RFQ27007140_Drawings.pdf
PDF 5 MB Posted
- Solicitation number
- RFQ27007140
- Issued by
- Providence County, Rhode Island
About this file
Construction Documents Summary
This file comprises the architectural and structural construction drawings for the Washburn Hall renovation project at the University of Rhode Island located at 75 Briar Lane, Kingston, Rhode Island 02881 (Project No. 2503449). The project scope includes structural reinforcements at the basement and first floor levels, with interior space reconfiguration proposed on the third floor of this existing educational facility classified as Group B (Business) Occupancy under the 2021 International Building Code. The building is a four-story structure with an attic level, designed as Type III-B construction with sprinkler protection. The work includes selective demolition of non-structural interior elements, installation of new structural supports including footings, bearing walls, headers, and posts, floor joist reinforcement through sistering, and comprehensive interior finishes on affected floors. All construction shall conform to the 2021 Rhode Island State Building Code and applicable national standards including the 2021 IBC, 2023 NEC, 2024 IECC, and NFPA codes. The project documents indicate that the contractor must obtain a ground penetrating radar survey of existing concrete slabs within thirty days of contract execution to identify embedded utilities and structural conditions.
The construction documents establish detailed technical requirements for all trades including structural, architectural, mechanical, electrical, fire protection, and plumbing work. Key structural requirements specify concrete with 4,000 PSI minimum compressive strength, lumber framing per NDS standards with specific grades and design values, and welding/fastening per applicable codes. The contractor is responsible for providing all temporary bracing and shoring during demolition and construction, field verification of all existing conditions and dimensions, coordination of building system penetrations, and proper handling of hazardous materials in coordination with the owner's abatement contractor. The documents note that flooring demolition in areas requiring hazardous materials abatement shall be completed by others under separate contract, with the general contractor assuming preparation of these areas for new finishes. All work outside designated project limits requires prior written owner approval, and the contractor must maintain operational continuity of existing life safety systems throughout construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ27007140 scope of work.pdf | ||
| RFQ27007140_Nov_17_26_solicitation_doc.pdf | ||
| RFQ27007140 Specifications.pdf | ||
| URI Washburn Hall Renovations locations.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO THE LATEST ADOPTED BUILDING CODE EDITION, AND TO CONDITIONS AND
SPECIFICATIONS OF ALL GOVERNING AUTHORITIES.
2. VERIFY AND CONFIRM ALL CONDITIONS, DIMENSIONS, AND LAYOUT INFORMATION PRIOR TO START OF CONSTRUCTION. NOTIFY CONSULTANT OF ANY DISCREPANCIES PRIOR TO START OF WORK. ANY CORRECTION WORK REQUIRED AS A RESULT OF NOT REPORTING SUCH DISCREPANCIES SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE TENANT.
3. CONTRACTOR AND SUBCONTRACTORS SHALL CAREFULLY EXAMINE THE SITE AND THE CONSTRUCTION DOCUMENTS OF THE ENTIRE WORK. INCONSISTENCIES IN THE PLANS OR SPECIFICATIONS SHALL BE CALLED TO THE ATTENTION OF THE CONSULTANT AND
TENANT.
4. REFER TO ENLARGED PLANS AND ELEVATIONS WHERE INDICATED FOR ADDITIONAL INFORMATION. ENLARGED PLANS TAKE PRECEDENCE OVER PLANS OF SMALLER SCALE, AND DETAILS TAKE PRECEDENCE OVER PLANS. IN THE CASE OF A CONFLICT, THE
HIGHEST COST OPTION SHOULD BE PRICED.
5. DETAIL REFERENCES SHALL BE APPLIED TO ALL INSTANCES WHERE THE SAME CONDITIONS OCCUR, UNLESS NOTED OTHERWISE.
6. DIMENSIONS ARE TO STRUCTURAL GRID, CENTER LINE OF COLUMNS, AND FACE OF STUDS/CONCRETE WALL, UNLESS NOTED
OTHERWISE.
7. THE TERMS "ABOVE FINISH FLOOR" (AFF) AND "FINISH FLOOR ELEVATION" (FFE) REFER TO FINAL FINISHED FLOOR ELEVATION, WHETHER BUILT-UP SLAB, COMPOSITE DECK AND/OR RAISED ACCESS FLOOR.
8. DO NOT SCALE DRAWINGS.
9. CUTTING AND DRILLING OF STRUCTURAL MEMBERS NOT DETAILED REQUIRES THE WRITTEN PERMISSION OF THE STRUCTURAL
ENGINEER OF RECORD.
10. SAVE AND RECYCLE DEMOLITION DEBRIS AS APPLICABLE. ALL DEMOLISHED OR REMOVED EXISTING MATERIAL SHALL BE LEGALLY
DISPOSED. COORDINATE WITH AUTHORITY HAVING JURISDICTION FOR REQUIREMENTS FOR RECYCLING AND RE-USE OF
DEMOLITION DEBRIS.
11. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE RESULTING FROM THEIR WORK. THE CONTRACTOR WILL COORDINATE CLEAN UP OF ALL AREAS AFFECTED BY DUST OR ANY MATERIALS, BOTH DURING CONSTRUCTION AND UPON COMPLETION OF THE PROJECT, INCLUDING THE INSIDE OF ALL WINDOWS AS NECESSARY SO THAT THE SPACE IS READY FOR OCCUPANCY BY TENANT.
N
DATE ISSUED:
PROJECT LOCATIONOWNER / DEVELOPER
PROJECT NO.:
DATE:
REVIEWED:
DRAWN BY:
DESIGNER:
TITLE:
SHEET NO.
ISSUED FOR:
BLDG.
Architecture Engineering
Environmental
Land Surveying
DESIGN STANDARDS
TRUE NORTH
PREPARED BY
CONSULTANT CONSULTANT
GENERAL NOTES
NOT FOR CONSTRUCTION
VICINITY MAP
UNIVERSITY OF RHODE ISLAND WASHBURN HALL
75 BRIAR LANE
KINGSTON, RHODE ISLAND 02881
09/21/2026
G0.00
COVER SHEET
2503449
09/21/2026
BR
LA, LR, MS
JM
BID
PROJECT LOCATION
BUILDING LOCATION
R E
V
SHEET NUMBER SHEET NAME
GENERAL
G0.00 COVER SHEET
G0.01 CODE ANALYSIS
STRUCTURAL
S0.01 STRUCTURAL GENERAL NOTES
S1.00 BASEMENT AND FOUNDATION PLAN
S1.01 FIRST FLOOR FRAMING PLAN
S1.02 SECOND FLOOR FRAMING PLAN
S1.03 THIRD FLOOR FRAMING PLAN
S2.00 STRUCTURAL SECTIONS
S3.00 TYPICAL DETAILS
ARCHITECTURAL
A0.01 GENERAL INFORMATION, PARTITION TYPES AND DETAILS
AD1.00 BASEMENT DEMOLITION PLAN
AD1.01 FIRST FLOOR DEMOLITION PLAN
AD1.02 SECOND FLOOR DEMOLITION PLAN
AD1.03 THIRD FLOOR DEMOLITION PLAN
AD1.04 ATTIC DEMOLITION PLAN
AD1.05 ROOF DEMOLITION PLAN
AD2.00 BASEMENT DEMOLITION RCP
AD2.01 FIRST FLOOR DEMOLITION RCP
AD2.02 SECOND FLOOR DEMOLITION RCP
AD2.03 THIRD FLOOR DEMOLITION RCP
A1.00 BASEMENT FLOOR PLAN
A1.01 FIRST FLOOR PLAN
A1.02 SECOND FLOOR PLAN
A1.03 THIRD FLOOR PLAN
A1.04 ATTIC PLAN
A1.05 ROOF PLAN
A2.00 BASEMENT FLOOR REFLECTED CEILING PLAN
A2.01 FIRST FLOOR REFLECTED CEILING PLAN
A2.02 SECOND FLOOR REFLECTED CEILING PLAN
A2.03 THIRD FLOOR REFLECTED CEILING PLAN
A6.01 DOOR SCHEDULE, ELEVATIONS, AND DETAILS
A8.00 BASEMENT AND FIRST FLOOR FINISH PLAN
A8.01 SECOND FLOOR FINISH PLAN & FURNITURE PLAN
A8.02 THIRD FLOOR FINISH PLAN & FURNITURE PLAN
FIRE PROTECTION
FP001 FIRE PROTECTION NOTES, DESIGN CRITERIA, LEGEND, &
ABBREVIATIONS
FP102 SECOND FLOOR & THIRD FLOOR PLAN
FP501 DETAILS
MECHANICAL
M001 NOTES, SYMBOL LEGEND, & ABBREVIATIONS
MD102 SECOND FLOOR MECHANICAL DEMOLITION PLAN
MD103 THIRD FLOOR MECHANICAL DEMOLITION PLAN
M102 BASEMENT & SECOND FLOOR MECHANICAL PLANS
M103 THIRD FLOOR MECHANICAL PLAN
M104 ATTIC & ROOF MECHANICAL PLAN
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
ELECTRICAL
E001 ELECTRICAL SYMBOL LEGENDS, NOTES & ABBREVIATIONS
E002 TELECOMMUNICATION NOTES
ED101 BASEMENT FLOOR ELECTRICAL DEMOLITION PLAN
ED102 SECOND & THIRD FLOOR ELECTRICAL DEMOLITION PLANS
E101 BASEMENT & SECOND FLOOR POWER PLANS
E102 THIRD FLOOR & ATTIC POWER PLANS
E122 SECOND & THIRD FLOOR LIGHTING PLANS
E501 DETAILS
E502 DETAILS
E601 PANELBOARD SCHEDULES
E602 SCHEDULES & PARTIAL RISER DIAGRAM
E603 PARTIAL FIRE ALARM RISER DIAGRAM & MATRIX
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
IO
N
PROJECT LOCATION:
PROJECT DATA:
KINGSTON, RI
BUILDING DEPARTMENT:
APPLICABLE CODES:
TOWN OF SOUTH KINGSTOWN BUILDING INSPECTION & ZONING DEPARTMENT
180 HIGH STREET
WAKEFIELD, RI 02879
CHAPTER 8 - INTERIOR FINISHES
OCCUPANCY B
AUTOMATIC SPRINKLER SYSTEM PROVIDED
AUTOMATIC SPRINKLER SYSTEM MONITORING AND ALARMS WILL BE PROVIDED.
PORTABLE FIRE EXTINGUISHERS - SHALL BE PROVIDED PER THIS SECTION - AS SHOWN ON FIRE EXTINGUISHER PLANS.
A FIRE COMMAND CENTER REQUIRED
YES
YES
YES
NO
VERTICAL EXITS & EXIT PASSAGEWAYS -
EXIT ACCESS CORRIDORS & OTHER EXITS -
ROOMS AND ENCLOSED SPACES -
CLASS B
CLASS C
CLASS C
MINIMUM CLASS FINISH ALLOWED
302.1 - CLASSIFICATION:
CHAPTER 3 - USE & OCCUPANCY CLASSIFICATION:
GROUP IBC SECTION
DESCRIPTION OF OCCUPANCY
304.1
THE EXISTING BUILDING IS USED AS AN EDUCATIONAL FACILITY FOR POST-SECONDARY STUDENTS. THE PROJECT SCOPE INCLUDES STRUCTURAL REINFORCEMENTS AT THE BASEMENT AND FIRST FLOOR LEVELS, WITH INTERIOR SPACE
RECONFIGURATION PROPOSED ON THE THIRD FLOOR.
DESCRIPTION CLASSIFICATION
CONSTRUCTION TYPE:
CHAPTER 5 - GENERAL BUILDING HEIGHTS & AREAS:
III-B
B / BUSINESS
SPRINKLER SYSTEM: SPRINKLERED
BUSINESS
CHAPTER 6 - TYPE OF CONSTRUCTION:
CONSTRUCTION CLASSIFICATION: SECTIONS 601 & 602
FIRE RESISTANCE RATING REQUIREMENTS (TABLE 601)
NR = NO RATING
N/A = NOT APPLICABLE, CONDITION NOT PRESENT IN
DESIGN
MAIN USE
CONSTRUCTION TYPE: III-B, SPRINKLERED
CHAPTER 9 FIRE PROTECTION SYSTEM
CHAPTER 10 - MEANS OF EGRESS
B/ BUSINESS
(SPRINKLERED)
GROUP
MAXIMUM TRAVEL
DISTANCE
(TABLE 10 17.2)
300'
CORRIDOR WIDTH
MIN. 36"
COMMON PATH
OF TRAVEL
(TABLE 1006.2.1)
100'
SECTION 1004 OCCUPANT LOAD (See table provided under occupancy SHEET G0.01)
1005.3.1 STAIRWAYS. MEANS OF EGRESS CAPACITY OF 0.3" PER OCCUPANT
1005.3.2 OTHER EGRESS COMPONENTS. THE CAPACITY OF MEANS OF EGRESS COMPONENTS OTHER THAN STAIRWAYS SHALL BE 0.2 INCHES
PER OCCUPANT.
1006.2.1 TWO EXITS SHALL BE PROVIDED WHERE TRAVEL DISTANCE AND OCCUPANT LOAD EXCEED VALUES IN TABLE 1006.2.1
1006.2.1.1 THREE EXITS SHALL BE PROVIDED FROM ANY SPACE WITH AN OCCUPANT LOAD OF 301 TO 1,000. FOUR EXITS SHALL BE PROVIDED FOR
SPACES OVER 1,000 OCCUPANTS.
CORRIDOR FIRE RESISTANCE RATING - TABLE 1020.1
OCCUPANCY (A, B, S) WITH OCCUPANCY > 30 - WITH SPRINKLERS - 0 HOURS
OCCUPANCY TABLE
FUNCTION
AREA SF
OCCUPANCY
TYPE
NUMBER OF
EXITS
LOAD FACTOR
SF/PERSON
(GROSS/NET)
OCCUPANT
LOAD
BASEMENT
USE 1
UNOCCUPIED AREA
1ST FLOOR
USE 2 OCCUPANCY
USE 3 OCCUPANCY
2ND FLOOR
USE 1
UNOCCUPIED AREA
3RD FLOOR
USE 1 OCCUPANCY
USE 2 OCCUPANCY
USE 3 OCCUPANCY
0SF
0 SF
N/A
N/A
EXIST.
EXIST.
EXIST.
EXIST.
EXIST.
EXIST.
TOTAL OCCUPIABLE AREA
DEAD END
CORRIDOR
(TABLE 1020.5)
50'
N/A
B B B
0SF
349 SF
4,258 SF
1,331 SF
EXIST.
15 NET
150 GROSS
20 NET
EXIST.
EXIST.
ETR
ETR
FUNCTION OF SPACE
BUSINESS AREAS
349 SF
= 24P
CONFERENCE
15 594 SF
= 30P
CLASSROOM
716 SF
= 36P
CLASSROOM
ETR EMERGENCY EXIT,
EXTERIOR STAIR ETR EMERGENCY EXIT,
EXTERIOR STAIR
ETR EMERGENCY EXIT,
EXTERIOR STAIR
O
C C
18 OCC
O
C C
15 OCC
61 OCC
25 OCC
OFFICE
= 29
DN
DN
DN
EXIST. F.E.
EXIST. F.E.
F
F
F F
F
F
F
F
F
LIFE SAFETY LEGEND
OCCUPANCY LOADS
ROOM NAME
150 SF
= 15P
ROOM SQUARE FOOTAGE
OCCUPANCY LOAD
FLOOR AREA IN SQ. FT. / OCCUPANT
SYMBOLS
DOORS STAIRS
ACTUAL EGRESS LOAD
ALLOWABLE EGRESS LOAD
CUMULATIVE OCCUPANCY LOAD ON EGRESS ROUTE
COMMON PATH OF TRAVEL (? MAX)
MAXIMUM TRAVEL DISTANCE TO FURTHEST EXIT
(300' MAX - SPRINKLERED)
EXIT SIGN
F
HORN/STROBE
F F
PULL STATION & HORN/STROBE
EXISTING EXIT SIGN TO REMAIN
PROJECT NO.:
DATE:
REVIEWED:
DRAWN:
DESIGNED:
TITLE:
SHEET NUMBER
© 2025 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
ISSUED FOR:
C o m p a n ie s
A rc h it e ct u re
E n g in ee ri n g
E n vi ro n m en ta l
L a n d
S u rv ey in g
C :\U se rs
\la nd re ia nu \D oc um en ts
\2
_U R
I_ W as hb ur n
H al l_ A rc h_
R
_l an dr ei an u.
rv t
/2
2/
2:
:5
A M
G0.01
CODE ANALYSIS
2503449
09/21/2026
BR
LA, LR
JM
B
R
IA
R L
A N
E
K
IN
G S
T O
N , R
H O
D E
IS
LA
N D
U N
IV
E
R S
IT
Y
O F
R H
O D
E
IS
LA
N
D W
A S
H B
U R
N H
A
LL
BID
355 Research Parkway
Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
BUILDING CODES - RHODE ISLAND
ALL CONSTRUCTION SHALL CONFORM WITH THE FOLLOWING CODES:
LAST UPDATE: 07/13/2026
RHODE ISLAND FIRE SAFETY CODE
1. 2021 INTERNATIONAL FIRE CODE (AS AMENDED BY THE STATE OF RHODE ISLAND)
2. 2021 NFPA 101 LIFE SAFETY CODE (AS AMENDED BY THE STATE OF RHODE ISLAND)
3. 2022 NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE
PURSUANT TO THE RHODE ISLAND STATE BUILDING CODE, R.I. GEN. LAWS CHAPTER
23-27.3, AND THE RHODE ISLAND CODE OF REGULATIONS, TITLE 510, THE FOLLOWING
NATIONAL MODEL CODES, AS AMENDED BY THE STATE OF RHODE ISLAND, ARE
ADOPTED AND SHALL BE KNOWN AS THE RHODE ISLAND STATE BUILDING CODE.
RHODE ISLAND’S CURRENT STATE BUILDING CODES ARE BASED PRIMARILY ON THE
2021 ICC CODES, WITH THE 2023 NEC AND 2024 IECC
1. 2021 INTERNATIONAL BUILDING CODE
2. 2021 INTERNATIONAL EXISTING BUILDING CODE
3. 2021 IBC CHAPTER 11 ACCESSIBILITY AND ICC A117.1-2017 ACCESSIBLE AND USABLE
BUILDINGS AND FACILITIES
4. 2021 INTERNATIONAL PLUMBING CODE
5. 2021 INTERNATIONAL MECHANICAL CODE
6. 2024 INTERNATIONAL ENERGY CONSERVATION CODE
7. 2023 NFPA 70, NATIONAL ELECTRICAL CODE, OF THE NATIONAL FIRE PROTECTION
ASSOCIATION INC.
1/8" = 1'-0"
3RD FLOOR
TRAVEL DISTANCE
PATH NO. TRAVEL DISTANCE MAX. DISTANCE ALLOWED
(IBC TABLE 1017.2)
1 97' - 8" 300'
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
IO
N
RECORD DRAWINGS FROM PRIOR RENOVATIONS INDICATE THAT THIS
STAIR ENCLOSURE AND DOORS PROVIDING ACCESS TO THE STAIR
FROM ADJACENT INTERIOR SPACES ARE 1-HOUR FIRE-RESISTANCE-
RATED. RECORD DRAWINGS FURTHER INDICATE THAT INTERIOR
DOORS INSTALLED WITHIN 1-HOUR FIRE-RESISTANCE-RATED
PARTITIONS IN THIS AREA ARE ALSO 1-HOUR FIRE-RESISTANCE-RATED.
AS THIS AREA IS OUTSIDE THE LIMITS OF NEW WORK, NO
INDEPENDENT FIELD VERIFICATION OF THESE CONDITIONS HAS BEEN
PERFORMED AS PART OF THIS PROJECT. THIS AREA IS EXISTING TO
REMAIN AND IS NOT INCLUDED IN THE SCOPE OF WORK.
GENERAL NOTES:
EGRESS INFORMATION IS PROVIDED FOR THE THIRD FLOOR ONLY. THE PROPOSED WORK
ON THE THIRD FLOOR RESULTS IN A REDUCTION IN OCCUPANT LOAD FROM THE PREVIOUS
USE; THEREFORE, THIRD FLOOR EGRESS INFORMATION HAS BEEN INCLUDED TO
DOCUMENT APPLICABLE EXIT ACCESS AND EXIT CAPACITY CONDITIONS FROM THIS FLOOR.
EGRESS INFORMATION FOR THE BASEMENT, FIRST FLOOR, SECOND FLOOR, AND ATTIC
HAS NOT BEEN PROVIDED. NO CHANGES TO EXISTING OCCUPANCY, OCCUPANT LOAD, EXIT
ACCESS, NUMBER OF EXITS, EGRESS CAPACITY, OR OTHER MEANS OF EGRESS
COMPONENTS ARE PROPOSED ON THOSE LEVELS. ALL EXISTING EGRESS FEATURES AND
OCCUPANCY CONDITIONS ON THOSE LEVELS ARE TO REMAIN, AND NO EGRESS
MODIFICATIONS ARE REQUIRED FOR EXECUTION OF THE WORK INDICATED IN THESE
CONSTRUCTION DOCUMENTS.
WORK IS OCCURRING WITHIN PORTIONS OF THE BASEMENT, FIRST, SECOND, AND THIRD
FLOORS. THE SCOPE OF WORK SHALL NOT REDUCE THE EXISTING NUMBER OF EXITS,
ALTER REQUIRED MEANS OF EGRESS COMPONENTS, INCREASE THE OCCUPANT LOAD
SERVED BY EXISTING EXITS, OR INCREASE THE REQUIRED EGRESS CAPACITY OF THE
EXISTING MEANS OF EGRESS SYSTEM. EXISTING EXIT ARRANGEMENTS, EXIT CAPACITY,
AND EGRESS REQUIREMENTS SHALL REMAIN UNCHANGED EXCEPT AS SPECIFICALLY
INDICATED IN THESE DOCUMENTS.
EXISTING FIRE ALARM DEVICES, INITIATING DEVICES, NOTIFICATION APPLIANCES, EXIT
SIGNS, EMERGENCY LIGHTING, AND OTHER LIFE SAFETY SYSTEM COMPONENTS LOCATED
OUTSIDE THE LIMITS OF NEW WORK SHALL REMAIN IN PLACE AND ARE NOT REQUIRED TO
BE REPLACED UNDER THIS CONTRACT UNLESS SPECIFICALLY NOTED OTHERWISE. ALL
EXISTING-TO-REMAIN DEVICES SHALL BE PROTECTED DURING CONSTRUCTION.
EXISTING LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL THROUGHOUT
CONSTRUCTION EXCEPT WHERE TEMPORARY INTERRUPTION IS REQUIRED TO COMPLETE
THE WORK. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL
REQUIRED NOTIFICATIONS AND OBTAINING ALL REQUIRED APPROVALS FROM THE
AUTHORITIES HAVING JURISDICTION PRIOR TO COMMENCEMENT OF ANY WORK THAT MAY
IMPACT THE OPERATION OR EFFECTIVENESS OF THE EXISTING FIRE ALARM SYSTEM.
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL
CONNECTIONS, MODIFICATIONS, TESTING, AND COMMISSIONING REQUIRED FOR
INTEGRATION OF NEW FIRE ALARM DEVICES INTO THE EXISTING FIRE ALARM SYSTEM.
COORDINATE ALL SUCH WORK WITH URI FACILITIES MANAGEMENT, URI PUBLIC SAFETY,
THE EXISTING FIRE ALARM SYSTEM SERVICE PROVIDER, THE BUILDING OFFICIAL, FIRE
DEPARTMENT, AND OTHER AUTHORITIES HAVING JURISDICTION AS REQUIRED.
THE GENERAL CONTRACTOR SHALL ANTICIPATE PROVIDING A FIRE ALARM TIE-IN PLAN,
NARRATIVE, AND/OR OTHER DOCUMENTATION REQUIRED BY THE AUTHORITIES HAVING
JURISDICTION AS PART OF THE PERMITTING PROCESS FOR FIRE ALARM SYSTEM
ALTERATIONS. REFER TO THE ELECTRICAL DRAWINGS FOR FIRE ALARM SCOPE OF WORK,
DEVICE LOCATIONS, AND ASSOCIATED REQUIREMENTS.
THESE CONSTRUCTION DOCUMENTS DO NOT REPRESENT A COMPREHENSIVE AS-BUILT
RECORD OF THE EXISTING FIRE ALARM SYSTEM. EXISTING FIRE ALARM DEVICES AND
SYSTEM COMPONENTS LOCATED OUTSIDE THE LIMITS OF NEW WORK MAY NOT BE SHOWN.
ONLY NEW DEVICES AND EXISTING DEVICES BEING MODIFIED, RELOCATED, OR
OTHERWISE IMPACTED BY THE WORK ARE INDICATED. THE GENERAL CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND COORDINATE WITH URI FACILITIES MANAGEMENT
AND THE EXISTING FIRE ALARM SYSTEM SERVICE PROVIDER TO DETERMINE THE FULL
EXTENT OF THE EXISTING SYSTEM.
GENERAL NOTES:
DESIGNED IN ACCORDANCE WITH THE 2021 RHODE ISLAND BUILDING CODE, 2021 IBC, WITH STATE
AMENDMENTS.
IF ANY FIELD CONDITIONS PRECLUDE COMPLIANCE WITH THESE DRAWINGS AND/OR CONDITIONS SPECIFIED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER AND SHALL NOT PROCEED
WITH THE AFFECTED WORK.
TYPICAL DETAILS AND NOTES SHOWN HEREIN SHALL APPLY UNLESS SPECIFICALLY SHOWN OR NOTED OTHERWISE. CONSTRUCTION DETAILS NOT FULLY SHOWN OR NOTED SHALL BE SIMILAR TO DETAILS
SHOWN FOR SIMILAR CONDITIONS.
WORK AREAS SHALL BE MARKED, FENCED, AND OTHERWISE SECURED SO AS TO PROVIDE PROPER
PROTECTION FOR THE PUBLIC, AND AS REQUIRED BY THE BUILDING INSPECTOR.
IT SHALL BE THE CONTRACTORS SOLE RESPONSIBILITY TO DESIGN AND PROVIDE ADEQUATE SHORING, BRACING AND FORMWORK, ETC., AS REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. THIS INCLUDES PROVIDING TEMPORARY BRACING, SHORING, GUYS OR TIE-DOWNS.
THESE TEMPORARY SUPPORTS SHALL REMAIN IN PLACE UNTIL ALL STRUCTURAL COMPONENTS ARE
STABLE AND COMPLETED.
DEAD LOADS:
3/4 HARDWOOD FLOORING 3.1 PSF
DROP CEILING 1.0 PSF
MEP 3.0 PSF
SHELVING 25.0 PSF
PARTITION WALLS 5.5 PSF
MISCELLANEOUS 0.4 PSF
TOTAL 38.0 PSF
ROOF LIVE LOADS:
LIVE LOAD = 20 PSF (MIN.)
GROUND SNOW LOAD, Pg = 30 PSF EXPOSURE FACTOR, Ce = 1.0 THERMAL FACTOR, Ct = 1.0 IMPORTANCE FACTOR, Is = 1.0 CALCULATED FLAT ROOF SNOW LOAD, Pf = 25.2 PSF DESIGN SNOW LOAD, Pf = 30.0 PSF (PER RI MINIMUM)
SNOW LOADS INCREASED FOR DRIFT, SLIDING, ETC. WHERE APPLICABLE.
WIND LOADS:
RISK CATEGORY II
ULTIMATE DESIGN WIND SPEED (3-SECOND GUST) = 129 MPH
IMPORTANCE FACTOR, Iw = 1.0
EXPOSURE = "B"
TOPGRAPHICAL FACTOR, Kzt = 1.0
COMPONENT AND CLADDING ITEMS NOT DESIGNED BY THE ENGINEER OF RECORD: REFER TO
COMPONENTS AND CLADDING WIND PRESSURE TABLES
SEISMIC DESIGN CRITERIA:
Ss = 0.188 S1 = 0.052 SEISMIC IMPORTANCE FACTOR, Ie = 1.0
SITE CLASS = "D"
SDS = 0.201 SD1 = 0.084
SEISMIC DESIGN CATEGORY = "B"
BUILDING FRAME SYSTEMS -
LIGHT-FRAMED WOOD WALLS SHEATHED WITH STRUCTURAL PANELS
(R = 6.5, Cd = 3) SEISMIC RESPONSE COEFFICIENT, Cs = 0.031 DESIGN BASE SHEAR, V = Cs x W
ANALYSIS PROCEDURE = ELFP
ALL SPECIAL INSPECTION REPORTS PERFORMED IN ACCORDANCE WITH THE STATEMENT OF SPECIAL INSPECTIONS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW IN A TIMELY MANNER. THE FINAL REPORT OF SPECIAL INSPECTIONS SHALL NOT BE ISSUED UNTIL ALL SPECIAL INSPECTION REPORTS
HAVE BEEN RECEIVED AND APPROVED BY THE ENGINEER.
CONCRETE NOTES:
ALL CONCRETE WORK SHALL CONFORM TO ACI "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", ACI-318 - LATEST EDITION, AND "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES", ACI-315 - LATEST EDITION.
ALL CONCRETE FORMWORK SHALL CONFORM WITH ACI "RECOMMENDED PRACTICES FOR CONCRETE FORMWORK", ACI-347.
ALL STRUCTURAL CONCRETE SHALL CONFORM WITH ACI "SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS", ACI-301.
AIR ENTRAIN ALL EXTERIOR CONCRETE AND CONCRETE EXPOSED TO WEATHER..
ALL CONCRETE FOR FOOTINGS, SLABS, AND FOUNDATIONS SHALL BE NORMAL WEIGHT CONCRETE WITH A MINIMUM COMPRESSIVE
STRENGTH AT 28 DAYS OF 4,000 PSI.
ALL CONCRETE SHALL BE CONTINUOUSLY MOIST CURED FOR SEVEN (7) DAYS MINIMUM. CONCRETE SHALL BE KEPT MOIST BY FOG
SPRAYING, CURING PAPER AND/OR ACCEPTABLE CURING COMPOUNDS.
CONTRACTOR SHALL SUBMIT MIX DESIGNS FOR APPROVAL. MIX DESIGN SHALL INDICATE 28-DAY STRENGTHS, CEMENT CONTENT, AIR CONTENT, WATER-CEMENT RATIO, AMOUNT OF FINE AND COARSE AGGREGATES, AND ADMIXTURES.
MAX. WATER-CEMENT RATIO = 0.45
MAX. SLUMP = 4"
MAX. AGGREGATE SIZE = 3/4" TO 1"
CEMENT SHALL BE PORTLAND CEMENT, TYPE I OR II, CONFORMING TO ASTM C-150. AGGREGATES SHALL CONFORM TO ASTM C-33. AIR ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C-260. NON-SHRINK GROUT SHALL CONFORM TO ASTM C-109. EXPANSION JOINTS SHALL BE 1/2" THICK ASPHALT IMPREGNATED FIBERBOARD JOINT MATERIAL, CONFORMING TO ASTM D-1751. CURING COMPOUND SHALL
BE CLEAR, CONFORMING TO ASTM C-309.
COLD WEATHER CONCRETE WORK SHALL CONFORM TO ACI-306.
HOT WEATHER CONCRETE WORK SHALL CONFORM TO ACI-305.
ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60. WELDED WIRE MESH SHALL CONFORM TO ASTM A185 AND ASTM A82.
WELDED WIRE MESH SHALL HAVE MINIMUM END AND SIDE LAPS OF 1'-0".
CONCRETE ACCESSORIES SHALL BE ADEQUATE TO MAINTAIN REINFORCING ACCURATELY IN PLACE AND BE NON-CORROSIVE, NON-
STAINING TYPE.
LAP ALL BAR REINFORCING PER ACI-318. STAGGER SPLICES IN WALLS AND SLABS AND ALL HORIZONTAL REINFORCEMENT.
CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL (AS IN WALLS AND COLUMNS) SO AS TO CAUSE SEGREGATION OF AGGREGATES. USE HOPPERS, CHUTES OR TRUNKS OF VARYING LENGTHS SO THAT THE FREE UNCONFINED FALL OF CONCRETE SHALL
NOT EXCEED FIVE (5) FEET.
MINIMUM REINFORCEMENT COVER, UNLESS NOTED OTHERWISE:
-CONCRETE CAST AGAINST EARTH: 3"
-CONCRETE EXPOSED TO EARTH OR WEATHER:
No. 6 TO No. 18 BARS - 2" No. 5 AND SMALLER - 1 1/2"
-CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
No. 11 AND SMALLER - 3/4"
ALL CONCRETE WORK, REINFORCING PLACEMENT, AND FORMWORK SHALL BE INSPECTED BY AN INDEPENDENT TESTING AGENCY
RETAINED BY THE OWNER FOR THE FOLLOWING ITEMS:
• INSPECT BOTTOM OF FOOTING SOIL CONDITIONS.
• INSPECT FORMWORK AND PLACEMENT OF CONCRETE.
• SAMPLING FRESH CONCRETE PER ASTM C-172, MODIFIED FOR SLUMP BY ASTM C-94.
• SLUMP PER ASTM C-143. ONE TEST AT POINT OF DISCHARGE FOR EACH DAYS POUR FOR EACH TYPE OF CONCRETE.
• AIR CONTENT PER ASTM C-173 (VOLUMETRIC) OR ASTM C-231 (PRESSURE). ONE TEST FOR EACH DAYS POUR FOR EACH TYPE
OF CONCRETE.
• COMPRESSION TEST CYLINDERS PER ASTM C-31 (4 CYLINDERS)
• CONCRETE TEMPERATURE - TEST EACH TIME A SET OF CYLINDERS IS CAST.
• COMPRESSION STRENGTH TEST PER ASTM C-39. ONE SET FOR EACH DAYS POUR PLUS ADDITIONAL SETS FOR EACH 50 cy
OVER AND ABOVE THE FIRST 25 cy. ONE CYLINDER TESTED AT 7 DAYS, TWO CYLINDERS TESTED AT 28 DAYS, AND ONE
CYLINDER RETAINED FOR LATER TESTING IF REQUIRED.
ABBREVATIONS:
AASHTO AMERICAN ASSOCIATION OF STATE HIGHWAY
TRANSPORTATION OFFICIALS
A.B. ANCHOR BOLT OR ANCHOR ROD
A.A.S. ADHESIVE ANCHORING INSTITUTE
ACI AMERICAN CONCRETE INSTITUTE
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
AFPA AMERICAN FOREST AND PAPER ASSOCIATION
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT. ALTERNATE
ALUM ALUMINUM
ANCH. ANCHOR OR ANCHORAGE
ARCH. ARCHITECTURAL OR ARCHITECT
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
B, BOTT. BOTTOM
B/, B.O. BOTTOM OF
BLDG. BUILDING
BM. BEAM
B.O.F. BOTTOM OF FOOTING
B.O.S. BOTTOM OF STEEL
BRG. BEARING
B/S BOTH SIDES
CF COLD-FORMED
CFMF COLD-FORMED METAL FRAMING
C.G. CENTER OF GRAVITY
C.I.P. CAST IN PLACE
C.J. CONTROL JOINT
CLR. CLEAR
CMU CONCRETE MASONRY UNIT
C.O. CLEAN OUT
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CONST. CONSTRUCTION
CONST. JT. CONSTRUCTION JOINT
CONT. CONTINUOUS
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CTR. CENTER
CWA COORDINATE WITH ARCHITECTURAL DRAWINGS
D-B DESIGN BUILD
DEPR. DEPRESSION
DEPT. DEPARTMENT
DET. DETAIL
DIA. DIAMETER
DIM. DIMENSION
DIR. DIRECTION
DN DOWN
D.O. DITTO (SAME AS ABOVE)
D.O.T. DEPARTMENT OF TRANSPORTATION
DWG. DRAWING
DWL. DOWEL(S)
EA. EACH
E.E. EACH END
E.F. EACH FACE
EL., ELEV. ELEVATION
ELEC. ELECTRICAL
EMBED. EMBEDMENT
ENGR. ENGINEER
E.O.D. EDGE OF DECK
E.O.S. EDGE OF STEEL
EQ. EQUAL
E.W. EACH WAY
EX., EXIST. EXISTING
EXP. EXPANSION
EXP. JT., E.J. EXPANSION JOINT
EXT. EXTENSION
F.D. FLOOR DRAIN
F.F. FAR FACE
FND. FOUNDATION
FIN. FINISH
FL. FLOOR
FLG. FLANGE
F.M. FACTORY MUTUAL
F.S. FAR SIDE
FT. FEET OR FOOT
FTG. FOOTING
F.O.W. FACE OF WALL
GA. GAUGE
G.B. GRADE BEAM
GALV. GALVANIZED
G.C. GENERAL CONTRACTOR
GEN., GENL GENERAL
GR. GRADE
HDR. HEADER
HOR., HORIZ. HORIZONTAL
H.P. HIGH POINT
H.S. HIGH STENGTH
HSS HOLLOW STRUCTURAL SECTION
HT. HEIGHT
ICC INTERNATIONCODE COUNCIL
I.D. INSIDE DIAMETER
I.F. INSIDE FACE
IN. INCH OR INCHES
INCL. INCLUDING
INFO INFORMATION
INT. INTERIOR
INV. INVERT
JST. JOIST
JT. JOINT
K KIP (1000 LBS.)
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
L.B. ANGLE BRACE (ALSO SEE SYMBOLS)
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC. LOCATION
L.P. LOW POINT
L.W. LIGHT WEIGHT
MAS. MASONRY
MATL. MATERIAL
MAX. MAXIMUM
MECH. MECHANICAL
M/E/P MECHANICAL/ELECTRICAL/PLUMBING
MEZZ. MEZZANINE
MID. MIDDLE
MID-PT MIDPOINT
MIN. MINIMUM
MM MILLIMETER
M.O. MASONRY OPENING
MTL METAL
N.F. NEAR FACE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
N.I.C. NOT IN CONTRACT
NO. NUMBER
N.S. NEAR SIDE
N.T.S. NOT TO SCALE
N.W. NORMAL WEIGHT
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F. OUTSIDE FACE
O.H. OPPOSITE HAND
O/H OVERHANG
OPNG. OPENING
OPP. OPPOSITE
P.A.F. POWER-ACTUATED FASTENER
PART. PARTIAL
PL. PLATE
PCA PORTLAND CEMENT ASSOCIATION
PCI PRE-STRESSED CONCRETE INSTITUTE
P/C PRECAST CONCRETE
PEN. PENETRATION
PLF, #/FT POUNDS PER SQUARE FOOT
PREFAB. PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POINDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT. POINT
P/T PRESERVATIVE TREATED
PTD. PAINTED
PVC POLYVINYL CHLORIDE
R RADIUS
R/C REINFORCED CONCRETE
R.C.P. REINFORCED CONCRETE PIPE
R.D. ROOF DRAIN
REF. REFERENCE
REINF. REINFORCING
REQ'D REQUIRED
RET. RETURN
R.F. ROOF FRAME
RFT. RAFTER
R.O. ROUGH OPENING
RTU ROOF TOP UNIT
SDI STEEL DECK INSTITUTE
SECT. SECTION
S.F. STEP FOOTING
SHTG. SHEATHING
SIM. SIMILAR
SJI STEEL JOIST INSTITUTE
SL. SLOPING BEAM OR GIRDER
S.O.G. SLAB ON GRADE
SPA. SPACES
SQ. SQUARE
S.S. STAINLESS STEEL
STD. STANDARD
STL. STEEL
STIFF. STIFFENER
T/, T.O. TOP OF
T&B TOP AND BOTTOM
TEMP. TEMPORARY
THK. THICK OR THICKNESS
THRD. THREADED
THRU THROUGH
T.O.C. TOP OF CONCRETE
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TS TUBE STEEL
TSF TONS PER SQUARE FOOT
TYP. TYPICAL
UL UNDERWRITER'S LABORATORIES
U.O.N. UNLESS OTHERWISE NOTED
VERT. VERTICAL
V.I.F. VERIFY IN FIELD
w/ WITH
W.O. WINDOW OPENING
W.P. WORKING POINT
W.W.F. WELDED WIRE FABRIC
GEOTECHNICAL NOTES:
ALL UNDERGROUND UTILITY LOCATIONS SHALL BE VERIFIED PRIOR TO STARTING EXCAVATION WORK.
CALL BEFORE YOU DIG PRIOR TO STARTING ANY EXCAVATION.
THE CONTRACTOR WILL PERFORM EXCAVATIONS, FOOTING CONSTRUCTION, AND PREPARATION OF THE SUBGRADE UNDER FOUNDATIONS IN ACCORDANCE WITH THE RECOMMENDATIONS CONTAINED IN THESE
DRAWINGS.
ALL FOOTINGS HAVE BEEN DESIGNED FOR AN ASSUMED ALLOWABLE NET SOIL BEARING PRESSURE OF 2,000 PSF PER SECTION 1806 OF THE BUILDING CODE. WHERE THE BUILDING OFFICIAL OR 3RD PARTY INSPECTOR DEEMS THE SOILS SUPPORTING THE STRUCTURAL FOOTINGS IS INADEQUATE, A FORMAL
GEOTECHNICAL INVESTIGATION SHALL BE REQUIRED TO CONFIRM THAT THE MINIMUM DESIGN
REQUIREMENTS NOTED IN THE GENERAL NOTES CAN BE MET. FOOTINGS SHALL BEAR ON UNDISTURBED SUBBASE. NO FOOTINGS SHALL BEAR ON LOAM OR SOIL FILL. IF ROCK IS ENCOUNTERED PRIOR TO THE PROPOSED BOTTOM OF FOOTING ELEVATION, THE ROCK SHALL BE OVEREXCAVATED BY 1'-0", AND BACKFILLED WITH 3/4" CRUSHED STONE TO THE BOTTOM OF FOOTING, AND COVERED WITH FILTER
FABRIC.
ALL COMPACTED CONTROLLED FILL BEING PLACED MUST BE TESTED BY AN APPROVED TESTING
LABORATORY DURING THE FILL OPERATION. ALL FOUNDATION SUBGRADES SHALL BE INSPECTED AND APPROVED UNDER THE SUPERVISION OF A REGISTERED PROFESSIONAL ENGINEER PRIOR TO BEING CONCRETED. SLABS AND FOOTINGS SHALL NOT BE PLACED UNTIL FILL TEST REPORTS HAVE BEEN CHECKED AND APPROVED BY THE ENGINEER. PROIR TO PLACING CONCRETE, EXISTING SOIL CONDITIONS SHALL BE INSPECTED AND VERIFIED BY THE ENGINEER. ALL UNSUITABLE SOIL SHALL BE REMEDIATED AS DIRECTED BY THE ENGINEER. CONTROLLED FILL, EITHER STRUCTURAL FILL OR SLAB BASE SHALL BE INERT, GRANULAR FILL, FREE FROM ORGANICS AND DEBRIS. ALL CONTROLLED FILL PLACED SHALL BE COMPACTED TO A MINIMUM OF 95% OF MAXIMUM DRY UNIT WEIGHT AS DETERMINED BY THE MODIFIED
PROCTOR TEST, ASTM D1557.
WOOD NOTES:
WOOD CONSTRUCTION SHALL BE IN ACCORDANCE WITH CHAPTER 23 OF THE BUILDING CODE.
ALL LUMBER FRAMING MEMBERS ARE TO HAVE THE FOLLOWING MINIMUM BASE DESIGN VALUES IN
ACCORDANCE WITH THE LATEST ISSUE OF THE NATIONAL DESIGN SPECIFICATION FOR WOOD
CONSTRUCTION (NDS) AS PUBLISHED BY THE AMERICAN FOREST AND PAPER ASSOCIATION (AFPA):
PSL 2.0E:
Fb = 2900 PSI Fv = 290 PSI Ft = 2300 PSI Fcll = 2900 PSI Fc,PERP = 525 PSI
E = 2,000,000 PSI.
ALL SILLS SHALL BE DOUGLAS FIR #2 OR GREATER
ALL FRAMING LUMBER SHALL BE AS GRADED PER AMERICAN LUMBER STANDARDS (U.N.O.) WITH
MINIMUM GRADES AS FOLLOWS:
STUDS: 2x - DOUGLAS FIR No.2 & BETTER, OR 1.5E LSL.
POSTS: MULTIPLE 2x - DOUGLAS FIR No. 2 & BETTER, OR 2.0E PSL.
PLATES, BLOCKS, AND MISC.: DOUGLAS FIR No. 2 OR BETTER, OR 2.0E PSL.
JOISTS: 2x - DOUGLAS FIR No. 2 OR BETTER, OR 2.0E PSL.
BEAMS AND HEADERS: MULTIPLE 2x - DOUGLAS FIR No. 2 OR BETTER, OR 2.0E PSL.
ALL WOOD SHEATHING SHALL BE STRUCTURAL 1 APA-RATED.
PLYWOOD SHALL BE CONTINUOUS OVER TWO (2) OR MORE SPANS AND FACE GRAIN PERPENDICULAR TO
SUPPORT.
NAILING OF MULTIPLE MEMBERS SHALL BE AS REQUIRED BY THE MANUFACTURER. BEARING OF ALL
BEAMS SHALL BE THREE (3) INCHES MINIMUM.
ALL WOOD OR ENGINEERED LUMBER MEMBERS IN CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE TREATED.
ROOF SHEATHING FASTENERS SHALL BE SPACED AT 6" o.c. AT EDGES, AND AT 12" o.c. AT INTERMEDIATE
SUPPORTS, U.N.O.
COMMON NAILS ARE REQUIRED FOR SHEAR WALLS, INCLUDING PLATE NAILING, TIE-DOWNS, HANGERS, AND LEDGERS.
BOX NAILS REQUIRE 1/3 MORE NAILS THAN LISTED ABOVE. CEMENT COATED SINKERS ARE CONSIDERED
BOX NAILS.
DF: DOUGLAS FIR, No. 2 OR BETTER:
Fb = 900 PSI Fv = 180 PSI Ft = 575 PSI Fcll = 1350 PSI Fc,PERP = 625 PSI
E = 1,600,000 PSI
STUDS:
NOTCHED AND/OR CUT STUDS TO CLEAR ANCHOR BOLTS ARE NOT ALLOWED. STUDS SHALL HAVE FULL
BEARING TO THE BOTTOM PLATES.
SEE ARCHITECTURAL DRAWINGS FOR ALL NON-BEARING AND NON-SHEAR WALLS.
STACK ALL BEARING STUDS, CRIPPLE STUDS AND POSTS FROM ROOF AND ALL FLOOR LEVELS DOWN TO
THE CONCRETE SLAB.
PROVIDE SOLID BLOCKING BETWEEN FLOORS FOR ALL POSTS. ALL POSTS SHALL STACK AND BE
CONTINUOUS TO THE CONCRETE SLAB.
CARPENTRY NOTES-
WALLS SHOWN ARE BELOW FRAMING LEVEL AT FLOOR AND ROOF FRAMING PLANS.
VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
SEE ARCHITECTURAL DRAWINGS FOR WALLS AND DIMENSIONS NOT SHOWN OR NOTED.
SEE ARCHITECTURAL OR CIVIL DRAWINGS FOR WALKS, RAMPS, PATIOS, ETC., NOT SHOWN OR NOTED.
VERIFY PLATE AND FRAMING ELEVATIONS WITH ARCHITECTURAL DRAWINGS.
SEE ARCHITECTURAL DRAWINGS FOR ROOF SLOPES, ELEVATION, AND DRAINAGE.
USE POWDER ACTUATED FASTENERS AT 16" OC MAX. WITH 2x PRESSURE TREATED SILL PLATES AT NON-
BEARING AND NON-SHEAR WALLS AT CONCRETE SLAB ONLY.
CRIPPLE WALLS SHALL BE A MINIMUM OF 12" IN HEIGHT. FOR LESSER HEIGHTS, STACK 2x PLATES (AND
SHIM AS REQUIRED).
NOTCHED AND/OR CUT JOISTS ARE NOT ALLOWED. VERIFY ALL JOIST OPENINGS WITH STRUCTURAL
ENGINEER PRIOR TO STARTING WORK.
WOOD CONSTRUCTION SHALL BE PER AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (AITC)
STANDARDS AND SPECIFICATIONS, AND NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION
(NDS) AS PUBLISHED BY THE AMERICAN FOREST AND PAPER ASSOCIATION (AFPA).
PROVIDE TWO (2) JACK STUDS AND TWO (2) KING STUDS AT EACH END OF WOOD HEADERS, TYPICAL, UNLESS NOTED OTHERWISE.
SHEATHING SHALL BE CONTINUOUS OVER TWO (2) OR MORE SPANS AND FACE GRAIN PERPENDICULAR
TO SUPPORT.
SHEATHING FOR ROOF: 5/8" STRUCTURAL 1 APA-RATED SHEATHING. SEE ARCHITECTURAL DRAWINGS
FOR EXPOSED OVERHANGS AND CEILINGS.
SHEATHING FOR SUBFLOORS: 3/4" STRUCTURAL 1 APA-RATED TONGUE AND GROOVE SHEATHING, U.N.O.
SHEATHING FOR EXTERIOR WALLS: 7/16" APA-RATED ZIP-SHEATHING, U.N.O.
SHEATHING FOR EXTERIOR AND INTERIOR SHEAR WALLS: STRUCTURAL 1 APA RATED SHEATHING, THICKNESS PER SHEARWALL SCHEDULE
JOIST HANGERS, STRAPS, CLIPS AND TIE-DOWNS SHALL BE MANUFACTURED BY THE "SIMPSON STRONG-
TIE COMPANY, INC." OR APPROVED EQUAL.
NAILING OF MULTIPLE MEMBERS SHALL BE AS REQUIRED BY THE MANUFACTURER. BEARING OF ALL
BEAMS SHALL BE 1 1/2" INCHES MINIMUM.
LAMINATED BEAMS SHALL NOT BE USED IN LOCATIONS EXPOSED TO WEATHER, UNLESS THEY HAVE
BEEN PRESSURE TREATED AND WATER REPELLENT APPLIED.
ALL WOOD OR ENGINEERED LUMBER MEMBERS IN CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE TREATED.
NAILING SCHEDULE - IN ACCORDANCE WITH CHAPTER 23, THE BUILDING CODE.
IF NAILING IS NOT NOTED OR SHOWN IN THE DETAILS OR PLANS, USE THE FOLLOWING MINIMUM CRITERIA:
JOIST TO SILL OR GIRDER, TOE NAIL.......................................(3)-8d CONTINUOUS RIM JOIST TO DBL TOP PLATES........................16d @ 8" o.c.
BRIDGING TO JOIST, TOENAIL EACH END................................(2)-8d SOLE PLATE TO JOIST OR BLOCKING, FACE NAIL..................16d @ 8" o.c.
TOP PLATE TO STUD, END NAIL.............................................(2)-16d STUD TO SOLE PLATE...............................................................(4)-8d, TOENAIL OR (2)-16D, END NAIL DOUBLE STUDS, FACE NAIL......................................................16d @ 24" o.c.
DOUBLE TOP PLATES, FACE NAIL............................................16d @ 16" o.c.
TOP PLATES, LAPS AND INTERSECTIONS, FACE NAIL............(2)-16d CONTINUOUS HEADER, TWO PIECES.........................................16d @ 16" o.c.
STAGGERED ALONG EDGE
CEILING JOISTS TO PLATE, TOE NAIL.......................................(3)-8d CONTINUOUS HEADER TO STUD, TOE NAIL..............................(4)-8d CEILING JOISTS, LAPS OVER PARTITION, FACE NAIL..............(3)-16d CEILING JOISTS TO PARALLEL RAFTERS, FACE NAIL..............(3)-16d RAFTER TO PLATE, TOE NAIL..................................................(3)-8d 1" BRACE TO EACH STUD AND PLATE, FACE NAIL...............(2)-8d 1"x8" SHEATHING OR LESS TO EACH BRG, FACE NAIL.........(3)-8d WIDER THAN 1"x8" SHEATHING TO EACH BRG, FACE NAIL...(3)-8d BUILT-UP CORNER STUDS........................................................16d @ 16" o.c.
PLYWOOD OR OSB:
FLOOR, WALL, AND ROOF SHEATHING (TO FRAMING):
1/2", 5/8", 3/4"..................................................10d
SUBFLOOR FASTENERS SHALL BE SPACED AT 6" OC. AT EDGES, AND AT 12" OC. AT INTERMEDIATE
SUPPORTS, UNLESS OTHERWISE NOTED. USE RING SHANK NAILS.
WALL SHEATHING FASTENERS SHALL BE SPACED AS NOTED ON THE SECTIONS AND DETAILS.
ROOF SHEATHING FASTENERS SHALL BE SPACED AT 6" OC AT EDGES, AND AT 12" OC AT INTERMEDIATE
SUPPORTS, U.N.O.
BOX NAILS MAY BE USED FOR ABOVE NAILING WITH APPROVAL FROM THE ENGINEER.
COMMON NAILS ARE REQUIRED FOR SHEAR WALLS, INCLUDING PLATE NAILING, TIE-DOWNS, HANGERS, AND
LEDGERS.
BOX NAILS REQUIRE 1/3 MORE NAILS THAN LISTED ABOVE. CEMENT COATED SINKERS ARE CONSIDERED BOX
NAILS.
355 Research Parkway Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
Project No.:
Date:
Reviewed:
Drawn:
Designed:
Title:
Sheet No.
© 2022 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
Issued for:
C o m p a n ie s
A rc h it e c tu re
E n g in e e ri n g
E n v ir o n m e n ta l
La n d S u rv e y in g
C U s e rs \K
P itz e r\
D o c u m e n ts
\r e v it_ lo c a l\
U R
I_ W a s h b u rn H a ll_
S tr u c t_
R k p it z e rP D
M
L .r v t
/2
/2
:2 :3
P
M
S0.01
STRUCTURAL GENERAL
NOTES
2503449
10/21/2026
JRM
KJP
KJP
B
R
IA
R L
A N
E K
IN
G
S
TO
N , R
H O
D E
IS
LA
N D
U R
I - W
A S
H B
U R
N H
A
LL
BID
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
Existing Bearing Walls, Typ.
Existing bearing walls, typ.
Existing Bearing Walls, Typ.
S2.00
S2.00
F35
F34
F3.5
F3.5
11'-9" V.I.F.
5'-6 3/4"
Existing Wall Footing, TO
REMAIN, V.I.F.
(7'-6" MAX.)
6'-4 1/2" V.I.F.
(7'-6" MAX.)
6'-4 1/2" V.I.F.
(7'-6" MAX.)
6'-11 3/4" V.I.F.
S3.00
S3.00
DOWEL INTO EXISTING FTG.,
SEE SECTION 6/S3.00
S3.00
TYP.
6'-2 1/2" 3'-6"
DOWEL INTO EXISTING
FTG. W/ #5 @ 12" O.C.
EMBED = 6", TYP.
3'-2 7/8" 3'-6"
3'-2 7/8" V.I.F. 3'-6" V.I.F.
F3.5
1' -6
V .I.
F.
2' -0
1'
-6
SEE NOTE 9
9' -0
/8
" V .I.
F.
9' -6
" V .I.
F.
7' -9
" V .I.
F.
5' -5
" V .I.
F.
8' -1
5/
8" V
.I.
F.
TYP. WALL
FTG.
S3.00
TYP. WALL
FTG.
SEE DETAIL xxxx
FOR TYPICAL
CONCRETE
PENETRATIONS
13/S3.00
S3.00
TYP. WALL
FTG.
S3.00
Existing Wall Footing, V.I.F.
DOWEL INTO EXISTING
FTG. W/ #5 @ 12" O.C.
EMBED = 6"
DOWEL INTO EXISTING
FTG. W/ #5 @ 12" O.C.
EMBED = 6", TYP.
DOWEL INTO EXISTING
FTG. W/ #5 @ 12" O.C.
EMBED = 6"
Existing Wall Footing, TO
REMAIN, V.I.F.
Existing Wall Footing, TO
REMAIN, V.I.F.
MIN.
1'-0"
Existing Wall Footing, TO
REMAIN, V.I.F.
F3.5
2'-0"
3' -0
S3.00
TYP.
TYP.
S3.00
TYP.
S3.00 TYP.
S3.00
TYP.
S3.00
F3.5
2'-0"
Existing Wall Footing, V.I.F. REMOVE AT NEW
FOOTING
Existing CMU Wall, REMOVE AND REBUILD
AT NEW FOOTING
DOWEL INTO EXISTING
FTG. W/ #5 @ 12" O.C.
EMBED = 6", TYP.
DOWEL INTO EXISTING
FTG. W/ #5 @ 12" O.C.
EMBED = 6", TYP.
7' -8
" V .I.
F.
2'
-0
FOUNDATION PLAN NOTES:
1. THE EXISTING PLANS ARE BASED OFF OF EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL
DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED.
2. COORDINATE ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
3. FLOOR FRAMING SHOWN IS SUPPORTING THE FLOOR ABOVE. SEE THE FIRST FLOOR FRAMING FOR WALL
AND HEADER SIZES.
4. CONTRACTOR TO PERFORM PRICING OPTION FOR JACKING OF THE EXISTING 1ST FLOOR. JACKING WILL
CONSIST OF USING JACK POSTS AND UNIFORMLY JACKING THE FLOOR IN 1/4 INCH INCREMENTS OVER THE COURSE OF 2 WEEKS UNTIL A UNIFORM TOLERANCE IS ACCEPTED. CURRENT DEFLECTIONS ARE
REPORTED BETWEEN 2" TO 4".
5. SEE SHEET S1.01 FOR WALL TYPES.
6. DIMENSIONS TO NEW SUPPORTS ARE APPROXIMATE. FIELD SHIFTING IS ALLOWABLE TO AVOID UTILITIES.
7. SHIMMING IS ALLOWABLE WHERE REQUIRED TO AVOID UTILITIES. VERIFY HEADER AND WALL HEIGHTS IN
FIELD.
8. CONTRACTOR TO PROVIDE NEW FRAMING PRIOR TO REMOVAL OF EXISTING SUPPORTS. ADDITIONAL
SHORING WILL BE REQUIRED WHERE STAGING CAN NOT BE SATISFIED TO LIMIT DEFLECTIONS.
9. AREA ASSUMED TO BE OFF-LIMITS FOR EXCAVATIONS. COORDINATE WITH ELECTRICAL PLANS
TO LIMIT DISTURBANCE IN THIS AREA.
10. CONTRACTOR SHALL FIELD VERIFY THE CONDITION, LOCATION, AND EXTENTS OF EXISTING
FOUNDATIONS PRIOR TO DRILLING OR DOWELING. IF DETERIORATED OR OTHERWISE UNSUITABLE
CONCRETE IS ENCOUNTERED, COORDINATE WITH THE EOR PRIOR TO PROCEEDING.
11. PROVIDE NEW UNDERSLAB VAPOR RETARDER BELOW ALL SLAB PATCHES ASSOCIATED WITH NEW
FOOTINGS. INSTALL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND MAINTAIN
CONTINUITY THROUGHOUT PATCH AREA. UNDERSLAB VAPOR RETARDER IS PROVIDED ONLY WITHIN LIMITS OF NEW WORK AND IS NOT INTENDED TO SERVE AS A COMPLETE BASEMENT WATERPROOFING SYSTEM OR TO CORRECT EXISTING MOISTURE, WATER INFILTRATION, GROUNDWATER, OR DRAINAGE
CONDITIONS.
12. THE GENERAL CONTRACTOR SHALL, WITHIN THIRTY (30) DAYS OF EXECUTION OF THE CONTRACT, OBTAIN A GROUND PENETRATING RADAR (GPR) SURVEY AND/OR SLAB X-RAY OF EXISTING CONCRETE SLABS IN AREAS AFFECTED BY THE WORK TO IDENTIFY REINFORCING, EMBEDDED ITEMS, SUBSURFACE STRUCTURES, UTILITIES, OR OTHER EXISTING CONDITIONS THAT MAY IMPACT THE EXECUTION OF THE WORK. UPON RECEIPT, THE GENERAL CONTRACTOR SHALL PROMPTLY SUBMIT THE SURVEY RESULTS
AND ALL ASSOCIATED FINDINGS TO THE OWNER AND ENGINEER OF RECORD FOR REVIEW AND
COORDINATION OF EXISTING CONDITIONS WITH THE PROPOSED WORK. ANY CONDITIONS THAT
CONFLICT WITH THE CONSTRUCTION DOCUMENTS OR MAY IMPACT THE EXECUTION OF THE WORK
SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER AND ENGINEER OF RECORD PRIOR TO
PERFORMANCE OF THE AFFECTED WORK.
N
355 Research Parkway Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
Project No.:
Date:
Reviewed:
Drawn:
Designed:
Title:
Sheet No.
© 2022 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
Issued for:
TRUE NORTH
C o m p a n ie s
A rc h it e c tu re
E n g in e e ri n g
E n v ir o n m e n ta l
La n d S u rv e y in g
C U s e rs \K
P itz e r\
D o c u m e n ts
\r e v it_ lo c a l\
U R
I_ W a s h b u rn H a ll_
S tr u c t_
R k p it z e rP D
M
L .r v t
/2
/2
:2 :3
P
M
S1.00
BASEMENT AND
FOUNDATION PLAN
2503449
10/21/2026
JRM
JRM
KJP
B
R
IA
R L
A N
E K
IN
G
S
TO
N , R
H O
D E
IS
LA
N D
U R
I - W
A S
H B
U R
N H
A
LL
BID
1/4" = 1'-0"
BASEMENT AND FOUNDATION PLAN
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
IO
N
FOOTING SCHEDULE
FOOTING MARK SIZE (LxWxH) REINFORCING (BOTTOM, UON) REFERENCE
F3.5 3'-6"x3'-6"x1'-0" w/ (5) - #5 Bars Each Way 7/S3.00
F34 3'-0"x4'-0"x1'-0" w/ (5) - #5 Bars Each Way 7/S3.00
F35 3'-0"x5'-0"x1'-0" w/ (5) - #5 Bars Each Way 7/S3.00
(E) STEEL GIRDER
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
S2.00
H4 H4
H4
S2.00
H4 H3H4
2X12 BLOCKING @ 24"
O.C., (2) BAYS EA SIDE OF
OFFICE PARTITIONS, TYP
P3
P2P3
P2
P3
P3
P3
P3
P2 P2
2X12 BLOCKING @ 24"
O.C., (2) BAYS EA SIDE OF
OFFICE PARTITIONS, TYP
W-3 W-3 W-3
2X12 BLOCKING @ 24"
O.C., (2) BAYS EA SIDE OF
OFFICE PARTITIONS, TYP2X12 BLOCKING @ 24"
O.C., (2) BAYS EA SIDE OF
OFFICE PARTITIONS, TYP
W-3
Existing Granite Bearing Walls
Existing Granite Bearing Walls
TYP. @
BLOCKING
S3.00
TYP.
S3.00
H
P2
P3
H 4W-3
W-3 W-3 W-3
P2 P2 P2 P2
H3 H3
FLOOR PLAN NOTES:
1. THE EXISTING PLANS ARE BASED OFF OF EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL
DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED.
2. COORDINATE ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
3. FLOOR FRAMING SHOWN IS FOR FRAMING BELOW SUPPORTING THE CURRENT FLOOR.
4. "P-x" DENOTES POST TYPE. SEE POST SCHEDULE ON THIS SHEET FOR SIZE AND TYPE.
5. "Hx" DENOTES HEADER TYPE. SEE HEADER SCHEDULE ON THIS SHEET FOR SIZE AND TYPE.
6. "W-x" DENOTES WALL TYPE. SEE WALL SCHEDULE ON THIS SHEET FOR SIZE, SPACING, AND FASTENING
REQUIREMENTS.
7. PROVIDE SIMPSON MGU5.5 HANGER AT PSL BEAM TO BEAM CONNECTION LOCATIONS.
8. SEE DETAIL xxxxx FOR TYPICAL FASTENING OF EXISTING FLOOR JOIST TO NEW SUPPORTS.
9. DIMENSIONS TO NEW SUPPORTS ARE APPROXIMATE. FIELD SHIFTING IS ALLOWABLE TO AVOID UTILITIES.
10. SHIMMING IS ALLOWABLE WHERE REQUIRED TO AVOID UTILITES. VERIFY HEADER AND WALL HEIGHTS IN
FIELD.
11/S3.00
WALL SCHEDULE
WALL
MARK
STUDS TOP PLATE BOTTOM PLATE
W-1 OPTION 1: 2x6 @ 16" O.C.
OPTION 2: (2) 2x4 @ 24" O.C.
DOUBLE 2x
MATCH STUD WIDTH
SINGLE 2x
MATCH STUD WIDTH
W-3 2x6 @ 16" O/C DOUBLE 2x6 SINGLE 2x6
W-2 OPTION 1: 2x6 @ 16" O.C.
OPTION 2: (2) 2x4 @ 16" O.C.
DOUBLE 2x
MATCH STUD WIDTH
SINGLE 2x
MATCH STUD WIDTH
NOTES:
1. ALL WOOD BEARING WALLS, SHALL BE BLOCKED AND SHEATHED W/ 1/2" PLYWOOD, ONE
SIDE.
2. SHEATHING SHALL BE FASTENED WITH 8d NAILS AT 6" O.C. AT ALL PANEL EDGES, AND 8d
NAILS AT 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS.
3. SEE DETAIL FOR WALL PANEL LAYOUT.
4. AT SILL TO CONCRETE CONNECTIONS, PROVIDE TITAN HD 1/2" W/ 3 1/4" EMBED AT 32" O.C.
5. AT SILL TO WOOD FLOOR CONNECTIONS, PROVIDE SIMPSON SDS 1/4x6" SCREW AT 16" O.C.
3/S3.00 N
355 Research Parkway Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
Project No.:
Date:
Reviewed:
Drawn:
Designed:
Title:
Sheet No.
© 2022 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
Issued for:
TRUE NORTH
C o m p a n ie s
A rc h it e c tu re
E n g in e e ri n g
E n v ir o n m e n ta l
La n d S u rv e y in g
C U s e rs \K
P itz e r\
D o c u m e n ts
\r e v it_ lo c a l\
U R
I_ W a s h b u rn H a ll_
S tr u c t_
R k p it z e rP D
M
L .r v t
/2
/2
:2 :3
P
M
S1.01
FIRST FLOOR FRAMING
PLAN
2503449
10/21/2026
JRM
JRM
KJP
B
R
IA
R L
A N
E K
IN
G
S
TO
N , R
H O
D E
IS
LA
N D
U R
I - W
A S
H B
U R
N H
A
LL
BID
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
IO
N
1/4" = 1'-0"
STRUCTURAL FIRST FLOOR FRAMING PLAN
HEADER SCHEDULE
HEADER MARK HEADER TYPE
H1 3.5x7 PARALLAM PSL 2.0E
H3 5.25x7 PARALLAM PSL 2.0E
H4 5.25x14 PARALLAM PSL 2.0E
POST SCHEDULE
MARK SIZE TYPE
P1 (2)-2x6 DF #2
P2 (3)-2x6 DF #2
P3 5 1/4x5 1/4 PSL
POST SCHEDULE NOTES:
1. PROVIDE SIMPSON PB66 POST BASES, OR EQUIVALENT, AT P3
POSTS.
2. PROVIDE SIMPSON CC66 POST CAPS, OR EQUIVALENT, AT P3
POSTS.
3. OPTION TO SUBSTITUTE P1 W/ (3)-2x4 WHERE 2X4 WALL OPTION
IS SELECTED.
4. OPTION TO SUBSTITUTE P2 W/ (4)-2x4 WHERE 2X4 WALL OPTION
IS SELECTED.
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
S2.00
S2.00
H1 H1 H1 H1 H1 H1
P1P1 P1 P1 P1 P2 P2 P1 P1 P1 P1 P1
H4
W-2
W-2
W-2 W-2 W-2 W-2W-2 W-2
P1
2X12 BLOCKING @ 24"
O.C., (2) BAYS EA SIDE OF
OFFICE PARTITIONS, TYP
Existing Granite Bearing Walls
Existing Granite Bearing Walls
S3.00
TYP.
S3.00
TYP.
WALL SCHEDULE
WALL
MARK
STUDS TOP PLATE BOTTOM PLATE
W-1 OPTION 1: 2x6 @ 16" O.C.
OPTION 2: (2) 2x4 @ 24" O.C.
DOUBLE 2x
MATCH STUD WIDTH
SINGLE 2x
MATCH STUD WIDTH
W-3 2x6 @ 16" O/C DOUBLE 2x6 SINGLE 2x6
W-2 OPTION 1: 2x6 @ 16" O.C.
OPTION 2: (2) 2x4 @ 16" O.C.
DOUBLE 2x
MATCH STUD WIDTH
SINGLE 2x
MATCH STUD WIDTH
NOTES:
1. ALL WOOD BEARING WALLS, SHALL BE BLOCKED AND SHEATHED W/ 1/2" PLYWOOD, ONE
SIDE.
2. SHEATHING SHALL BE FASTENED WITH 8d NAILS AT 6" O.C. AT ALL PANEL EDGES, AND 8d
NAILS AT 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS.
3. SEE DETAIL FOR WALL PANEL LAYOUT.
4. AT SILL TO CONCRETE CONNECTIONS, PROVIDE TITAN HD 1/2" W/ 3 1/4" EMBED AT 32" O.C.
5. AT SILL TO WOOD FLOOR CONNECTIONS, PROVIDE SIMPSON SDS 1/4x6" SCREW AT 16" O.C.
3/S3.00
FLOOR PLAN NOTES:
1. THE EXISTING PLANS ARE BASED OFF OF EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL
DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED.
2. COORDINATE ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
3. FLOOR FRAMING SHOWN IS FOR FRAMING BELOW SUPPORTING THE CURRENT FLOOR.
4. "P-x" DENOTES POST TYPE. SEE POST SCHEDULE ON THIS SHEET FOR SIZE AND TYPE.
5. "Hx" DENOTES HEADER TYPE. SEE HEADER SCHEDULE ON THIS SHEET FOR SIZE AND TYPE.
6. "W-x" DENOTES WALL TYPE. SEE WALL SCHEDULE ON THIS SHEET FOR SIZE, SPACING, AND FASTENING
REQUIREMENTS.
7. PROVIDE SIMPSON MGU5.5 HANGER AT PSL BEAM TO BEAM CONNECTION LOCATIONS.
8. SEE DETAIL xxxxx FOR TYPICAL FASTENING OF EXISTING FLOOR JOIST TO NEW SUPPORTS.
9. DIMENSIONS TO NEW SUPPORTS ARE APPROXIMATE. FIELD SHIFTING IS ALLOWABLE TO AVOID UTILITIES.
10. SHIMMING IS ALLOWABLE WHERE REQUIRED TO AVOID UTILITES. VERIFY HEADER AND WALL HEIGHTS IN
FIELD.
11/S3.00
N
355 Research Parkway Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
Project No.:
Date:
Reviewed:
Drawn:
Designed:
Title:
Sheet No.
© 2022 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
Issued for:
TRUE NORTH
C o m p a n ie s
A rc h it e c tu re
E n g in e e ri n g
E n v ir o n m e n ta l
La n d S u rv e y in g
C U s e rs \K
P itz e r\
D o c u m e n ts
\r e v it_ lo c a l\
U R
I_ W a s h b u rn H a ll_
S tr u c t_
R k p it z e rP D
M
L .r v t
/2
/2
:2 :3
P
M
S1.02
SECOND FLOOR FRAMING
PLAN
2503449
10/21/2026
JRM
JRM
KJP
B
R
IA
R L
A N
E K
IN
G
S
TO
N , R
H O
D E
IS
LA
N D
U R
I - W
A S
H B
U R
N H
A
LL
BID
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
IO
N
1/4" = 1'-0"
STRUCTURAL SECOND FLOOR FRAMING PLAN
HEADER SCHEDULE
HEADER MARK HEADER TYPE
H1 3.5x7 PARALLAM PSL 2.0E
H3 5.25x7 PARALLAM PSL 2.0E
H4 5.25x14 PARALLAM PSL 2.0E
POST SCHEDULE
MARK SIZE TYPE
P1 (2)-2x6 DF #2
P2 (3)-2x6 DF #2
P3 5 1/4x5 1/4 PSL
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
(E
2x
4" O
.C
S2.00
S2.00
Existing Granite Bearing Walls
Existing Granite Bearing Walls
1' -0
T
Y P
2x
2x
2x
2x
2x
2x
S
IS
T E
R E
D
S
IS
T E
R E
D
S
IS
T E
R E
D
S
IS
T E
R E
D
S
IS
T E
R E
D
S
IS
T E
R E
D
S3.00
TYP.
WALL SCHEDULE
WALL
MARK
STUDS TOP PLATE BOTTOM PLATE
W-1 OPTION 1: 2x6 @ 16" O.C.
OPTION 2: (2) 2x4 @ 24" O.C.
DOUBLE 2x
MATCH STUD WIDTH
SINGLE 2x
MATCH STUD WIDTH
W-3 2x6 @ 16" O/C DOUBLE 2x6 SINGLE 2x6
W-2 OPTION 1: 2x6 @ 16" O.C.
OPTION 2: (2) 2x4 @ 16" O.C.
DOUBLE 2x
MATCH STUD WIDTH
SINGLE 2x
MATCH STUD WIDTH
NOTES:
1. ALL WOOD BEARING WALLS, SHALL BE BLOCKED AND SHEATHED W/ 1/2" PLYWOOD, ONE
SIDE.
2. SHEATHING SHALL BE FASTENED WITH 8d NAILS AT 6" O.C. AT ALL PANEL EDGES, AND 8d
NAILS AT 12" O.C. ALONG INTERMEDIATE FRAMING MEMBERS.
3. SEE DETAIL FOR WALL PANEL LAYOUT.
4. AT SILL TO CONCRETE CONNECTIONS, PROVIDE TITAN HD 1/2" W/ 3 1/4" EMBED AT 32" O.C.
5. AT SILL TO WOOD FLOOR CONNECTIONS, PROVIDE SIMPSON SDS 1/4x6" SCREW AT 16" O.C.
3/S3.00
FLOOR PLAN NOTES:
1. THE EXISTING PLANS ARE BASED OFF OF EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL
DIMENSIONS AND ELEVATIONS SHALL BE FIELD VERIFIED.
2. COORDINATE ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
3. FLOOR FRAMING SHOWN IS FOR FRAMING BELOW SUPPORTING THE CURRENT FLOOR.
4. "P-x" DENOTES POST TYPE. SEE POST SCHEDULE ON THIS SHEET FOR SIZE AND TYPE.
5. "Hx" DENOTES HEADER TYPE. SEE HEADER SCHEDULE ON THIS SHEET FOR SIZE AND TYPE.
6. "W-x" DENOTES WALL TYPE. SEE WALL SCHEDULE ON THIS SHEET FOR SIZE, SPACING, AND FASTENING
REQUIREMENTS.
7. PROVIDE SIMPSON MGU5.5 HANGER AT PSL BEAM TO BEAM CONNECTION LOCATIONS.
8. SEE DETAIL xxxxx FOR TYPICAL FASTENING OF EXISTING FLOOR JOIST TO NEW SUPPORTS.
9. DIMENSIONS TO NEW SUPPORTS ARE APPROXIMATE. FIELD SHIFTING IS ALLOWABLE TO AVOID UTILITIES.
10. SHIMMING IS ALLOWABLE WHERE REQUIRED TO AVOID UTILITES. VERIFY HEADER AND WALL HEIGHTS IN
FIELD.
11/S3.00
N
355 Research Parkway Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
Project No.:
Date:
Reviewed:
Drawn:
Designed:
Title:
Sheet No.
© 2022 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
Issued for:
TRUE NORTH
C o m p a n ie s
A rc h it e c tu re
E n g in e e ri n g
E n v ir o n m e n ta l
La n d S u rv e y in g
C U s e rs \K
P itz e r\
D o c u m e n ts
\r e v it_ lo c a l\
U R
I_ W a s h b u rn H a ll_
S tr u c t_
R k p it z e rP D
M
L .r v t
/2
/2
:2 :3
P
M
S1.03
THIRD FLOOR FRAMING
PLAN
2503449
10/21/2026
JRM
JRM
KJP
B
R
IA
R L
A N
E K
IN
G
S
TO
N , R
H O
D E
IS
LA
N D
U R
I - W
A S
H B
U R
N H
A
LL
BID
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
IO
N
1/4" = 1'-0"
STRUCTURAL THIRD FLOOR FRAMING PLAN
POST SCHEDULE
MARK SIZE TYPE
P1 (2)-2x6 DF #2
P2 (3)-2x6 DF #2
P3 5 1/4x5 1/4 PSL
HEADER SCHEDULE
HEADER MARK HEADER TYPE
H1 3.5x7 PARALLAM PSL 2.0E
H3 5.25x7 PARALLAM PSL 2.0E
H4 5.25x14 PARALLAM PSL 2.0E
FOUNDATION
-11' - 0"
FOUNDATION
-11' - 0"
ATTIC
33' - 0"
ATTIC
33' - 0"
3RD FLOOR
22' - 0"
3RD FLOOR
22' - 0"
2ND FLOOR
11' - 0"
2ND FLOOR
11' - 0"
1ST FLOOR
0' - 0"
1ST FLOOR
0' - 0"
GRADE
-6' - 0"
GRADE
-6' - 0"
BEARING WALL, SEE PLAN
HEADER, SEE PLAN
NEW FOOTING,
SEE PLAN
HEADER, SEE PLAN
POST, SEE PLAN
NEW FOOTING,
SEE PLAN
S3.00
8S3.00
NEW SISTERED JOIST, SEE PLAN
FOR SIZE AND LOCATIONS
S3.00
FOUNDATION
-11' - 0"
FOUNDATION
-11' - 0"
ATTIC
33' - 0"
ATTIC
33' - 0"
3RD FLOOR
22' - 0"
3RD FLOOR
22' - 0"
2ND FLOOR
11' - 0"
2ND FLOOR
11' - 0"
1ST FLOOR
0' - 0"
1ST FLOOR
0' - 0"
GRADE
-6' - 0"
GRADE
-6' - 0"
BEARING WALL, SEE PLAN
HEADER, SEE PLAN
BEARING WALL, SEE PLAN
HEADER, SEE PLAN
JOIST BLOCKING,
SEE PLAN
JOIST BLOCKING,
SEE PLAN
NEW FOOTING, SEE PLAN
HEADER, SEE PLAN
SECTION NOTES:
1. DRAWINGS ARE BASED OFF OF EXISTING DRAWINGS AND FIELD MEASUREMENTS. ALL DIMENSIONS AND
ELEVATIONS SHALL BE FIELD VERIFIED.
2. COORDINATE ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
3. SEE GENERAL NOTES ON SHEET S0.01
355 Research Parkway Meriden, CT 06450
(203) 630-1406
(203) 630-2615 Fax
Project No.:
Date:
Reviewed:
Drawn:
Designed:
Title:
Sheet No.
© 2022 BL COMPANIES, INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF BL COMPANIES.
Issued for:
C o m p a n ie s
A rc h it e c tu re
E n g in e e ri n g
E n v ir o n m e n ta l
La n d S u rv e y in g
C U s e rs \K
P itz e r\
D o c u m e n ts
\r e v it_ lo c a l\
U R
I_ W a s h b u rn H a ll_
S tr u c t_
R k p it z e rP D
M
L .r v t
/2
/2
:2 :3
P
M
S2.00
STRUCTURAL SECTIONS
2503449
10/21/2026
JRM
KJP
KJP
B
R
IA
R L
A N
E K
IN
G
S
TO
N , R
H O
D E
IS
LA
N D
U R
I - W
A S
H B
U R
N H
A
LL
BID
1/4" = 1'-0"
SECTION AT OFFICES
1/4" = 1'-0"
SECTION AT OFFICES
R E
V
IS
IO
N
S
N O
D A
T E
D E
S C
R
IP
T
NOTES:
1. CONNECT BUILT-UP POSTS WITH NAILS OR BOLTS TO ALLOW FINISHED
MEMBER TO ACT COMPOSITELY. COMPLY WITH THE REQUIREMENTS OF
THE LATEST EDITION OF THE NDS, BUT IN NO CASE LESS THAN THE
FOLLOWING.
· (2) PLY 2x4: (1) ROW OF STAGGERED 10d COMMON NAILS AT 12" O.C, SPACED AT 11/2" HORIZ. AND 6" VERT. CENTERED ON MEMBER, WITH
ADJACENT NAILS DRIVEN FROM OPPOSITE SIDES OF THE BUILT-UP
MEMBER.
· (2) PLY 2x6: (1) ROW OF STAGGERED 10d COMMON NAILS AT 12" O.C, SPACED AT 21/2" HORIZ. AND 6" VERT. CENTERED ON MEMBER, WITH
ADJACENT NAILS DRIVEN FROM OPPOSITE SIDES OF THE BUILT-UP
MEMBER.
· (3) PLY 2x4: (1) ROW OF STAGGERED 30d COMMON NAILS AT 16" O.C, SPACED AT 11/2" HORIZ. AND 8" VERT. CENTERED ON MEMBER, WITH
ADJACENT NAILS DRIVEN FROM OPPOSITE SIDES OF THE BUILT-UP
MEMBER.
· (3) PLY 2x6: (2) ROWS OF 30d COMMON NAILS AT 8" O.C EA. SIDE, SPACED AT 11/2" HORIZ. FROM EDGE.
· (4) PLY 2x6: (2) ROWS OF SIMPSON SDS25600 SCREWS AT 8" O.C EA.
SIDE, SPACED AT 11/2" HORIZ. FROM EDGE.
2. "+" DENOTES NAIL LOCATIONS DRIVEN FROM BACK FACE OF ADDITIONAL
NAILS WHERE (2) ROWS OF NAILS ARE REQUIRED.
3 PLY 2x4:(1) ROW 30d
COMMON NAILS.
3 PLY 2x6:(2) ROW 30d
COMMON NAILS.
4 PLY 2x6:(2) ROW SDS25600
SCREWS.
5 PLY 2x6:(2) ROW SDS25600
SCREWS.
DRIVE FROM OPPOSITE
SIDE AT STAGGERED
ROWS
0'
1/
2" 0'
6"
0'
6"
0' - 1"
2 1/2" AT 2x6 1 1/2" AT 2x4
0' - 1"
2 PLY: ONE ROW OF
STAGGERED 10d
COMMON NAILS.
0'
8" 0'
8"
0'
1/
2"
0' - 1 1/2"
0' - 1 1/2"
LVL BEAM OR
HEADER
JACK STUDS
STRAP PER CODE IF TOP PLATE
IS NOT CONTINUOUS OVER
HEADER
LVL BEAM
WOOD POST
BELOW
SIMPSON 'CC/ECC'
COLUMN CAP SERIES
WOOD BEAM
NOTE:
2 ROWS OF 16d NAILS @12" OC FOR 9 1/2" DEPTH 3 ROWS OF 16d NAILS @12" OC FOR 11 7/8" DEPTH
3 ROWS OF 1/2" Ø BOLTS @24" OC FOR 16" & 18" DEPTH
3 ROWS OF 16d NAILS @12" OC FOR UP TO 16" DEPTH (TOP LOAD)
(TYPICAL UNLESS OTHERWISE NOTED)
3 ROWS OF 1/2" Ø BOLTS @24" OC, STAGGERED EVERY 8" FOR 20"
DEPTH
WALL BOUNDARY
APA RATED PANEL
NAIL SPACING AT WALL
BOUNDARY AND
SUPPORTED EDGES
NAILING TO INTERMEDIATE
FRAMING MEMBERS
WOOD STUDS
PROVIDE 2x BLOCKING
AT ALL AT PANEL
EDGES, IF PANEL EDGES
DO NOT SPAN TOP TO
BOTTOM
Existing Wall, TO REMAIN
NEW POST, SEE PLAN
Existing Foundation (V.I.F.), TO REMAIN
#5 DOWEL x 12" LONG, DRILL AND
EPOXY TO EXIST. FTG. W/ 6" EMBED
NEW FOOTING, SEE PLAN.
MATCH DEPTH OF EXISTING
FOOTING
Existing Slab, SAW CUT
FOR NEW FOUNDATION
#5 @ 12" O.C., EACH WAY
SAWCUT EXIST. SLAB AT NEW FTG.
DRILL AND EPOXY #5 @ 12"…