )1 6" x1 2" R /A

(E )2 E -1 A

M A K E -U P

A

IR

(E )1 2" Ø R /A

(E)16"x16" S/A

(E)12"x10" S/A

(E)8"Ø S/A

(E)8"Ø S/A

(E)8"Ø S/A

(E)A36-1

(E)8"Ø S/A

(E)40"x24" R/A

(E)10"Ø R/A

(E)12"Ø R/A

(E)8"Ø S/A

(E)8"Ø S/A

(E)A36-4

(E)10"Ø S/A

(E )5 "Ø

S /A

(E )1 0" Ø S /A

FD FD

AD

AD

AD

6"Ø S/A

FD

FD

DRAIN PAN

M102

M102

AD

(E )8 "Ø

S /A

K K

J J

2" CWS/R TO

REMAIN

1" DHW/R TO

REMAIN

2 Interstitial -

Mechanical

42' - 0"

Level 3

50' - 10"

2" CWS/R

AD

(E)16"x16" S/A(E)12"x16" S/A (E)AHU-36

(E)24"x40" R/A

(E)12"Ø S/A

(E)A36-1

(E)12"Ø S/A

(E)A36-2

(E)14"Ø R/A

FD

FD

(E)8"Ø S/A

(E)10"Ø R/A

(E)8"Ø S/A

SEAL AND FIRE CAULK

ALL PIPES COMING

THROUGH NEW WALL

EXISTING

DRAIN PAN

TO REMAIN

NEW RATED

WALL

K

1" DHW/R

TO REMAIN

2 Interstitial -

Mechanical

42' - 0"

Level 3

50' - 10"

6"Ø S/AAD6"Ø S/A

(E)8"Ø S/A

(E)A36-1 (E)2E-1A

MAKE-UP

AIR

FD

(E)8"Ø S/A

2" CWS/

CWR

NEW RATED WALL(E)AHU-36

(E)16"x16" R/A

(E )8 "Ø

S /A

(E)10"Ø S/A

1" DHW/R

TO REMAIN

FIRE DAMPER IN NEW

WALL. SEE FLOOR PLAN

EXISTING

DRAIN PAN

P

R O

F E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

SECOND FLOOR INTERSTITIAL HVAC

NEW WORK FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

M102

516-19-111

JMK JSW06/25/2021

0 4' 8'2' 1/4" = 1'-0"M102

2 SECOND FLOOR INTERSTITIAL NEW HVAC PLAN

M102 NEW WORK NOTES

NOTE

NUMBER NOTE TEXT

1 RELOCATE EXISTING SUPPLY AIR TAKE OFF TO A36-2 TO BE INSIDE NEW

RATED ENCLOSURE.

2 ADD FIRE DAMPER WITH ACCESS PANEL TO DUCTS AT PENETRATION OF

NEW RATED ENCLOSURE.

3 ALL UTILITIES AROUND AND ABOVE UNIT TO REMAIN ACTIVE AND IN

OPERATION. SEAL AROUND ALL MECHANICAL PENETRATIONS.

0 4' 8'2' 1/4" = 1'-0"M102

3 SECOND FLOOR INTERSTITIAL NEW HVAC PLAN

0 4' 8'2' 1/4" = 1'-0"M102

4 SECOND FLOOR INTERSTITIAL NEW HVAC PLAN

2 3

TRUE

NORTH

PLAN

NORTH

G . 5

2 72 6

2 52 42 32 22 12 0

F . 5

E . 6

F . 3

F

E

D . 4

D

1 91 81 71 61 5

1 41 3

H

J

K

G. 7

2 72 61 41 3

H

DN

(E)40"/36" S/A(E)36"Ø S/A(E)34"Ø S/A

(E)52"/40" R/A(E)44"/40" R/A(E)42"/40" R/A

(E )2 2" /1 6" R /A(E)10"x8" R/A

(E)6"Ø R/A

(E)6"Ø R/A

(E )2 2" /1 6" S /A(E

)2 2" /1 6" R /A

(E)8"Ø S/A

(E)4B-6

(E)10"x8" S/A

(E)8"x4" S/A

(E )8 "x 4" S /A

(E)6"x6" S/A

(E )6 "x 6" S /A

(E )5 "Ø

S /A

(E)10"x8" S/A

(E)4B-7

(E)10"x8" S/A

(E)10"x8" S/A

(E )8 "Ø

S /A

(E)4B-9(E)14"Ø S/A

(E)4B-10

(E )1 6" Ø R /A

(E )1 2" Ø R /A

(E)8"x8" R/A

(E )6 "Ø

R /A

(E )8 "Ø

R /A

(E)16"x8" R/A

(E )8 "Ø

R /A

(E)8"Ø R/A

(E )6 "Ø

R /A

(E)12"x10" R/A

(E )1 2" x1 0" R /A

(E)10"Ø R/A

(E )6 "Ø

R /A

(E)8"Ø S/A

(E)4B-15

(E)10"x14" S/A

(E )1 0" x1 4" S /A

(E)10"x14" S/A

(E)12"Ø S/A

(E )8 "Ø

S /A

(E )1 2" Ø S /A

(E)6"Ø S/A

(E)4B-16

(E )1 2" x6 S /A

(E )8 "Ø

S /A

(E)8"Ø S/A

(E)8"x8" R/A

(E )6 "Ø

R /A

(E )6 "Ø

R /A

(E)12"x10" R/A

(E )1 2" x1 0" R /A

(E )1 0" x1 0" R /A

(E)10"Ø R/A

(E)6"Ø R/A

(E)8"Ø R/A

(E)AHU-40

(E )1 2" Ø S /A

(E )1 0" Ø R /A

(E )1 2" x1 0" R /A

(E)4B-9

(E)22"Ø S/A

(E )2 2" Ø S /A

(E)10"Ø S/A

(E )2 2" Ø R /A

(E)4B-8

(E)10"Ø R/A

(E)16"x8" R/A

(E)12"x6" S/A

(E)10"Ø S/A

(E )1 2" Ø S /A

(E )1 2" Ø S /A

(E)10"Ø S/A(E)12"Ø S/A

(E )1 6" Ø S /A

(E )2 2" /1 6" S /A

(E )1 4" Ø S /A

58"x32" R/A

M103

M103

AD

"x S /A

FD

FD

J J

H H

AD

AD

(E) 1" HW

(E) 1 1/4" CD

Level 5

106' - 10"

4 Interstitial -

Mechanical

98' - 0"

(E) 1" HW

1" SHUTOFF

(E)AHU-40

32"x58" R/A

10"Ø R/A

(E) 1" HW

AD

FD

FD

(E) 1 1/4" CD

AD

Level 5

106' - 10"

4 Interstitial -

Mechanical

98' - 0"(E) 1" HW

AD

(E) 1" HW

(E)22"Ø R/A

(E)10"Ø S/A

(E)10"Ø R/A

58"X32" R/A

PLENUM

NEW RATED WALL

(E)12"Ø S/A

(E) 1 1/4" CD

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

FOURTH FLOOR INTERSTITIAL HVAC NEW

WORK FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

M103

516-19-111

JMK JSW06/25/2021

TRUE

NORTH

PLAN

NORTH

0 4' 8'2' 1/4" = 1'-0"M103

1 FOURTH FLOOR INTERSTITIAL HVAC PLAN

M103 NEW WORK NOTES

NOTE

NUMBER NOTE TEXT

1 PROVIDE NEW RETURN AIR PLENUM FULL SIZE UNIT CONNECTION. (SIZE

INDICATED IS APPROXIMATE.) PROVIDE FIRE DAMPER AND ACCESS

DOOR.

2 RECONNECT EXISTING RETURN AIR DUCT TO NEW PLENUM WITH

BELLMOUTH CONNECTION.

3 PROVIDE NEW SUPPLY AIR DUCT FULL SIZE OF UNIT CONNECTION

THROUGH RATED ENCLOSURE. TRANSITION TO EXISTING DUCT WORK

AS INDICATED. SIZE INDICATED IS APPROXIMATE. CONTRACTOR TO

FIELD VERIFY.

4 RELOCATE RETURN AIR TEMPATURE SENSOR AND ASSOCIATED

CONTROL WIRING TO RETURN AIR PLENUM OUTSIDE NEW RATED

ENCLOSURE.

5 AHU-40 WILL REMAIN IN PLACE.

6 RELOCATE SMOKE DETECTOR AND ASSOCIATED CONTROL WIRING TO

SUPPLY AIR DUCT OUTSIDE NEW RATED ENCLOSURE.

7 INSTALL NEW BALL VALVE. SEE MD104 FOR BALL VALVE THAT IS TO BE

RELOCATED.

8 INSTALL NEW 1" DIA COPPER PIPING AND RE-INSULATE.

9 INSTALL NEW 1 1/4" DIA CONDENSATE PIPE AND RE-INSULATE.

10 ALL UTILITIES AROUND AND ABOVE UNIT TO REMAIN ACTIVE AND IN

OPERATION. SEAL AROUND ALL MECHANICAL PENETRATIONS.

11 14"x14" ACCESS DOOR ON BOTH SIDES OF DUCT.

0 4' 8'2' 1/4" = 1'-0"M103

2 FOURTH FLOOR INTERSTITIAL HVAC PLAN

0 4' 8'2' 1/4" = 1'-0"M103

3 FOURTH FLOOR INTERSTITIAL NEW HVAC PLAN

KEY PLAN B100

P102E

P102D

P102B

P102A

P102C

ELEV.

P-1 P-2

ELEV.

P-3

ELEV.

ELEV.

S-6S-5

ELEV.ELEV.

S-4

ELEV.

MH-10

ELEV.

S-7

ELEV.

S-8

ELEV.

S-9

ELEV.

MH-11 MH-12

ELEV.

R O O F

R O O F

F.5

G.5

G

47'- 2"

D N

252423222120

F. 5

G. 5

G

E. 6

F. 3

F

E

D. 4

D

1918171615

H

J

K

G. 7

KEY PLAN B100

(E)36"x36" E/A

(E )8 0" x1 6" E /A

FD

(E )2 4" x1 8" E /A

(E )8 0" x1 6" E /A

(E )4 0" x3 6" E /A

FD

(E)36"x36" E/A

(E )8 0" x1 6" E /A

(E )8 0" x1 6" E /A

(E )4 4" x3 6" E /A

FD

(E)32"x24" E/A

(E )8 0" x1 6" E /A

(E )8 0" x1 6" E /A

(E )3 2" x2 4" E /A

FD

FD

(E )2 4" x1 8" E /A

(E )8 0" x1 6" E /A

(E )8 0" x1 6" E /A

(E)36"x36" E/A

FD

FD

(E )4 6" x3 6" E /A

(E)24"x18" E/A

AD

AD

M104

M104

M104

M104

AD

AD

(E)36"x36" E/A

AD

AD

AD

(E)

(E)

(E)

(E)

(E)

(E)

(E)

5 Interstitial -

Mechanical

129' - 0"

Level 6 Penthouse

145' - 0"

(E)36"x46" E/A

(E)80"x16" E/A

FD

(E) 80"X16" E/A

AD

(E)

5 Interstitial -

Mechanical

129' - 0"

Level 6 Penthouse

145' - 0"

(E)80"x16" E/A

(E)24"x32" E/A FD

(E) 80"X16" E/A

G.8G

AD

(E)

5 Interstitial -

Mechanical

129' - 0"

Level 6 Penthouse

145' - 0"

(E)36"x44" E/A

(E)80"x16" E/A

FD

(E) 80"X16" E/A

AD

(E)

5 Interstitial -

Mechanical

129' - 0"

Level 6 Penthouse

145' - 0"

(E)36"x40" E/A(E)18"x24" E/A

(E)80"x16" E/A

FD FD

(E) 80"X16" E/A

AD

AD

(E)(E)

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

FIFTH FLOOR INTERSTITIAL HVAC NEW

WORK FLOOR PLAN

RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

M104

516-19-111

JMK JSW06/25/2021

TRUE

NORTH

PLAN

NORTH

1 2

1 3

0 4' 8'2' 1/8" = 1'-0"M104

1 FIFTH FLOOR INTERSTITIAL NEW HVAC PLAN

M104 NEW WORK NOTES

NOTE

NUMBER NOTE TEXT

1 REMOVE EXISTING DUCT ACCESS DOOR. PATCH, SEAL, AND REPAIR

EXISTING DUCTWORK.

2 PROVIDE NEW 18"x18" DUCT ACCESS DOOR.

3 PROVIDE NEW 14"x14" DUCT ACCESS DOOR.

0 4' 8'2' 1/4" = 1'-0"M104

5 FIFTH FLOOR INTERSTITIAL NEW HVAC PLAN

0 4' 8'2' 1/4" = 1'-0"M104

4 FIFTH FLOOR INTERSTITIAL NEW HVAC PLAN

0 4' 8'2' 1/4" = 1'-0"M104

3 FIFTH FLOOR INTERSTITIAL NEW HVAC PLAN

0 4' 8'2' 1/4" = 1'-0"M104

2 FIFTH FLOOR INTERSTITIAL NEW HVAC PLAN

1 1

2 2

SECTION"A-A"

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET HANDLE INSIDE

FLEXIBLE

WAHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

WALL OR CEILING

2"x2"x1/4" ANGLE IRON

SIDES, MITERED AND

WELDED AT CORNERS.

OMIT FRAME ON ROOM

SIDE OF WALL WHEN

CONNECTING DIRECTLY.

FACTORY

FABRICATE 16

GAUGE SLEEVE.

DUCT

1" MINIMUM ALL ROUND

1/4" TO 1/2" CLEARANCE

FUSIBLE LINK SET AT 165 F°

'S' LOCK DUCT CONNECTIONS

DUCT ACCESS PANEL

FOLDING BLADE FIRE

DAMPER IN TYPE 'B'

FRAME, EXCEPT USE

TYPE 'C' WHEN

CONNECTING DIRECTLY

TO ROUND DUCT.

NOTES:

1. HORIZONTAL FIRE DAMPER SIMILAR. PROVIDE SPRING LOADED CURTAIN

WITH FUSIBLE LINK SET AT 165°F.

2. DETAIL FOR GENERAL GUIDANCE, INSTALL EACH FIRE DAMPER IN STRICT

ACCORDANCE WITH INSTALLATION INSTRUCTIONS PACKED WITH FIRE

DAMPER TO ENSURE UL RATING.

6"6"

DRYWALL PARTITION

INSULATED PIPE

FIRESTOP MATERIAL PIPE SLEEVE

6"6"

MASONRY PARTITION

3/4" APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

PARTITION SUPPORT

(ENCIRCLING PIPE)

1/2" 1/2" 1 1/2"

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION ON

FAN SIDE

WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED. 6" NOMINAL WITH

MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" DRAW BAND

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

5/16" FLANGE

DUCT

SHEET METAL SCREWS ON 12"

CENTERS

RIVET ON 4"

CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

1" FLANGE & HEMALTERNATE

POSITION OF

BOLT 1 1/2" POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1 1/2" MIN. TO 3" MAX. INSTALLED. 6" NOMINAL WITH

MATERIAL TAUTFLANGED

CONNECTION ON

FAN SIDE

WASHER

FLEXIBLE MATERIAL AS

SPECIFIED

P R

O F

E

S S

I ONA L

EN

G

I N

E E

R

J E R

EM

Y

M. KNOW

L E

SL

I C ENS E

F L O R I D

A

No. 90210

STATE OF

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

DUCTWORK AND PIPING DETAILS RESOLVE STATEMENT OF

CONDITIONS DEFICIENCIES

BAY PINES, FL

M501

516-19-111

JMK JSW06/25/2021

0 4' 8'2'

NOT TO SCALEM501

1 ACCESS PANEL AND DOOR DETAIL

0 4' 8'2'

NOT TO SCALEM501

2 FIRE DAMPER DETAIL

0 4' 8'2' 12" = 1'-0"M501

3 PIPE PENETRATION OF FIRE/SMOKE BARRIERS

0 4' 8'2' 12" = 1'-0"M501

4 FLEXIBLE CONNECTION RECTANGULAR/ROUND

Sheets
M001 - LEGENDS, ABBREVIATIONS, AND NOTES
M101 - FIRST FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN
M102 - SECOND FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN
M103 - FOURTH FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN
M104 - FIFTH FLOOR INTERSTITIAL HVAC NEW WORK FLOOR PLAN
M501 - DUCTWORK AND PIPING DETAILS
MD101 - FIRST FLOOR INTERSTITIAL HVAC DEMOLITION FLOOR PLAN
MD102 - SECOND FLOOR INTERSTITIAL HVAC DEMOLITION FLOOR PLAN
MD103 - FOURTH INTERSTITIAL HVAC DEMOLITION FLOOR PLAN