SC-27-723 Gas Cabinet Installation - Spedding Hall DWGs.pdf

PDF 7 MB Posted

Attached to
RFP SC-27-723 Hazardous & Flammable Gas Cabinets and Install
Solicitation number
RFP-SC-27-723
Issued by

About this file

This file is a set of architectural and engineering construction drawings for a hazardous and flammable gas cabinet installation project. Project SC-27-723 is located at Ames National Laboratory in Spedding Hall at 2416 Pammel Drive, Ames, Iowa, with an issue date of November 16, 2026. The project involves installation of multiple gas safety cabinets throughout the facility's basement, ground, first, second, and third floors, with cabinets ranging from single to triple capacity units designed to store both hazardous and flammable materials. The gas cabinet schedule identifies 29 cabinet locations with specific dimensions (primarily 18"W x 19"D x 75"H, 24"W x 19"D x 75"H, or 36"W x 19"D x 75"H), indicating which cabinets are new installations and which are existing to remain. Hazardous-level cabinets include sprinkler systems, while flammable-level cabinets do not.

Work scope includes selective demolition of existing walls, doors, ceilings, and mechanical systems; installation of new acoustical ceiling tile grids with salvaged tile reuse; coordination with mechanical, electrical, and plumbing trades; and installation of new fire suppression systems where required. The drawings specify compliance with 10 CFR 851.C safety regulations, establishment of utility location protocols prior to excavation, and coordination of lockout/tagout procedures with advance notice to building management. Contractors must register through TASF, obtain security badges, complete site safety orientation, verify hazardous materials including asbestos and beryllium contamination, and schedule penetration permits 10–15 days prior to work. All cabinet installations must coordinate with manufacturer specifications, and all new ductwork and conduit must be prepped and painted. The project documents multiple fire suppression plans, floor plans across all building levels, mechanical and electrical plans, and door and hardware schedules, with professional engineering certifications from Iowa-licensed engineers.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U P

R R

U P R R

U P R R

U P

R R

Walls

Earth

Granular Fill

Sand, Mortar

Concrete

Concrete Block

Brick

Stone

Aluminum

Steel

Bronze

Wood

Structural

Blocking

Particle Board

Plywood

Glass

Batt Insulation

Rigid

Insulation Tile

Plastic Laminate

Gypsum Board

Plaster

Acoustic Tile

Terrazzo

Metal Stud

Wood Stud

2 8

1 6

1. Prior to excavation and site planting on the job site, the contractor shall contact utility companies to locate underground utilities effecting the excavations and planting on the job site. Excavation shall not proceed until all utilities are located and indicated. The contractor shall maintain the identifying devices throughout the duration of the project.

2. The contractor shall comply with 10 CFR 851.C rules and regulations throughout the construction activities on the project. None of the work contemplated in the construction documents shall be construed as being in conflict with applicable 10 CFR 851.C rules and regulations.

3. Contractors shall verify all dimensions and conditions effecting the work shown on the contract documents. Any conflicts found shall be reported to the Architect before proceeding with the work.

4. During the process of work, all penetrations through walls, ceilings, and floors will require a permit to be filed to ensure that radiation scanning can be completed prior to work commencing.

5. All LOTO and electrical shutdowns will need to be communicated to the owner with ample amount of time for building wide notification that will need to be scheduled.

See table for required timelines.

6. Every member of the construction crew will be required to be registered through

TASF and have possession of a badge while on site.

7. All construction crew members must complete an Ames Lab site and safety orientation before beginning work.

8. Verify all legacy hazardous material in scope of work with Ames Lab ESH, including asbestos, radiation contamination, and beryllium contamination before work begins.

Index to Drawings

ARCHITECTURAL

Material Symbols x

A4.0

A7.0

A4.4

A4.2

XXX

X

Plan Detail

Detail

Wall Section Revision No.X

Room Name/No.

Wall Type

Door Number

Column Grid

Floor Line

Test Bore

Building Section

XX

XX.X

Drawing Number

Sheet Call Out

Site Access Map

Abbreviation Key

Certification

Graphic Symbols

MECHANICAL/ELECTRICAL/PLUMBING

General Notes

1i

Casework Tag

D00 Demolition Note

0 Equipment Tag

0 Material Key Tag

Toilet Accessory

Key Tag

N North Arrow

1i Plumbing Fixture Tag

RAILING

'A'

Railing Tag

1t Window Tag

Name 101

Room Tag w/ Occ.

Load

PROJECT LOCATION PAMMEL DR

OSBORN DR

B

IS

S E

LL

R D

S T A N G

E R

D

N UNIVERSITY BLVD

TASF

GENERAL SCHEDULING REQUIREMENTS

• NORMAL HOURS OF OPERATION ARE 7:30 AM TO 4:30 PM,

MONDAY THROUGH FRIDAY.

• NOTIFY OWNER NOT LESS THAN THE FOLLOWING IN ADVANCE

OF ACTIVITIES THAT WILL AFFECT OWNER'S OPERATIONS:

1. NO LESS THAN TWO (2) MONTHS AHEAD OF

SCHEDULED ACTIVITY, PROVIDE ACCURACRY WITHIN

ONE (1) WEEK.

2. NO LESS THAT TWO (2) WEEKS AHEAD OF SCHEDULED

ACTIVITY, PROVIDE ACCURACT WITHIN ONE (1) DAY.

• FIRE SUPPRESSION SHUTDOWN

1. ALLOWABLE SHUTDOWN DURING NORMAL WORKING

HOURS

2. MAXIMUM CONTINUOUS DURATION = 8 HOURS

• MECHANICAL EXHAUST SHUTDOWN

1. ALLOWABLE SHUTDOWN DURING NORMAL WORKING

HOURS

2. MAXIMUM CONTINUOUS DURATION = 4 HOURS

• PENETRATION PERMIT

• 10-15 DAYS FOR APPROVAL

• NON-CITIZEN WORKER REVIEW PROCESS

• 45 DAYS FOR REVIEW/APPROVAL

Vicinity Map Legend

PROJECT SITE LOCATION

CONTRACTOR PARKING AREA

CONTRACTOR TO PURCHASE PARKING PASSES AND

UTILIZE HIGHLIGHTED LOT

M O

R R

IL

L R D

N

LOT 29

LOT 29

W O

I R D

KOOSER DR

W

IN

LO

C

K R

D

N

Vicinity Map

N

Enlarged Campus Map

HWY 30

S U

N

IV

E R S

IT

Y A

V E

LINCOLN WAY

I-35

D U F F A

V E

S T A N G

E R

D

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERONSAL

SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.

CLINTON ROGER RABE, PE

REG. NO. DATE:

MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026

PAGES OR SHEETS COVERED BY THIS SEAL:

P19481

ALL MECHANICAL AND PLUMBING SHEETS

L

IC

E N S E

D

PR

OFE

SSIONAL

E

N G I N E E R

O WI A

CLINTON

ROGER

RABE

P19481

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERONSAL

SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.

TIMOTHY A. HILTON, P.E.

REG. NO. DATE:

MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026

PAGES OR SHEETS COVERED BY THIS SEAL:

P19392

ALL MECHANICAL AND PLUMBING SHEETS

L

IC

E N S E

D

PR

OFE

SSIONAL

E

N G I N E E R

O WI A

TIMOTHY

A

HILTON

P19392 Consultant

Revision Record

Print Record

Project Number

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

SC-27-723 - AMES NATIONAL LABORATORY HAZARDOUS & FLAMMABLE GAS CABINET INSTALLATION

SPEDDING HALL

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

11/16/2026ISSUE SET

25011

A0.0

TITLE SHEET

11/16/2026

2416 PAMMEL DR, AMES, IA 50011

Jeffrey S. Harris Date License number: 3594 My license renewal date is: June 30, 2028 Pages or sheets covered by this seal:

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed architect under the laws of the state of Iowa.

A0.0

A2.0

A2.1

IOWA

A R

E

J E

F

F

HSY .

R

S R

I

CH

N

IC

E

DES

A R

E

TI

C

L

T

AL,ALUM ALUMINUM

AT ACOUSTICAL CEILING TILE

BLDG BUILDING

BLK BLOCK (CONCRETE)

BRK BRICK

CG CORNER GUARD

CJ CONTROL JOINT

CL CENTER LINE

CMU CONCRETE MASONRY UNIT

CONC CONCRETE

CONC/S SEALED CONCRETE

CONV CONVENIENCE

CPT CARPET

CT CERAMIC TILE

DN DOWN

DTL DETAIL

EJ,EXP JT EXPANSION JOINT

EXT EXTERIOR

FC FOAM CORE

FGT FIBERGLASS CEILING TILE

FGW FIBERGLASS WALL TILE

FT FOOT, FEET

GALV GALVANIZED

GB,GYP BD, GWB GYPSUM WALLBOARD

GR GRANITE

GYP GYPSUM

HDW HARDWARE

HM HOLLOW METAL

IG INSULATED GLASS

INSUL INSULATION, INSULATED

ISG INSULATING SAFETY GLASS

LH LEFT HAND

MIN MINIMUM

MTL, MET METAL

NIC NOT IN CONTRACT

NOM NOMINAL

A2.2

A2.3

A2.4

A2.5

A2.6

A2.7

A2.8

A2.9

A2.10

NTS NOT TO SCALE

O.C. ON CENTER

P LAM PLASTIC LAMINATE

PART BD PARTICLE BOARD

PC PRECAST CONCRETE

PLYWD PLYWOOD

R RISER,RADIUS

RH RIGHT HAND

RSR RUBBER STAIR RISER

RST RUBBER STAIR TREAD

SC SOLID CORE

SCH SCHEDULE

SFP SPRAYED FIRE PROTECTION

SG SAFETY GLASS

SG SPANDREL GLASS

SH STEEL

SIM SIMILAR

SK SINK

SND SANITARY NAPKIN DISPOSAL

SOG SLAB ON GRADE

SPEC SPECIFICATIONS, SPECIFIED

SS, ST STL STAINLESS STEEL

SVF SHEET VINYL FLOORING

THRE'D THRESHOLD

TR TREAD

TYP TYPICAL

UR URINAL

VB VINYL BASE

VF VINYL WALL FABRIC

VP VENEER PLASTIC

VT VINYL TILE

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WD WOOD

WG WIRE GLASS

A0.0 TITLE SHEET

A2.0 BASEMENT FLOOR PLAN

A2.1 GROUND LEVEL FLOOR PLAN

A2.2 FIRST FLOOR PLAN

A2.3 SECOND FLOOR PLAN

A2.4 THIRD FLOOR PLAN

A2.5 ROOFTOP PENTHOUSE PLAN

A2.6 ENLARGED ROOM FLOOR PLANS - BASEMENT - BASE BID

A2.7 ENLARGED ROOM FLOOR PLANS - GROUND LEVEL - BASE BID

A2.8 ENLARGED ROOM FLOOR PLANS - FIRST FLOOR - BASE BID

A2.9 ENLARGED ROOM FLOOR PLANS - SECOND & THIRD FLOOR - BASE

BID

A2.10 FIRST FLOOR CONTROL ZONES - ALTERNATE #1 - DEMO

A2.11 FIRST FLOOR CONTROL ZONES - ALTERNATE #1 - NEW WORK

E0.0 ELECTRICAL SYMBOL LEGEND

E0.1 ELECTRICAL PROJECT NOTES AND ABBREVIATIONS

E0.2 ELECTRICAL PROJECT NOTES

E0.3 ELECTRICAL PROJECT SCHEDULES

E2.0 BASEMENT ELECTRICAL PLAN

E2.1 GROUND FLOOR ELECTRICAL PLAN

E2.3 SECOND FLOOR POWER PLAN

E2.4 THIRD LEVEL POWER PLAN

E2.6 ENLARGED ELECTRICAL PLANS

E2.7 ENLARGED ELECTRICAL PLANS - FIRST FLOOR CONTROL ZONE -

ALTERNATE #1

FP0.0 FIRE SUPPRESSION SYMBOLS AND ABBREVIATIONS

FP1.0 BASEMENT FIRE PROTECTION PLAN

FP1.2 FIRST FLOOR FIRE SUPPRESSION PLAN

FP1.3 SECOND FLOOR FIRE SUPPRESSION PLAN

FP1.4 THIRD FLOOR FIRE SUPPRESSION PLAN

FP7.0 FIRE PROTECTION DETAILS & SCHEDULES

M0.0 HVAC SYMBOLS AND ABBREVIATIONS

M2.0 BASEMENT MECHANICAL PLAN

M2.1 GROUND LEVEL MECHANICAL PLAN

M2.2 FIRST FLOOR MECHANICAL PLAN

M2.3 SECOND FLOOR MECHANICAL PLAN

M2.4 THIRD FLOOR MECHANICAL PLAN

M2.5 ROOFTOP PENTHOUSE MECHANICAL PLAN

M2.6 ENLARGED MECHANICAL PLANS - BASEMENT - BASE BID

M2.7 ENLARGED MECHANICAL PLANS - GROUND FLOOR - BASE BID

M2.8 ENLARGED MECHANICAL PLANS - FIRST FLOOR - BASE BID

M2.9 ENLARGED MECHANICAL PLANS - SECOND AND THIRD FLOORS -

BASE BID

M2.10 ENLARGED MECHANICAL PLANS - FIRST FLOOR CONTROL ZONES -

DEMOLITION - ALTERNATE #1

M2.11 ENLARGED MECHANICAL PLANS - FIRST FLOOR CONTROL ZONES -

NEW WORK - ALTERNATE #1

M6.0 RISER DIAGRAM

M7.0 MECHANICAL DETAILS

M8.0 MECHANICAL SCHEDULES

A2.11

UP

TO METALS DEVELOPMENT

TO WILHELM HALL

STEAM

ROOM

HEATING TUNNEL

A2.6

A2.6

A2.6

A2.6

B1

B2 B3

B4

B5B5C

B5B B7A

B7

B8

B9

B10

B11 B15

B15A

B16 B17 B18 B19

ROOM B20

B22B24B27ROOM B28B31

B31A

BASEMENT B33BASEMENT B34B35ROOM B36ROOM B37

B39AB39B40B43

B44

B45 B46

B47

B51

B52

B53

B54 B55

B56

B56A

B56B

A2.0

Sim

19 20 21

C

D

D02

D02

D01

D01

19 20 21

C

D

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.0

BASEMENT FLOOR PLAN

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/8" = 1'-0"1

BASEMENT

1/4" = 1'-0"2

BSMNT ENLARGED RCP DEMO

1/4" = 1'-0"3

BSMNT ENLARGED RCP NEW WORK

A2.7

A2.7

A2.7

A2.7

A2.7

6 7

10 15 16

ROOM 17 ROOM 18 ROOM 19

20ROOM 22ROOM 23ROOM 242526ROOM 272829

313233343536373839404142

43 44 45 46 47

ROOM 53

56A

56B

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.1

GROUND LEVEL FLOOR PLAN

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/8" = 1'-0"1

GROUND LEVEL

UPUP

DOCK

A2.8

A2.8

A2.8

Room 114 Room 113

115 116

114A 116A

117 118 119

120122124125

127A127B

129130

130B

Room 132Room 133Room 134Room 135136Room 138Room 139Room 140Room 141142

145 146 147 148

144A

153153A

A2.11

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.2

FIRST FLOOR PLAN

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

1ST FLR

UP

UP

A2.9

A2.9

A2.9

Room 214 217 219

220221222224225226227228229 230231232

234235236237238239

232A

Room 240Room 241Room 242

244 246 Room 247 Room 248

201C

201B

258 258A

201A

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.3

SECOND FLOOR PLAN

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

2ND FLR

A2.9

314 315 316 317 318 319

320321322323324325326Room 328Room 329330331332

333A

334335336337338339

340B 340A

343 344 345 346 347 348 349-352

355 356

301A301B

301C

301D

301E

301F

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.4

THIRD FLOOR PLAN

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

3RD FLOOR

402403

401A

EQUIPMENT ROOM 401

FAN ROOM

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.5

ROOFTOP PENTHOUSE PLAN

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

ROOF

FUME HOOD

C A B

IN

E T S

O H C

A B

EP

ET

T O

O L

B O

X D

E S

K O

H C

A B

O H C

A

G C

C C

A B

IN

E T

M/CM/C

TABLETABLE

11'-6"

BEAM

+12'-8"

STICK-ON TILE

M/C

ROOM B20

V E R

IF

Y

TABLE

EP

OH CAB

C A B

IN

E T

O H C

A B

EXISTING ELECTRICAL

OUTLETS TO REMAIN

11'-6"

BEAM

ROOM B28FUME

HOOD

C A B

IN

E T S

O H C

A B

O H C

A B

C A B

IN

E T

CAB

TABLE

TABLE

FURNACE

DESK

SLOPE UP TO

DOOR

13'-1"

DECK

11'-7"

BEAM

SHELVING

EP

BASEMENT B34 BASEMENT B33

FURNACE

FURNACE

DO NOT

BLOCK

AREA

SHIFT EP CLEAR

FLOOR SPACE TO

ALLOW FOR CABINET

INSTALLATION

FUME

HOOD

C A B

IN

E T S

O H C

A B

C O

U N T E R

O H C

A B

FURNACE

DESK

DESK

MCMC

11'-6"

BEAM

RELOCATED

EXISTING

STORAGE

CONTAINER

ROOM B36ROOM B37

+13'-1"

DECK

FURNACE

FURNACE

FURNACE

FURNACE

V E R

IF

Y

D03

D01

DEMO PORTION

OF COUNTER; TEST &

REMOVE ANY

PRESENT ASBESTOS

GENERAL NOTES

1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM

CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER

AND ARE NOT INTENDED TO SHOW EVERY EXISTING

CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE

CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.

EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE

ARCHITECTS OFFICE FOR REVIEW.

2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,

AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE

RIGHTS WITH OWNER.

3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS

ARE INDICATED ON CEILING PLANS.

4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND

RECESSED CONDUIT AND WIRING, WALL SWITCHES AND

OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT

BOXES, & FLOOR BOXES THAT WOULD EXIST IN A

DORMANT STATE UPON COMPLETION OF THE PROJECT.

REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT

PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.

(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE

RIGHTS WITH OWNER.

5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING

SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,

AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN

A DORMANT STATE AT THE COMPLETION OF THE

PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE

RIGHTS WITH OWNER.

6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST

AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY

THE NEW CONSTRUCTION, AND ANY EXTRANEOUS

MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT

STATE AT THE COMPLETION OF THE PROJECT.

7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.

8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT

ALL CEILING AND WALL MOUNTED ACCESSORIES

INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,

AND MISCELLANEOUS ITEMS.

NEW WORK NOTES

1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED

AND PAINTED FOR FINAL FINISH.

2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH

MANUFACTURER'S STANDARD INSTALLATION

INSTRUCTIONS.

3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE

EXISTING TILES FOR REUSE. SEE SPEC FOR

REPLACEMENT IF REQD.

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.6

ENLARGED ROOM FLOOR PLANS

- BASEMENT - BASE BID

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/4" = 1'-0"1

ROOM B20 - BASE BID

N1/4" = 1'-0"2

ROOM B28 - BASE BID

N1/4" = 1'-0"3

ROOM B33-34 - BASE BID

N1/4" = 1'-0"4

ROOM B36-37 - BASE BID

GAS CABINET SCHEDULE

MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS

019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

023A DOUBLE HAZARDOUS EXISTING YES NO ETR

023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H

023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

114 DOUBLE FLAMMABLE EXISTING NO NO ETR

133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

214 DOUBLE HAZARDOUS EXISTING YES NO ETR

242A DOUBLE HAZARDOUS EXISTING YES NO ETR

242B DOUBLE FLAMMABLE EXISTING NO NO ETR

247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

329A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

329B DOUBLE FLAMMABLE EXISTING NO NO ETR

N1/4" = 1'-0"13

ROOM B20 DEMO - BASE BID

1" = 20'-0"14

B 20 EXISTING IMAGES

1" = 20'-0"15

B 28 EXISTING IMAGES

1" = 20'-0"16

B 33-34 EXISTING IMAGES

1" = 20'-0"17

B 36-37 EXISTING IMAGES

DEMOLITION ITEMS

D01 EXIST'G TO REMAIN

D02 DEMO EXISTING ACT CEILING SYSTEM AS

INDICATED; SALVAGE TILES FOR REINSTALLATION

WHERE APPLICABLE

D03 DEMO COUNTER & ASSOC. CASEWORK

D04 DEMO WALL

D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW

D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED

WALL INFILL

D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN

ROOM 160

D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE

RATED SEAL

PROJECT MATERIAL LIST

1 EXISTING TO REMAIN

2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;

REINSTALL SALVAGED CEILING TILES

FUME

HOOD

FUME

HOOD

REF FC

REF

TABLE

TABLE

M/C

O H C

A B

C A B

IN

E T S

TABLE TABLE

TABLE

SHELF

C A B

IN

E T S

O H C

A B

7'-10"

BEAM

9'-5"

DECK

SHIFT

EXISTING EQUIP.

EAST

FUME

HOOD

REFRIGERATOR RELOCATED

BY OWNER

C O

U N T E R

FUME

HOOD

O H C

A

B FUME

HOOD

O H C

A B

C O

U N T E R

TABLE

8'-0"

BEAM

9'-6"

DECK

022A

022B

DEMO DOOR &

FRAME; TOOTH-IN

CMU & FINISH

MODIFY FILTER

SYSTEM LOCATION

AS REQD./SHIFT

CABINET TO

MAINTAIN

CLEARANCE. VIF

FINAL LOC. W/

OWNER

TABLE

TABLE

C A B

IN

E T S

C A B

IN

E T S

FUME

HOOD

FUME

HOOD

O H C

A B

O H C

A B

8'-0" BEAM

9'-6"

DECK

RELOCATE EXISTING

OUTLET

023C

023B 023A

FUME

HOOD

C A B

IN

E T S

T A B

LE

T A B

LE

O H C

A B

9'-6"

DECK

GLOVE

BOX

GLOVE

BOX

GLOVE

BOX

SHELFCABTABLE

NOTE: NO ACTIVE EXHAUST IN ROOM

8'-0"

BEAM

+9'-6"

DECK

INSTALL SS FLANGE AROUND

NEW OPENING TO CONCEAL

DEMO PORTION OF WALL

FLASHING TO CONCEAL

WALL PENETRATION

GENERAL NOTES

1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM

CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER

AND ARE NOT INTENDED TO SHOW EVERY EXISTING

CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE

CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.

EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE

ARCHITECTS OFFICE FOR REVIEW.

2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,

AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE

RIGHTS WITH OWNER.

3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS

ARE INDICATED ON CEILING PLANS.

4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND

RECESSED CONDUIT AND WIRING, WALL SWITCHES AND

OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT

BOXES, & FLOOR BOXES THAT WOULD EXIST IN A

DORMANT STATE UPON COMPLETION OF THE PROJECT.

REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT

PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.

(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE

RIGHTS WITH OWNER.

5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING

SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,

AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN

A DORMANT STATE AT THE COMPLETION OF THE

PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE

RIGHTS WITH OWNER.

6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST

AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY

THE NEW CONSTRUCTION, AND ANY EXTRANEOUS

MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT

STATE AT THE COMPLETION OF THE PROJECT.

7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.

8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT

ALL CEILING AND WALL MOUNTED ACCESSORIES

INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,

AND MISCELLANEOUS ITEMS.

NEW WORK NOTES

1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED

AND PAINTED FOR FINAL FINISH.

2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH

MANUFACTURER'S STANDARD INSTALLATION

INSTRUCTIONS.

3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE

EXISTING TILES FOR REUSE. SEE SPEC FOR

REPLACEMENT IF REQD.

DEMO WALL INFILL;

REFERENCE IMAGE

BELOW 1

' - 6

D04

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.7

ENLARGED ROOM FLOOR PLANS

- GROUND LEVEL - BASE BID

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/4" = 1'-0"1

ROOM 19 - BASE BID

1" = 20'-0"2

ROOM 19 EXISTING IMAGES

N1/4" = 1'-0"3

ROOM 22 - BASE BID

1" = 20'-0"4

ROOM 22 EXISTING IMAGES

N1/4" = 1'-0"5

ROOM 23-24 - BASE BID

1" = 20'-0"6

ROOM 23-24 EXISTING IMAGES

N1/4" = 1'-0"7

ROOM 27 - BASE BID

1" = 20'-0"8

ROOM 27 EXISTING IMAGES

N1/4" = 1'-0"9

ROOM 53 - BASE BID

1" = 20'-0"10

ROOM 53 EXISTING IMAGES

DEMOLITION ITEMS

D01 EXIST'G TO REMAIN

D02 DEMO EXISTING ACT CEILING SYSTEM AS

INDICATED; SALVAGE TILES FOR REINSTALLATION

WHERE APPLICABLE

D03 DEMO COUNTER & ASSOC. CASEWORK

D04 DEMO WALL

D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW

D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED

WALL INFILL

D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN

ROOM 160

D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE

RATED SEAL

PROJECT MATERIAL LIST

1 EXISTING TO REMAIN

2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;

REINSTALL SALVAGED CEILING TILES

N1/4" = 1'-0"11

ROOM 53 DEMO - BASE BID

GAS CABINET SCHEDULE

MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS

019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

023A DOUBLE HAZARDOUS EXISTING YES NO ETR

023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H

023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

114 DOUBLE FLAMMABLE EXISTING NO NO ETR

133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

214 DOUBLE HAZARDOUS EXISTING YES NO ETR

242A DOUBLE HAZARDOUS EXISTING YES NO ETR

242B DOUBLE FLAMMABLE EXISTING NO NO ETR

247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

329A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

329B DOUBLE FLAMMABLE EXISTING NO NO ETR

FUME

HOOD

CAB.

GLOVE BOX

COUNTER W/ OH. CAB.

C O

U N T E R W

O

H

C A B

G

LO

V E B

O X

C O

U N T E R W

O

H

C A B

CAB.

Room 114 Room 113

ACT2

+9' - 5"

D02

D01

CEILING HEIGHT

TO MATCH

EXISTING

O H

C A B

IN

E T

SFUME HOOD

CABINETSCABINETSCABINETS

M/C

M/C

M/C

M/C

D E S

K D

E S

K

ACT - 9'-5"

SHIFT

EXISTING M/C

RELOCATE

DESK

D E S

K

FUME HOOD

Room 135 Room 134 Room 133

Room 132

133A

133B

135B

135A

ALT #1

ACT

+9' - 5"

D02

D01

D02

ALT #1

ACT

+9' - 5"

ACT

+9' - 5"

ACT

+9' - 5"

ALT #1

FUME HOOD

FUME HOOD

CABINETSCABINETSCABINETS

O H

C A B

IN

E T S

T A B

LE

REF

DESK

T A B

LE

M/C

M/C

ACT + 9'-5"

Room 138Room 139Room 140Room 141

141A

141B

141C

ACT

+9' - 5"

D02

D01

D02

D02

ACT

+9' - 5"

ACT

+9' - 5"

ACT

+9' - 5"

GENERAL NOTES

1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM

CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER

AND ARE NOT INTENDED TO SHOW EVERY EXISTING

CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE

CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.

EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE

ARCHITECTS OFFICE FOR REVIEW.

2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,

AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE

RIGHTS WITH OWNER.

3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS

ARE INDICATED ON CEILING PLANS.

4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND

RECESSED CONDUIT AND WIRING, WALL SWITCHES AND

OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT

BOXES, & FLOOR BOXES THAT WOULD EXIST IN A

DORMANT STATE UPON COMPLETION OF THE PROJECT.

REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT

PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.

(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE

RIGHTS WITH OWNER.

5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING

SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,

AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN

A DORMANT STATE AT THE COMPLETION OF THE

PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE

RIGHTS WITH OWNER.

6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST

AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY

THE NEW CONSTRUCTION, AND ANY EXTRANEOUS

MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT

STATE AT THE COMPLETION OF THE PROJECT.

7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.

8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT

ALL CEILING AND WALL MOUNTED ACCESSORIES

INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,

AND MISCELLANEOUS ITEMS.

NEW WORK NOTES

1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED

AND PAINTED FOR FINAL FINISH.

2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH

MANUFACTURER'S STANDARD INSTALLATION

INSTRUCTIONS.

3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE

EXISTING TILES FOR REUSE. SEE SPEC FOR

REPLACEMENT IF REQD.

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.8

ENLARGED ROOM FLOOR PLANS

- FIRST FLOOR - BASE BID

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/4" = 1'-0"1

ROOM 113-114 - BASE BID

N1/4" = 1'-0"2

113-114 RCP DEMO - BASE BID

N1/4" = 1'-0"3

113-114 RCP NEW - BASE BID

1" = 20'-0"4

ROOM 113-114 EXISTING IMAGES

N3/16" = 1'-0"5

ROOM 132-135 - BASE BID

N1/4" = 1'-0"6

132-135 RCP DEMO - BASE BID

N1/4" = 1'-0"7

132-135 RCP NEW - BASE BID

1" = 20'-0"8

ROOM 132-135 EXISTING IMAGES

N3/16" = 1'-0"9

ROOM 138-141 - BASE BID

N1/4" = 1'-0"10

138-141 RCP DEMO - BASE BID

N1/4" = 1'-0"11

138-141 RCP NEW - BASE BID

1" = 20'-0"12

ROOM 138-141 EXISTING IMAGES

DEMOLITION ITEMS

D01 EXIST'G TO REMAIN

D02 DEMO EXISTING ACT CEILING SYSTEM AS

INDICATED; SALVAGE TILES FOR REINSTALLATION

WHERE APPLICABLE

D03 DEMO COUNTER & ASSOC. CASEWORK

D04 DEMO WALL

D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW

D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED

WALL INFILL

D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN

ROOM 160

D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE

RATED SEAL

PROJECT MATERIAL LIST

1 EXISTING TO REMAIN

2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;

REINSTALL SALVAGED CEILING TILES

GAS CABINET SCHEDULE

MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS

019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

023A DOUBLE HAZARDOUS EXISTING YES NO ETR

023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H

023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

114 DOUBLE FLAMMABLE EXISTING NO NO ETR

133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

214 DOUBLE HAZARDOUS EXISTING YES NO ETR

242A DOUBLE HAZARDOUS EXISTING YES NO ETR

242B DOUBLE FLAMMABLE EXISTING NO NO ETR

247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

M/C

GLOVE BOX

GLOVE BOX

C A B

IN

E T S

O V E R H

E A D

C A B

IN

E T S

T A B

LE

W C A B

IN

E T S

12'-0"

BEAM

13'-7"

GYP

Room 214

T A B

LE

T A B

LE

TABLE

SHELF

GLOVE BOX M/C

M/CM/C M/C

M/C

12'-8"

ACT

12'-0"

BEAM

FH

FH

FH

Room 242 Room 241 Room 240

242B

242A

C A B

IN

E T S

T A B

LE

T A B

LE

TABLE W/ GB

C O

O

LE

R

F R E E Z E R

TABLE

EXHAUST

M/C

DIVIDER

12'-0"

BEAM

12'-5"

STICK ON

ACT

Room 247 Room 248

M/C

G

LO

V E B

O X

F C

C A B

IN

E T S

O

S

E

LF

FH

11'-3"

DECK

9'-4"

ACT

E

FIRE

FH

HE TANK AND HE

PLUMBING MOVED

TO UNISTRUT BY

WINDOW

Room 328Room 329

329A

329B

D02

ACT

+9' - 5"

D01

ACT

+9' - 5"

ACT

+9' - 5"

GENERAL NOTES

1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM

CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER

AND ARE NOT INTENDED TO SHOW EVERY EXISTING

CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE

CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.

EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE

ARCHITECTS OFFICE FOR REVIEW.

2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,

AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE

RIGHTS WITH OWNER.

3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS

ARE INDICATED ON CEILING PLANS.

4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND

RECESSED CONDUIT AND WIRING, WALL SWITCHES AND

OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT

BOXES, & FLOOR BOXES THAT WOULD EXIST IN A

DORMANT STATE UPON COMPLETION OF THE PROJECT.

REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT

PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.

(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE

RIGHTS WITH OWNER.

5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING

SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,

AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN

A DORMANT STATE AT THE COMPLETION OF THE

PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE

RIGHTS WITH OWNER.

6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST

AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY

THE NEW CONSTRUCTION, AND ANY EXTRANEOUS

MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT

STATE AT THE COMPLETION OF THE PROJECT.

7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.

8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT

ALL CEILING AND WALL MOUNTED ACCESSORIES

INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,

AND MISCELLANEOUS ITEMS.

NEW WORK NOTES

1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED

AND PAINTED FOR FINAL FINISH.

2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH

MANUFACTURER'S STANDARD INSTALLATION

INSTRUCTIONS.

3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE

EXISTING TILES FOR REUSE. SEE SPEC FOR

REPLACEMENT IF REQD.

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.9

ENLARGED ROOM FLOOR PLANS

- SECOND & THIRD FLOOR - BASE

BID

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/4" = 1'-0"1

ROOM 214 - BASE BID

1" = 20'-0"2

ROOM 214 EXISTING IMAGES

N1/4" = 1'-0"3

ROOM 240-242 - BASE BID

1" = 20'-0"4

ROOM 240-242 EXISTING IMAGES

N1/4" = 1'-0"5

ROOM 247-248 - BASE BID

1" = 20'-0"6

ROOM 247-248 EXISTING IMAGES

N1/4" = 1'-0"7

ROOM 328-329 - BASE BID

DEMOLITION ITEMS

D01 EXIST'G TO REMAIN

D02 DEMO EXISTING ACT CEILING SYSTEM AS

INDICATED; SALVAGE TILES FOR REINSTALLATION

WHERE APPLICABLE

D03 DEMO COUNTER & ASSOC. CASEWORK

D04 DEMO WALL

D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW

D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED

WALL INFILL

D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN

ROOM 160

D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE

RATED SEAL

PROJECT MATERIAL LIST

1 EXISTING TO REMAIN

2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;

REINSTALL SALVAGED CEILING TILES

N1/4" = 1'-0"8

328-329 RCP DEMO - BASE BID

N1/4" = 1'-0"9

328-329 RCP NEW - BASE BID

1" = 20'-0"10

ROOM 328-329 EXISTING IMAGES

GAS CABINET SCHEDULE

MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS

019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

023A DOUBLE HAZARDOUS EXISTING YES NO ETR

023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H

023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

114 DOUBLE FLAMMABLE EXISTING NO NO ETR

133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H

133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H

141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H

141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H

214 DOUBLE HAZARDOUS EXISTING YES NO ETR

242A DOUBLE HAZARDOUS EXISTING YES NO ETR

242B DOUBLE FLAMMABLE EXISTING NO NO ETR

247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H

1213141517

C

D

E

F

G

H

J

K

L

G.1

A

12A

D05

D05

D05

D06

D06

D06

D06

D06

D07

D08

ROOM 132ROOM 133ROOM 134ROOM 135

130B

DEMO ACT ABOVE AS

REQ. FOR MEP SCOPE

D02

GENERAL NOTES

1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM

CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER

AND ARE NOT INTENDED TO SHOW EVERY EXISTING

CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE

CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.

EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE

ARCHITECTS OFFICE FOR REVIEW.

2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,

AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE

RIGHTS WITH OWNER.

3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS

ARE INDICATED ON CEILING PLANS.

4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND

RECESSED CONDUIT AND WIRING, WALL SWITCHES AND

OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT

BOXES, & FLOOR BOXES THAT WOULD EXIST IN A

DORMANT STATE UPON COMPLETION OF THE PROJECT.

REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT

PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.

(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE

RIGHTS WITH OWNER.

5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING

SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,

AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN

A DORMANT STATE AT THE COMPLETION OF THE

PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE

RIGHTS WITH OWNER.

6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST

AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY

THE NEW CONSTRUCTION, AND ANY EXTRANEOUS

MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT

STATE AT THE COMPLETION OF THE PROJECT.

7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.

8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT

ALL CEILING AND WALL MOUNTED ACCESSORIES

INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,

AND MISCELLANEOUS ITEMS.

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.10

FIRST FLOOR CONTROL ZONES -

ALTERNATE #1 - DEMO

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/4" = 1'-0"1

FIRST FLOOR CONTROL ZONES - DEMO PLAN - ALTERNATE #1

DEMOLITION ITEMS

D01 EXIST'G TO REMAIN

D02 DEMO EXISTING ACT CEILING SYSTEM AS

INDICATED; SALVAGE TILES FOR REINSTALLATION

WHERE APPLICABLE

D03 DEMO COUNTER & ASSOC. CASEWORK

D04 DEMO WALL

D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW

D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED

WALL INFILL

D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN

ROOM 160

D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE

RATED SEAL

1213141517

C

D

E

F

G

H

J

K

L

G.1

A

12A

135A

135B

Room 132Room 133Room 134Room 135

130B

CMU TOOTH-IN INFILL

@ EXSTG DOOR

DEMO

TOOTH-IN CMU @

DEMOLISHED ELEVATOR

ACCESSORIES

NEW/REINSTALLED ACT AS

REQ. FOR MEP SCOPE

*SEAL ALL PENETRATIONS @ 1 HOUR RATED BARRIER*

CMU TOOTH-IN INFILL

@ EXSTG DOOR

DEMO

CMU TOOTH-IN INFILL

@ EXSTG DOOR

DEMO

CMU TOOTH-IN INFILL

@ EXSTG DOOR

DEMO

CMU TOOTH-IN INFILL

@ EXSTG DOOR

DEMODOOR & FRAME TYPES

* = PROVIDE PROJECT SPECIFIC INFORMATION

SCHEDULE - FRAME

WIDTH 1

DOOR

WIDTH 2

DOOR

HM

S C

H E D

U

LE

SCHEDULE

HM

S C

H E D

U

LE

A

HM

SCHEDULE

S C

H E D

U

LE

B

HM

SCHEDULE

8" 8"

S C

H E D

U

LE

FR

FR

8" 8"

5/8" TYPE "X" GYP

INSULATOR

RATED FRAME; SEE SCHED.

RATED DOOR; SEE SCHED.

3 5/8"

/8

5/8" TYPE "X" GYP

INSULATOR

RATED FRAME;

SEE SCHED.

RATED DOOR;

SEE SCHED.

/8

5/8" 2"

TOOTH IN CMU @

DOOR DEMO

LOCATIONS; TYP.

FIRE SEAL ALL

PENETRATIONS

TOOTH IN CMU @

DOOR DEMO

LOCATIONS

TOOTH IN CMU @

DOOR DEMO

LOCATIONS PATCH ALL PENETRATIONS @

CONTINUOUS FIRE SEPARATION

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION

SPEDDING HALL

A2.11

FIRST FLOOR CONTROL ZONES -

ALTERNATE #1 - NEW WORK

11/16/2026ISSUE SET

11/16/2026

25011

2416 PAMMEL DR, AMES, IA 50011

N1/4" = 1'-0"1

1ST FLOOR CONTROL ZONES - NEW WORK - ALTERNATE #1

DOOR SCHEDULE

NO DOOR WIDTH 1 DOOR WIDTH 2 DOOR HEIGHT DOOR THICKNESS

DOOR

MATERIAL

DOOR

GLAZING DOOR TYPE FRAME TYPE FRAME WIDTH FRAME HEIGHT

FRAME

MATERIAL

FRAME

GLAZING

HEAD

DETAIL

JAMB

DETAIL HDW GROUP REMARK

007 3' - 6" 3' - 6" 7' - 0" 1 3/4" HM FR B 2 7' - 0" 7' - 0" HM - 2/ 3/ 1

135A 3' - 0" 7' - 0" 1 3/4" HM FR A 1 3' - 0" 7' - 0" HM - 2/ 3/ 2

135B 3' - 0" 7' - 0" 1 3/4" HM FR A 1 3' - 0" 7' - 0" HM - 2/ 3/ 2

161 3' - 0" 3' - 0" 7' - 0" 1 3/4" HM FR B 2 6' - 0" 7' - 0" HM - 2/ 3/ 1

DOOR HARDWARE GROUPS

HDW

GROUP HINGES LOCKSET

EXIT DEVICE

CLOSER STOP SMOKE/SOUND SEAL ASTRAGAL FINISH NOTES

1 (6) FBB191; 4 1/2X4 1/2 SCH CO-100 (2) VON

9927-F

(2) LCN 4040SE

SERIES

(2) IVES WS406CVX REE 797B PEM S771 US26D

2 (3) FBB179; 4 1/2X4 1/2 SCH CO-100

(1) LCN 4040SE

SERIES

(1) IVES WS406CVX REE 797B --- US26D

3" = 1'-0"2

DOOR HEAD DTL

3" = 1'-0"3

DOOR JAMB DTL

EXISTING IMAGES

D

APPLICABLE CODES:

A. 2024 INTERNATIONAL BUILDING CODE (IBC)

B. 2024 INTERNATIONAL FIRE CODE (IFC)

C. 2024 INTERNATIONAL PLUMBING CODE (IPC)

D. 2024 INTERNATIONAL MECHANICAL CODE (IMC)

E. 2024 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

(E)

2"

2"

4"

4"

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING PIPE TAG

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

PIPE RISE

PIPE DROP

PIPE TEE REDUCING 45

DEGREE TEE

45 DEGREE TEE

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN

THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE

USED IN THIS SET OF DRAWINGS.

Room

INVERT: -105' - 1"

1/8" / 12" SLOPE

FIRE PROTECTION SYMBOLS

OBSTRUCTION FROM DUCTWORK 48"

AND GREATER

FP-DOM-W

FP-W

FP-PA

FP-O

FP-D

FIRE PROTECTION OTHER

FIRE PROTECTION DRY

FIRE PROTECTION PRE-ACTION

FIRE PROTECTION WET

COMBINATION FIRE & DOMESTIC

48"x18" SA

Ø ROUND

ABV ABOVE

AC AIR CONDITIONING

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CB CATCH BASIN

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

CW COLD WATER

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FDV FIRE DEPARTMENT VALVE

FL FLOOR

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

GAL GALLON

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GW GREASE WASTE

HB HOSE BIB

HP HORSE POWER

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INV INVERT

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SF SQUARE FOOT

SD SMOKE DAMPER

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

STM STEAM

T THERMOSTAT

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VENT VENTILATION

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

AC AIR CONDITIONING UNIT

ACCU AIR COOLING CONDENSING UNIT

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CH CHILLER

CT COOLING TOWER

CUH CABINET UNIT HEATER

CHWP CHILLED WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

HWP HEATING WATER PUMP

HRU HEAT RECOVERY UNIT

PRV POWER ROOF VENTILATOR

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SP SUMP PUMP

UH UNIT HEATER

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

UPRIGHT SPRINKLER HEAD

UPRIGHT SPRINKLER HEAD

'D' REPRESENTS DRY SPRINKLER HEAD

CAP

PLUG

SIDEWALL SPRINKLER HEAD

EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD

RECESSED SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

PIPE ACCESSORY TAGS

DOMESTIC WATER METER

BALANCING VALVE

SHUTOFF BALL VALVE

CHECK VALVE

3-WAY MIXING VALVE

MOTORIZED CONTROL VALVE

3 WAY MOTORIZED CONTROL

VALVE

PRESSURE REDUCING VALVE

REFRIGERANT SOLENOID VALVE

BUTTERFLY VALVE

S

SECTION VIEW

ELEVATION VIEW

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

RESOURCE CONSULTING ENGINEERS, L.L.C.

301 ALEXANDER AVE, SUITE C

AMES, IA

515-292-2500

FP0.0

FIRE SUPPRESSION SYMBOLS

AND ABBREVIATIONS

11/16/2026ISSUE SET

11/16/2026

2025.014.00

2416 PAMMEL DR, AMES, IA 50011

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION -

SPEDDING HALL

INV INVERT

INFO INFORMATION

IN INCH / INCHES

IMC INTERNATIONAL MECHANICAL CODE

IFGC INTERNATIONAL FUEL GAS CODE

IECC INTERNATIONAL ENERGY CONSERVATION CODE

ID INSIDE DIAMETER

IBC INTERNATIONAL BUILDING CODE

HZ HERTZ WG WATER GAUGE

HVAC HEATING, VENTILATION, AND AIR CONDITIONING WC WATER COLUMN

HP HORSEPOWER WB WET BULB

H ENTHALPY W/ WITH

GYP GYPSUM BOARD W WATT

GS GALVANIZED STEEL VTR VENT THROUGH ROOF

GPM GALLONS PER MINUTE VP VELOCITY PRESSURE

GPH GALLONS PER HOUR VENT VENTILATION

GC GENERAL CONTRACTOR VAV VARIABLE AIR VOLUME

GAL GALLON V VOLTS

GA GAUGE UL UNDERWRITERS LABORATORIES

FTG FOOTING UG UNDERGROUND

FT FOOT / FEET TYP TYPICAL

FSP FIRE SUPPRESSION TSP TOTAL STATIC PRESSURE

FPS FEET PER SECOND TOP TOP OF PIPE

FPM FEET PER MINUTE TOD TOP OF DUCT

FLA FULL LOAD AMPS THRU THROUGH

FL FLOOR TEMP TEMPERATURE

EXH EXHAUST TCC TEMPERATURE CONTROL CONTRACTOR

EWT ENTERING WATER TEMPERATURE STD STANDARD

EWB ENTERING WET BULB SS STAINLESS STEEL

ETR EXISTING TO REMAIN SPEC SPECIFY / SPECIFIED / SPECIFICATION

ETC ET CETERA SP STATIC PRESSURE

ESP EXTERNAL STATIC PRESSURE SM SURFACE MOUNT

EQUIP EQUIPMENT SF SQUARE FOOT/FEET

ELEV ELEVATOR SCH SCHEDULE

ELEC ELECTRICAL RPM REVOLUTIONS PER MINUTE

EDB ENTERING DRY BULB RM ROOM

EC ELECTRICAL CONTRACTOR RH RELATIVE HUMIDITY

EAT ENTERING AIR TEMPERATURE REV REVISION

E.G. FOR EXAMPLE RED REDUCER

DP DIFFERENTIAL PRESSURE REC RECESSED

DN DOWN RCP REFLECTED CEILING PLAN

DIA (ALSO Ø) DIAMETER RCE RESOURCE CONSULTING ENGINEERS, LLC

DEMO DEMOLISH / DEMOLITION QTY QUANTITY

DDC DIRECT DIGITAL CONTROL PWR POWER

DBA A-WEIGHTED DECIBELS PSIG POUNDS PER SQUARE INCH GAUGE

DB DRY BULB PSIA POUNDS PER SQUARE INCH ABSOLUTE

CxA COMMISSIONING AGENT PSI POUNDS PER SQUARE INCH Cx COMMISSIONING PSF POUNDS PER SQUARE FOOT

CV CONSTANT VOLUME PRESS PRESSURE

CU COPPER PLBG PLUMBING

CS CARBON STEEL PG PROPYLENE GLYCOL

COP CENTER OF PIPE PD PRESSURE DROP

CONT CONTINUED PCF POUNDS PER CUBIC FOOR

COD CENTER OF DUCT PC PLUMBING CONTRACTOR

CLG CEILING OFOI OWNER FURNISHED, OWNER INSTALLED

CL CENTERLINE OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

CFM CUBIC FEET PER MINUTE OD OUTSIDE DIAMETER

CFH CUBIC FEET PER HOUR OC ON CENTER

CAP CAPACITY NTS NOT TO SCALE

BTUH BRITISH THERMAL UNITS PER HOUR NPS NOMINAL PIPE SIZE

BTU BRITISH THERMAL UNITS NO NUMBER

BOP BOTTOM OF PIPE NIC NOT IN CONTRACT

BOD BOTTOM OF DUCT NFPA NATIONAL FIRE PROTECTION ASSOCIATION

BMS BUILDING MANAGEMENT SYSTEM NC NOISE CRITERIA

BLW BELOW N/A (ALSO NA) NOT APPLICABLE

BFF BELOW FINISHED FLOOR MTR MOTOR

BAS BUILDING AUTOMATION SYSTEM MOCP (ALSO MCP) MAXIMUM OVERCURRENT PROTECTION

AUTO AUTOMATIC MISC MISCELLANEOUS

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS MIN MINIMUM

ARCH ARCHITECT/ARCHITECTURAL MFR MANUFACTURER

AP ACCESS PANEL MEP MECHANICAL, ELECTRICAL, AND PLUMBING

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MECH MECHANICAL

ALT ALTERNATE MCF ONE THOUSAND CUBIC FEET

AL ALUMINUM MCA MAXIMUM CURRENT AMPACITY

AHJ AUTHORITY HAVING JURISDICTION MC MECHANICAL CONTRACTOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY MBH ONE THOUSAND BTU PER HOUR

AFF ABOVE FINISHED FLOOR MAX MAXIMUM

ADJ ADJUSTABLE LWT LEAVING WATER TEMPERATURE

ADD ADDENDUM LWB LEAVING WET BULB

ACT ACOUSTICAL CEILING TILES LRA LOCKER ROTOR AMPS

ABV ABOVE LF LINEAL / LINEAR FOOT

A AMPS / AMPERE LDB LEAVING DRY BULB

°F DEGREES FAHRENHEIT LB/HR POUNDS PER HOUR

(R) RELOCATED LB POUND

(E) EXISTING LAT LEAVING AIR TEMPERATURE

(D) DEMOLISHED KW KILOWATT

ABBREVIATIONS ABBREVIATIONS CONT.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 20 21 22 23 24

C

D

E

F

G

H

J

K

L

G.1

A

6A 7A 8A 9A 11A 12A 12.5 13A 14A 16A 17A 18A 19A

BACKFLOW PREVENTOR (E)

1 1/4" FP-W (E) 1 1/4" FP-W (E)

1 1/4" FP-W (E) 1 1/4" FP-W (E)

4" FP-W (E) 4" FP-W (E)

1 1/4" FP-W (E)

1 1/4" FP-W (E)

4" FP-W (E)

1 1/4" FP-W (E) 1 1/4" FP-W (E)

1 1/4" FP-W (E)

1 1/4" FP-W (E)

1 1/4" FP-W (E)

1 1/4" FP-W (E)

4" FP-W (E)

4" FP-W (E) 4" FP-W (E)

1 1/4" FP-W (E)

4" FP-W (E)

1 1/4" FP-W (E)

1 1/4" FP-W (E)

4" FP-W (E)

1 1/4" FP-W (E)

1 1/4" FP-W (E)

4" FP-W (E)

Space

B22

Space

B24

Space

B27

Space

B28 Space

B20

Space

B19 Space

B17

Space

B15A

Space

B10

Space

B11

Space

B3

Space

B2

Space

B4

Space

B5C

Space

B5B

Space

B57

Space

B53

Space

B47B

Space

B52

Space

B47

Space

B34 Space

B35

Space

B33

Space

B36

Space

B37

Space

B39A Space

B39

Space

B40

Space

B43

Space

B7

Space

B8-9

Space

B5

Space

B47C

Space

B56B

Space

B56A

Consultant

Revision Record

Print Record

1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010

515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com

Project Number

RESOURCE CONSULTING ENGINEERS, L.L.C.

301 ALEXANDER AVE, SUITE C

AMES, IA

515-292-2500

FP1.0

BASEMENT FIRE SUPPRESSION

PLAN

11/16/2026ISSUE SET

11/16/2026

2025.014.00

2416 PAMMEL DR, AMES, IA 50011

SC-27-723

AMES NATIONAL LABORATORY

HAZARDOUS & FLAMMABLE GAS

CABINET INSTALLATION -

SPEDDING HALL

AUTOMATIC SPRINKLER SYSTEM DESIGN CRITERIA

SYMBOL

OCCUPANCY HAZARD

CLASSIFICATION DESIGN DENSITY (GPM/SF) DESIGN AREA

LH LIGHT HAZARD

OCCUPANCY

0.10 1500 SF

OH1 ORDINARY HAZARD,

GROUP 1 OCCUPANCY

0.15 1500 SF

OH2 ORDINARY HAZARD,

GROUP 2 OCCUPANCY

0.20 1500 SF

N 1/8" = 1'-0"

BASEMENT FIRE PROTECTION PLAN

FIRE PROTECTION GENERAL NOTES

A PROVIDE ALTERATIONS TO THE EXISTING FIRE PROTECTION SYSTEM AS REQUIRED

TO ACCOMMODATE THE NEW FLOOR PLAN AND NEW CEILING TYPES. PROVIDE A

COMPLETE WET TYPE SYSTEM INCLUDING NEW MAINS, BRANCHES, HEADS,

VALVES, AND ACCESSORIES AS REQUIRED. REUSE EXISTING SYSTEM EQUIPMENT

WHERE APPLICABLE. THE SYSTEM SHALL BE INSTALLED ACCORDING TO

MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS AND AS PER

REQUIREMENTS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT, AND

ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, AND NFPA.

B THE BUILDINGS COMPLETE OPERATIONAL FIRE PROTECTION SYSTEMS SHALL

REMAIN IN PLACE. CONTRACTOR SHALL REPAIR ANY DAMAGE TO SYSTEM

CREATED BY THE REMOVAL OF ANY OTHER MECHANICAL SYSTEMS OR

COMPONENTS.

C CONTRACTOR SHALL COORDINATE PHASING OF SPRINKLER WORK WITH THE

GENERAL CONTRACTOR PRIOR TO STARTING WORK.

D PROVIDE A COMPLETE WET TYPE FIRE PROTECTION SYSTEM AS REQUIRED TO

ACCOMMODATE THE FLOOR PLAN AND CEILING TYPES INCLUDING MAINS,

BRANCHES, HEADS, VALVES, AND ACCESSORIES AS REQUIRED. THE SYSTEM SHALL

BE INSTALLED ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND

RECOMMENDATIONS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT,

AND ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, NFPA, AND FACTORY

MUTUAL.

E THE SPRINKLER SYSTEM SHALL BE DESIGNED BASED UPON ACTUAL WATER FLOW

TEST DATA OBTAINED AT OR NEAR THE JOB SITE.

F REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION REGARDING

SPRINKLER HEAD LOCATION AND PIPE, UNLESS NOTED OTHERWISE.

G COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR PROPER INSTALLATION OF

THE FIRE PROTECTION SYSTEMS ALARM DEVICES INVOLVED WITH FIRE SPRINKLER

SYSTEM.

H ALL SPRINKLER SYSTEM PIPING SHALL BE CONCEALED ABOVE THE SUSPENDED

CEILING SYSTEM, UNLESS NOTED OTHERWISE. WRITTEN AUTHORIZATION SHALL

BE OBTAINED FROM THE ARCHITECT PRIOR TO EXPOSING ANY PIPING IN ANY

ROOM WHICH HAS A SUSPENDED CEILING.

J CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SPRINKLER HEADS AS REQUIRED

TO ENSURE AN APPROVED FIRE PROTECTION SYSTEM AT NO ADDITIONAL COST TO

THE OWNER.

K AUXILIARY DRAINS SHALL BE EXPOSED WITH 1" DRAIN VALVES. WHEN 5 OR MORE

GALLONS ARE TRAPPED, CONTRACTOR SHALL PROVIDE FIXED PIPING TO AN

ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW

OF THE DRAIN. WHEN LESS THAN 5 GALLONS ARE TRAPPED, A HOSE BIB SHALL BE

PROVIDED AT THE DRAIN VALVE.

L AUXILIARY DRAINS SHALL NOT BE LOCATED ABOVE PLASTER OR GYPSUM BOARD

CEILING SYSTEMS.

M AN INSPECTOR'S TEST CONNECTION SHALL BE PROVIDED FOR EACH FIRE

SPRINKLER ZONE. CONTRACTOR SHALL PROVIDE FIXED PIPING FROM THE TEST

CONNECTION TO AN ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF

ACCEPTING THE FULL FLOW OF THE TEST. EXTERIOR DISCHARGE OF THE TEST

CONNECTION SHALL BE PERMITTED ONLY BY SPECIFIC WRITTEN INSTRUCTION

FROM THE ENGINEER.

N SHOW ALL ROOM NUMBERS ON SHOP DRAWING PLANS.

P FLOW TEST DATA FROM 2024/12/15 INDICATES THE FOLLOWING: STATIC PRESSUR

81.4 PSI. RESIDUAL PRESSURE: 77.1 PSI AT 500 GPM. THE HYDRANTS TESTED ARE

LOCATED OFF THE 8" WATER MAINAT THE CORNER OF PAMMEL DRIVE AND MORIL

ROAD. STREET AT AN ELEVATION OF 971 FEET ABOVE SEA LEVEL. SEE CIVIL PLANS

FOR HYDRANT LOCATION. THE CONTRACTOR SHALL PERFORM A FIRE FLOW TEST

IN ACCORDANCE WITH NFPA 291 TO VERIFY THE FLOW TEST DATA GIVEN ABOVE.

THE DATA GIVEN ABOVE SHALL BE THE BASIS OF DESIGN UNLESS THE AVAILABLE

PRESSURE OR FLOW HAS DECREASED. NOTIFY OWNERS REPRESENTATIVE IF FLOW

TEST DATA DIFFERS FROM THE DATA ABOVE. A FIRE PROTECTION ENGINEER OR AN

ENGINEER EXPERIENCED IN WATER FLOW TESTING SHALL PERFORM OR WITNESS

THE REQUIRED FLOW TESTING AND SIGN THE REPORT PRIOR TO THE FIRST

SPRINKLER SYSTEM SUBMITTAL.

Q ROUTE SPRINKLER PIPING SUCH THAT IT DOES NOT RUN ABOVE ELECTRICAL

PANELS, SWITCHGEAR, OR SIMILAR EQUIPMENT. SPRINKLER MAINS SHALL NOT

RUN THROUGH ELECTRICAL OR COMMUNICATION ROOMS. SPRINKLER HEADS IN

THESE ROOMS SHALL BE SERVED BY A DEDICATED BRANCH LINE FOR EACH ROOM.

R DRAWING INDICATES A GENERAL PIPING ARRANGEMENT AND SUGGESTED…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .