Federal Bureau of Prisons Federal Correctional Institution Butner, N.C.
RFQP01061600022
Retubing Boilers Project 1B5N RFI (Request for Information)
Company Name: ABC Inc. "Anthony Boiler Co., Inc."
Requester Name: Chris Anthony
Question:
On the hydro of both boilers, do we leave the relief valves on and hydro over the normal working pressure but under the set pressure of the relief valves, or do we remove the relief valves and hydro to design pressure of the boiler?
BOP reply:
Remove the relief valves and take hydro to the design pressure of the boiler.