SC-27-723 Gas Cabinet Installation - Metals Development DWGs.pdf
PDF 4 MB Posted
- Solicitation number
- RFP-SC-27-723
- Issued by
-
Department of Energy Ames Laboratory
About this file
This document is a comprehensive set of architectural and engineering construction drawings for the SC-27-723 Ames National Laboratory Hazardous & Flammable Gas Cabinet Installation project at the Metals Development facility located at 2415 Pammel Drive, Ames, Iowa 50011.
The project involves the installation of hazardous and flammable gas safety cabinets across multiple rooms on the first and second floors of the building. Six gas cabinets are scheduled for installation: Room 130 (single flammable, 18"W x 19"D x 75"H), Room 147 (double hazardous/existing, 24"W x 19"D x 75"H with sprinkler), Room 150C (double flammable, 24"W x 19"D x 75"H), Room 160A (double flammable, 24"W x 19"D x 75"H), Room 187 (single flammable, 18"W x 19"D x 75"H), and Room 220 (double flammable, 24"W x 19"D x 75"H). The drawings include detailed floor plans, mechanical systems (HVAC ductwork, exhaust air valve schedules, manifold connections), fire suppression modifications, and electrical power plans. Key mechanical infrastructure requirements include dedicated exhaust air handling systems with constant volume balancing valves, stainless steel piping for corrosive-rated cabinets, and fire protection sprinkler heads integrated into cabinet assemblies where specified. The project requires coordination with Ames Laboratory Environmental Safety & Health, compliance with 10 CFR 851.C safety regulations, penetration permits (10-15 days approval), and adherence to 2024 International Building Code, Fire Code, Plumbing Code, Mechanical Code, and Energy Conservation Code standards.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R38
R50
R63
R38
Col leg e C reek
Clear Creek
Squaw Creek
Squaw Creek
Sku n k R iv er
S k u n k R iv er
Worrell Creek
ZUMWALT STATION RD
S
TA
G E C
O A
C H
R D
S D
A Y
TO
N
A V
E
TH
A V
E
TH
A V
E
TH
A V
E
240TH ST
TH
A V
E
R
IV
E R
S
ID
E D
R
245TH ST
TH
A V
E
S A
N D
H
IL
L
TR
L
TH
A V
E
T H
A V
E
220TH ST
TH
A V
E
210TH ST
200TH STRIVERSIDE RD
OLD BLOOMINGTON RD
OLD BLOOMINGTON RD
TH
A V
E
ONEIL DR
190TH ST
G E O
R G
E W
C A
R V
E R
A V
E
CAMERON SCHOOL RD
N O
R
TH
D A
K O
TA
A
V E
215TH ST
260TH ST
245TH
ST
ARRASMITH TRL
WOODHAVEN
CIR
FLETCHER
CIRTAYLOR
CIR
DR C
O
LU
M
B I N
E
A V
E
STONE BROOKE
HEMLOCK
CIR
RD
CIR
A
SP
EN
C
IR
ALDER-
WOOD
CIR
CIR
SU
M
A C
REDBUD
CIR
R D
C
IR
CIRCIR
CIR
RD
GREENWOOD
RD
C
IR
C
IR
R D
RD
C
IR
GREENWOOD
C
IR
A V
E
REAGAN
DR
S D
A K O
TA
A
V E
D O
Y
LE
A V
E
HEMI NGWAY DR
ONTARIO
N O
R
TH
W
ESTER
N
G R
A N
D W
O O
D
D R
SQUAW
CREEKDR
S
TO
N E
H A
V
EN
D R
MAIN
B
LA
C K W
O O
D
GABLE LN G
R
A Y
A V
E
G R
A Y
A V
E
LY
N
N A
V E
A V
E A
S H
BAKER ST
DONALD ST
STORM ST
S
TA
N
TO
N A
V E
LITTLE
ST
KNAPP
HUNT ST
CHAMBERLAIN ST
ARBOR ST
WOOD ST
H A
Y W
A R D
A V
E
G A
TE
W
A Y H
IL
L S
S
TA
TE
A
V E
S K
E
LL
O G
G
S 17TH ST
S 16TH ST
S H
IG
H
A V
E
SE 16TH ST
CHESTNUT
ST
B U
C K
E Y E A
V E
AIRPORT RD
DR
SUNSET
E
GRE EL
Y
DR
L EE
FRILEY RD
B E A
C H
ST
HU
G
HE
S A G
G
G A
S K
IL
L
D R
GREENBRI AR
CIR
A V
E
C
IR
CT
ASH
A V
E
SMORTEN EN W
PK
Y
TI
M
B E R
REDOAK
WHITE
W O
O D
V
IE
W R
D
C E D
A R
MARICOPA
A
IR
PO
RT
R D
S D
U F F
A V
E
CIR
CRYSTAL ST
ST
C I R
TU
R
Q U
O
IS
E ONYX
CIR
JEWEL
DR
P L
E M
E R
A
LD
D R
DR
RD
DR
KEN MARIL RD
DR
DULUTH
ST
V
IO
LA
M
A E
A V
E
ELYD
R
C
IR
J E W
E L
D R
DIAMOND
D R
SE 16TH ST
5TH
ST
F R
E E L
D R
C A
R N
E G
IE
A
V E
A V
E
EDISON ST
FORD ST
B E
LL
A V
E
S 5TH ST SE 5TH ST
S
W
A
LN
U T
A V
E
W A
S H
IN
G
TO
N
A V
E
3RD ST
ST4TH
ST2NDS
A V
E
S U
M N
E R
A V
E
A V
E H
IG
H
SE 2ND ST
K
IN
G
SB
U R
Y
A V
E
C H
E R R
Y
A V
E
2ND ST
3RD STS
R
IV
E R
SI
D
E D
R
S
M
A P
LE
A
V E
S 4TH ST
M A
N N
IN
G
A V
E
D R
V
IL
LA
G
E
TRIPP ST
F R
A N
K
LI
N
W
IL
M O
TH
COY ST
D O
TS
O
N
D R
B E E D
LE
D
R
BAUGHMAN
RD
APLIN RD
TODD DR
WELLON'S
A V
E
A V
E
R O
C K
W E
LL
A V
E
C I R
SC
H
U
BE
R T
TH
A
C
KE
RY
TODD
DR
A
LC
O
TT
A V
E
A V
E
S A
N D
BU
R
G
C T
ST
DRF
R
O S T B
LV
D
ST
C
IR
DR
C
HEL
SE
A
C T
S O
U
TH
-WESTBEND DR
IDAHO
CIR
A V
E
DR
D E
LA
W A
R E A
V E
N D
A K
O
TA
A V
E
ROSS
RD
QUEBEC ST
J A
R R
E
TT
P H O
EN
IX
C
IR
ARI ZONA
CIR
DR
A V
E
A V
E
V E
R D
E
P
LYU
M A
Y U
M A
N
EW
H A
M P
S H
IR
E
V E R
M O
N T
TRAIL
RIDGE
DR
W
IL
D
M C
D O
N A
LD
D
R
A V
E
C R
A N
EA
V
E
W E S
TW
O O
D D
R
A V
E
CIR
C I R
O L I
V E R
A V
E
S C
H O
LL
ANNEAR
GARFIELD
CIRA
V
E
ONTARIO ST
A V
E
W
IS
C O
N S
IN
A V
E
S C
O
TT
A V
E
IO
W
A A
V E
RD
OAKLAND ST
LINCOLN WAY
H O
W A
R D
A V
E
ST
STORY
A V
E
A V
E C
IR
C O
LO
R A
D O
A V
E
ELLIS ST
ST
G
LE
N
F O
R E
ST
H A
W
TH
O R
N E
A V
E
C A
M P
U S
A V
E
A V
E H
Y
LA
N D
S H
E
LD
O N
A V
E
R U
S
SE
LL
N
A V
E
4TH ST
N
STN
A V
E H
A Z E L
N
A V
E
2ND ST
N O
A K
V E
E
LM
A V
E
LEE ST
CIR
S U
M M
IT
A
V E
W O
O D
R
ID
G E
R
ID
G
EW
O O
D A
V E
20TH ST 20TH ST
H A
Y
ES A
V E
FILLM
O
RE A
V
E
PULLMAN ST
SONDROL
V E
6TH ST
ST7TH
C
LA
R K
ST8TH W
IL
S O
N
ST
H O
D G
E A
V E
9TH
10TH
B U
R N
E
TT
K E
LL
O G
G
D O
U G
LA
S
A V
E
D U
FF
C R
A W
FO
R
D
A V
E
GILCHRIST ST
12TH ST
A V
E
11TH
A V
E
ST
A V
E
A V
E
ST
A V
E
A V
E
A V
E
13TH ST
C E N
T E R
A V
E
3RD ST
E A
S T
A V
E
A V
E
2ND
ST
A V
E
MARYLAND ST
TEXAS
CIR
KANSAS DR
K E N
TU
C
K Y
A V
E
I N
D I A
N A
A V
E
A V
E
ID
A H
O
RELIABLE
A V
E
ST
W O
O D
ST
O
C K
A V
E
ST
G E O
R G
IA
A
V E
TU
SCON
TORONTO ST
W
IN
D S O
R
C T
LN
W
IS
C O
N S
IN
A V
E
CT
S C
O
TT
R D
PINES RD
TO
R
R
EY
TORREY
CIR
PINES
GREENSBORO
DR
PIN
EHURST D
R
GREENSBORO
CIR
V
IE
W
W E
ST
V
IE
W E
A S T
PINEHURST
CIR
24TH ST
G E O
R G
E
W PIERCE
CIR
PIERC
EC
T
DR
CLEVELAND
28TH ST
JOHNSON ST
MC KINLEY
CIR
M C
M E
LR
O
SE
A
V E
F E R
N D
A
LE
A V
E
25TH ST
A V
E
TY
LE
R
N O
R
TH
W
ES
TE
R
N
C U
R
TI
SS
A
V E
R O
O
SE
V
EL
T A
V E
G R
A N
D A
V E
DURRELL
CIR
18TH ST
MURRAY DR
NARLAND
ROOSEVELT
CIR
A V
EBE
L-
A
IR
C
IR
16TH ST
B U
R N
E
TT
18TH
C
LA
R K
A V
E
23RD ST
B A
R R
D R
A V
E
24TH ST
25TH ST
A V
E
A V
E
BROADMOORCIR
21ST ST
20TH ST
17TH ST
D R
A V
E
A
LL
E N
CARRDR
E 16TH ST
M A
X W
E
LL
14TH ST
26TH ST
LU
TH
E R
28TH ST
LUTHER
G R
A N
D A
V E
K E
LL
O G
G
A V
E
DUFF AVE
B R
IG
G
S C
IR
RIVER
D R
A V
E
J O
Y
C
IR
30TH ST
G R
A N
D A
V E
N O
R
TH
W
ES
TE
R
N
A V
E
KENNEDY ST
R E G
E N
C Y
C T
TRUMAN
A V
E
CIR
JEFFERSON
CIR
ST
NIXONCIR
WHEELER ST
B U
C H
A N
A N
C T
M A
D
IS
O N
C T
STEVENSON DR
C
LI
N
TO
N
C T
M O
N R O
E
C
IR
MONROEDR
EISENHOWER
CIR
DR
BLOOMINGTON RD
BUCHANAN
A V
E
TOP-O-HOLLOW RD
BLOOMINGTON RD
ADAMS ST
D A
W
ES D
R
P E A
R
LE
ALLAN DR
JACKSON
D R
H U
N
ZI
K E
R D
R
STLETTIE
WEBSTER ST
A V
E
CIR
TUPELO
RD
GREEN
EVER
A
IR
P O
R T
D R
D R
O A
K
C O
M M
E R
C E S
T
B
LA
N
SH
A N
NEVADA
CIR
DR
DR
DOVER
HARRIS ST
DR
F
LO
W
ER
D R
CASTLE
WOOD
PL
DR
D R
ST
A V
E
A V
E
C
IR
S H
E
LD
O N
A V
E
A V
E
ST
H A
Y W
A R D
A V
E
C
LU
B
CONEFLOWER
A
SH
M O
R E
C T
A V
E
S H
E R
M A
N A
V E
A V
E
A P P
LE
P L
CIR
OAKWOOD RD
C
IR
SE
HUTCHINSON
D E
LA
W A
R
ETORONTO ST
CANTERBURY
RD
C
IR
R
ID
G
ET
O P
MAPLEWOOD
LINDENWOOD
PKWY
S O
U
TH
R
ID
G E
N O
R
TH
R
ID
G E
V
IE
W
VA
LL
EY
VIE
W
SYCAMORE RD
ASPEN
BALSAM
A V
E
A V
E
N
IX
O N
A V
E
PARK
WAY
DR
R D
ID
A H O
AVE
M E
SA
ST
A V
E
AVE
C R
E S
TW
O O
D
C T
POLK DR
STE
V
E N
S O
N
E
IS
E N
H O
W E
E
TA
FT
R O
Y K
E Y
A V
E
S
IN
C
LA
IR
RAPHAEL
WESTBEND
CIR
CIR
LN
C
IRC
IR
CIR
TWAIN ST
BAYBERRY
RD
ORI ON
D R
DR
A V
E
HUNT ST
J E N
SE
N
ST
C A
LH
O
U N
A V
E
R
ID
G E
TO
P
D R
CIR
ARROWWOOD
M A
G N
O
LI
A
C
IR
R D
DR
CIR
GRANT
PKWY
NORTHRIDGE
DR
DR
S
TA
N G
E R
D
CHESTER
DR
S O
M E R
SE
T
D R
KEN
T A
V E
C T
M E A
D O
W
LA
N E A
V E
S K
E
LL
O G
G A
V E
S S
H E R
M A
N A
V E
N M
A P
LE
N R
IV
E R
SI
D
E D
R
IO
W
A C
IR
VISIONAIRE PL
KDALE
R O
Y K
E Y
A V
E
ST
JE
W
EL
L
C
IR
E
LINCOLN WAY
3RD ST
DR
6TH ST
E 20TH ST
OPAL CIR
G O
LD
E N
R O
D
SHERWOOD
AVE
B
LV
D
C I R
S A
P P
H
IR
E
D
IC
K
IN
SO
N
CT
WATERBURY
CIR
A V
E
BALTIMORE DR
B O
S
TO
N A
V E
B R
IA
R
W O
O D
B U
C H A
N A
N
D R
M A
R K
E T
S T
C I R
C
IR
C
IR
C
IR
C
IR
RD
SUNDOWN
DR
H Y
D E A
V E
V A
LL
E Y
V
IE
W R
D
PRESTON CIR
H O
O V
E R
A V
E
PANORAMIC
CT
LA
U
R A
C T
KINGSTON DR
CLAYTON DR
TENNESSEE
ST
MARIGOLD DR
D R
S U
N F
LO
W E R
T E N
N Y
SO
N
A V
E KEATS ST
WALLER ST
ST
STEINBECK
DR
S R
IV
E R
SI
D
E D
R
SE 18TH ST
B U
R
EN
A V
E
A V
E
A
LE
X A
N D
E R
GRAHAM
ST
W H
IT
N
E Y
A
WATT ST
M c
C O
R M
IC
K
A V
E
PHILADELPHIA ST
E A
S
TG
A
TE
D R
PLYMOUTH
DR
BILLY SUNDAY RD
KITTY HAWK DR
TEAGARDEN
GARDEN
O P
A L
D R
PATRICIA
G A
R N
ET
MEADOW
CRYSTAL ST
RUBY
CT
ONYX
S T
S R
IV
E R
SI
D
E D
R
W H
IT
E
BURR OAK
DR
M
IL
LE
R
A V
E
C T
B R
O W
N
CLEMENS BLVD
S M
IL
E Y A
V E
S
TA
TE
A
V E
TO
D
D C
IR
A B
R A
H A
M D
R
J E F
FE
R Y L
N
H
IL
L
TO
P R
D
ST
P A
R K
D R
E M
CT
C T
A
SH
M O
R E
B E A
C H
S 4TH ST
BLVD
K I D
A V
E
W E
LC
H
PEACH LN
A V
E B
O R
N E
B E N
D D
R
C
IR
U
TA
H
DR V
E R
M O
N T
C T
O K
LA
H
O M
A
ST
D R
M A
R S H
A
LL
STORY ST
WEST ST
MARY
C O
LO
R
A D
O
H
IL
L C
R E S T
P L
CIR
O N
TA
R
IO
C
IR
Q U
E BE
C
G A
R
FI
E
LD
ROSS
M
IC
H
IG
A N
A V
E
13TH ST
M A
R S
TO
N A
V E
H A
R D
IN
G
A V
E
C
RESC
ENT
C O
O
LID
G E
DR
A R
TH
U
R C
IR
D R
BEL-AIR
DRHUN
ZIK
ER
C
IR
FURMAN
K
IN
LE
Y
CT
24TH ST
26TH ST
H O
O V
E R
PIERC
E
DR
TRUMAN DR
WHEELER DR
H O
O V
E
E
EISEN
H
O W
E R A
V E
TA
FT
P L
JEFFERSON
A V
E
P O
LA
R
IS
WHEELER ST
F R A
N C
I S E
D A
V
IS
C T
EDGEWATER
CT
F
LE
TC
H
E R
CIR
DR
BRO
O CIR
D R
W
ELBEC
K
YORKSHIRE ST
ASPEN
HAMPTON
ST
E A
TO
N
A V
E
B R
A D
FO
R
D D
R
AVE
BUCKINGHAM
PARK VISTA
CIR
V A
LL
EY
C
YR
ES
S
C
IR
V
IE
WC
IR
D E S M
O
IN
E S
A V
E
ST5TH
C A
R R
O
LL
15TH ST
A V
E
G
LE
N D
A
LE
A V
E
LI
N
D E N
D R
ST
K E
LL
O G
G
B U
R N
E
TT
22ND
E 24TH ST
D R
KELLOGG AVE
N O
R
TH
W O
O D
G R
O V
E
OAK DR
YORKSHIRE
CIR
RD
A V
E
P R
A
IR
IE
P R
A
IR
IE
DR
D O
U G
LA
S
A V
E
A V
E
A V
E
E
S
S
SE
S
S
SE 5TH ST
CT
N
S
S
TA
TE
A
V E
A V
E
MC CARTHY RD
ST
ST
H Y
LA
N
D
S
S A
V E
S W
IL
M
O
TH
A V
E
S F R
A N
K
LI
N A
V E
S H
E
LL
E Y
A V
E
N
PHOENIX
ST
C A
LI
F O
R N
IA
A
V E
C
LI
N
TO
N A
V E
DR
B R
ID
G
E P
O R
T
DR
W E M
B
LE
Y A
V E
K E N
T A
V E
M A
Y F
IE
LD
D
R
W A
LT
O
N D
R
S E A
G R
A V
E B
LV
D
H A
R
TF
O R
D D
R
DURANT ST
STOCKBURY ST
SEDWICK ST V
A
L
LE
Y V
I EW
I
LL
I N
O
IS
A V
E
DALTON ST B
U C
H A
N A N
BU
C
H A
N A
NC
IR
C
IR
NORRIS
RD
ROXBORO
DR
R D
V A
N
G R
A N
T A
V E
A V E
S
D
A Y
TO
N
A V
E
A V
E S
H
A Z E L
S
R
U S
SE
LL
S
M
A P
LE
S
O
A K
A V
E
A V
E
A V
E
DR
R I D G E T O P
B R O O K D A L E
B R O A D M O O R
DR
S
TA
F
FO
R D
N O R T H R I D G
E LN
U N
IV
E R
SI
TY
B L V
D
HA
RR ISON CIR
SOUTHERN
HILLS RD
R E D
F O
X R
D
W H
IT
E
TA
IL
L
N
C O
TT
O
N
TA
IL
LN
RD
COTTO
NWOOD
M O
O R
DARTMOOR LN
D A
R T-
MOORDART
D R
W E
LL
O N
'S D
R
B E
LL
F
LO
W E R
D R
WESTON DR
R D
D R
SO
U
TH
D
A
LE
S D
A Y
TO
N
A V
E
C R E
STM
O O
R A
V E
B A Y
BER
RY
C
IR
M I N
N E S O
T A
MORNINGSIDE
E 14TH ST
E 13TH ST
E 12TH ST
E 11TH ST
E 9TH ST
E 7TH ST
E 6TH ST
E 5TH ST
3RD
OAK CIR
C
IR
A
LB
E R
TA
A V
E
COCHRANE PKWY
W
IL
D E R
A V
E
W
ESTFIELD
RD
YO R K
D R
C A
M
BRIDGE DR
O X
FO
R D
A V
E
SH
E
FF
IE
LD
A V
E
PI
C
A D
IL
LY
S Q
C U
LL
E N
DR
TIV
ER
TO
N
C T
S B
E
LL
A V
E S B
E
LL
A V
E
WAKEFIELD CIR
HYATT CIR
S
Y
TO
N P
L
TIMBER RI D
G
E D
R
Q U
A M
C
IR
A
IR
P O
R T
C T
D O
TS
O
N D
R
SPRINGBROO
K
DR
C H
A M
B E R
LA
IN
P L
ASPEN RIDGE RD
E MAIN ST
E 8TH ST
M
IN
N E
TO
N K
A
G A
RDEN
RD
W
IL
LO
W
BRO
O
K
H A
R C
O U
R T
DIA
M
O N
D
TOPAZ
F R
O N
T A G
E R D
O P
LO
LO
O P
SUNCREST RD
LA
N
D R
D
IRONWOOD
C T
ISAAC NEW
TO
N
GRAEBER
P E A
R S O
N A
V E
LITTLE
TEM
BLUES
B
IG
B
LU
E
ASHMORE
GRASSAN
CTIN
DI
P O
E A
V E
P O
E
C O
C O
N
IN
O
THACKERY
CERVANTES
CLEMENS BLVD
LINCOLN SWING
B R
O O
K R
ID
G
E
R I D
G
EW
O O
D A
V E
TH
O
M P S O
N D
R
MC KINLEY
FERNDALE
KINGM
AN
AMHERST DR
ARIZONA
A R
KA
N
SA
S
ARKANSAS
A
LA
B
AM
A
F
LO
R
ID
A
N O
RTH
BR
O O
K
P A
R K
R
ID
G
E HIC
KO
RY
TR
A
IL
R
ID
G
E R
D
WESTBRO
O
K
O
LI
V E R
WOODLAND
BRISTOL
CAMDEN
C A
RV
E R
ROSEWOOD
MAPLEWOOD
N O
R
TH
R
ID
G E
VALL
EY
EVERGREEN
HONEY
S U
C K L E
BURNHAM
ALMOND RD
FOXLEY DR
HARRISON
LAUREL ST
B R
IC
K M
A N
W
ES
TL
A
W N
H Y
D E
A V E
B E R
KS
H
IR
E
WYNGATE
STO
N
E
E
IS
E
NH
O W
E R
KINYON CIR
TA
BO
R
DR
N
EB
R A
SK
A
MORTENSEN RD
CESSNA ST
SCHUBERT
W
ILD
E R
ID
A
HO
C T
ARTHUR DR
G A
RN
E R
H A
R R
IS
O N
RD
BROOKE
WINDFIELD
EMERSON
COUN
TR
Y
AVE
O
RC
HA
RD
CARROLL
O'NEAL
MAXW
ELL
SON
P A
UL
G E O
R G
E
H A
S
TIN
G S
A V
E
G R
A Y
H A
W K
D R
STANGE
RD
BECKLEY ST
A S P
E N
D R
LD
E N
G O
ALLERTON DR
G R
A N
D A
V E
FOREST
HILLS
DR
C O
YOTE DR
COY ST
MISSOURI ST
MILSTEAD
RD
B A
LLEN
TIN
E D
R
DANBURY
R D
C
IR
B R
IG
H
TO
N
UNIVERSITY BLVD
IR
O
N W
O O
D
C R
E E K
S
ID
E
F O
U N
TA
IN
V
IE
W
LAKEVIEW
LN
COOPERBACH
FAULKNER
P
IN
O N
D R
IV
E (P
R
HAMILTON DRIVE (PR)
HAMILTON CT
(PR)
PL (PR)
C A
R D
IN
A
L R
D
ORIOLE ST
W R
E N
A V
E
LA
R
K A
V E
ROBIN ST
FINCH ST
KEN MARIL RD (PR)
BRECKINRIDGE
CT
HEATHROW DR
T U R
N B E R
R Y
C T
C T
C H
A R
L O
TT
E
DR
W E S
SE
X
R H A
V
EN
RD
B R
I A
A S H
TO
N
D R
FARNHAM DR
LAKESIDE DR
B R
IT
IS
H
BARKLEY
CT
WESTWIND DR
W O
R
LE
L N
DR (PR)
FLETCHER CT (PR)
MEADOW GLEN RD (PR)
C O
LU
M
B
IA
A V
E (P
R
(PR)
MEADOW
CT
Walls
Earth
Granular Fill
Sand, Mortar
Concrete
Concrete Block
Brick
Stone
Aluminum
Steel
Bronze
Wood
Structural
Blocking
Particle Board
Plywood
Glass
Batt Insulation
Rigid
Insulation Tile
Plastic Laminate
Gypsum Board
Plaster
Acoustic Tile
Terrazzo
Metal Stud
Wood Stud
2 8
1 6
Index to Drawings
ARCHITECTURAL
Material Symbols x
A4.0
A7.0
A4.4
A4.2
XXX
X
Plan Detail
Detail
Wall Section Revision No.X
Room Name/No.
Wall Type
Door Number
Column Grid
Floor Line
Test Bore
Building Section
XX
XX.X
Drawing Number
Sheet Call Out
Site Access Map
Abbreviation Key
Certification
Graphic Symbols
MECHANICAL/ELECTRICAL/PLUMBING
General Notes
1i
Casework Tag
D00 Demolition Note
0 Equipment Tag
0 Material Key Tag
Toilet Accessory
Key Tag
N North Arrow
1i Plumbing Fixture Tag
RAILING
'A'
Railing Tag
1t Window Tag
Name 101
Room Tag w/ Occ.
Load
PROJECT
LOCATION
PAMMEL DR
OSBORN DR
B
IS
S E
LL
R D
S T A N G
E R
D
N UNIVERSITY BLVD
TASF
Vicinity Map Legend
PROJECT SITE LOCATION
CONTRACTOR PARKING AREA
CONTRACTOR TO PURCHASE PARKING PASSES AND
UTILIZE HIGHLIGHTED LOTLOT 29
LOT 29
Vicinity Map Enlarged Campus Map
1. Prior to excavation and site planting on the job site, the contractor shall contact utility companies to locate underground utilities effecting the excavations and planting on the job site. Excavation shall not proceed until all utilities are located and indicated. The contractor shall maintain the identifying devices throughout the duration of the project.
2. The contractor shall comply with 10 CFR 851.C rules and regulations throughout the construction activities on the project. None of the work contemplated in the construction documents shall be construed as being in conflict with applicable 10 CFR 851.C rules and regulations.
3. Contractors shall verify all dimensions and conditions effecting the work shown on the contract documents. Any conflicts found shall be reported to the Architect before proceeding with the work.
4. During the process of work, all penetrations through walls, ceilings, and floors will require a permit to be filed to ensure that radiation scanning can be completed prior to work commencing.
5. All LOTO and electrical shutdowns will need to be communicated to the owner with ample amount of time for building wide notification that will need to be scheduled.
See table for required timelines.
6. Every member of the construction crew will be required to be registered through
TASF and have possession of a badge while on site.
7. All construction crew members must complete an Ames Lab site and safety orientation before beginning work.
8. Verify all legacy hazardous material in scope of work with Ames Lab ESH, including asbestos, radiation contamination, and beryllium contamination before work begins.
GENERAL SCHEDULING REQUIREMENTS
• NORMAL HOURS OF OPERATION ARE 7:30 AM TO 4:30 PM,
MONDAY THROUGH FRIDAY.
• NOTIFY OWNER NOT LESS THAN THE FOLLOWING IN ADVANCE
OF ACTIVITIES THAT WILL AFFECT OWNER'S OPERATIONS:
1. NO LESS THAN TWO (2) MONTHS AHEAD OF
SCHEDULED ACTIVITY, PROVIDE ACCURACRY WITHIN
ONE (1) WEEK.
2. NO LESS THAT TWO (2) WEEKS AHEAD OF SCHEDULED
ACTIVITY, PROVIDE ACCURACT WITHIN ONE (1) DAY.
• FIRE SUPPRESSION SHUTDOWN
1. ALLOWABLE SHUTDOWN DURING NORMAL WORKING
HOURS
2. MAXIMUM CONTINUOUS DURATION = 8 HOURS
• MECHANICAL EXHAUST SHUTDOWN
1. ALLOWABLE SHUTDOWN DURING NORMAL WORKING
HOURS
2. MAXIMUM CONTINUOUS DURATION = 4 HOURS
• PENETRATION PERMIT
• 10-15 DAYS FOR APPROVAL
• NON-CITIZEN WORKER REVIEW PROCESS
• 45 DAYS FOR REVIEW/APPROVAL
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERONSAL
SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.
CLINTON ROGER RABE, PE
REG. NO. DATE:
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026
PAGES OR SHEETS COVERED BY THIS SEAL:
P19481
ALL MECHANICAL AND PLUMBING SHEETS
L
IC
E N S E
D
PR
OFE
SS IONAL
E
N G I N E E R
O WI A
CLINTON
ROGER
RABE
P19481
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERONSAL
SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL
ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.
TIMOTHY A. HILTON, P.E.
REG. NO. DATE:
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026
PAGES OR SHEETS COVERED BY THIS SEAL:
P19392
ALL MECHANICAL AND PLUMBING SHEETS
L
IC
E N S E
D
PR
OFE
SS IONAL
E
N G I N E E R
O WI A
TIMOTHY
A
HILTON
P19392
Consultant
Revision Record
Print Record
Project Number
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
SC-27-723 - AMES NATIONAL LABORATORY HAZARDOUS & FLAMMABLE GAS CABINET INSTALLATION
METALS DEVELOPMENT
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
METALS DEVELOPMENT
11/16/2026ISSUE SET
25011
A0.0
TITLE SHEET
11/16/2026
2415 PAMMEL DR., AMES, IA 50011
Jeffrey S. Harris Date License number: 3594 My license renewal date is: June 30, 2028 Pages or sheets covered by this seal:
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly licensed architect under the laws of the state of Iowa.
A0.0
A2.0
A2.1
IOWA
A R
E
J E
F
F
HSY .
R
S R
I
CH
N
IC
E
DES
A R
E
TI
C
L
T
AL,ALUM ALUMINUM
AT ACOUSTICAL CEILING TILE
BLDG BUILDING
BLK BLOCK (CONCRETE)
BRK BRICK
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTER LINE
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONC/S SEALED CONCRETE
CONV CONVENIENCE
CPT CARPET
CT CERAMIC TILE
DN DOWN
DTL DETAIL
EJ,EXP JT EXPANSION JOINT
EXT EXTERIOR
FC FOAM CORE
FGT FIBERGLASS CEILING TILE
FGW FIBERGLASS WALL TILE
FT FOOT, FEET
GALV GALVANIZED
GB,GYP BD, GWB GYPSUM WALLBOARD
GR GRANITE
GYP GYPSUM
HDW HARDWARE
HM HOLLOW METAL
IG INSULATED GLASS
INSUL INSULATION, INSULATED
ISG INSULATING SAFETY GLASS
LH LEFT HAND
MIN MINIMUM
MTL, MET METAL
NIC NOT IN CONTRACT
NOM NOMINAL
A2.2
A2.3
A2.4
NTS NOT TO SCALE
O.C. ON CENTER
P LAM PLASTIC LAMINATE
PART BD PARTICLE BOARD
PC PRECAST CONCRETE
PLYWD PLYWOOD
R RISER,RADIUS
RH RIGHT HAND
RSR RUBBER STAIR RISER
RST RUBBER STAIR TREAD
SC SOLID CORE
SCH SCHEDULE
SFP SPRAYED FIRE PROTECTION
SG SAFETY GLASS
SG SPANDREL GLASS
SH STEEL
SIM SIMILAR
SK SINK
SND SANITARY NAPKIN DISPOSAL
SOG SLAB ON GRADE
SPEC SPECIFICATIONS, SPECIFIED
SS, ST STL STAINLESS STEEL
SVF SHEET VINYL FLOORING
THRE'D THRESHOLD
TR TREAD
TYP TYPICAL
UR URINAL
VB VINYL BASE
VF VINYL WALL FABRIC
VP VENEER PLASTIC
VT VINYL TILE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WG WIRE GLASS
A0.0 TITLE SHEET
A2.0 BASEMENT FLOOR PLAN
A2.1 FIRST FLOOR PLAN
A2.2 SECOND FLOOR PLAN
A2.3 ENLARGED ROOM PLANS - 160A - 147 -
A2.4 ENLARGED ROOM PLANS - 150C - 187 -
E0.0 ELECTRICAL SYMBOL LEGEND
E0.1 ELECTRICAL PROJECT NOTES AND
ABBREVIATIONS
E0.2 ELECTRICAL PROJECT NOTES
E0.3 ELECTRICAL PROJECT SCHEDULES
E2.1 FIRST FLOOR ELECTRICAL PLAN
E2.2 SECOND FLOOR ELECTRICAL PLAN
E2.3 ENLARGED ELECTRICAL PLANS
FP0.0 FIRE SUPPRESSION SYMBOLS AND
ABBREVIATIONS
FP1.1 FIRST FLOOR FIRE SUPPRESSION PLAN
FP1.2 SECOND FLOOR FIRE SUPPRESSION PLAN
FP7.0 FIRE PROTECTION DETAILS & SCHEDULES
M0.0 HVAC SYMBOLS AND ABBREVIATIONS
M2.0 BASEMENT MECHANICAL PIPING PLAN
M2.1 FIRST FLOOR MECHANICAL PLAN
M2.2 SECOND FLOOR MECHANICAL PLAN
M2.3 ENLARGED MECHANICAL PLANS - 160A -
147 - 130
M2.4 ENLARGED MECHANCIAL PLANS - 150C -
M6.0 RISER DIAGRAM - AIR
M7.0 MECHANICAL DETAILS
M8.0 MECHANICAL SCHEDULES
EL. EQUIP BE19
LOBBY BE17
CORRIDOR BB18MECH ROOM BB16
MECH BD17
PIPE TUNNEL PIPE TUNNEL
P
IP
E T
U N N E L
NOT EXCAVATED
NOT EXCAVATED
NOT EXCAVATED
NOT EXCAVATED
NOT EXCAVATED
NOT EXCAVATED
NOT EXCAVATED
NOT EXCAVATED
TUNNEL
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
METALS DEVELOPMENT
A2.0
BASEMENT FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2415 PAMMEL DR., AMES, IA 50011
N1/8" = 1'-0"1
BASEMENT FLOOR PLAN
UP
158I158H158G158F158E158D158C158B
158N 158M 158J
157A
Room 147
150B
Room 150C
160D
160C
A2.3
Sim
A2.3
Sim
A2.4
Sim
A2.3
Sim
A2.4
Sim
160B ROOM 160A
162A162163164
167C 167B
167A167
167D
ROOM 187
189190192
104105106107108109
111A
111B 111C
Room 130
120121122124125126 123128
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
METALS DEVELOPMENT
A2.1
FIRST FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2415 PAMMEL DR., AMES, IA 50011
1ST FLOOR PLAN
Room 220221222223
224B
225227228
STAIR204205206208209211211A
STAIR
HALL
BB55
BB56
BB57
BB58
BB59
BB60
210 207
228A
STAIR
A2.4
Sim
ROOF BELOW
132133134135136
137138139140
142 143 144
145 146 148
150151
OPEN
156 157
158159160161
Room 173
Room 174
179180
181 182
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
METALS DEVELOPMENT
A2.2
SECOND FLOOR PLAN
11/16/2026ISSUE SET
11/16/2026
25011
2415 PAMMEL DR., AMES, IA 50011
2ND FLOOR PLAN
MC
MC
COUNTER
W/ O.H.
CABINETS
TABLE
W/ O.H.
CABINETS
EP
MC
EP
EP
C O
U N
T E R
SHELF
16' - 5''
DECK
16' - 0"
BEAMS
EP
Room 130
DEMO
PORTION OF
COUNTER
THERMOSTAT AND
OUTLETS TO
BE RELOCATED
EXSTG DBL GAS CAB. W/ EXHAUST; NEED SPRINKLER
NOTE: FIELD MEASUREMENTS
UNATTAINED DUE TO AUTHORIZED
PERSONEL ACCESS AND
HAZARDOUS MATERIALS PRESENT
SPACING AND SIZING APPROX.
HYDROFLUOR.
SYSTEM
S H
E
LF
TABLE
EH
MC
MC
TABLE/WORK
BENCH
Room 147
RESTRICTED ACCESS AREA
NO ENTRY WITHOUT PRIOR TRAINING
AND NOTIFICATION TO OWNER
23' - 10 1/2"
DECK
T A B
LE
MC
MC
COUNTER W/ O.H. CABINETS
CABINET
160A
EB
MOVE J-BOXES FOR VFD, AND
REROUTE VFD CONDUIT AROUND
CABINET. MOUNT CABINET TO
RECEPTACLE CONDUIT.
ROOM 160A
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
NEW WORK NOTES
1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED
AND PAINTED FOR FINAL FINISH.
2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH
MANUFACTURER'S STANDARD INSTALLATION
INSTRUCTIONS.
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
METALS DEVELOPMENT
A2.3
ENLARGED ROOM PLANS - 160A -
147 - 130
11/16/2026ISSUE SET
11/16/2026
25011
2415 PAMMEL DR., AMES, IA 50011
N1/4" = 1'-0"1
1ST FLOOR ROOM 130 - ALTERNATE # 5
N1/4" = 1'-0"3
1ST FLOOR ROOM 147 - BASE BID
N1/4" = 1'-0"5
1ST FLOOR ROOM 160A - ALTERNATE #5
GAS CABINET SCHEDULE
MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS
130 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
147 DOUBLE HAZARDOUS EXISTING YES YES ETR
150C DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
160A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
187 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
220 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
1" = 1'-0"6
160 EXISTING IMAGES
1" = 1'-0"2
130 EXISTING IMAGES
1" = 1'-0"4
147 EXISTING IMAGES
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO COUNTER
11' - 7" DECK
10' - 6" BEAM
EP
MC
MC
TABLE
MISC. TABLES, MC, CABINETS, SHELVES
SHELF
T A B
LE
C A B
Room 150C150C
COUNTER
TOOL
BOX
MC
EP
MCMC
EP
GLOVE
BOX
COUNTER W/ O.H. CABINETS
MCMC
MC
COUNTER
W/ O.H.
CABINETS
SINK
TABLE
MC
MC
MC
MC
MC
S H E
LF
ROOM 187
11' - 1" DECK
9' - 10 1/2"
BEAM
MC
TABLE GLOVE BOX
TABLE
TABLES
H E
LF
COUNTER WITH
O.H. CABINETS
SINK
TABLE
W/ FH
SHELF
MC
MC
Room 220
GENERAL NOTES
1. EXISTING CONDITION DRAWINGS WERE COMPILED FROM
CONSTRUCTION DRAWINGS PROVIDED BY THE OWNER
AND ARE NOT INTENDED TO SHOW EVERY EXISTING
CONDITION. CONTRACTOR SHOULD VERIFY ALL SITE
CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING.
EXISTING BUILDING DRAWINGS ARE AVAILABLE AT THE
ARCHITECTS OFFICE FOR REVIEW.
2. REMOVE ALL EXISTING WALLS, DOOR FRAMES, DOORS,
AND MILLWORK WHERE REQUIRED. VERIFY SALVAGE
RIGHTS WITH OWNER.
3. REMOVE ALL EXISTING CEILINGS WHERE NEW CEILINGS
ARE INDICATED ON CEILING PLANS.
4. REMOVE ALL EXISTING LIGHT FIXTURES, SURFACE AND
RECESSED CONDUIT AND WIRING, WALL SWITCHES AND
OUTLETS, VOICE/DATAOUTLETS AND WIRING, CIRCUIT
BOXES, & FLOOR BOXES THAT WOULD EXIST IN A
DORMANT STATE UPON COMPLETION OF THE PROJECT.
REMOVE ALL WIRING AND CONDUIT BACK TO CIRCUIT
PANEL OR PHONE PANEL LEAVING NO DORMANT WIRE.
(SEE FLOOR PLAN FOR DETAILS)VERIFY SALVAGE
RIGHTS WITH OWNER.
5. REMOVE ALL EXISTING PLUMBING FIXTURES, PLUMBING
SOIL AND VENT STACKS, FLOOR DRAINS, AREA DRAINS,
AND ANY EXTRANEOUS PLUMBING THAT WOULD EXIST IN
A DORMANT STATE AT THE COMPLETION OF THE
PROJECT. (SEE PLANS FOR DETAILS) VERIFY SALVAGE
RIGHTS WITH OWNER.
6. REMOVE EXISTING MECHANICAL EQUIPMENT, EXHAUST
AND SUPPLY DUCTING AND PIPING NOT REQUIRED BY
THE NEW CONSTRUCTION, AND ANY EXTRANEOUS
MECHANICAL ITEMS THAT WOULD EXIST IN A DORMANT
STATE AT THE COMPLETION OF THE PROJECT.
7. PREPARE WALLS TO REMAIN FOR REQUIRED FINISH.
8. REMOVE AND REINSTALL AT COMPLETION OF PROJECT
ALL CEILING AND WALL MOUNTED ACCESSORIES
INCLUDING SIGNAGE,ELECTRICAL DEVICES, ART WORK,
AND MISCELLANEOUS ITEMS.
NEW WORK NOTES
1. ALL NEW DUCTWORK AND CONDUIT TO BE PREPPED
AND PAINTED FOR FINAL FINISH.
2. ALL CABINET MOUNTING DETAILS TO COORDINATE WITH
MANUFACTURER'S STANDARD INSTALLATION
INSTRUCTIONS.
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION
METALS DEVELOPMENT
A2.4
ENLARGED ROOM PLANS - 150C -
187 - 220
11/16/2026ISSUE SET
11/16/2026
25011
2415 PAMMEL DR., AMES, IA 50011
GAS CABINET SCHEDULE
MARK CAPACITY HZRD LEVEL PHASE SPRINKLER EXHAUST DIMENSIONS REMARKS
130 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
147 DOUBLE HAZARDOUS EXISTING YES YES ETR
150C DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
160A DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
187 SINGLE FLAMMABLE NEW NO YES 18"W x 19"D x 75"H
220 DOUBLE FLAMMABLE NEW NO YES 24"W x 19"D x 75"H
N1/4" = 1'-0"1
1ST FLOOR ROOM 150C - ALTERNATE #5
1" = 1'-0"2
150C EXISTING IMAGES
N1/4" = 1'-0"3
1ST FLOOR ROOM 187 - ALTERNATE #5
1" = 1'-0"4
187 EXISTING IMAGES
N1/4" = 1'-0"5
2ND FLOOR ROOM 220 - ALTERNATE #6
N1" = 1'-0"6
220 EXISTING IMAGES
DEMOLITION ITEMS
D01 EXIST'G TO REMAIN
D02 DEMO COUNTER
APPLICABLE CODES:
A. 2024 INTERNATIONAL BUILDING CODE (IBC)
B. 2024 INTERNATIONAL FIRE CODE (IFC)
C. 2024 INTERNATIONAL PLUMBING CODE (IPC)
D. 2024 INTERNATIONAL MECHANICAL CODE (IMC)
E. 2024 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
(E)
2"
2"
4"
4"
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN
THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
Room
INVERT: -105' - 1"
1/8" / 12" SLOPE
FIRE PROTECTION SYMBOLS
OBSTRUCTION FROM DUCTWORK 48"
AND GREATER
FP-DOM-W
FP-W
FP-PA
FP-O
FP-D
FIRE PROTECTION OTHER
FIRE PROTECTION DRY
FIRE PROTECTION PRE-ACTION
FIRE PROTECTION WET
COMBINATION FIRE & DOMESTIC
48"x18" SA
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWCELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPMGALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWRPOWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWHELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
UPRIGHT SPRINKLER HEAD
PENDENT SPRINKLER HEAD
'D' REPRESENTS DRY SPRINKLER HEAD
CAP
PLUG
SIDEWALL SPRINKLER HEAD
EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD
RECESSED SPRINKLER HEAD
CONCEALED SPRINKLER HEAD
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
SHUTOFF BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
S
SECTION VIEW
ELEVATION VIEW
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
RESOURCE CONSULTING ENGINEERS, L.L.C.
301 ALEXANDER AVE, SUITE C
AMES, IA
515-292-2500
FP0.0
FIRE SUPPRESSION SYMBOLS
AND ABBREVIATIONS
11/16/2026ISSUE SET
11/16/2026
2025.014.00
2415 PAMMEL DR., AMES, IA 50011
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION - METALS
DEVELOPMENT
N O 3 4 5 6 7 8 9 10 11 12 13 14
L
M
C
D
E
F
G
H
I
J
K
Space
Space
Space
Space
150B
Space
Space
Space
Space
Space
Space
128 Space
Space
Space
Space
123 Space
Space
121 Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
111B
Space
111A
Space
Space
Space
Space
167C Space
167B
Space
Space
Space
Space
160B
Space
160C
Space
160D
Space
Space
158B
Space
158C
Space
158D
Space
158E
Space
158F
Space
158G
Space
158H
Space
158I Space
Space
158J
Space
158L
Space
158M
Space
158L
Space
150C
Space
150C
Space
Space
Space
1 1/2" FP-W (E)
1 1/2" FP-W (E) 1 1/2" FP-W (E)1 1/2" FP-W (E)
3" FP-W (E)
3" FP-W (E)
8" FP-W UP (E)
Space
1 1/2" FP-W
3" FP-W (E)
1 1/2" FP-W (E)
1 1/2" FP-W (E)
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
RESOURCE CONSULTING ENGINEERS, L.L.C.
301 ALEXANDER AVE, SUITE C
AMES, IA
515-292-2500
FP1.1
FIRST FLOOR FIRE SUPPRESSION
PLAN
11/16/2026ISSUE SET
11/16/2026
2025.014.00
2415 PAMMEL DR., AMES, IA 50011
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION - METALS
DEVELOPMENT
AUTOMATIC SPRINKLER SYSTEM DESIGN CRITERIA
SYMBOL
OCCUPANCY HAZARD
CLASSIFICATION
DESIGN DENSITY
(GPM/SF) DESIGN AREA
LH LIGHT HAZARD
OCCUPANCY
0.10 1500 SF
OH1 ORDINARY HAZARD,
GROUP 1 OCCUPANCY
0.15 1500 SF
OH2 ORDINARY HAZARD,
GROUP 2 OCCUPANCY
0.20 1500 SF
N
1/8" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN
FIRE PROTECTION GENERAL NOTES
A PROVIDE ALTERATIONS TO THE EXISTING FIRE PROTECTION SYSTEM AS REQUIRED TO
ACCOMMODATE THE NEW SAFETY CABINETS. PROVIDE A COMPLETE WET TYPE SYSTEM
INCLUDING NEW MAINS, BRANCHES, HEADS, VALVES, AND ACCESSORIES AS REQUIRED.
REUSE EXISTING SYSTEM EQUIPMENT WHERE APPLICABLE. THE SYSTEM SHALL BE
INSTALLED ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS
AND AS PER REQUIREMENTS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT, AND
ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, AND NFPA.
B THE BUILDINGS COMPLETE OPERATIONAL FIRE PROTECTION SYSTEMS SHALL REMAIN IN
PLACE. CONTRACTOR SHALL REPAIR ANY DAMAGE TO SYSTEM CREATED BY THE REMOVAL
OF ANY OTHER MECHANICAL SYSTEMS OR COMPONENTS.
C CONTRACTOR SHALL COORDINATE PHASING OF SPRINKLER WORK WITH THE GENERAL
CONTRACTOR PRIOR TO STARTING WORK.
D PROVIDE A COMPLETE WET TYPE FIRE PROTECTION SYSTEM AS REQUIRED TO
ACCOMMODATE THE FLOOR PLAN AND CEILING TYPES INCLUDING MAINS, BRANCHES,
HEADS, VALVES, AND ACCESSORIES AS REQUIRED. THE SYSTEM SHALL BE INSTALLED
ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS OF THE STATE
BUILDING CODE, LOCAL FIRE DEPARTMENT, AND ALL FEDERAL, STATE, AND LOCAL
AUTHORITIES, NFPA, AND FACTORY MUTUAL.
E THE SPRINKLER SYSTEM SHALL BE DESIGNED BASED UPON ACTUAL WATER FLOW TEST
DATA OBTAINED AT OR NEAR THE JOB SITE.
F REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION REGARDING
SPRINKLER HEAD LOCATION AND PIPE, UNLESS NOTED OTHERWISE.
G COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR PROPER INSTALLATION OF THE FIRE
PROTECTION SYSTEMS ALARM DEVICES INVOLVED WITH FIRE SPRINKLER SYSTEM.
H ALL SPRINKLER SYSTEM PIPING SHALL BE CONCEALED ABOVE THE SUSPENDED CEILING
SYSTEM, UNLESS NOTED OTHERWISE. WRITTEN AUTHORIZATION SHALL BE OBTAINED FROM
THE ARCHITECT PRIOR TO EXPOSING ANY PIPING IN ANY ROOM WHICH HAS A SUSPENDED
CEILING.
J CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SPRINKLER HEADS AS REQUIRED TO
ENSURE AN APPROVED FIRE PROTECTION SYSTEM AT NO ADDITIONAL COST TO THE OWNER.
K AUXILIARY DRAINS SHALL BE EXPOSED WITH 1" DRAIN VALVES. WHEN 5 OR MORE GALLONS
ARE TRAPPED, CONTRACTOR SHALL PROVIDE FIXED PIPING TO AN ADEQUATELY SIZED
RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW OF THE DRAIN. WHEN LESS
THAN 5 GALLONS ARE TRAPPED, A HOSE BIB SHALL BE PROVIDED AT THE DRAIN VALVE.
L AUXILIARY DRAINS SHALL NOT BE LOCATED ABOVE PLASTER OR GYPSUM BOARD CEILING
SYSTEMS.
M AN INSPECTOR'S TEST CONNECTION SHALL BE PROVIDED FOR EACH FIRE SPRINKLER ZONE.
CONTRACTOR SHALL PROVIDE FIXED PIPING FROM THE TEST CONNECTION TO AN
ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW OF THE
TEST. EXTERIOR DISCHARGE OF THE TEST CONNECTION SHALL BE PERMITTED ONLY BY
SPECIFIC WRITTEN INSTRUCTION FROM THE ENGINEER.
N SHOW ALL ROOM NUMBERS ON SHOP DRAWING PLANS.
P FLOW TEST DATA FROM 12/14/2024 iNDICATES THE FOLLOWING: STATIC PRESSURE 81.4
PSI. RESIDUAL PRESSURE 77.1 PSI AT 500 GPM. THE HYDRANTS TESTED ARE LOCATED OFF
THE 8" WATER MAIN AT THE CORNER OF PAMMEL DRIVE AND MORRILL ROAD AT AN
ELEVATION OF 971 FEET ABOVE SEA LEVEL. THE CONTRACTOR SHALL PERFORM A FIRE
FLOW TEST IN ACCORDANCE WITH NFPA 291 TO VERIFY THE FLOW TEST DATA GIVEN ABOVE.
THE DATA GIVEN ABOVE SHALL BE THE BASIS OF DESIGN UNLESS THE AVAILABLE PRESSURE
OR FLOW HAS DECREASED. NOTIFY OWNERS REPRESENTATIVE IF FLOW TEST DATA DIFFERS
FROM THE DATA ABOVE. A FIRE PROTECTION ENGINEER OR AN ENGINEER EXPERIENCED IN
WATER FLOW TESTING SHALL PERFORM OR WITNESS THE REQUIRED FLOW TESTING AND
SIGN THE REPORT PRIOR TO THE FIRST SPRINKLER SYSTEM SUBMITTAL.
Q ROUTE SPRINKLER PIPING SUCH THAT IT DOES NOT RUN ABOVE ELECTRICAL PANELS,
SWITCHGEAR, OR SIMILAR EQUIPMENT. SPRINKLER MAINS SHALL NOT RUN THROUGH
ELECTRICAL OR COMMUNICATION ROOMS. SPRINKLER HEADS IN THESE ROOMS SHALL BE
SERVED BY A DEDICATED BRANCH LINE FOR EACH ROOM.
R DRAWING INDICATES A GENERAL PIPING ARRANGEMENT AND SUGGESTED SIZING ONLY.
CONTRACTOR SHALL DETERMINE THE ACTUAL PIPE SIZING REQUIRED AND COORDINATE
WORK WITH ALL OTHER TRADES TO AVOID CONFLICTS.
S CONTRACTOR SHALL PREPARE HYDRAULIC CALCULATIONS BASED UPON THE
CONFIGURATION OF THE ACTUAL SYSTEM DESIGN AS SHOWN ON CONTRACTOR'S SHOP
DRAWINGS.
T ALL FIRE PROTECTION SYSTEM COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH
THE REQUIREMENTS OF NFPA 13 FOR WET-PIPE SPRINKLER SYSTEMS.
U CONTRACTOR SHALL PERFORM HYDRAULIC CALCULATIONS REQUIRED TO VERIFY SYSTEM
MODIFICATIONS PROVIDE ADEQUATE FLOW AND PRESSURE TO EXISTING SYSTEM
COMPONENTS, AS WELL AS TO NEW SYSTEM COMPONENTS.
V COORDINATE SPRINKLER SYSTEM LAYOUT WITH WORK OF OTHER TRADES. SPRINKLER
HEAD LAYOUTS SHALL BE COORDINATED WITH REFLECTED CEILING PLANS AND OTHER
CEILING MOUNTED COMPONENTS. WHERE SPRINKLERS ARE INSTALLED IN LAY-IN CEILINGS,
SPRINKLERS SHALL BE CENTERED IN TILES.
W FURNISH AND INSTALL FIRE SUPPRESSION PRODUCTS IN COMPLIANCE WITH LOCAL
BUILDING CODES AND THE AUTHORITY HAVING JURISDICTION, AND IN ACCORDANCE WITH
GENERALLY ACCEPTED INDUSTRY STANDARDS AND PRACTICES AND MANUFACTURER'S
RECOMMENDATIONS.
X VERIFY ACTUAL LOCATIONS OF SPRINKLER HEADS AND DEVICES WITH ARCHITECTURAL.
REFER TO ARCHITECTURAL PRINTS FOR CEILING HEIGHTS AND TYPES.
KEYNOTE LEGEND
KEY VALUE KEYNOTE TEXT
1 ZONE VALVE ASSEMBLY.
2 NEW SAFETY CABINET LOCATION.
3 PROVIDE STAINLESS STEEL SPRINKLER HEAD INSIDE THIS SAFETY CABINET.
M
C
D
E
F
G
H
I
J
K
1 1/2" FP-W (E)
1 1/2" FP-W (E)
8" FP-W (E)
8" FP-W (E)
4" FP-W (E)
4" FP-W (E)
4" FP-W (E)
4" FP-W (E)
Space
211A
Space
Space
209-210
Space
Space
Space
Space
205 Space
Space
Space
224B
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
285-286
Space
Space
Space
Space
Space
Space
257A
Space
257B
Space
257C
Space
258A
Space
Space
258E
Space
258F
Space
258G
Space
258H
Space
258I
Space
Space
258K
Space
258L
Space
258N
Space
241B
Space
241B
Space
241A
Space
Space
Space
295Space
295A
Space
Space
Space
1 1/2" FP-W (E)
1 1/2" FP-W (E)
1 1/2" FP-W (E)
1 1/2" FP-W (E)1 1/2" FP-W (E)
1 1/2" FP-W (E)1 1/2" FP-W (E)
1 1/2" FP-W (E)
3" FP-W (E)
3" FP-W (E)
4" FP-W (E) 4" FP-W (E) 1 1/2" FP-W (E)
1 1/2" FP-W (E)4" FP-W (E)4" FP-W (E)
4" FP-W (E) 4" FP-W (E) 1 1/2" FP-W (E)
1 1/2" FP-W (E)2" FP-W (E)2" FP-W (E) 1 1/2" FP-W (E)
1 1/4" FP-W (E)
1" FP-W (E)
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
RESOURCE CONSULTING ENGINEERS, L.L.C.
301 ALEXANDER AVE, SUITE C
AMES, IA
515-292-2500
FP1.2
SECOND FLOOR FIRE
SUPPRESSION PLAN
11/16/2026ISSUE SET
11/16/2026
2025.014.00
2415 PAMMEL DR., AMES, IA 50011
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION - METALS
DEVELOPMENT
AUTOMATIC SPRINKLER SYSTEM DESIGN CRITERIA
SYMBOL
OCCUPANCY HAZARD
CLASSIFICATION
DESIGN DENSITY
(GPM/SF) DESIGN AREA
LH LIGHT HAZARD
OCCUPANCY
0.10 1500 SF
OH1 ORDINARY HAZARD,
GROUP 1 OCCUPANCY
0.15 1500 SF
OH2 ORDINARY HAZARD,
GROUP 2 OCCUPANCY
0.20 1500 SF
N
1/8" = 1'-0"
SECOND FLOOR FIRE SUPPRESSION PLAN
FIRE PROTECTION GENERAL NOTES
A PROVIDE ALTERATIONS TO THE EXISTING FIRE PROTECTION SYSTEM AS REQUIRED TO
ACCOMMODATE THE NEW SAFETY CABINETS. PROVIDE A COMPLETE WET TYPE SYSTEM
INCLUDING NEW MAINS, BRANCHES, HEADS, VALVES, AND ACCESSORIES AS REQUIRED.
REUSE EXISTING SYSTEM EQUIPMENT WHERE APPLICABLE. THE SYSTEM SHALL BE
INSTALLED ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS
AND AS PER REQUIREMENTS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT, AND
ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, AND NFPA.
B THE BUILDINGS COMPLETE OPERATIONAL FIRE PROTECTION SYSTEMS SHALL REMAIN IN
PLACE. CONTRACTOR SHALL REPAIR ANY DAMAGE TO SYSTEM CREATED BY THE REMOVAL
OF ANY OTHER MECHANICAL SYSTEMS OR COMPONENTS.
C CONTRACTOR SHALL COORDINATE PHASING OF SPRINKLER WORK WITH THE GENERAL
CONTRACTOR PRIOR TO STARTING WORK.
D PROVIDE A COMPLETE WET TYPE FIRE PROTECTION SYSTEM AS REQUIRED TO
ACCOMMODATE THE FLOOR PLAN AND CEILING TYPES INCLUDING MAINS, BRANCHES,
HEADS, VALVES, AND ACCESSORIES AS REQUIRED. THE SYSTEM SHALL BE INSTALLED
ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS OF THE STATE
BUILDING CODE, LOCAL FIRE DEPARTMENT, AND ALL FEDERAL, STATE, AND LOCAL
AUTHORITIES, NFPA, AND FACTORY MUTUAL.
E THE SPRINKLER SYSTEM SHALL BE DESIGNED BASED UPON ACTUAL WATER FLOW TEST
DATA OBTAINED AT OR NEAR THE JOB SITE.
F REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION REGARDING
SPRINKLER HEAD LOCATION AND PIPE, UNLESS NOTED OTHERWISE.
G COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR PROPER INSTALLATION OF THE FIRE
PROTECTION SYSTEMS ALARM DEVICES INVOLVED WITH FIRE SPRINKLER SYSTEM.
H ALL SPRINKLER SYSTEM PIPING SHALL BE CONCEALED ABOVE THE SUSPENDED CEILING
SYSTEM, UNLESS NOTED OTHERWISE. WRITTEN AUTHORIZATION SHALL BE OBTAINED FROM
THE ARCHITECT PRIOR TO EXPOSING ANY PIPING IN ANY ROOM WHICH HAS A SUSPENDED
CEILING.
J CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SPRINKLER HEADS AS REQUIRED TO
ENSURE AN APPROVED FIRE PROTECTION SYSTEM AT NO ADDITIONAL COST TO THE OWNER.
K AUXILIARY DRAINS SHALL BE EXPOSED WITH 1" DRAIN VALVES. WHEN 5 OR MORE GALLONS
ARE TRAPPED, CONTRACTOR SHALL PROVIDE FIXED PIPING TO AN ADEQUATELY SIZED
RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW OF THE DRAIN. WHEN LESS
THAN 5 GALLONS ARE TRAPPED, A HOSE BIB SHALL BE PROVIDED AT THE DRAIN VALVE.
L AUXILIARY DRAINS SHALL NOT BE LOCATED ABOVE PLASTER OR GYPSUM BOARD CEILING
SYSTEMS.
M AN INSPECTOR'S TEST CONNECTION SHALL BE PROVIDED FOR EACH FIRE SPRINKLER ZONE.
CONTRACTOR SHALL PROVIDE FIXED PIPING FROM THE TEST CONNECTION TO AN
ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW OF THE
TEST. EXTERIOR DISCHARGE OF THE TEST CONNECTION SHALL BE PERMITTED ONLY BY
SPECIFIC WRITTEN INSTRUCTION FROM THE ENGINEER.
N SHOW ALL ROOM NUMBERS ON SHOP DRAWING PLANS.
P FLOW TEST DATA FROM 12/14/2024 iNDICATES THE FOLLOWING: STATIC PRESSURE 81.4
PSI. RESIDUAL PRESSURE 77.1 PSI AT 500 GPM. THE HYDRANTS TESTED ARE LOCATED OFF
THE 8" WATER MAIN AT THE CORNER OF PAMMEL DRIVE AND MORRILL ROAD AT AN
ELEVATION OF 971 FEET ABOVE SEA LEVEL. THE CONTRACTOR SHALL PERFORM A FIRE
FLOW TEST IN ACCORDANCE WITH NFPA 291 TO VERIFY THE FLOW TEST DATA GIVEN ABOVE.
THE DATA GIVEN ABOVE SHALL BE THE BASIS OF DESIGN UNLESS THE AVAILABLE PRESSURE
OR FLOW HAS DECREASED. NOTIFY OWNERS REPRESENTATIVE IF FLOW TEST DATA DIFFERS
FROM THE DATA ABOVE. A FIRE PROTECTION ENGINEER OR AN ENGINEER EXPERIENCED IN
WATER FLOW TESTING SHALL PERFORM OR WITNESS THE REQUIRED FLOW TESTING AND
SIGN THE REPORT PRIOR TO THE FIRST SPRINKLER SYSTEM SUBMITTAL.
Q ROUTE SPRINKLER PIPING SUCH THAT IT DOES NOT RUN ABOVE ELECTRICAL PANELS,
SWITCHGEAR, OR SIMILAR EQUIPMENT. SPRINKLER MAINS SHALL NOT RUN THROUGH
ELECTRICAL OR COMMUNICATION ROOMS. SPRINKLER HEADS IN THESE ROOMS SHALL BE
SERVED BY A DEDICATED BRANCH LINE FOR EACH ROOM.
R DRAWING INDICATES A GENERAL PIPING ARRANGEMENT AND SUGGESTED SIZING ONLY.
CONTRACTOR SHALL DETERMINE THE ACTUAL PIPE SIZING REQUIRED AND COORDINATE
WORK WITH ALL OTHER TRADES TO AVOID CONFLICTS.
S CONTRACTOR SHALL PREPARE HYDRAULIC CALCULATIONS BASED UPON THE
CONFIGURATION OF THE ACTUAL SYSTEM DESIGN AS SHOWN ON CONTRACTOR'S SHOP
DRAWINGS.
T ALL FIRE PROTECTION SYSTEM COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH
THE REQUIREMENTS OF NFPA 13 FOR WET-PIPE SPRINKLER SYSTEMS.
U CONTRACTOR SHALL PERFORM HYDRAULIC CALCULATIONS REQUIRED TO VERIFY SYSTEM
MODIFICATIONS PROVIDE ADEQUATE FLOW AND PRESSURE TO EXISTING SYSTEM
COMPONENTS, AS WELL AS TO NEW SYSTEM COMPONENTS.
V COORDINATE SPRINKLER SYSTEM LAYOUT WITH WORK OF OTHER TRADES. SPRINKLER
HEAD LAYOUTS SHALL BE COORDINATED WITH REFLECTED CEILING PLANS AND OTHER
CEILING MOUNTED COMPONENTS. WHERE SPRINKLERS ARE INSTALLED IN LAY-IN CEILINGS,
SPRINKLERS SHALL BE CENTERED IN TILES.
W FURNISH AND INSTALL FIRE SUPPRESSION PRODUCTS IN COMPLIANCE WITH LOCAL
BUILDING CODES AND THE AUTHORITY HAVING JURISDICTION, AND IN ACCORDANCE WITH
GENERALLY ACCEPTED INDUSTRY STANDARDS AND PRACTICES AND MANUFACTURER'S
RECOMMENDATIONS.
X VERIFY ACTUAL LOCATIONS OF SPRINKLER HEADS AND DEVICES WITH ARCHITECTURAL.
REFER TO ARCHITECTURAL PRINTS FOR CEILING HEIGHTS AND TYPES.
KEYNOTE LEGEND
KEY VALUE KEYNOTE TEXT
1 NEW SAFETY CABINET LOCATION.
CONCEALED SPRINKLER HEAD
CEILING (TYP.)
BRANCH/MAIN PIPE (TYP.)
ARM OVER (TYP.)
RISER NIPPLE (TYP.)
REDUCER (TYP.)
DROP (TYP.)
HANGER (TYP.)
SEMI-RECESSED SPRINKLER HEADEXPOSED SPRINKLER HEAD
1.
2.
NOTES:
NO CONNECTION SHALL BE MADE ON THE BOTTOM OF THE PIPE. TOP CONNECTIONS ONLY.
MOUNT SPRINKLER HEADS IN LAY-IN CEILING IN CENTER OF TILE.
FSP DROP
(TYP.)
THREADED BRASS CONNECTION
INTEGRAL TO GAS CABINET
INTEGRAL SPRINKLER:
160-165F ACTIVATION COATED
WITH WAX FOR PROTECTION IN
CORROSIVE ENVIRONMENTS 30
GPM (K-FACTOR MAY VARY)
REFER TO GAS CABINET
SCHEDULE TO UNDERSTAND
WHAT CABINETS GET A
SPRINKLER HEAD
PROVIDE STAINLESS STEEL
SPRINKLER HEAD IS GAS
CABINET WITH CORROSIVE
RATING ONLY
GAS CABINET
Consultant
Revision Record
Print Record
1615 Golden Aspen Drive Suite 110 Ames, Iowa 50010
515 292 6075 Phone 515 292 6370 Fax mail@rmharchitects.com www.rmharchitects.com
Project Number
RESOURCE CONSULTING ENGINEERS, L.L.C.
301 ALEXANDER AVE, SUITE C
AMES, IA
515-292-2500
FP7.0
FIRE PROTECTION DETAILS &
SCHEDULES
11/16/2026ISSUE SET
11/16/2026
2025.014.00
2415 PAMMEL DR., AMES, IA 50011
SC-27-723
AMES NATIONAL LABORATORY
HAZARDOUS & FLAMMABLE GAS
CABINET INSTALLATION - METALS
DEVELOPMENT
NOT TO SCALE
ARM OVER SPRINKLER DETAIL
NOT TO SCALE
FIRE CABINET CONNECTION DETAIL
T H
C O
CHS
CD
STC
CWR
CWS
HWR
HWS
NG
STM-L
-E
CHR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIN
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
STEAM
RL
RS
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
2"
4"
4"
RHG REFRIGERANT-HOT GAS
MECHANICAL PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE
REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN
THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
LP PROPANE GAS
Room
INVERT: -105' - 1"
1/8" / 12" SLOPE
16"x8"
16"/8"
(E)
F
S
M
B
D
C
16"Ø
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
THROW-150FPM/ 100FPM/ 50FPM
NECK SIZE / MODULE SIZE
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE) NUMBER OF SLOTS /
ACTIVE SLOT LENGTH (PLENUM LENGTH) /
NECK SIZE
DUCT BEING DEMOLISHED
ELEVATION (CENTER OF FACE)
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
CORROSIVE EXHAUST AIR
SMOKE EXHAUST AIR
EXHAUST GAS FLUE
COMBUSTION AIR
CONDITIONED OUTSIDE AIR
48"x2 1/2"
SLB3 400
10" / 24x24
SD3 300
12" / ---
SD9 400
LINEAR BAR GRILLE
LINEAR SLOT
DIFFUSER
PERFORATED
DIFFUSER WITH
DEFLECTORS
ROUND DIFFUSER
WITH ADJUSTABLE
PATTERNS
LOUVERED DOUBLE
DEFLECTION GRILLE 12"x10"
SG5 500
TYPE (SEE SCHEDULE)
10" / 24x24 H-5/7/1422
SD1 400
3-CONE DIFFUSER
THROW PATTERN
MAX NC RATING
1 / 4' - 0" / 8"
LSD1 200
8' - 0"AFF
1 / 4' - 0" / 8"
LSD1 200
6' - 0"
1 / 4' - 0" / 8"
LSD1 200
SECTION TOTAL TRACK LENGTH
12"x10" / 24x12
RG11 500
LOUVERED GRILLE
12"x10" / 24x24
RG2 500
EGGCRATE RETURN
GRILLE
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
SHUTOFF BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
DATA DEVICE TAGS
DAMPER TAGS
EQUIPMENT ID
SYMBOL
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
EQUIPMENT ABBREVIATIONS
A AMPS
AAV AUTOMATIC AIR VENT
ABV ABOVE
AC AIR CONDITIONING
ADJ ADJUSTABLE
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BAS BUILDING AUTOMATION SYSTEM
BFF BELOW FINISHED FLOOR
BLW BELOW
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
°C DEGREES CELSIUS
CAP CAPACITY
CB CATCH BASIN
CC COOLING COIL
CEA CORROSIVE EXHAUST AIR (LAB/GENERAL)
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTERLINE
CLG CEILING
CO CLEAN OUT
COD CENTER OF DUCT
COND CONDENSATE/CONDENSER
COP CENTER OF PIPE
CS CARBON STEEL
CU COPPER
CV CONSTANT VOLUME
CW COLD WATER
D DEGREE
DB DRY BULB
DBA A-WEIGHTED DECIBELS
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DP DIFFERENTIAL PRESSURE
DN DOWN
DT DIFFERENTIAL TEMPERATURE
DW DISTILLED WATER
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB TEMPERATURE
EFT ENTERING FLUID TEMPERATURE
EG ETHYLENE GLYCOL
EL ELEVATION
ELEC ELECTRICAL
EQUIP EQUIPMENT
ERV ENERGY RECOVERY VENTILATION
ESP EXTERNAL STATIC PRESSURE
ETR EXISTING TO REMAIN
EWB ENTERING WET BULB TEMPERATURE
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATUR
EXH EXHAUST
EXST EXISTING
°F DEGREES FAHRENHEIT
FC FAIL CLOSED
FCO FLOOR CLEANOUT OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FH FUME HOOD
FL FAIL LAST POSITION
FL FLOOR
FLA FULL LOAD AMPS
FO FAIL OPEN
FO FUEL OIL
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD COMBINATION FIRE/SMOKE DAMPER
FT FOOT OR FEET
FTG FOOTING
GA GAGE
GAL GALLONS
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H ENTHALPY
HB HOSE BIBB
HD HUB DRAIN
HP HORSEPOWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
HZ HERTZ
ID INDIRECT
IN INCH OR INCHES
INV INVERT
KW KILOWATTDV
KWH KILOWATT-HOURS
LAT LEAVING AIR TEMPERATURE
LB POUND OR POUNDS
LB/HR POUND PER HOUR
LBS POUNDS
LDB LEAVING DRY BULB TEMPERATURE
LF LINEAL FOOT/LINEAL FEET
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LRA LOCKED ROTOR AMPS
LVR LOUVER
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCF ONE THOUSAND CUBIC FEET
MCP MAXIMUM OVERCURRENT
PROTECTION (ALSO MOCP)
MD MOTORIZED DAMPER
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL AND
PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANOUS
MTR MOTOR
NA NOT APPLICABLE (ALSO N/A)
NC NORMALLY CLOSED
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NPS NOMINAL PIPE SIZE
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
O OXYGEN
OC ON CENTER
OED OPEN ENDED DUCT
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED, OWNER
INSTALLED
OV OUTLET VELOCITY
PC PLUMBING CONTRACTOR
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PG PROPYLENE GLYCOL
PH PHASE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSF POUNDS PER SQUARE FOOT
PSI PONDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
QTY. QUANTITY
RCP REFLECTED CEILING PLAN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RM ROOM
RPM REVOLUTIONS PER MINUTE
SCH SCHEDULE
SD SMOKE DAMPER
SF SQUARE FEET
SM SURFACE MOUNT
SP STATIC PRESSURE
STM STEAM
SS STAINLESS STEEL
TC TEMPERATURE CONTROL
TD TEMEPRATURE DROP
TEMP TEMPERATURE
TEMP TEMPORARY
TOD TOP OF DUCT
TOP TOP OF PIPE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UG UNDERGROUND
V VENT
V VOLTS
VAC VACUUM
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VFD VARIABLE FREQUENCY DRIVE
VP VELOCITY PRESSURE
W WASTE
WB WET BULB
WC WATER COLUMN
WCO WALL CLEAN OUT
WG WATER GAUGE
WH WALL HYDRANT
W/ WITH
WMS WIRE MESH SCREEN
ABBREVIATIONS
SA
SOA
OA
RA
TA
EA
RLA
CEA
SEA
FLUE
CA
T.O.D. (5' - 6")
TOP TAKEOFF
BOTTOM TAKEOFF
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FOS
FOR
FOV
ELBOW
PLAQUE DIFFUSER
ELBOW-RADIUS
ELBOW-MITERED
BOTTOM TAKE-OFF
TOP TAKE-OFF
TAKE-OFF
DUCT TRANSITION
AC AIR-COOLED CHILLER
ACCU AIR COOLING CONDENSING UNIT
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CB…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .