BID DRAWINGS SUMMARY
This document comprises the comprehensive bid drawings for Project 550-25-108, a bathroom renovation project at VA Danville Medical Center, Building 103. The project involves the phased renovation of five bathroom areas totaling approximately 868 square feet across five distinct rooms: Women's Shower/Laundry (136C), Male Restrooms (159C, 160C, 106B, 107B, 106C, 107C), and a Bariatric Stall (107Ca). The work is organized into four sequential phases, with each phase requiring full completion and operational status before the next phase begins. The project incorporates strict infection control protocols, including temporary fire-rated smoke barrier walls, temporary infection control plastic barriers, and continuous coordination with facility personnel to maintain operations in an occupied healthcare facility. All work must comply with NFPA codes, VA design manuals, and healthcare facility guidelines, including provisions for fire suppression system modifications, fire alarm system extensions, plumbing fixture replacements, mechanical ventilation upgrades, and complete electrical system updates with both normal and emergency power considerations.
The bid documents specify detailed requirements across all construction trades including demolition of existing fixtures and finishes, installation of new porcelain tile flooring and wall finishes, provision of ADA-compliant fixtures (water closets, lavatories, showers), new exhaust ventilation systems with four roof-mounted fans, fire protection sprinkler modifications, fire alarm device relocation and additions, plumbing rough-in modifications for domestic water and sanitary waste, and electrical work including new LED lighting fixtures, receptacles, and nurse call system integration. Contractor responsibilities include hazardous materials abatement (asbestos-containing pipe insulation and lead-containing ceramic tile estimated at approximately 130 fittings and 9,680 square feet), complete coordination among trades to avoid conflicts, maintenance of fire and smoke ratings for existing partitions, phasing of construction to accommodate occupied facility operations with work limited to 8:00 AM to 5:00 PM, and comprehensive testing and commissioning of all new systems prior to project completion.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 103 KEY PLAN
MALE RESTROOM
159C & 160C
WOMEN'S SHOWER & LAUNDRY
136C
MALE RESTROOM
106C & 107C
MALE RESTROOM
106B & 107B
N
A. ALTERNATE A - ELIMINATE ALL WORK IN MALE RESTROOMS 106C AND 107C
NO WORK TO OCCUR IN MALE RESTROOM 106C AND 107C. RESTROOM TO
REMAIN EXISTING.
B. ALTERNATE B - ELIMINATE ALL WORK IN MALE RESTROOMS 106B AND 107B
NO WORK TO OCCUR IN MALE RESTROOMS 106B AND 107B. RESTROOMS TO
REMAIN EXISTING.
C. ALTERNATE C - ELIMINATE ALL WORK IN MALE RESTROOMS 159C AND 160C
NO WORK TO OCCUR IN MALE RESTROOM 159C AND 160C. RESTROOM TO
REMAIN EXISTING.
BID ITEM #1: BASE BID TO INCLUDE ALL WORK.
BID ITEM #2: ALL WORK AS DESCRIBED FOR BID ITEM #1 ABOVE MINUS THAT
PORTION OF WORK SHOWN AS ALTERNATE A.
BID ITEM #3: ALL WORK AS DESCRIBED FOR BID ITEM #1 ABOVE MINUS THAT
PORTION OF WORK SHOWN AS ALTERNATE A AND B.
BID ITEM #4: ALL WORK AS DESCRIBED FOR BID ITEM #1 ABOVE MINUS THAT
PORTION OF WORK SHOWN AS ALTERNATE A, B, AND C.
STATEMENT OF BID ITEMS
NOTE: CONTRACTOR TO PRICE RESTROOM PHASES SEPARATELY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
GI000
COVER SHEET VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
550-25-108
VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
VA ILLIANA HEALTHCARE SYSTEM
1900 E. Main Street, Danville, IL 61832
BID DOCUMENTS
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI101 LIFE SAFETY PLAN
GC101 INFECTION CONTROL / PHASING PLAN
GC102 BID ALTERNATES
HA101 HAZARDOUS MATERIAL REMOVAL PLAN
ARCHITECTURAL
AE001 ARCHITECTURAL ABBREVIATIONS AND SYMBOLS
AE002 WALL TYPES
AD101 OVERALL DEMOLITION PLANS
AD102 ENLARGED DEMOLITION PLANS
AE101 OVERALL ARCHITECTURAL FLOOR PLANS
AE102 ENLARGED ARCHITECTURAL FLOOR PLANS
AE111 OVERALL REFLECTED CEILING PLANS
AE112 ENLARGED REFLECTED CEILING PLANS
AE600 DOOR SCHEDULE
AI001 FINISH SCHEDULES & LEGENDS
AI102 OVERALL FINISH PLAN
AI103 ENLARGED PLAN & INTERIOR ELEVATIONS
AI104 ENLARGED PLANS & INTERIOR ELEVATIONS
AI105 ENLARGED PLANS & INTERIOR ELEVATIONS
AI106 ENLARGED PLANS & INTERIOR ELEVATIONS
AI500 CASEWORK, FINISH & TRANSITION DETAILS
FIRE PROTECTION
FA001 FIRE ALARM - SYMBOLS, NOTES AND DRAWING INDEX
FA002 FIRE ALARM - GENERAL NOTES
FA003 FIRE ALARM - I/O MATRIX & INTERIM FIRE REQUIREMENTS
FA004 FIRE ALARM - DETAILS
FA100 FIRE ALARM - BUILDING 103 - NEW WORK
FX001 FIRE SUPPRESSION - SYMBOLS, NOTES AND DRAWING INDEX
FX002 FIRE SUPPRESSION - GENERAL NOTES
FX003 FIRE SUPPRESSION - INTERIM FIRE REQUIREMENTS
FX004 FIRE SUPPRESSION - DETAILS
FX100 FIRE SUPRESSION - BUILDING 103 - DEMOLITION
FX101 FIRE SUPPRESSION - BUILDING 103 - NEW WORK
PLUMBING
P001 PLUMBING - SCHEDULES, SYMBOLS, AND DRAWING INDEX
P002 PLUMBING - DETAILS
PD100 PLUMBING - BUILDING 103 - DEMOLITION
PP100 PLUMBING - BUILDING 103 - NEW WORK - SANITARY WASTE
PP101 PLUMBING - BUILDING 103 - NEW WORK - DOMESTIC WATER
MECHANICAL
M001 MECHANICAL - SYMBOLS, NOTES, AND DRAWING INDEX
M002 MECHANICAL - MECHANICAL ABBREVIATIONS
M003 MECHANICAL - DETAILS
M004 MECHANICAL - SCHEDULES & SEQUENCE
MD100 MECHANICAL - BUILDING 103 - DEMOLITION
MD200 MECHANICAL - ROOF PLAN - DEMOLITION
MH100 MECHANICAL - BUILDING 103 - NEW WORK
MH200 MECHANICAL - ROOF PLAN - NEW WORK
ELECTRICAL
E001 ELECTRICAL - SYMBOLS, NOTES, AND DRAWING INDEX
E002 ELECTRICAL - DETAILS
E003 ELECTRICAL - SCHEDULES AND PARTIAL RISER DIAGRAM
E004 ELECTRICAL - PANELBOARD SCHEDULES
E005 ELECTRICAL - PANELBOARD SCHEDULES
ED100 ELECTRICAL - BUILDING 103 - DEMOLITION
ED200 ELECTRICAL - BUILDING 103 ROOF - DEMOLITION
EL100 ELECTRICAL - BUILDING 103 - NEW WORK - LIGHTING
EP100 ELECTRICAL - BUILDING 103 - NEW WORK - POWER
EP200 ELECTRICAL - BUILDING 103 ROOF - NEW WORK - POWER
Contact:CONTACT: CONTACT:
CHARLOTTE ENGINEERS
AVERY STANLEY
MECHANICAL ENGINEER
MECHANICAL, ELECTRICAL,
PLUMBING & FIRE PROTECTION
VA ILLIANA HEALTH CARE SYSTEM
ISELA ARVIZU
COR
BLDG.102, ROOM 106 G
1900 E. MAIN ST.
DANVILLE, IL 61832
p: 217.554.4736 e: ISELA.ARVIZU@VA.GOV
OWNER
GUIDON DESIGN INC.
DYLAN CHRISTENSEN
PROJECT ARCHITECT
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 155 e: DCHRISTENSEN@GUIDON.COM
ARCHITECT
5838 MONROE ROAD
CHARLOTTE, NC 28212
p: 704.531.3000 X 106 e: ACALLAHAN@CHARLOTTEENGINEERS.COM
VICINITY MAP
CAMPUS MAP
N
N
CONTACT:
GUIDON DESIGN INC.
BRANDEN SONGER
PROJECT MANAGER
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 160 e: BSONGER@GUIDON.COM
PROJECT MANAGER
PROJECT CAMPUS
PROJECT AREA:
BUILDING 103
CONTACT:
GUIDON DESIGN INC.
BEENISH AMJAD
INTERIOR DESIGNER
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 166 e: BAMJAD@GUIDON.COM
INTERIOR DESIGNER
Revisions: Date:
FD
FD
FD
FD
FD FD
FD
FD
FD
FD
FD
FD
FD
FD
EXIT
EXIT
EXIT
E X
IT
E X
IT
E X
IT
E X
IT
E X
IT
E X
IT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
WARD 5
WARD 6
WARD 7
WARD 8
WARD 1
WARD 2
WARD 3
WARD 4
103-5
ZONE: 1G HEALTHCARE
SMOKE COMPARTMENT 7,710 SF
103-6
ZONE: 1H HEALTHCARE
SMOKE COMPARTMENT 7,694 SF
103-7
ZONE: 1I HEALTHCARE
SMOKE COMPARTMENT 7,772 SF
103-8
ZONE: 1J HEALTHCARE
SMOKE COMPARTMENT 7,745 SF
WARD 103-1
ZONE: 1A HEALTHCARE
SMOKE COMPARTMENT 7,641 SF
WARD 103-2
ZONE: 1B HEALTHCARE
SMOKE COMPARTMENT 7,681 SF
WARD 103-3
ZONE: 1C HEALTHCARE
SMOKE COMPARTMENT 7,680 SF
WARD 103-4
ZONE: 1D HEALTHCARE
SMOKE COMPARTMENT 7,680 SF
ZONE: 1E HEALTHCARE
SMOKE COMPARTMENT 3,382 SF
ZONE: 1F HEALTHCARE
SMOKE COMPARTMENT 11,570 SF
NO CHANGES TO THE EXISTING LIFE SAFETY PLAN ARE INTENDED AS A PART OF
THIS PROJECT. LIFE SAFETY PLAN DEPICTS THE EXISTING CONDITIONS FOR
CONTRACTOR TO BE ACCOMMODATE WALL RATINGS TO BE MAINTAINED.
CODE ANALYSIS
BUILDING 103 KEY PLAN
MALE RESTROOM
159C & 160C
WOMEN'S SHOWER & LAUNDRY
136C
MALE RESTROOM
106C & 107C
MALE RESTROOM
106B & 107B
N
EXISTING 2 HR FIRE RATED
EXISTING 1 HR FIRE RATED
EXISTING SMOKE PARTITION
WALL RATING LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
GI101
LIFE SAFETY PLAN VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SCALE: 1" = 30'-0"GI101
3 LIFE SAFETY PLAN - B103
SUSTAINABILITY
REFER TO
TIL
STEAM, HEATING, HOT WATER, AND OUTSIDE DISTRIBUTION SYSTEMS May-24
SIGNAGE Mar-23
PLUMBING Feb-24
LIGHTING DESIGN Jan-22
INTERIOR DESIGN Nov-20
HVAC Mar-24
FIRE PROTECTION Nov-23
ESTIMATING CES Mar-11
ELECTRICAL Dec-19
COMMISSIONING AND RETRO COMMISSIONING Nov-13
ASBESTOS ABATEMENT Jul-11
ARCHITECTURAL Aug-14
VA DESIGN MANUALS PG-18-10
CODES AND GUIDELINES REFERENCED WITHIN NFPA AND ICC CODES ARE TO ALSO BE FOLLOWED AND APPLIED TO ALL DESIGN AND CONSTRUCTION. REFER TO VA MANUAL PG-18-3, SPECIFICATIONS FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND REGULATIONS. CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTING WORK COMPLIANT WITH OSHA, OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION STANDARDS.
OSHA, OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION STANDARDS.
SYSTEMS RELATING TO MAINTENANCE OF FACILITIES
BEHAVIORAL HEALTH DESIGN GUIDE 2019 ED.
GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS 2022 ED.
FGI, THE FACILITY GUIDELINES INSTITUTE
VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS
ADAAG, ADA ACCESSIBILITY GUIDELINES
ACCESSIBILITY CODES
STANDARD 188-2018, LEGIONELLOSIS: RISK MANAGEMENT FOR BUILDING WATER SYSTEMS
STANDARD 170-2024, VENTILATION OF HEALTHCARE FACILITIES
ASHRAE STANDARDS, AS REFERENCED WITHIN OTHER CODES INCLUDING, BUT NOT LIMITED TO:
INTERNATIONAL ENERGY AND CONSERVATION CODE 2024 ED.
INTERNATIONA FUEL GAS CODE 2024 ED.
INTERNATIONAL MECHANICAL CODE 2024 ED.
INTERNATIONAL PLUMBING CODE 2024 ED.
INTERNATIONAL BUILDING CODE 2024 ED.
ICC CODES, INTERNATIONAL CODE COUNCIL FULL LISTING OF CURRENT CODES, INCLUDING BUT NOT LIMITED TO:
NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS 2022 ED.
NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION 2024 ED.
NPFA 101 LIFE SAFETY CODE 2024 ED.
NFPA 99 HEALTHCARE FACILITIES CODE 2024 ED.
NFPA 90A STANDARD FOR INSTALLTION FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING
SYSTEMS
2021 ED.
NFPA 80 STANDARD FOR FIRE DOORS AND FIRE WINDOWS 2022 ED.
NFPA 72 FIRE ALARM CODE 2022 ED.
NFPA 70, NEC NATIONAL ELECTRICAL CODE 2023 ED.
NFPA 54, ANSI Z223.1 NATIONAL FUEL GAS CODE 2021 ED
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022 ED.
NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHER 2022 ED.
NPFA, NATIONAL FIRE PROTECTION ASSOCIATION FULL LISTING OF CURRENT CODES, INCLUDING BUT NOT LIMITED TO:
GOVERNING BUIDLING CODES
BUILDING CODES
OTHER
DRINKING FOUNTAINS 0 0
BATHTUB OR SHOWER 5 1
LAVATORIES 15 0
URINALS 4 0
WATER CLOSETS 9 0 2902.1
EXISTING (IN SCOPE) NEW
MINIMUM NUMBER REQUIRED PLUMBING FIXTURES (IBC)
SEISMIC DESIGN CATEGORY C
STRUCTURE...
DEAD END CORRIDOR DISTANCE = >30' EXISTING 1020.5
MINIMUM CORRIDOR WIDTH MIN. WIDTH= 96" EXISTING 1020.3
CORRIDOR RATING 0HR . FIRE RATING EXISTING 1020.2
CORRIDORS
EXIT ACCESS TRAVEL DISTANCE DISTANCE 200' EXISTING 1017.2
COMMON PATH OF TRAVEL DISTANCE 75' EXISTING 1006.2.1
EXITS PER FLOOR 3 EXISTING
MINIMUM NUMBER OF EXITS 1006
EXIT DOOR WIDTH 100X0.3=30" EXISTING 1005.3.2
EXIT STAIR WIDTH N/A 1005.3.1
EGRESS WIDTH PROVIDED 1005
MEANS OF EGRESS -OCCUPANT LOAD FACTOR 1004.5
MEANS OF EGRESS
SHAFT ENCLOSURE RATING 0
ROOF CONSTRUCTION 0
FLOOR CONSTRUCTION 0
NON BEARING WALLS - INTERIOR 0
NON BEARING WALLS - EXTERIOR 0
BEARING WALLS - INTERIOR 0
BEARING WALLS - EXTERIOR 0
STRUCTURAL FRAME 0
FIRE RESISTANT RATING REQUIREMENTS FOR BUILDING
ELEMENTS (HOURS)
FIRE RATING 601
CONSTRUCTION RATING OF BUILDING ELEMENTS.
SMOKE COMPARTMENT YES EXISTING
OCCUPANCY SEPARATION NO 508.4
BUILDING AREA 44,000 UNLIMITED 506.2
BUILDING STORIES 1 UNLIMITED 504.4
BUILDING HEIGHT ABOVE GRADE 55'-0" UNLIMITED 504.3
ACTUAL ALLOWABLE
BUILDING FULLY FIRE SPRINKLERD YES
CONSTRUCTION TYPE TYPE 2-B
BUILDING USE AND OCCUPANCY CLASSIFICATION GROUP I-2 CH. 3
BUILDING INFORMATION IBC ADDITIONAL INFO IBC
1. NFPA 101 primarily addresses life safety and fire protection features while the IBC addresses a wide range of considerations, including, but not limited to, structural strength, seismic stability, sanitation, adequate light and ventilation, and energy conservation. VA buildings must meet the requirements of NFPA 101 and documents referenced by NFPA 101 in order to comply with the accreditation requirements of The Joint Commission.
Therefore, designs shall comply with the requirements of the latest edition of NFPA 101 and documents referenced therein. Design features not addressed by NFPA 101 or documents referenced therein shall comply with the requirements of the latest edition of the IBC or as otherwise addressed in VA Design Manuals. For design features that are addressed by both the IBC as well as NFPA 101 or a document referenced by NFPA 101, the requirements of NFPA 101 or the document referenced by NFPA 101 shall be used exclusively (this applies even if the IBC requirements are different).
2. Conflicts between Nationally Recognized Codes and Standards and VA Requirements – Should a conflict exist between VA requirements and VA adopted nationally recognized codes and standards, the conflict shall be brought to the attention of VA. The resolution of the conflict shall be made by the authority having jurisdiction for VA to ensure a consistency system wide. Conflicts and deficiencies that are inherent to the existing layout and...
VA GOVERNING CODE PROVISIONS PG 18 - 13
BUILDING ADDRESS 1900 E. MAIN STREET, DANVILLE, IL...
BUILDING CODE PROJECT ANALYSIS
FD
FD
FD
FD FD
FD
FD
FD
FD
FD
FD
FD
FD
MALE RESTROOM
159C
WOMEN'S SHOWER/
LAUNDRY
136C
MALE SHOWER &
RESTROOM
107C
MALE RESTROOM
106B
MALE RESTROOM
107B
PHASE 1
PHASE 4
PHASE 2
PHASE 3
CLEAR
6' - 0"
C
LE
A R
6'
C
LE
A R
5'
C
LE
A R
6'
CLEAR
6' - 0"
1 2
1 2
MALE RESTROOM
160C
MALE RESTROOM
106C
PHASING DESCRIPTION
PHASE 1 - RENOVATE WOMEN'S SHOWER/ LAUNDRY 136C
WHILE THIS RESTROOM IS RENOVATED, RESTROOMS
159C AND 160 WILL BE CONVERTED INTO WOMENS
RESTROOMS USING SIGNAGE.
PHASE 2 - RENOVATE MEN'S RESTROOM 159C AND 160C.
PHASE 3 -RENOVATE MALE SHOWER & RESTROOM 106B AND
107B.
PHASE 4 - RENOVATE MALE RESTROOM 106C AND 107C.
NOTE: EACH PHASE TO BE FULLY COMPLETE AND RESTROOM
OPERATIONAL BEFORE NEXT PHASE SHALL BEGIN.
BUILDING 103 KEY PLAN
MALE RESTROOM
159C & 160C
WOMEN'S SHOWER & LAUNDRY
136C
MALE RESTROOM
106C & 107C
MALE RESTROOM
106B & 107B
N
PUBLIC
SIDE
1 HOUR FIRE RATED METAL DOOR ASSEMBLY
AND FRAME WITH SEALS, CARD READER OR
CONTRACTOR CORE PER OWNER'S
PREFERENCE, HARDWARE AND CLOSER
AIR PRESSURE MONITOR
HAND SANITIZER
SEAL ALL EDGES WITH TAPE
SEAL ALL EDGES WITH TAPE
REFER TO TEMPORARY BARRIER TYPE FOR
REQUIRED CONDITION TO STRUCTURE ABOVE
VA / OSHA TEMPORARY SIGNAGE
CONTINUOUSLY ADHERED FIRE
RETARDANT POLY TO FLOOR WITH TAPE
BEAD OF CONT. SEALANT
6 MIL. FIRE RETARDANT POLY
INTERIOR SIDE
CONSTRUCTION
SIDE
CONTINUOUSLY ADHERED 6 MIL. FIRE
RETARDANT POLY TO DECK WITH TAPE
UNDERSIDE OF STRUCTURAL DECK
CEILING
TO DECK
OCCUPIED
SIDE
6-MIL FIRE RETARDANT POLY
INTERIOR SIDE
EXISTING CEILING
CONTINUOUSLY ADHERE 6-MIL. FIRE
RETARDANT POLY TO CEILING WITH TAPE
CONTINUOUSLY ADHERE FIRE
RETARDANT POLY TO FLOOR WITH TAPE
EXISTING DECK
CONSTRUCTION
SIDE
OCCUPIED
SIDE
TO CEILING
CONTINUOUS FIRESAFE SEALANT
TOP AND BOTTOM, & BOTH SIDES
3 1/2" SOUND ATTENUATION BATT.
5/8" TYPE X GYPSUM BOARD, BOTH SIDES
3 5/8" METAL STUD @ 16" O.C. WITH
RUNNER CHANNELS ALONG TOP
AND BOTTOM
CONSTRUCTION
SIDE
PUBLIC
SIDE
6 MIL. FIRE RETARDANT VISQUEEN
MEMBRANE. CONTINUOUSLY ADHERE
TO THE STRUCTURAL DECK ABOVE AND
TO THE FLOOR BELOW WITH TAPE.
UNDERSIDE OF STRUCTURAL DECK
UL LISTING: U465
COORDINATE WITH EXISTING CEILING
CONSTRUCTION ACTIVITY - INFECTION RISK: TYPE C
PATIENT RISK GROUP: HIGH
CLASS OF PRECAUTION MATRIX: IV
1. PROVIDE TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL
CONSTRUCTION PER NFPA 241. REFER TO DETAIL 3/GC101.
2. PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH
CARD READER ACCESS. REFER TO ELEVATION 4/GC101.
3. PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL
CONSTRUCTION. REFER TO DETAIL 2/GC101 AND SPECIFICATION FOR
ADDITIONAL INFORMATION.
A. REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED
BY CLASS IN SPECIFICATION 010110 AND ADDITIONAL INFORMATION.
B. REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE
FOR ADDITIONAL INFORMATION.
C. PROJECT SHALL BE COMPLETED IN 4 PHASES.
D. COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND
FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE
CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE
PROJECT BOUNDARY.
E. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER
WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR
AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY
IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE
APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND
PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA
PROTOCOLS AND PLAN IS APPROVED.
F. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR
AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE
PHASING INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR
PROVIDED CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW
THE FLOOR PLATE OF THE PROJECT BOUNDARY.
G. ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 8:00 AM
AND 5:00 PM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE
CEILINGS ARE TO REMAIN OUTSIDE OF BATHROOMS, CEILING TILES SHALL
BE REMOVED AND STORED IN A SAFE MANOR UNTIL CEILING TILES CAN BE
REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED
BY CONTRACTOR.
H. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED
DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF
OPERATION.
I. WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN
THE HOURS OF 8:00 AM AND 5:00 PM. EVERY EFFORT SHALL BE MADE TO
KEEP NOISE AND VIBRATION TO A MINIMUM.
J. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36"
STICKY WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR
LOCATION. MAT SHALL BE REPLACED OR CLEANED AS NECESSARY
K. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH
TEMPORARY DOOR LOCATION.
L. CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,
MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE
LIQUIDS UP TO 30 GALLONS.
M. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED
WITH 4 MIL. POLY SHEET.
N. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT
BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED
ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED
WITH A LID.
O. ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY
STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE
MATERIALS SHALL NOT BE STORED IN THE FACILITY.
P. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE
PROJECT BOUNDARY.
A. PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT
CONSTRUCTION.
B. CONSTRUCTION WORK BEHIND TEMPORARY CONSTRUCTION PARTITIONS
SHALL BE COMPLETED DURING DAY SHIFTS, 8:00 AM TO 5:00 PM.
COORDINATE WITH COR.
C. REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION
FOR EACH PHASE AND AREA OF WORK.
PHASING GENERAL NOTES
INFECTION CONTROL PLAN NOTES
INFECTION CONTROL GENERAL NOTES
INFECTION CONTROL PROJECT INFORMATION
TEMPORARY WALLS. SEE PLAN AND PLAN NOTES
TEMPORARY CONSTRUCTION ACCESS DOORS
BEYOND PROJECT BOUNDARY
IC / PHASING LEGEND
SCALE: 1 1/2" = 1'-0"GC101
TEMPORARY 1 HR FIRE RATED SMOKE BARRIER
WALL CONSTRUCTION NFPA 241
SCALE: 1/4" = 1'-0"GC101
4 TEMPORARY WALL CONSTRUCTION ELEVATION
SCALE: 1 1/2" = 1'-0"GC101
2 TEMPORARY INFECTION CONTROL PLASTIC BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
GC101
INFECTION CONTROL /
PHASING PLAN
VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SCALE: 1/16" = 1'-0"GC101
1 CONSTRUCTION PHASING PLAN - B103
A. ALTERNATE A - ELIMINATE ALL WORK IN MALE RESTROOMS 106C AND 107C
NO WORK TO OCCUR IN MALE RESTROOM 106C AND 107C. RESTROOM TO
REMAIN EXISTING.
B. ALTERNATE B - ELIMINATE ALL WORK IN MALE RESTROOMS 106B AND 107B
NO WORK TO OCCUR IN MALE RESTROOMS 106B AND 107B. RESTROOMS TO
REMAIN EXISTING.
C. ALTERNATE C - ELIMINATE ALL WORK IN MALE RESTROOMS 159C AND 160C
NO WORK TO OCCUR IN MALE RESTROOM 159C AND 160C. RESTROOM TO
REMAIN EXISTING.
BID ITEM #1: BASE BID TO INCLUDE ALL WORK.
BID ITEM #2: ALL WORK AS DESCRIBED FOR BID ITEM #1 ABOVE MINUS THAT
PORTION OF WORK SHOWN AS ALTERNATE A.
BID ITEM #3: ALL WORK AS DESCRIBED FOR BID ITEM #1 ABOVE MINUS THAT
PORTION OF WORK SHOWN AS ALTERNATE A AND B.
BID ITEM #4: ALL WORK AS DESCRIBED FOR BID ITEM #1 ABOVE MINUS THAT
PORTION OF WORK SHOWN AS ALTERNATE A, B, AND C.
STATEMENT OF BID ITEMS
NOTE: CONTRACTOR TO PRICE RESTROOM PHASES SEPARATELY.
BUILDING 103 KEY PLAN
MALE RESTROOM
159C & 160C
WOMEN'S SHOWER & LAUNDRY
136C
MALE RESTROOM
106C & 107C
MALE RESTROOM
106B & 107B
N
WOMEN'S SHOWER/
LAUNDRY
136C
MALE RESTROOM
159C
MALE SHOWER &
RESTROOM
107C
MALE RESTROOM
106B
MALE RESTROOM
107B
A
B
C
MALE RESTROOM
160C
MALE RESTROOM
106C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
GC102
BID ALTERNATES VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SCALE: 1/16" = 1'-0"GC102
1 BID ALTERNATES PLAN
A. HAZMAT REMOVAL NOTES APPLY TO ENTIRE ROOMS. CONTRACTOR SHALL
IDENTIFY ALL MATERIALS DESCRIBED BY NOTE IN EACH ROOM AND
REMOVE ACCORDING TO SAFETY STANDARDS. REFERENCE
SPECIFICATIONS.
B. ALL HAZARDOUS MATERIALS SHALL BE REMOVED IN COMPLIANCE WITH
APPLICABLE CODES AND LAWS.
C. THE CONTRACTOR IS RESPONSIBLE TO VERIFY THE HAZARD(S) AND LEVEL
OF PROTECTION REQUIRED FOR ALL EMPLOYEES OR SUBCONTRACTORS
TO COMPLETE THE CONSTRUCTION WORK.
D. PROVIDE COST FOR REMOVAL OF COUNTED AND UNFORESEEN MUD
FITTINGS ON FIBERGLASS INSULATED DOMESTIC WATER LINES FOR 130
FITTINGS.
E. PROVIDE COST FOR REMOVAL OF LEAD CONTAINING CERAMIC WALL TILE.
APPROXIMATELY 9,680 SQ.FT.
F. REFER TO SPECIFICATION AND ATTACHMENTS FOR ADDITIONAL
INFORMATION.
G. BASED ON THE DATE OF THE EXISTING CONSTRUCTION IT IS ASSUMED
LEAD PAINT IS WITHIN THE PROJECT AREA. CONDUCT DEMOLITION OF THE
EXISTING SPACE WITH THE ASSUMPTION OF LEAD PAINT ON EXPOSED
PLASTER WALLS AND PAINTED SURFACES. REFER TO SPECIFICATION
SECTION 02 83 33.13. LEAD-BASED PAINT REMOVAL, DISPOSAL AND FOR
ADDITIONAL INFORMATION.
H. CONTRACTOR TO SUBMIT LEAD SURFACES STABILIZATION PLAN AND
PROCEDURES PRIOR TO COMMENCING WORK. SUBMITTAL SHALL BE IN
ACCORDANCE WITH SPECIFICATIONS.
1. ASBESTOS CONTAINING PIPE INSULATION MUD FITTINGS ON DOMESTIC
WATER LINES.
2. LEAD CONTAINING TAN CERAMIC WALL TILE.
HAZARDOUS MATERIAL REMOVAL GENERAL NOTES
HAZARDOUS MATERIAL REMOVAL PLAN NOTES
MALE RESTROOM
107B
MALE RESTROOM
106B
MALE SHOWER &
RESTROOM
107C
WOMEN'S SHOWER/
LAUNDRY
136C
MALE RESTROOM
159C
MALE RESTROOM
106C
MALE RESTROOM
160C
BUILDING 103 KEY PLAN
MALE RESTROOM
159C & 160C
WOMEN'S SHOWER & LAUNDRY
136C
MALE RESTROOM
106C & 107C
MALE RESTROOM
106B & 107B
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
HA101
HAZARDOUS MATERIAL
REMOVAL PLAN
VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SCALE: 1/16" = 1'-0"HA101
1 HAZMAT PLAN - B103
1. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING REVIT®
SOFTWARE IN A MICROSOFT WINDOWS ENVIRONMENT. A BUILDING INFORMATION
MODEL (BIM) HAS BEEN DEVELOPED FOR DESIGN COMMUNICATION. THE MODEL
DOES NOT CONTAIN COMPLETE INFORMATION FOR USE IN COST ESTIMATING,
SYSTEMS PERFORMANCE, COORDINATION, SCHEDULING, OR FACILITIES
MANAGEMENT.
2. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING THE
CONSTRUCTION SPECIFICATIONS INSTITUTE'S UNIFORM DRAWING SYSTEM AND THE
NATIONAL CAD STANDARD AS GUIDES.
3. DISCREPANCIES IN THE CONTRACT DOCUMENTS SHALL BE IMMEDIATELY BROUGHT
TO THE ATTENTION OF THE ARCHITECT AND OWNER’S REPRESENTATIVE/COR.
CONTRACTOR SHALL PROVIDE THE HIGHER GRADE OF QUALITY AND/OR GREATER
QUANTITY OF WORK WHEN BIDDING IF A CLARIFICATION CAN NOT BE OBTAINED BY
THE BID DUE DATE.
4. CONTRACTOR IS RESPONSIBLE FOR COORDINATING SCOPE OF WORK WITH
OWNER’S REPRESENTATIVE/COR AND VARIOUS FACILITY PERSONNEL INVOLVED
WITH UTILITY SHUT DOWN, INFECTION CONTROLS, OCCUPANT/EMPLOYEE SAFETY,
ACCESS CONTROL, ETC.
5. ANY INDICATION OF PROJECT LIMITS OR BOUNDARY OF DEMARCATION ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR, THE FULL SCOPE OF THE PROJECT
LIMIT OF BOUNDARY REQUIRES COORDINATION WITH THE DESIGN SCOPE OF WORK
AND ACCESS TO EXISTING UTILITIES FOR TIE IN.
6. DRAWINGS ARE PREPARED FROM FIELD VERIFICATION, EXISTING FACILITY DRAWING
BASE FILES, AND USING DIMENSIONS, CONFIGURATIONS AND DETAILS OF SPECIFIC
MANUFACTURERS AS A BASIS OF DESIGN. CONTRACTOR IS RESPONSIBLE FOR
VERIFICATION OF ACTUAL DIMENSIONS, THE COORDINATION OF THE DETAILS WITH
THE PRODUCTS WHICH ARE PROVIDED PER THE SCOPE OF THE SPECIFICATIONS
AND THE SURROUNDING CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS,
ROUGH-IN DIMENSIONS, CONNECTIONS, AND OVERALL INSTALLATION
REQUIREMENTS.
7. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE ENTIRE SCOPE OF
WORK OUTLINED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE
FOR THE COORDINATION OF ALL SUB-CONTRACTORS AND THE SCOPE OF WORK
THEY PROVIDE. SUB-CONTRACTORS ARE RESPONSIBLE FOR THEIR FULL SCOPE OF
WORK WITHIN THE CONTRACT DOCUMENTS, TRADES ARE NOT SEGMENTED TO ONLY
CERTAIN SHEETS AND SPECIFICATIONS, CROSS COORDINATION IS REQUIRED.
8. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR
UNDERSTANDING INFORMATION OUTLINED IN THE SPECIFICATIONS, KEY NOTES,
GENERAL NOTES, LEGEND, CODES, ETC., PROVIDED IN THE CONTRACT DOCUMENTS.
9. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR PROVIDING
AND MAINTAINING SMOKE/FIRE RATINGS OF NEW CONSTRUCTION AND EXISTING
CONSTRUCTION AS INDICATED ON DRAWINGS. THIS INCLUDES PATCHING
PENETRATIONS IN SHAFTS, WALLS, SLABS AND ROOF. ONLY U.L. APPROVED
METHODS, MATERIALS AND INSTALLATION ARE ACCEPTABLE.
10. MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS SHOW
INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL
CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL MECHANICAL, PLUMBING
AND ELECTRICAL EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL AND
STRUCTURAL DETAILING OF SHAFTS, CHASES, CEILING CONSTRUCTION, ETC.
11. CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IDENTIFIED AND NOT
IDENTIFIED IN THE CONTRACT DOCUMENTS WITH THE EXISTING AND NEW
CONSTRUCTION ELEMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION
BETWEEN THE CONTRACT DOCUMENTS, INSTALLED AND UNINSTALLED
CONSTRUCTION BEFORE THE ORDERING OF MATERIALS AND EQUIPMENT. NOTIFY
ARCHITECT AND OWNER’S REPRESENTATIVE/COR OF ANY DISCREPANCIES OR
MISSING DIMENSIONS.
CONSTRUCTION GENERAL NOTES
SECTION REFERENCE
DRAWING NUMBER
SHEET LOCATION
DRAWING NUMBER
SHEET
LOCATION
DETAIL REFERENCE
OBJECT
REFERENCED
OBJECT
REFERENCED
X
XXXX
X
XXXX
SCALE: ??
VIEW TITLE
N
NORTH ARROW
EXTENT OF REVISION
REVISION SET
PROJECT BOUNDARY
BEYOND PROJECT BOUNDARY, NIC
DETAIL/DRAWING SCALE
TITLE OF DETAIL/DRAWING
DETAIL/DRAWING NUMBER
SHEET NUMBER
X
X
XXXX
SHEET LOCATION
VIEW NUMBER
X X
X
SHEET LOCATION
VIEW NUMBER
XXXX
BUILDING SECTION REFERENCE
DRAWING NUMBER
SHEET LOCATION
BUILDING X
XXXX
X
XXXX
ELEVATION REFERENCES
NEW WALL
WALL TO BE
REMOVED
S3A.G
INDICATES STRUCTURAL MATERIAL
INDICATES NOMINAL SIZE
INDICATES STRUCTURE AND FINISH HEIGHTS
INDICATES QUALIFER
EXISTING WALL TO
REMAIN
TEMPORARY IC
BARRIER WALL
CONSTRUCTION
ROOM
ROOM TAG
REVISION TO PLAN CALLOUT
WALLS
DOOR TAG
KEY NOTE TAGS
WALL TAG : REFER TO WALL LEGEND FOR MORE INFORMATION
DOORS
PT-1
A
T
101 EQUIPMENT/FURNITURE TAG
1 PLAN NOTE
1 DEMOLITION NOTE
ALTERNATE/BID DEDUCT ITEM
KEY NOTE SYMBOLS
ARCHITECTURAL SYMBOLS
A 9'-0"
CEILING TAG CEILING TYPE
FINISHED CEILING HEIGHT
REFER TO CEILING LEGEND FOR MORE
INFORMATION
CEILING EQUIPMENT: REFER TO MEP SHEETS AS APPLICABLE
REFLECTED CEILING PLAN SYMBOLS
12. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR GENERAL
ORIENTATION AND CONTEXT ONLY.
13. THE TERM "ALIGN" MEANS TO INSTALL DIFFERENT/SIMILAR COMPONENTS OF
CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.
14. ALL DIMENSIONS INDICATED ARE TO FACE OF EXISTING MEMBERS, FACE OF NEW
STRUCTURAL MEMBERS, FACE OF NEW MASONRY, FACE OF NEW STUDS OR COLUMN
GRID LINES UNLESS NOTED OTHERWISE.
15. FLOOR ELEVATION 100’-0 IS EQUAL TO THE FINISH FLOOR SLAB OF THE EXISTING
SLAB FLOOR CONSTRUCTION UNLESS OTHERWISE NOTED.
16. ROUGH OPENINGS SHALL ALLOW FOR SHIM SPACE.
17. CONTRACTOR TO PROVIDE WORK WHERE DETAILS AND NOTES ARE IDENTIFIED AS
“TYPICAL” OR “SIMILAR” EACH INSTANCE THAT IS THE SAME IN NATURE TO THE
DETAIL, AREA, OR ITEM REFERENCED.
18. PROVIDED WORK SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF DELIVERY, MOUNTING,
INSTALLATION, NECESSARY BLOCKING AND ROUGH-IN.
19. INSTALLED WORK IS THE CONTRACTOR INSTALLING OWNER FURNISHED MATERIALS
AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF MATERIAL
DELIVERY, MOUNTING, INSTALLATION AND ROUGH IN.
20. FURNISHED WORK IS THE CONTRACTOR FURNISHING THE MATERIALS AND
EQUIPMENT TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF
DELIVERY AND ROUGH-IN.
21. ALL PROVIDED WORK SHALL BE WITH NEW MATERIALS UNLESS SPECIFICALLY
CALLED OUT AS SALVAGED OR RELOCATED WITHIN THE CONTRACT DOCUMENTS.
22. ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE
FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND
HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.
23. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL
UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO
UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE
OWNER.
24. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING AND SHORING
REQUIRED DURING CONSTRUCTION.
25. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ADJACENT
CONSTRUCTION, FINISHES, EQUIPMENT, AND TRAVEL ROUTE TO AND FROM THE
CONSTRUCTION SITE. ANY DAMAGE OR UNACCEPTABLE WEAR BY THE
CONSTRUCTION TEAM SHALL BE REPAIRED/REPLACED BY THE CONTRACTOR AT NO
COST TO THE OWNER.
26. IN THE CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT
DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER
QUALITY OF WORK, AS DETERMINED BY THE COR , SHALL BE PROVIDED.
27. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND COORDINATING HARDWARE,
ACCESS CONTROL AND AUTOMATIC OPERATORS ARE PROVIDED WITH COMPLETE
AND COMPATIBLE SYSTEMS REQUIRED FOR THEIR OPERATION. REFER TO DOOR
HARDWARE SCHEDULE, HARDWARE SPECIFICATIONS, AUTOMATIC OPERATOR
SPECIFICATIONS, ACCESS CONTROL SPECIFICATIONS AND ELECTRICAL DRAWINGS.
LED LIGHT FIXTURE - LAY-IN
LED LIGHT FIXTURE - DOWNLIGHT
DIFFUSER
A/C AIR CONDITION
A/E ARCHITECT/ENGINEER
ACT ACOUSTICAL CEILING TILE
ADMIN ADMINISTRATION
AHJ AUTHORITY HAVING JURISDICTION
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ARCH ARCHITECT
ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION
AUTO AUTOMATIC
BLDG BUILDING
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CG CORNER GUARD
CJ CONSTRUCTION JOINT OR CONTROL JOINT
CL CENTER LINE
COORD COORDINATE
DEMO DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DN DOWN
E EAST
ELEC ELECTRIC
EQ EQUAL
FEC FIRE EXTINGUISHER CABINET
FT FEET OR FOOT
GYP GYPSUM
HAZ MAT HAZARDOUS MATERIALS
HM HECTOMETER OR HOLLOW METAL
MIN MINIMUM MINUTE OR MINUTE MINIMUM
N NORTH
OF/OI OWNER FURNISHED/OWNER INSTALLED
QTY QUANTITY
RO ROUGH OPENING
SF SQUARE FOOT (FEET)
SIM SIMILAR
S SOUTH
SQ SQUARE
TA TOILET ACCESSORY
TO TOP OF ___
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
ARCHITECTURAL ABBREVIATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
AE001
ARCHITECTURAL
ABBREVIATIONS AND
SYMBOLS
VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212Revisions: Date:
A. ALL WALLS WILL BE WALL TYPES S3A.TBi UNLESS OTHERWISE NOTED.
B. ALL WALL TYPE INDICATORS REFER TO THIS SHEET UNLESS OTHERWISE
NOTED.
C. REFER TO DIMENSION PLANS FOR PARTITION TYPE LOCATIONS.
PARTITIONS ARE DISTINGUISHED ON PLANS BY SYMBOL DESIGNATION
GRAPHIC DESIGNATION, OR A COMBINATION OF BOTH. NOT ALL
PARTITIONS ON THIS SHEET MAY BE USED. REFER TO PARTITION TYPE
SCHEDULE ON THIS SHEET FOR PARTITIONS USED ON THIS PROJECT.
D. ALL DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD, OR TO FACE
OF BLOCK. REFER TO WALL TYPES LEGEND FOR PARTITION WIDTH
DIMENSIONS.
E. ALL WALL STUD FRAMING TO BE 16" O.C. UNLESS OTHERWISE NOTED.
F. REFER TO SPECIFICATIONS AND TO TABLE ON THIS SHEET FOR MINIMUM
STUD GAUGE, MAXIMUM SPACING AND ALLOWABLE LIMITING HEIGHT
DEFLECTION CRITERIA FOR GYPSUM BOARD ASSEMBLIES AND REQUIRED
FINISHES. FOR WALLS WHERE STUDS ARE ATTACHED TO STRUCTURE
ABOVE, PROVIDE CROSS BRACING AS NECESSARY MEETING THE CRITERIA
INDICATED TO ACCOMMODATE THE SPECIFIED DEFLECTION CRITERIA OF
THE WALL.
G. ALL INTERIOR NON-BEARING STUDS TO BE DESIGNED FOR A DEFLECTION
EQUAL TO BUT NOT GREATER THAN L/240, UNLESS FULL HEIGHT FINISH IS
DETERMINED TO BE FRAGILE OR BRITTLE, THEN DEFLECTION TO BE L/360.
EXAMPLES OF FRAGILE FINISHES WOULD INCLUDE BUT NOT LIMITED TO
ANY TYPE OF WALL TILE, PLASTER OR PLASTER SKIM COAT.
H. ALTHOUGH WALL STUD SIZES ARE LISTED ON PLANS AND WALL TYPE
LEGEND, IN AREAS WHERE STUDS ARE TO STRUCTURE ABOVE OR HIGH
AREAS, CONTRACTOR TO VERIFY SIZED INDICATED IS ADEQUATE FOR
HEIGHT LISTED. PROVIDE ADEQUATE SIZE STEEL STUD FRAMING AND
NOTIFY ARCHITECT OF ANY DISCREPANCY PRIOR TO FABRICATION OR
INSTALLATION.
I. KING STUDS AT DOOR FRAMES TO BE 18 GA. UNLESS OTHERWISE NOTED.
J. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD FOR ALL OTHER WALL
CONSTRUCTION, UNLESS OTHERWISE NOTED.
K. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD IN BULKHEAD CONSTRUCTION.
L. REFER TO LIFE SAFETY PLANS FOR LOCATIONS AND RATINGS OF SMOKE
AND FIRE RATED PARTITIONS. REFERENCE TEST NUMBERS APPLY ONLY TO
PARTITIONS INDICATED TO BE RATED.
M. FIRE RATING TEST NUMBERS ARE FOR UNDERWRITER'S LABORATORIES
(UL) ASSEMBLIES UNLESS OTHERWISE NOTED.
N. FIRE RESISTANT RATED PARTITIONS SHALL EXTEND TO THE INSIDE FACE
OF EXTERIOR SHEATHING, INCLUDING EXTENSIONS THROUGH SOFFITS.
O. SEAL ALL OPENINGS, GAPS, PENETRATIONS, AND JOINTS IN PARTITIONS
TYPES AS FOLLOWS:
a. FIRE RATED PARTITIONS: SEAL IN ACCORDANCE WITH THE
REQUIREMENTS SPECIFIED FOR THROUGH PENETRATION
FIRESTOP SYSTEMS AND FIRE RESISTIVE JOINT SYSTEMS.
b. SMOKE TIGHT PARTITIONS: SEAL COMPLETELY WITH
ELECTROMETRIC SEALANT. FOR THE LOCATION AND EXTENT OF
PARTITIONS, DESIGNATED AS "SMOKE TIGHT", REFER TO THE LIFE
SAFETY DRAWINGS.
c. ALL OTHER LOCATIONS: SEAL AS INDICATED AND REQUIRED
ELSEWHERE BY THE CONTRACT DOCUMENTS.
P. INSULATION HEAD CONDITIONS AT FLOOR / ROOF DECK:
a. FIRE RESISTANT RATED PARTITIONS SHALL USE MINERAL WOOL
INSULATION AND APPROPRIATE FIRE RATED SEALANT.
b. NON-RATED PARTITIONS REQUIRING SOUND ATTENUATION SHALL
USE SOUND ATTENUATION BATTS (SAB).
Q. PROVIDE STENCILED IDENTIFICATION FOR RATED PARTITIONS.
R. STC RATING APPLIES WHERE PARTITIONS TAG QUALIFIER INDICATES WITH
AN "i". PROVIDE SOUND ATTENUATION BATTS OF THICKNESS INDICATED ON
SCHEDULE WHERE INDICATED BY QUALIFIER.
S. FOR PARTITIONS WITH STC RATINGS INDICATED SOUND ATTENUATION
BATTS TO EXTEND FULL HEIGHT OF PARTITION UNLESS OTHERWISE
NOTED. FLOOR TRACK TO BE SET IN A CONTINUOUS BED OF SEALANT.
T. WHERE PARTITION TYPE INDICATES SOUND ACOUSTICAL BAT, WITH FINISH
BOARD GOING TO DECK ON ONE SIDE ONLY, PROVIDE VAPOR BARRIER TO
SECURE INSULATION IN PLACE.
U. PROVIDE 5/8" MOISTURE/MOLD RESISTANT GYPSUM BOARD IN SOILED
ROOMS, BATHROOMS, TOILET ROOMS, ON WALLS BEHIND PLUMBING
FIXTURES, AND IN ALL WET LOCATIONS EXCEPT IN SHOWER AREA.
V. PROVIDE 5/8" CEMENTITIOUS BACKER BOARD BEHIND CERAMIC WALL TILE &
SHOWER AREA. COORDINATE LOCATIONS WITH FINISH WALL PLANS.
W. PROVIDE CORNER AND END WALL FRAMING AS DETAILED ON 1/AE002.
WALL TYPES LEGEND AND GENERAL NOTES
X#X.#
INDICATES STRUCTURAL MATERIAL
CH = SHAFT WALL
F = FURRING
S = STEEL
M = MASONRY
W = WOOD
INDICATES NOMINAL SIZE
INDICATES STRUCTURE AND
FINISH HEIGHTS
QUALIFIER'S (X-X-X)
G GYPSUM BOARD FINISH
1SB 1 HR RATED SMOKE BARRIER
2SB 2 HR RATED SMOKE BARRIER
1F 1 HR FIRE RATED
2F 2 HR FIRE RATED
i SOUND INSULATION t THERMAL INSULATION
B BULLET RESISTANT
L LEAD LINED
M MESH (STEEL SECURITY MESH)
MR MOIST/MOLD RESISTANT GYPSUM
SP SMOKE PARTITION
TB TILE BACKER CEMENT BOARD
A = STRUCTURE TO DECK, FINISH TO DECK
B = STRUCTURE TO DECK, FINISH ONE SIDE TO DECK
C = STRUCTURE TO DECK, FINISH TO ABOVE CEILING
D = STRUCTURE TO ABOVE CEILING, FINISH TO ABOVE CEILING
P = PARTIAL HEIGHT WALL
U = STRUCTURE TO UNDERSIDE OF CEILING, FINISH TO UNDERSIDE OF CEILING
*SEE WALL TYPES FOR PROJECT SPECIFIC CONSTRUCTION
CH
2 1/2" 4" 6"
F 7/8
1 1/2" 2 1/2" 3 5/8"
4" 6" 8" 12"
S
2 1/2" 3 5/8"
4" 6" 8" 12"
M
2 5/8" 3 5/8" 5 5/8" 7 5/8" 11 5/8"
W
3/4"
3 1/2"
5 1/2" 7 1/4" 11 1/4"
" 1 HR FIRE/SMOKE
10'-0" MAX 10'-0" MAX
A. LETTERED STENCILS SHALL BE APPLIED TO EACH SIDE OF RATED PARTITIONS
AT 10'-0" INTERVALS; BUT NO LESS THAN ONCE PER PARTITION LENGTH.
B. USE THE FOLLOWING LANGUAGE FOR STENCILS:
"1 HR FIRE/SMOKE" "1 HR FIRE"
"2 HR FIRE/SMOKE" "2 HR FIRE"
"LIMIT TRANSFER OF SMOKE"
PERMANENT RED PAINT
LETTERING, TYP.
CEILING LINE
STENCILING NOTES
WALL TAG LEGEND
WALL TYPES
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
COMMENTS
S6D.TB 6" 7 1/4" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
5/8" TILE BACKER BOARD (BOTH SIDES)
BEAD OF CONT. SEALANT
INSULATION PRESENT WITH QUALIFER (i OR t)
NOTE:
COORDINATE HEIGHT OF TILE BACKER
BOARD WITH HEIGHT OF TILE.
RE: INTERIOR ELEVATIONS
TILE, RE: ELEVATIONS
5/8" TYPE X GYP BD (ABOVE TILE BACKER BOARD)
FINISH DIMENSION
STEEL STUDS @ 16" O.C.
6"
3 5/8" 4 7/8" NAN/ANANAS3D.TB
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
COMMENTS
3 5/8" 4 7/8" NA40NANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
STRUCTURAL SIZE
5/8"
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
DEEP LEG SLIP TRACK AT DECK
HOLD GYPSUM BACK FROM DECK FOR
DEFLECTION
5/8" TILE BACKER BOARD (ONE SIDE)
BEAD OF CONT. SEALANT
5/8" TYPE X GYP BD (ONE SIDE)
INSULATION PRESENT WITH QUALIFER (i OR t)
S3A.GTBi
NOTE:
COORDINATE HEIGHT OF TILE BACKER
BOARD WITH HEIGHT OF TILE.
RE: INTERIOR ELEVATIONS
TILE, RE: ELEVATIONS
5/8" TYPE X GYP BD (ABOVE TILE BACKER BOARD)
FINISH DIMENSION
STEEL STUDS @ 16" O.C.
NOTE:
REFERENCE DETAIL FOR REBUILD OF EXISTING WALLS.
EXISTING 2 HR FIRE RATED
EXISTING 1 HR FIRE RATED
EXISTING SMOKE PARTITION
WALL RATING LEGEND
NOTE:
• TYPICAL LIMITING HEIGHTS-INTERIOR PARTITIONS, L/240 (5 PSF), WITH 5/8"GYPSUM BOARD EACH SIDE.
• PROVIDE DIAGONAL STUD BRACING AT ALL NON FULL HEIGHT INTERIOR PARTITIONS STAGGERED AT 48" O.C. TO DECK ABOVE. PROVIDE
STUD ATTACHMENT TO DECK w/ MIN. SPAN OF 2 DECK FLUTES. BRACING TO BE THE SAME SIZE AND GAUGE AS VERTICAL STUDS.
25 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 6'-11"1-5/8"
24" L/240 6'-0"162S125-18
16" L/240 9'-6"2-1/2"
24" L/240 8'-4"250S125-18
16" L/240 12'-5"3-5/8"
24" L/240 10'-10"362S125-18
16" L/240 13'-9"4"
24" L/240 12'-0"400S125-18
22 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 8'-1"1-5/8"
24" L/240 7'-1"162S125-27
16" L/240 11'-2"2-1/2"
24" L/240 9'-9"250S125-27
16" L/240 14'-6"3-5/8"
24" L/240 12'-8"362S125-27
16" L/240 16'-1"4"
24" L/240 14'-0"400S125-27
20 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 8'-4"1-5/8"
24" L/240 7'-3"162S125-30
16" L/240 11'-7"2-1/2"
24" L/240 10'-1"250S125-30
16" L/240 15'-0"3-5/8"
24" L/240 13'-1"362S125-30
16" L/240 16'-8"4"
24" L/240 14'-7"400S125-30
16" L/240 22'-4"6"
24" L/240 19'-6"600S125-27
16" L/240 23'-1"6"
24" L/240 20'-2"600S125-30
18 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 13'-0"2-1/2"
24" L/240 11'-5"250S125-43
16" L/240 17'-5"3-5/8"
24" L/240 15'-3"362S125-43
16" L/240 18'-10"4"
24" L/240 16'-5"400S125-43
16" L/240 26'-1"6"
24" L/240 22'-10"600S125-43
SSMA NON-COMPOSITE STUDS
TOP OF METAL DECK OR CONCRETE
FIRE CAULKING AS REQUIRED BY UL# HWS0001
(BY FRAMING CONTRACTOR)
PACK FLUTES OF DECK WITH FIRE SAFING AS
REQUIRED PER UL# HWS0001
Z-CLIPS 2" WIDTH
BOTTOM OF METAL DECK
LIGHT GAUGE FRAMING DEFLECTION TRACK,
CONFORMING TO UL# HW-D-0060
5/8" TYPE X GYP. BD. EACH SIDE OF STUD
SCRIBED TO DECK UL# U465
METAL STUD
PARALLEL NOTE:
NON-RATED CONSTRUCTION SIMILAR w/o
FIRE SAFING & SCRIBING BYP. BD. TO DECK
6"
TOP OF METAL DECK OR CONCRETE
FIRE CAULKING AS REQUIRED BY UL# HWS0001
(BY FRAMING CONTRACTOR)
PACK FLUTES OF DECK WITH FIRE SAFING AS
REQUIRED PER UL# HWS0001
Z-CLIPS 2" WIDTH
BOTTOM OF METAL DECK
LIGHT GAUGE FRAMING DEFLECTION TRACK,
CONFORMING TO UL# HW-D-0060
5/8" TYPE X GYP. BD. EACH SIDE OF STUD
SCRIBED TO DECK UL# U465
METAL STUD
PERPENDICULAR NOTE:
NON-RATED CONSTRUCTION SIMILAR w/o
FIRE SAFING & SCRIBING BYP. BD. TO DECK
HIGH PRIORITY PARTITION
LOWER PRIORITY PARTITION
HIGH PRIORITY CEILING /
ROOF ASSEMBLY
LOWER PRIORITY PARTITION
RATING
3 HOUR ASSEMBLY
2 HOUR ASSEMBLY
1 HOUR ASSEMBLY
SMOKE-RATED ASSEMBLY
NON-RATED ASSEMBLY
PRIORITY
NOTE: LOWER NUMBER, HIGHER PRIORITY
INSULATION STUFFED INSIDE BOX
METAL STUD FRAMING
CORNER BEAD AT ALL
OUTSIDE CORNERS (TYPICAL)
20 GA. METAL STUDS WRAPPED WITH
20 GA. TRACK ON BOTH SIDES,
CONTINUOUS FROM FLOOR TO DECK
INSULATION STUFFED INSIDE BOX
METAL STUD FRAMING
CORNER BEAD AT ALL
OUTSIDE CORNERS (TYPICAL)
20 GA. METAL STUDS WRAPPED WITH
20 GA. TRACK ON BOTH SIDES,
CONTINUOUS FROM FLOOR TO DECK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:4
P M
AE002
WALL TYPES VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DMC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SCALE: 1 1/2" = 1'-0"AE002
2 RATED WALL PRIORITY
SCALE: 1 1/2" = 1'-0"AE002
3 DEFLECTION TRACK
WALL TYPE SCHEDULE
WALL TYPES USED IN THIS PROJECT
S3D.TB
S6D.TB
SCALE: 3" = 1'-0"AE002
1 TYPICAL CORNER FRAMING DETAIL
WOMEN'S SHOWER/
LAUNDRY
136C
AD102
AD102
AD102
AD102
MALE RESTROOM
107B
MALE RESTROOM
106B
MALE RESTROOM
160C
MALE RESTROOM
159C
MALE RESTROOM
106C
MALE SHOWER &
RESTROOM
107C
A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND
REPAIR NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION
SHALL BE PROVIDED. CONTRACTOR SHALL REMOVE EXISTING
IMPROVEMENTS WHETHER OR NOT SPECIFICALLY INDICATED ON THE
DRAWINGS TO FACILITATE THE COMPLETION OF ALL REQUIRED WORK.
CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES AND
ITEMS REQUIRED TO BE REMOVED.
B. REFER TO ARCHITECTURAL SYMBOLS ON SHEET AE001 FOR DEMOLITION
SYSTEMS AND DRAWING NOMENCLATURE.
C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN
UNLESS OTHERWISE NOTED.
D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE
PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO
VERIFY NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH
CONDITIONS SHALL BE RECTIFIED BEFORE WORK MAY PROCEED.
E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE
ARCHITECTURAL FLOOR PLANS AND ENGINEERING DRAWINGS FOR
ADDITIONAL INFORMATION.
F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED
ARE APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF
WORK TO BE REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE
NEW CONSTRUCTION. COORDINATE DEMOLITION WORK WITH DESIGN
INTENT OF NEW CONSTRUCTION TO PROVIDE ADEQUATE AREA FOR THIS
WORK.
G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION
ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHER WISE NOTED, TO
ACCOMMODATE NEW CONSTRUCTION.
H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE
NEW FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH
THAT THE CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE
SMOOTH AND UNDETECTABLE.
I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES
SHALL BE REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES
CAN BE REINSTALLED WHERE LOCATED OUTSIDE OF RESTROOMS.
DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED BY
CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED AND PAINTED
TO SEAMLESSLY MATCH EXISTING CEILING COLOR FOLLOWING ABOVE
CEILING DEMOLITION ACTIVITY. THIS SHALL INCLUDE REPAIR TO THE
CEILING GRID, SUSPENSION SYSTEM AND ALL ASSOCIATED ASSEMBLIES AS
WELL AS THE REPLACEMENT OF DAMAGED CEILING PANELS, WITHIN AND
BEYOND PROJECT LIMITS.
J. COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND
VENDOR DRAWINGS.
K. WHERE EXISTING FLOOR FINISH IS REMOVED, FLOORING AND ADHESIVE
SHALL BE REMOVED TO PROVIDE A CLEAN FLOOR SLAB. FLOOR SLAB SHALL
BE FILLED/ LEVELED TO PROVIDE A LEVEL FINISH PER NEW FLOORING
MANUFACTURES RECOMMENDATIONS. REFER TO SPECIFICATION 09 05 16.
L. REMOVE WALL MOUNTED ACCESSORIES AND MOUNTING HARDWARE
THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE NOTED.
M. ALL TOILET ACCESSORIES AND TOILET / URINAL PARTITIONS TO BE
REMOVED THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE NOTED.
REFER TO INTERIOR DRAWINGS FOR ADDITIONAL INFORMATION.
N. ALL DOORS, FRAMES, AND HARDWARE TO REMAIN EXISTING THROUGHOUT
PROJECT BOUNDARY UNLESS OTHERWISE NOTED.
O. ANY DAMAGED FLOOR AND WALL TILE TO BE REMOVED AND REPLACED.
COORDINATE WITH INTERIORS DRAWINGS.
DEMOLITION GENERAL NOTES
BUILDING 103 KEY PLAN
MALE RESTROOM
159C & 160C
WOMEN'S SHOWER & LAUNDRY
136C
MALE RESTROOM
106C & 107C
MALE RESTROOM
106B & 107B
N
EXISTING 2 HR FIRE RATED
EXISTING 1 HR FIRE RATED
EXISTING SMOKE PARTITION
WALL RATING LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
21 4 5 6 7 8
Phase
STAMP
321 4 5 6 7 8
ARCHITECT/ENGINEER OF RECORD
CIVIL ENG., ARCH., STRUCT. ENG. FIRE PROTECTION, MEP ENGINEER
A u to d e s k D o c s /2
.4
.0
V
A D
A N
V
IL
L E
R E
N O
V A
T E
B A
T H
R O
O M
S /2
.4
.0
A v
.r v t
/9
/2
:4
:5
P M
AD101
OVERALL DEMOLITION
PLANS
VA DANVILLE RENOVATE B103
PRRTP BATHROOMS
1900 E. Main Street, Danville, IL 61832
550-25-108
B103
03/11/2026 AO DC
BID DOCUMENTS
RESUBMITTAL
FULLY SPRINKLEREDGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
CHARLOTTE ENGINEERS
5838 MONROE ROAD
CHARLOTTE, NC 28212
SCALE: 1/16" = 1'-0"AD101
5 DEMOLITION FLOOR PLAN - B103
NOTE:
OVERALL PLANS ARE INTENDED TO GIVE A GENERAL SCOPE FOR THE
ENTIRE PROJECT AREA. MORE SPECIFIC INFORMATION IS PROVIDED IN
THE ENLARGED PLAN DRAWINGS FOLLOWING THIS SHEET.
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
1. REMOVE INDICATED PORTION OF WALL TO ACCOMMODATE NEW WORK.
COORDINATE WITH ARCHITECTURAL PLANS.
2. REMOVE INDICATED PORTION OF WALL TO ACCOMMODATE NEW DOOR.
COORDINATE WITH ARCHITECTURAL PLANS.
3. REMOVE PLUMBING FIXTURE. COORDINATE WITH PLUMBING DRAWINGS FOR
EXTENT OF DEMOLITION.
4. SAWCUT FLOOR SLAB AS REQUIRED TO INSTALL NEW PLUMBING.
APROXIMATE LOCATION INDICATED BY HATCH. COORDINATE WITH
PLUMBING DRAWINGS.
5. REMOVE ACOUSTIC PANEL CEILING ASSEMBLY IN ITS ENTIRETY.
6. REMOVE DOOR LEAF, FRAME, AND HARDWARE IN ITS ENTIRETY.
7. REMOVE GYPSUM BOARD CEILING ASSEMBLY IN ITS ENTIRETY.
8. REMOVE FULL WALL FINISH INCLUDING CERAMIC WALL TILE AND BACKER
BOARD ON PROJECT SIDE OF WALL TO EXPOSE EXISTING STEEL STUDS.
REVIEW CONDITION OF STUD FRAMING WITH COR. COR TO DIRECT EXTENT
OF REMOVAL OF EXISTING STEEL STUDS THAT ARE DAMAGED / RUSTED.
WALL FINISH TO REMAIN IN PLACE ON NON-CONSTRUCTION SIDE OF WALL.
CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE CAUSED TO OTHER SIDE
OF ROOM AND REMAINING WALL CONSTRUCTION.
9. REMOVE WASHER AND DRYER. SALVAGE FOR REINSTALLATION.
10. REMOVE SHOWER FIXTURE AND ALL ASSOCIATED ACCESSORIES. WALL /
FLOOR TILE AND/OR SURROUND AND PAN TO BE REMOVED IN SHOWER.
FLOOR DRAIN TO BE REMOVED AND PREP FOR NEW. COORDINATE WITH
PLUMBING DRAWINGS.
11. REMOVE CERAMIC TILE FLOORING, ASSUME 2" THICKSET MORTAR BED, AND
3/4" WALL TILE.
#DEMOLITION PLAN NOTES
109 SF
WOMEN'S SHOWER/
LAUNDRY
136C
213 SF
MALE RESTROOM
159C
29 SF
STORAGE
159C1
187 SF
MALE RESTROOM
107B
176 SF
MALE RESTROOM
106B
A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND
REPAIR NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION
SHALL BE PROVIDED. CONTRACTOR SHALL REMOVE EXISTING
IMPROVEMENTS WHETHER OR NOT SPECIFICALLY INDICATED ON THE
DRAWINGS TO FACILITATE THE COMPLETION OF ALL REQUIRED WORK.
CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES AND
ITEMS REQUIRED TO BE REMOVED.
B. REFER TO ARCHITECTURAL SYMBOLS ON SHEET AE001 FOR DEMOLITION
SYSTEMS AND DRAWING NOMENCLATURE.
C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN
UNLESS OTHERWISE NOTED.
D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE
PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO
VERIFY NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH
CONDITIONS SHALL BE RECTIFIED BEFORE WORK MAY PROCEED.
E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE
ARCHITECTURAL FLOOR PLANS AND ENGINEERING DRAWINGS FOR
ADDITIONAL INFORMATION.
F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED
ARE APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF
WORK TO BE REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE
NEW CONSTRUCTION. COORDINATE DEMOLITION WORK WITH DESIGN
INTENT OF NEW CONSTRUCTION TO PROVIDE ADEQUATE AREA FOR THIS
WORK.
G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION
ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHER WISE NOTED, TO
ACCOMMODATE NEW CONSTRUCTION.
H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE
NEW FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH
THAT THE CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE
SMOOTH AND UNDETECTABLE.
I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES
SHALL BE REMOVED AND…
This is the start of the file's text. The full file is on GovTribe.