This file is a set of architectural and engineering construction drawings for a hazardous and flammable gas cabinet installation project. Project SC-27-723 is located at Ames National Laboratory in Spedding Hall at 2416 Pammel Drive, Ames, Iowa, with an issue date of November 16, 2026. The project involves installation of multiple gas safety cabinets throughout the facility's basement, ground, first, second, and third floors, with cabinets ranging from single to triple capacity units designed to store both hazardous and flammable materials. The gas cabinet schedule identifies 29 cabinet locations with specific dimensions (primarily 18"W x 19"D x 75"H, 24"W x 19"D x 75"H, or 36"W x 19"D x 75"H), indicating which cabinets are new installations and which are existing to remain. Hazardous-level cabinets include sprinkler systems, while flammable-level cabinets do not.
Work scope includes selective demolition of existing walls, doors, ceilings, and mechanical systems; installation of new acoustical ceiling tile grids with salvaged tile reuse; coordination with mechanical, electrical, and plumbing trades; and installation of new fire suppression systems where required. The drawings specify compliance with 10 CFR 851.C safety regulations, establishment of utility location protocols prior to excavation, and coordination of lockout/tagout procedures with advance notice to building management. Contractors must register through TASF, obtain security badges, complete site safety orientation, verify hazardous materials including asbestos and beryllium contamination, and schedule penetration permits 10–15 days prior to work. All cabinet installations must coordinate with manufacturer specifications, and all new ductwork and conduit must be prepped and painted. The project documents multiple fire suppression plans, floor plans across all building levels, mechanical and electrical plans, and door and hardware schedules, with professional engineering certifications from Iowa-licensed engineers.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U P
R R
U P R R
U P R R
U P
R R
Walls
Earth
Granular Fill
Sand, Mortar
Concrete
Concrete Block
Brick
Stone
Aluminum
Steel
Bronze
Wood
Structural
Blocking
Particle Board
Plywood
Glass
Batt Insulation
Rigid
Insulation Tile
Plastic Laminate
Gypsum Board
Plaster
Acoustic Tile
Terrazzo
Metal Stud
Wood Stud
2 8
1 6
1. Prior to excavation and site planting on the job site, the contractor shall contact utility companies to locate underground utilities effecting the excavations and planting on the job site. Excavation shall not proceed until all utilities are located and indicated. The contractor shall maintain the identifying devices throughout the duration of the project.
2. The contractor shall comply with 10 CFR 851.C rules and regulations throughout the construction activities on the project. None of the work contemplated in the construction documents shall be construed as being in conflict with applicable 10 CFR 851.C rules and regulations.
3. Contractors shall verify all dimensions and conditions effecting the work shown on the contract documents. Any conflicts found shall be reported to the Architect before proceeding with the work.
4. During the process of work, all penetrations through walls, ceilings, and floors will require a permit to be filed to ensure that radiation scanning can be completed prior to work commencing.
5. All LOTO and electrical shutdowns will need to be communicated to the owner with ample amount of time for building wide notification that will need to be scheduled.
See table for required timelines.
6. Every member of the construction crew will be required to be registered through
TASF and have possession of a badge while on site.
7. All construction crew members must complete an Ames Lab site and safety orientation before beginning work.
8. Verify all legacy hazardous material in scope of work with Ames Lab ESH, including asbestos, radiation contamination, and beryllium contamination before work begins.
Index to Drawings
ARCHITECTURAL
Material Symbols x
A4.0
A7.0
A4.4
A4.2
XXX
X
Plan Detail
Detail
Wall Section Revision No.X
Room Name/No.
Wall Type
Door Number
Column Grid
Floor Line
Test Bore
Building Section
XX
XX.X
Drawing Number
Sheet Call Out
Site Access Map
Abbreviation Key
Certification
Graphic Symbols
MECHANICAL/ELECTRICAL/PLUMBING
General Notes
1i
Casework Tag
D00 Demolition Note
0 Equipment Tag
0 Material Key Tag
Toilet Accessory
Key Tag
N North Arrow
1i Plumbing Fixture Tag
RAILING
'A'
Railing Tag
1t Window Tag
Name 101
Room Tag w/ Occ.
Load
PROJECT LOCATION PAMMEL DR
OSBORN DR
B
IS
S E
LL
R D
S T A N G
E R
D
N UNIVERSITY BLVD
TASF
GENERAL SCHEDULING REQUIREMENTS
• NORMAL HOURS OF OPERATION ARE 7:30 AM TO 4:30 PM,
MONDAY THROUGH FRIDAY.
• NOTIFY OWNER NOT LESS THAN THE FOLLOWING IN ADVANCE
OF ACTIVITIES THAT WILL AFFECT OWNER'S OPERATIONS:
1. NO LESS THAN TWO (2) MONTHS AHEAD OF
SCHEDULED ACTIVITY, PROVIDE ACCURACRY WITHIN
ONE (1) WEEK.
2. NO LESS THAT TWO (2) WEEKS AHEAD OF SCHEDULED
ACTIVITY, PROVIDE ACCURACT WITHIN ONE (1) DAY.
• FIRE SUPPRESSION SHUTDOWN
1. ALLOWABLE SHUTDOWN DURING NORMAL WORKING
HOURS
2. MAXIMUM CONTINUOUS DURATION = 8 HOURS
• MECHANICAL EXHAUST SHUTDOWN
1. ALLOWABLE SHUTDOWN DURING NORMAL WORKING
HOURS
2. MAXIMUM CONTINUOUS DURATION = 4 HOURS
• PENETRATION PERMIT
• 10-15 DAYS FOR APPROVAL
• NON-CITIZEN WORKER REVIEW PROCESS
• 45 DAYS FOR REVIEW/APPROVAL
Vicinity Map Legend
PROJECT SITE LOCATION
CONTRACTOR PARKING AREA
CONTRACTOR TO PURCHASE PARKING PASSES AND
UTILIZE HIGHLIGHTED LOT
M O
R R
IL
L R D
N
LOT 29
LOT 29
W O
I R D
KOOSER DR
W
IN
LO
C
K R
D
N
Vicinity Map
N
Enlarged Campus Map
HWY 30
S U
N
IV
E R S
IT
Y A
V E
LINCOLN WAY
I-35
D U F F A
V E
S T A N G
E R
D
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERONSAL
SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.
CLINTON ROGER RABE, PE
REG. NO. DATE:
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026
PAGES OR SHEETS COVERED BY THIS SEAL:
P19481
ALL MECHANICAL AND PLUMBING SHEETS
L
IC
E N S E
D
PR
OFE
SSIONAL
E
N G I N E E R
O WI A
CLINTON
ROGER
RABE
P19481
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERONSAL
SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.
TIMOTHY A. HILTON, P.E.
REG. NO. DATE:
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026
PAGES OR SHEETS COVERED BY THIS SEAL:
P19392
ALL MECHANICAL AND PLUMBING SHEETS
L
IC
E N S E
D
PR
OFE
SSIONAL
E
N G I N E E R
O WI A
TIMOTHY
A
HILTON
P19392 Consultant
Revision Record
Print Record
Project Number
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
SC-27-723 - AMES NATIONAL LABORATORY HAZARDOUS & FLAMMABLE GAS CABINET INSTALLATION
SPEDDING HALL
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
11/16/2026ISSUE SET
25011
A0.0
TITLE SHEET
11/16/2026
2416 PAMMEL DR, AMES, IA 50011
Jeffrey S. Harris Date License number: 3594 My license renewal date is: June 30, 2028 Pages or sheets covered by this seal:
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed architect under the laws of the state of Iowa.
A0.0
A2.0
A2.1
IOWA
A R
E
J E
F
F
HSY .
R
S R
I
CH
N
IC
E
DES
A R
E
TI
C
L
T
AL,ALUM ALUMINUM
AT ACOUSTICAL CEILING TILE
BLDG BUILDING
BLK BLOCK (CONCRETE)
BRK BRICK
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTER LINE
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONC/S SEALED CONCRETE
CONV CONVENIENCE
CPT CARPET
CT CERAMIC TILE
DN DOWN
DTL DETAIL
EJ,EXP JT EXPANSION JOINT
EXT EXTERIOR
FC FOAM CORE
FGT FIBERGLASS CEILING TILE
FGW FIBERGLASS WALL TILE
FT FOOT, FEET
GALV GALVANIZED
GB,GYP BD, GWB GYPSUM WALLBOARD
GR GRANITE
GYP GYPSUM
HDW HARDWARE
HM HOLLOW METAL
IG INSULATED GLASS
INSUL INSULATION, INSULATED
ISG INSULATING SAFETY GLASS
LH LEFT HAND
MIN MINIMUM
MTL, MET METAL
NIC NOT IN CONTRACT
NOM NOMINAL
A2.2
A2.3
A2.4
A2.5
A2.6
A2.7
A2.8
A2.9
A2.10
NTS NOT TO SCALE
O.C. ON CENTER
P LAM PLASTIC LAMINATE
PART BD PARTICLE BOARD
PC PRECAST CONCRETE
PLYWD PLYWOOD
R RISER,RADIUS
RH RIGHT HAND
RSR RUBBER STAIR RISER
RST RUBBER STAIR TREAD
SC SOLID CORE
SCH SCHEDULE
SFP SPRAYED FIRE PROTECTION
SG SAFETY GLASS
SG SPANDREL GLASS
SH STEEL
SIM SIMILAR
SK SINK
SND SANITARY NAPKIN DISPOSAL
SOG SLAB ON GRADE
SPEC SPECIFICATIONS, SPECIFIED
SS, ST STL STAINLESS STEEL
SVF SHEET VINYL FLOORING
THRE'D THRESHOLD
TR TREAD
TYP TYPICAL
UR URINAL
VB VINYL BASE
VF VINYL WALL FABRIC
VP VENEER PLASTIC
VT VINYL TILE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WG WIRE GLASS
A0.0 TITLE SHEET
A2.0 BASEMENT FLOOR PLAN
A2.1 GROUND LEVEL FLOOR PLAN
A2.2 FIRST FLOOR PLAN
A2.3 SECOND FLOOR PLAN
A2.4 THIRD FLOOR PLAN
A2.5 ROOFTOP PENTHOUSE PLAN
A2.6 ENLARGED ROOM FLOOR PLANS - BASEMENT - BASE BID
A2.7 ENLARGED ROOM FLOOR PLANS - GROUND LEVEL - BASE BID
A2.8 ENLARGED ROOM FLOOR PLANS - FIRST FLOOR - BASE BID
A2.9 ENLARGED ROOM FLOOR PLANS - SECOND & THIRD FLOOR - BASE
BID
A2.10 FIRST FLOOR CONTROL ZONES - ALTERNATE #1 - DEMO
A2.11 FIRST FLOOR CONTROL ZONES - ALTERNATE #1 - NEW WORK
E0.0 ELECTRICAL SYMBOL LEGEND
E0.1 ELECTRICAL PROJECT NOTES AND ABBREVIATIONS
E0.2 ELECTRICAL PROJECT NOTES
E0.3 ELECTRICAL PROJECT SCHEDULES
E2.0 BASEMENT ELECTRICAL PLAN
E2.1 GROUND FLOOR ELECTRICAL PLAN
E2.3 SECOND FLOOR POWER PLAN
E2.4 THIRD LEVEL POWER PLAN
E2.6 ENLARGED ELECTRICAL PLANS
E2.7 ENLARGED ELECTRICAL PLANS - FIRST FLOOR CONTROL ZONE -
ALTERNATE #1
FP0.0 FIRE SUPPRESSION SYMBOLS AND ABBREVIATIONS
FP1.0 BASEMENT FIRE PROTECTION PLAN
FP1.2 FIRST FLOOR FIRE SUPPRESSION PLAN
FP1.3 SECOND FLOOR FIRE SUPPRESSION PLAN
FP1.4 THIRD FLOOR FIRE SUPPRESSION PLAN
FP7.0 FIRE PROTECTION DETAILS & SCHEDULES
M0.0 HVAC SYMBOLS AND ABBREVIATIONS
M2.0 BASEMENT MECHANICAL PLAN
M2.1 GROUND LEVEL MECHANICAL PLAN
M2.2 FIRST FLOOR MECHANICAL PLAN
M2.3 SECOND FLOOR MECHANICAL PLAN
M2.4 THIRD FLOOR MECHANICAL PLAN
M2.5 ROOFTOP PENTHOUSE MECHANICAL PLAN
M2.6 ENLARGED MECHANICAL PLANS - BASEMENT - BASE BID
M2.7 ENLARGED MECHANICAL PLANS - GROUND FLOOR - BASE BID
M2.8 ENLARGED MECHANICAL PLANS - FIRST FLOOR - BASE BID
M2.9 ENLARGED MECHANICAL PLANS - SECOND AND THIRD FLOORS -
BASE BID
M2.10 ENLARGED MECHANICAL PLANS - FIRST FLOOR CONTROL ZONES -
DEMOLITION - ALTERNATE #1
M2.11 ENLARGED MECHANICAL PLANS - FIRST FLOOR CONTROL ZONES -
NEW WORK - ALTERNATE #1
M6.0 RISER DIAGRAM
M7.0 MECHANICAL DETAILS
M8.0 MECHANICAL SCHEDULES
A2.11
UP
TO METALS DEVELOPMENT
TO WILHELM HALL
STEAM
ROOM
HEATING TUNNEL
A2.6
A2.6
A2.6
A2.6
B1
B2 B3
B4
B5B5C
B5B B7A
B7
B8
B9
B10
B11 B15
B15A
B16 B17 B18 B19
ROOM B20
B22B24B27ROOM B28B31
B31A
BASEMENT B33BASEMENT B34B35ROOM B36ROOM B37
B39AB39B40B43
B44
B45 B46
B47
B51
B52
B53
B54 B55
B56
B56A
B56B
A2.0
Sim
19 20 21
C
D
D02
D02
D01
D01
19 20 21
C
D
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.0
BASEMENT FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/8" = 1'-0"1
BASEMENT
1/4" = 1'-0"2
BSMNT ENLARGED RCP DEMO
1/4" = 1'-0"3
BSMNT ENLARGED RCP NEW WORK
A2.7
A2.7
A2.7
A2.7
A2.7
6 7
10 15 16
ROOM 17 ROOM 18 ROOM 19
20ROOM 22ROOM 23ROOM 242526ROOM 272829
313233343536373839404142
43 44 45 46 47
ROOM 53
56A
56B
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.1
GROUND LEVEL FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/8" = 1'-0"1
GROUND LEVEL
UPUP
DOCK
A2.8
A2.8
A2.8
Room 114 Room 113
115 116
114A 116A
117 118 119
120122124125
127A127B
129130
130B
Room 132Room 133Room 134Room 135136Room 138Room 139Room 140Room 141142
145 146 147 148
144A
153153A
A2.11
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.2
FIRST FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
1ST FLR
UP
UP
A2.9
A2.9
A2.9
Room 214 217 219
220221222224225226227228229 230231232
234235236237238239
232A
Room 240Room 241Room 242
244 246 Room 247 Room 248
201C
201B
258 258A
201A
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.3
SECOND FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
2ND FLR
A2.9
314 315 316 317 318 319
320321322323324325326Room 328Room 329330331332
333A
334335336337338339
340B 340A
343 344 345 346 347 348 349-352
355 356
301A301B
301C
301D
301E
301F
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.4
THIRD FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
3RD FLOOR
402403
401A
EQUIPMENT ROOM 401
FAN ROOM
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.5
ROOFTOP PENTHOUSE PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
ROOF
FUME HOOD
C A B
IN
E T S
O H C
A B
EP
ET
T O
O L
B O
X D
E S
K O
H C
A B
O H C
A
G C
C C
A B
IN
E T
M/CM/C
TABLETABLE
11'-6"
BEAM
+12'-8"
STICK-ON TILE
M/C
ROOM B20
V E R
IF
Y
TABLE
EP
OH CAB
C A B
IN
E T
O H C
A B
EXISTING ELECTRICAL
OUTLETS TO REMAIN
11'-6"
BEAM
ROOM B28FUME
HOOD
C A B
IN
E T S
O H C
A B
O H C
A B
C A B
IN
E T
CAB
TABLE
TABLE
FURNACE
DESK
SLOPE UP TO
DOOR
13'-1"
DECK
11'-7"
BEAM
SHELVING
EP
BASEMENT B34 BASEMENT B33
FURNACE
FURNACE
DO NOT
BLOCK
AREA
SHIFT EP CLEAR
FLOOR SPACE TO
ALLOW FOR CABINET
INSTALLATION
FUME
HOOD
C A B
IN
E T S
O H C
A B
C O
U N T E R
O H C
A B
FURNACE
DESK
DESK
MCMC
11'-6"
BEAM
RELOCATED
EXISTING
STORAGE
CONTAINER
ROOM B36ROOM B37
+13'-1"
DECK
FURNACE
FURNACE
FURNACE
FURNACE
V E R
IF
Y
D03
D01
DEMO PORTION
OF COUNTER; TEST &
REMOVE ANY
PRESENT ASBESTOS
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
NEW WORK NOTES
1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED
AND PAINTED FOR FINAL FINISH.
2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH
MANUFACTURER'S STANDARD INSTALLATION
INSTRUCTIONS.
3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE
EXISTING TILES FOR REUSE. SEE SPEC FOR
REPLACEMENT IF REQD.
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.6
ENLARGED ROOM FLOOR PLANS
- BASEMENT - BASE BID
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/4" = 1'-0"1
ROOM B20 - BASE BID
N1/4" = 1'-0"2
ROOM B28 - BASE BID
N1/4" = 1'-0"3
ROOM B33-34 - BASE BID
N1/4" = 1'-0"4
ROOM B36-37 - BASE BID
GAS CABINET SCHEDULE
MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS
019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
023A DOUBLE HAZARDOUS EXISTING YES NO ETR
023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H
023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
114 DOUBLE FLAMMABLE EXISTING NO NO ETR
133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
214 DOUBLE HAZARDOUS EXISTING YES NO ETR
242A DOUBLE HAZARDOUS EXISTING YES NO ETR
242B DOUBLE FLAMMABLE EXISTING NO NO ETR
247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
329A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
329B DOUBLE FLAMMABLE EXISTING NO NO ETR
N1/4" = 1'-0"13
ROOM B20 DEMO - BASE BID
1" = 20'-0"14
B 20 EXISTING IMAGES
1" = 20'-0"15
B 28 EXISTING IMAGES
1" = 20'-0"16
B 33-34 EXISTING IMAGES
1" = 20'-0"17
B 36-37 EXISTING IMAGES
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO EXISTING ACT CEILING SYSTEM AS
INDICATED; SALVAGE TILES FOR REINSTALLATION
WHERE APPLICABLE
D03 DEMO COUNTER & ASSOC. CASEWORK
D04 DEMO WALL
D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW
D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED
WALL INFILL
D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN
ROOM 160
D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE
RATED SEAL
PROJECT MATERIAL LIST
1 EXISTING TO REMAIN
2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;
REINSTALL SALVAGED CEILING TILES
FUME
HOOD
FUME
HOOD
REF FC
REF
TABLE
TABLE
M/C
O H C
A B
C A B
IN
E T S
TABLE TABLE
TABLE
SHELF
C A B
IN
E T S
O H C
A B
7'-10"
BEAM
9'-5"
DECK
SHIFT
EXISTING EQUIP.
EAST
FUME
HOOD
REFRIGERATOR RELOCATED
BY OWNER
C O
U N T E R
FUME
HOOD
O H C
A
B FUME
HOOD
O H C
A B
C O
U N T E R
TABLE
8'-0"
BEAM
9'-6"
DECK
022A
022B
DEMO DOOR &
FRAME; TOOTH-IN
CMU & FINISH
MODIFY FILTER
SYSTEM LOCATION
AS REQD./SHIFT
CABINET TO
MAINTAIN
CLEARANCE. VIF
FINAL LOC. W/
OWNER
TABLE
TABLE
C A B
IN
E T S
C A B
IN
E T S
FUME
HOOD
FUME
HOOD
O H C
A B
O H C
A B
8'-0" BEAM
9'-6"
DECK
RELOCATE EXISTING
OUTLET
023C
023B 023A
FUME
HOOD
C A B
IN
E T S
T A B
LE
T A B
LE
O H C
A B
9'-6"
DECK
GLOVE
BOX
GLOVE
BOX
GLOVE
BOX
SHELFCABTABLE
NOTE: NO ACTIVE EXHAUST IN ROOM
8'-0"
BEAM
+9'-6"
DECK
INSTALL SS FLANGE AROUND
NEW OPENING TO CONCEAL
DEMO PORTION OF WALL
FLASHING TO CONCEAL
WALL PENETRATION
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
NEW WORK NOTES
1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED
AND PAINTED FOR FINAL FINISH.
2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH
MANUFACTURER'S STANDARD INSTALLATION
INSTRUCTIONS.
3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE
EXISTING TILES FOR REUSE. SEE SPEC FOR
REPLACEMENT IF REQD.
DEMO WALL INFILL;
REFERENCE IMAGE
BELOW 1
' - 6
D04
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.7
ENLARGED ROOM FLOOR PLANS
- GROUND LEVEL - BASE BID
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/4" = 1'-0"1
ROOM 19 - BASE BID
1" = 20'-0"2
ROOM 19 EXISTING IMAGES
N1/4" = 1'-0"3
ROOM 22 - BASE BID
1" = 20'-0"4
ROOM 22 EXISTING IMAGES
N1/4" = 1'-0"5
ROOM 23-24 - BASE BID
1" = 20'-0"6
ROOM 23-24 EXISTING IMAGES
N1/4" = 1'-0"7
ROOM 27 - BASE BID
1" = 20'-0"8
ROOM 27 EXISTING IMAGES
N1/4" = 1'-0"9
ROOM 53 - BASE BID
1" = 20'-0"10
ROOM 53 EXISTING IMAGES
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO EXISTING ACT CEILING SYSTEM AS
INDICATED; SALVAGE TILES FOR REINSTALLATION
WHERE APPLICABLE
D03 DEMO COUNTER & ASSOC. CASEWORK
D04 DEMO WALL
D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW
D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED
WALL INFILL
D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN
ROOM 160
D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE
RATED SEAL
PROJECT MATERIAL LIST
1 EXISTING TO REMAIN
2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;
REINSTALL SALVAGED CEILING TILES
N1/4" = 1'-0"11
ROOM 53 DEMO - BASE BID
GAS CABINET SCHEDULE
MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS
019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
023A DOUBLE HAZARDOUS EXISTING YES NO ETR
023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H
023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
114 DOUBLE FLAMMABLE EXISTING NO NO ETR
133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
214 DOUBLE HAZARDOUS EXISTING YES NO ETR
242A DOUBLE HAZARDOUS EXISTING YES NO ETR
242B DOUBLE FLAMMABLE EXISTING NO NO ETR
247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
329A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
329B DOUBLE FLAMMABLE EXISTING NO NO ETR
FUME
HOOD
CAB.
GLOVE BOX
COUNTER W/ OH. CAB.
C O
U N T E R W
O
H
C A B
G
LO
V E B
O X
C O
U N T E R W
O
H
C A B
CAB.
Room 114 Room 113
ACT2
+9' - 5"
D02
D01
CEILING HEIGHT
TO MATCH
EXISTING
O H
C A B
IN
E T
SFUME HOOD
CABINETSCABINETSCABINETS
M/C
M/C
M/C
M/C
D E S
K D
E S
K
ACT - 9'-5"
SHIFT
EXISTING M/C
RELOCATE
DESK
D E S
K
FUME HOOD
Room 135 Room 134 Room 133
Room 132
133A
133B
135B
135A
ALT #1
ACT
+9' - 5"
D02
D01
D02
ALT #1
ACT
+9' - 5"
ACT
+9' - 5"
ACT
+9' - 5"
ALT #1
FUME HOOD
FUME HOOD
CABINETSCABINETSCABINETS
O H
C A B
IN
E T S
T A B
LE
REF
DESK
T A B
LE
M/C
M/C
ACT + 9'-5"
Room 138Room 139Room 140Room 141
141A
141B
141C
ACT
+9' - 5"
D02
D01
D02
D02
ACT
+9' - 5"
ACT
+9' - 5"
ACT
+9' - 5"
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
NEW WORK NOTES
1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED
AND PAINTED FOR FINAL FINISH.
2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH
MANUFACTURER'S STANDARD INSTALLATION
INSTRUCTIONS.
3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE
EXISTING TILES FOR REUSE. SEE SPEC FOR
REPLACEMENT IF REQD.
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.8
ENLARGED ROOM FLOOR PLANS
- FIRST FLOOR - BASE BID
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/4" = 1'-0"1
ROOM 113-114 - BASE BID
N1/4" = 1'-0"2
113-114 RCP DEMO - BASE BID
N1/4" = 1'-0"3
113-114 RCP NEW - BASE BID
1" = 20'-0"4
ROOM 113-114 EXISTING IMAGES
N3/16" = 1'-0"5
ROOM 132-135 - BASE BID
N1/4" = 1'-0"6
132-135 RCP DEMO - BASE BID
N1/4" = 1'-0"7
132-135 RCP NEW - BASE BID
1" = 20'-0"8
ROOM 132-135 EXISTING IMAGES
N3/16" = 1'-0"9
ROOM 138-141 - BASE BID
N1/4" = 1'-0"10
138-141 RCP DEMO - BASE BID
N1/4" = 1'-0"11
138-141 RCP NEW - BASE BID
1" = 20'-0"12
ROOM 138-141 EXISTING IMAGES
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO EXISTING ACT CEILING SYSTEM AS
INDICATED; SALVAGE TILES FOR REINSTALLATION
WHERE APPLICABLE
D03 DEMO COUNTER & ASSOC. CASEWORK
D04 DEMO WALL
D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW
D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED
WALL INFILL
D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN
ROOM 160
D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE
RATED SEAL
PROJECT MATERIAL LIST
1 EXISTING TO REMAIN
2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;
REINSTALL SALVAGED CEILING TILES
GAS CABINET SCHEDULE
MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS
019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
023A DOUBLE HAZARDOUS EXISTING YES NO ETR
023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H
023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
114 DOUBLE FLAMMABLE EXISTING NO NO ETR
133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
214 DOUBLE HAZARDOUS EXISTING YES NO ETR
242A DOUBLE HAZARDOUS EXISTING YES NO ETR
242B DOUBLE FLAMMABLE EXISTING NO NO ETR
247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
M/C
GLOVE BOX
GLOVE BOX
C A B
IN
E T S
O V E R H
E A D
C A B
IN
E T S
T A B
LE
W C A B
IN
E T S
12'-0"
BEAM
13'-7"
GYP
Room 214
T A B
LE
T A B
LE
TABLE
SHELF
GLOVE BOX M/C
M/CM/C M/C
M/C
12'-8"
ACT
12'-0"
BEAM
FH
FH
FH
Room 242 Room 241 Room 240
242B
242A
C A B
IN
E T S
T A B
LE
T A B
LE
TABLE W/ GB
C O
O
LE
R
F R E E Z E R
TABLE
EXHAUST
M/C
DIVIDER
12'-0"
BEAM
12'-5"
STICK ON
ACT
Room 247 Room 248
M/C
G
LO
V E B
O X
F C
C A B
IN
E T S
O
S
E
LF
FH
11'-3"
DECK
9'-4"
ACT
E
FIRE
FH
HE TANK AND HE
PLUMBING MOVED
TO UNISTRUT BY
WINDOW
Room 328Room 329
329A
329B
D02
ACT
+9' - 5"
D01
ACT
+9' - 5"
ACT
+9' - 5"
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
NEW WORK NOTES
1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED
AND PAINTED FOR FINAL FINISH.
2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH
MANUFACTURER'S STANDARD INSTALLATION
INSTRUCTIONS.
3. INSTALL NEW ACT GRID TO MATCH EXISTING; SALVAGE
EXISTING TILES FOR REUSE. SEE SPEC FOR
REPLACEMENT IF REQD.
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.9
ENLARGED ROOM FLOOR PLANS
- SECOND & THIRD FLOOR - BASE
BID
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/4" = 1'-0"1
ROOM 214 - BASE BID
1" = 20'-0"2
ROOM 214 EXISTING IMAGES
N1/4" = 1'-0"3
ROOM 240-242 - BASE BID
1" = 20'-0"4
ROOM 240-242 EXISTING IMAGES
N1/4" = 1'-0"5
ROOM 247-248 - BASE BID
1" = 20'-0"6
ROOM 247-248 EXISTING IMAGES
N1/4" = 1'-0"7
ROOM 328-329 - BASE BID
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO EXISTING ACT CEILING SYSTEM AS
INDICATED; SALVAGE TILES FOR REINSTALLATION
WHERE APPLICABLE
D03 DEMO COUNTER & ASSOC. CASEWORK
D04 DEMO WALL
D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW
D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED
WALL INFILL
D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN
ROOM 160
D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE
RATED SEAL
PROJECT MATERIAL LIST
1 EXISTING TO REMAIN
2 NEW ACT GRID SYSTEM TO MATCH EXISTING HEIGHT;
REINSTALL SALVAGED CEILING TILES
N1/4" = 1'-0"8
328-329 RCP DEMO - BASE BID
N1/4" = 1'-0"9
328-329 RCP NEW - BASE BID
1" = 20'-0"10
ROOM 328-329 EXISTING IMAGES
GAS CABINET SCHEDULE
MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS
019 DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
0020 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
022A DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
022B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
023A DOUBLE HAZARDOUS EXISTING YES NO ETR
023B TRIPLE HAZARDOUS NEW YES YES 36"W x 19"D x 75"H
023C SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
027 DOUBLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0028 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
0034 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
0037 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
053 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
114 DOUBLE FLAMMABLE EXISTING NO NO ETR
133A SINGLE HAZARDOUS NEW YES YES 18"W x 19"D x 75"H
133B TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
135 TRIPLE FLAMMABLE NEW NO YES 36"W x 19"D x 75"H
141A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141B DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
141C DOUBLE HAZARDOUS NEW YES YES 24"W x 19"D x 75"H
214 DOUBLE HAZARDOUS EXISTING YES NO ETR
242A DOUBLE HAZARDOUS EXISTING YES NO ETR
242B DOUBLE FLAMMABLE EXISTING NO NO ETR
247 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
1213141517
C
D
E
F
G
H
J
K
L
G.1
A
12A
D05
D05
D05
D06
D06
D06
D06
D06
D07
D08
ROOM 132ROOM 133ROOM 134ROOM 135
130B
DEMO ACT ABOVE AS
REQ. FOR MEP SCOPE
D02
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.10
FIRST FLOOR CONTROL ZONES -
ALTERNATE #1 - DEMO
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/4" = 1'-0"1
FIRST FLOOR CONTROL ZONES - DEMO PLAN - ALTERNATE #1
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO EXISTING ACT CEILING SYSTEM AS
INDICATED; SALVAGE TILES FOR REINSTALLATION
WHERE APPLICABLE
D03 DEMO COUNTER & ASSOC. CASEWORK
D04 DEMO WALL
D05 DEMO EXISTING DOOR & FRAME; PREP FOR NEW
D06 DEMO EXISTING DOOR & FRAME; PREP FOR RATED
WALL INFILL
D07 DEMO ALL RELATED ELEVATOR CONTROLS WITHIN
ROOM 160
D08 DEMO ABANDONED CONDUIT & PREP FOR NEW FIRE
RATED SEAL
1213141517
C
D
E
F
G
H
J
K
L
G.1
A
12A
135A
135B
Room 132Room 133Room 134Room 135
130B
CMU TOOTH-IN INFILL
@ EXSTG DOOR
DEMO
TOOTH-IN CMU @
DEMOLISHED ELEVATOR
ACCESSORIES
NEW/REINSTALLED ACT AS
REQ. FOR MEP SCOPE
*SEAL ALL PENETRATIONS @ 1 HOUR RATED BARRIER*
CMU TOOTH-IN INFILL
@ EXSTG DOOR
DEMO
CMU TOOTH-IN INFILL
@ EXSTG DOOR
DEMO
CMU TOOTH-IN INFILL
@ EXSTG DOOR
DEMO
CMU TOOTH-IN INFILL
@ EXSTG DOOR
DEMODOOR & FRAME TYPES
* = PROVIDE PROJECT SPECIFIC INFORMATION
SCHEDULE - FRAME
WIDTH 1
DOOR
WIDTH 2
DOOR
HM
S C
H E D
U
LE
SCHEDULE
HM
S C
H E D
U
LE
A
HM
SCHEDULE
S C
H E D
U
LE
B
HM
SCHEDULE
8" 8"
S C
H E D
U
LE
FR
FR
8" 8"
5/8" TYPE "X" GYP
INSULATOR
RATED FRAME; SEE SCHED.
RATED DOOR; SEE SCHED.
3 5/8"
/8
5/8" TYPE "X" GYP
INSULATOR
RATED FRAME;
SEE SCHED.
RATED DOOR;
SEE SCHED.
/8
5/8" 2"
TOOTH IN CMU @
DOOR DEMO
LOCATIONS; TYP.
FIRE SEAL ALL
PENETRATIONS
TOOTH IN CMU @
DOOR DEMO
LOCATIONS
TOOTH IN CMU @
DOOR DEMO
LOCATIONS PATCH ALL PENETRATIONS @
CONTINUOUS FIRE SEPARATION
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
SPEDDING HALL
A2.11
FIRST FLOOR CONTROL ZONES -
ALTERNATE #1 - NEW WORK
11/16/2026ISSUE SET
11/16/2026
25011
2416 PAMMEL DR, AMES, IA 50011
N1/4" = 1'-0"1
1ST FLOOR CONTROL ZONES - NEW WORK - ALTERNATE #1
DOOR SCHEDULE
NO DOOR WIDTH 1 DOOR WIDTH 2 DOOR HEIGHT DOOR THICKNESS
DOOR
MATERIAL
DOOR
GLAZING DOOR TYPE FRAME TYPE FRAME WIDTH FRAME HEIGHT
FRAME
MATERIAL
FRAME
GLAZING
HEAD
DETAIL
JAMB
DETAIL HDW GROUP REMARK
007 3' - 6" 3' - 6" 7' - 0" 1 3/4" HM FR B 2 7' - 0" 7' - 0" HM - 2/ 3/ 1
135A 3' - 0" 7' - 0" 1 3/4" HM FR A 1 3' - 0" 7' - 0" HM - 2/ 3/ 2
135B 3' - 0" 7' - 0" 1 3/4" HM FR A 1 3' - 0" 7' - 0" HM - 2/ 3/ 2
161 3' - 0" 3' - 0" 7' - 0" 1 3/4" HM FR B 2 6' - 0" 7' - 0" HM - 2/ 3/ 1
DOOR HARDWARE GROUPS
HDW
GROUP HINGES LOCKSET
EXIT DEVICE
CLOSER STOP SMOKE/SOUND SEAL ASTRAGAL FINISH NOTES
1 (6) FBB191; 4 1/2X4 1/2 SCH CO-100 (2) VON
9927-F
(2) LCN 4040SE
SERIES
(2) IVES WS406CVX REE 797B PEM S771 US26D
2 (3) FBB179; 4 1/2X4 1/2 SCH CO-100
(1) LCN 4040SE
SERIES
(1) IVES WS406CVX REE 797B --- US26D
3" = 1'-0"2
DOOR HEAD DTL
3" = 1'-0"3
DOOR JAMB DTL
EXISTING IMAGES
D
APPLICABLE CODES:
A. 2024 INTERNATIONAL BUILDING CODE (IBC)
B. 2024 INTERNATIONAL FIRE CODE (IFC)
C. 2024 INTERNATIONAL PLUMBING CODE (IPC)
D. 2024 INTERNATIONAL MECHANICAL CODE (IMC)
E. 2024 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
(E)
2"
2"
4"
4"
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN
THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
Room
INVERT: -105' - 1"
1/8" / 12" SLOPE
FIRE PROTECTION SYMBOLS
OBSTRUCTION FROM DUCTWORK 48"
AND GREATER
FP-DOM-W
FP-W
FP-PA
FP-O
FP-D
FIRE PROTECTION OTHER
FIRE PROTECTION DRY
FIRE PROTECTION PRE-ACTION
FIRE PROTECTION WET
COMBINATION FIRE & DOMESTIC
48"x18" SA
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
UPRIGHT SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
'D' REPRESENTS DRY SPRINKLER HEAD
CAP
PLUG
SIDEWALL SPRINKLER HEAD
EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD
RECESSED SPRINKLER HEAD
CONCEALED SPRINKLER HEAD
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
SHUTOFF BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
S
SECTION VIEW
ELEVATION VIEW
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
RESOURCE CONSULTING ENGINEERS, L.L.C.
301 ALEXANDER AVE, SUITE C
AMES, IA
515-292-2500
FP0.0
FIRE SUPPRESSION SYMBOLS
AND ABBREVIATIONS
11/16/2026ISSUE SET
11/16/2026
2025.014.00
2416 PAMMEL DR, AMES, IA 50011
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION -
SPEDDING HALL
INV INVERT
INFO INFORMATION
IN INCH / INCHES
IMC INTERNATIONAL MECHANICAL CODE
IFGC INTERNATIONAL FUEL GAS CODE
IECC INTERNATIONAL ENERGY CONSERVATION CODE
ID INSIDE DIAMETER
IBC INTERNATIONAL BUILDING CODE
HZ HERTZ WG WATER GAUGE
HVAC HEATING, VENTILATION, AND AIR CONDITIONING WC WATER COLUMN
HP HORSEPOWER WB WET BULB
H ENTHALPY W/ WITH
GYP GYPSUM BOARD W WATT
GS GALVANIZED STEEL VTR VENT THROUGH ROOF
GPM GALLONS PER MINUTE VP VELOCITY PRESSURE
GPH GALLONS PER HOUR VENT VENTILATION
GC GENERAL CONTRACTOR VAV VARIABLE AIR VOLUME
GAL GALLON V VOLTS
GA GAUGE UL UNDERWRITERS LABORATORIES
FTG FOOTING UG UNDERGROUND
FT FOOT / FEET TYP TYPICAL
FSP FIRE SUPPRESSION TSP TOTAL STATIC PRESSURE
FPS FEET PER SECOND TOP TOP OF PIPE
FPM FEET PER MINUTE TOD TOP OF DUCT
FLA FULL LOAD AMPS THRU THROUGH
FL FLOOR TEMP TEMPERATURE
EXH EXHAUST TCC TEMPERATURE CONTROL CONTRACTOR
EWT ENTERING WATER TEMPERATURE STD STANDARD
EWB ENTERING WET BULB SS STAINLESS STEEL
ETR EXISTING TO REMAIN SPEC SPECIFY / SPECIFIED / SPECIFICATION
ETC ET CETERA SP STATIC PRESSURE
ESP EXTERNAL STATIC PRESSURE SM SURFACE MOUNT
EQUIP EQUIPMENT SF SQUARE FOOT/FEET
ELEV ELEVATOR SCH SCHEDULE
ELEC ELECTRICAL RPM REVOLUTIONS PER MINUTE
EDB ENTERING DRY BULB RM ROOM
EC ELECTRICAL CONTRACTOR RH RELATIVE HUMIDITY
EAT ENTERING AIR TEMPERATURE REV REVISION
E.G. FOR EXAMPLE RED REDUCER
DP DIFFERENTIAL PRESSURE REC RECESSED
DN DOWN RCP REFLECTED CEILING PLAN
DIA (ALSO Ø) DIAMETER RCE RESOURCE CONSULTING ENGINEERS, LLC
DEMO DEMOLISH / DEMOLITION QTY QUANTITY
DDC DIRECT DIGITAL CONTROL PWR POWER
DBA A-WEIGHTED DECIBELS PSIG POUNDS PER SQUARE INCH GAUGE
DB DRY BULB PSIA POUNDS PER SQUARE INCH ABSOLUTE
CxA COMMISSIONING AGENT PSI POUNDS PER SQUARE INCH Cx COMMISSIONING PSF POUNDS PER SQUARE FOOT
CV CONSTANT VOLUME PRESS PRESSURE
CU COPPER PLBG PLUMBING
CS CARBON STEEL PG PROPYLENE GLYCOL
COP CENTER OF PIPE PD PRESSURE DROP
CONT CONTINUED PCF POUNDS PER CUBIC FOOR
COD CENTER OF DUCT PC PLUMBING CONTRACTOR
CLG CEILING OFOI OWNER FURNISHED, OWNER INSTALLED
CL CENTERLINE OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
CFM CUBIC FEET PER MINUTE OD OUTSIDE DIAMETER
CFH CUBIC FEET PER HOUR OC ON CENTER
CAP CAPACITY NTS NOT TO SCALE
BTUH BRITISH THERMAL UNITS PER HOUR NPS NOMINAL PIPE SIZE
BTU BRITISH THERMAL UNITS NO NUMBER
BOP BOTTOM OF PIPE NIC NOT IN CONTRACT
BOD BOTTOM OF DUCT NFPA NATIONAL FIRE PROTECTION ASSOCIATION
BMS BUILDING MANAGEMENT SYSTEM NC NOISE CRITERIA
BLW BELOW N/A (ALSO NA) NOT APPLICABLE
BFF BELOW FINISHED FLOOR MTR MOTOR
BAS BUILDING AUTOMATION SYSTEM MOCP (ALSO MCP) MAXIMUM OVERCURRENT PROTECTION
AUTO AUTOMATIC MISC MISCELLANEOUS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS MIN MINIMUM
ARCH ARCHITECT/ARCHITECTURAL MFR MANUFACTURER
AP ACCESS PANEL MEP MECHANICAL, ELECTRICAL, AND PLUMBING
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE MECH MECHANICAL
ALT ALTERNATE MCF ONE THOUSAND CUBIC FEET
AL ALUMINUM MCA MAXIMUM CURRENT AMPACITY
AHJ AUTHORITY HAVING JURISDICTION MC MECHANICAL CONTRACTOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY MBH ONE THOUSAND BTU PER HOUR
AFF ABOVE FINISHED FLOOR MAX MAXIMUM
ADJ ADJUSTABLE LWT LEAVING WATER TEMPERATURE
ADD ADDENDUM LWB LEAVING WET BULB
ACT ACOUSTICAL CEILING TILES LRA LOCKER ROTOR AMPS
ABV ABOVE LF LINEAL / LINEAR FOOT
A AMPS / AMPERE LDB LEAVING DRY BULB
°F DEGREES FAHRENHEIT LB/HR POUNDS PER HOUR
(R) RELOCATED LB POUND
(E) EXISTING LAT LEAVING AIR TEMPERATURE
(D) DEMOLISHED KW KILOWATT
ABBREVIATIONS ABBREVIATIONS CONT.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 20 21 22 23 24
C
D
E
F
G
H
J
K
L
G.1
A
6A 7A 8A 9A 11A 12A 12.5 13A 14A 16A 17A 18A 19A
BACKFLOW PREVENTOR (E)
1 1/4" FP-W (E) 1 1/4" FP-W (E)
1 1/4" FP-W (E) 1 1/4" FP-W (E)
4" FP-W (E) 4" FP-W (E)
1 1/4" FP-W (E)
1 1/4" FP-W (E)
4" FP-W (E)
1 1/4" FP-W (E) 1 1/4" FP-W (E)
1 1/4" FP-W (E)
1 1/4" FP-W (E)
1 1/4" FP-W (E)
1 1/4" FP-W (E)
4" FP-W (E)
4" FP-W (E) 4" FP-W (E)
1 1/4" FP-W (E)
4" FP-W (E)
1 1/4" FP-W (E)
1 1/4" FP-W (E)
4" FP-W (E)
1 1/4" FP-W (E)
1 1/4" FP-W (E)
4" FP-W (E)
Space
B22
Space
B24
Space
B27
Space
B28 Space
B20
Space
B19 Space
B17
Space
B15A
Space
B10
Space
B11
Space
B3
Space
B2
Space
B4
Space
B5C
Space
B5B
Space
B57
Space
B53
Space
B47B
Space
B52
Space
B47
Space
B34 Space
B35
Space
B33
Space
B36
Space
B37
Space
B39A Space
B39
Space
B40
Space
B43
Space
B7
Space
B8-9
Space
B5
Space
B47C
Space
B56B
Space
B56A
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
RESOURCE CONSULTING ENGINEERS, L.L.C.
301 ALEXANDER AVE, SUITE C
AMES, IA
515-292-2500
FP1.0
BASEMENT FIRE SUPPRESSION
PLAN
11/16/2026ISSUE SET
11/16/2026
2025.014.00
2416 PAMMEL DR, AMES, IA 50011
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION -
SPEDDING HALL
AUTOMATIC SPRINKLER SYSTEM DESIGN CRITERIA
SYMBOL
OCCUPANCY HAZARD
CLASSIFICATION DESIGN DENSITY (GPM/SF) DESIGN AREA
LH LIGHT HAZARD
OCCUPANCY
0.10 1500 SF
OH1 ORDINARY HAZARD,
GROUP 1 OCCUPANCY
0.15 1500 SF
OH2 ORDINARY HAZARD,
GROUP 2 OCCUPANCY
0.20 1500 SF
N 1/8" = 1'-0"
BASEMENT FIRE PROTECTION PLAN
FIRE PROTECTION GENERAL NOTES
A PROVIDE ALTERATIONS TO THE EXISTING FIRE PROTECTION SYSTEM AS REQUIRED
TO ACCOMMODATE THE NEW FLOOR PLAN AND NEW CEILING TYPES. PROVIDE A
COMPLETE WET TYPE SYSTEM INCLUDING NEW MAINS, BRANCHES, HEADS,
VALVES, AND ACCESSORIES AS REQUIRED. REUSE EXISTING SYSTEM EQUIPMENT
WHERE APPLICABLE. THE SYSTEM SHALL BE INSTALLED ACCORDING TO
MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS AND AS PER
REQUIREMENTS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT, AND
ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, AND NFPA.
B THE BUILDINGS COMPLETE OPERATIONAL FIRE PROTECTION SYSTEMS SHALL
REMAIN IN PLACE. CONTRACTOR SHALL REPAIR ANY DAMAGE TO SYSTEM
CREATED BY THE REMOVAL OF ANY OTHER MECHANICAL SYSTEMS OR
COMPONENTS.
C CONTRACTOR SHALL COORDINATE PHASING OF SPRINKLER WORK WITH THE
GENERAL CONTRACTOR PRIOR TO STARTING WORK.
D PROVIDE A COMPLETE WET TYPE FIRE PROTECTION SYSTEM AS REQUIRED TO
ACCOMMODATE THE FLOOR PLAN AND CEILING TYPES INCLUDING MAINS,
BRANCHES, HEADS, VALVES, AND ACCESSORIES AS REQUIRED. THE SYSTEM SHALL
BE INSTALLED ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND
RECOMMENDATIONS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT,
AND ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, NFPA, AND FACTORY
MUTUAL.
E THE SPRINKLER SYSTEM SHALL BE DESIGNED BASED UPON ACTUAL WATER FLOW
TEST DATA OBTAINED AT OR NEAR THE JOB SITE.
F REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION REGARDING
SPRINKLER HEAD LOCATION AND PIPE, UNLESS NOTED OTHERWISE.
G COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR PROPER INSTALLATION OF
THE FIRE PROTECTION SYSTEMS ALARM DEVICES INVOLVED WITH FIRE SPRINKLER
SYSTEM.
H ALL SPRINKLER SYSTEM PIPING SHALL BE CONCEALED ABOVE THE SUSPENDED
CEILING SYSTEM, UNLESS NOTED OTHERWISE. WRITTEN AUTHORIZATION SHALL
BE OBTAINED FROM THE ARCHITECT PRIOR TO EXPOSING ANY PIPING IN ANY
ROOM WHICH HAS A SUSPENDED CEILING.
J CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SPRINKLER HEADS AS REQUIRED
TO ENSURE AN APPROVED FIRE PROTECTION SYSTEM AT NO ADDITIONAL COST TO
THE OWNER.
K AUXILIARY DRAINS SHALL BE EXPOSED WITH 1" DRAIN VALVES. WHEN 5 OR MORE
GALLONS ARE TRAPPED, CONTRACTOR SHALL PROVIDE FIXED PIPING TO AN
ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW
OF THE DRAIN. WHEN LESS THAN 5 GALLONS ARE TRAPPED, A HOSE BIB SHALL BE
PROVIDED AT THE DRAIN VALVE.
L AUXILIARY DRAINS SHALL NOT BE LOCATED ABOVE PLASTER OR GYPSUM BOARD
CEILING SYSTEMS.
M AN INSPECTOR'S TEST CONNECTION SHALL BE PROVIDED FOR EACH FIRE
SPRINKLER ZONE. CONTRACTOR SHALL PROVIDE FIXED PIPING FROM THE TEST
CONNECTION TO AN ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF
ACCEPTING THE FULL FLOW OF THE TEST. EXTERIOR DISCHARGE OF THE TEST
CONNECTION SHALL BE PERMITTED ONLY BY SPECIFIC WRITTEN INSTRUCTION
FROM THE ENGINEER.
N SHOW ALL ROOM NUMBERS ON SHOP DRAWING PLANS.
P FLOW TEST DATA FROM 2024/12/15 INDICATES THE FOLLOWING: STATIC PRESSUR
81.4 PSI. RESIDUAL PRESSURE: 77.1 PSI AT 500 GPM. THE HYDRANTS TESTED ARE
LOCATED OFF THE 8" WATER MAINAT THE CORNER OF PAMMEL DRIVE AND MORIL
ROAD. STREET AT AN ELEVATION OF 971 FEET ABOVE SEA LEVEL. SEE CIVIL PLANS
FOR HYDRANT LOCATION. THE CONTRACTOR SHALL PERFORM A FIRE FLOW TEST
IN ACCORDANCE WITH NFPA 291 TO VERIFY THE FLOW TEST DATA GIVEN ABOVE.
THE DATA GIVEN ABOVE SHALL BE THE BASIS OF DESIGN UNLESS THE AVAILABLE
PRESSURE OR FLOW HAS DECREASED. NOTIFY OWNERS REPRESENTATIVE IF FLOW
TEST DATA DIFFERS FROM THE DATA ABOVE. A FIRE PROTECTION ENGINEER OR AN
ENGINEER EXPERIENCED IN WATER FLOW TESTING SHALL PERFORM OR WITNESS
THE REQUIRED FLOW TESTING AND SIGN THE REPORT PRIOR TO THE FIRST
SPRINKLER SYSTEM SUBMITTAL.
Q ROUTE SPRINKLER PIPING SUCH THAT IT DOES NOT RUN ABOVE ELECTRICAL
PANELS, SWITCHGEAR, OR SIMILAR EQUIPMENT. SPRINKLER MAINS SHALL NOT
RUN THROUGH ELECTRICAL OR COMMUNICATION ROOMS. SPRINKLER HEADS IN
THESE ROOMS SHALL BE SERVED BY A DEDICATED BRANCH LINE FOR EACH ROOM.
R DRAWING INDICATES A GENERAL PIPING ARRANGEMENT AND SUGGESTED…