Fire Alarm Replacement - Phase 2 - Addendum 02.pdf

PDF 54 KB Posted

Attached to
RFP SC-25-664 Fire Alarm Replacement Phase 2
Solicitation number
RFP-SC-25-664
Issued by

About this file

This document is an Addendum (Number 002) to a Request for Proposal (RFP SC-25-664) for the Fire Alarm Replacement – Phase 2 project at Ames National Laboratory. The addendum, dated April 29, 2025, modifies specifications for the digital, addressable fire-alarm system installation, specifically updating requirements for installer qualifications and certifications. Key changes include referencing Division 26 for additional material and installation requirements, and specifying NICET certification levels for Johnson Controls (JCI) workers, including a requirement for a State of Iowa Fire Alarm System Installer License for workers programming, testing, and commissioning the system.

The addendum applies to the project manual section 28 31 11 and clarifies that NICET certification does not apply to electricians installing conduit, j-boxes, pulling/terminating wire, or installing devices. It mandates that JCI project managers overseeing the installation must possess a NICET II certification, the JCI Foreman must have a NICET II and thorough understanding of the specification, and all JCI workers performing the installation must have a NICET Level I certification. The bid due date remains April 30, 2025, and the document consists of two pages with no changes to drawings or additional product systems.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BBS 24044 / April 29, 2025 ADDENDUM NUMBER 002

Fire Alarm Replacement – Phase 2

Ames National Laboratory

ADDENDUM NUMBER 002

ADDENDUM DATE: April 29, 2025

PROJECT: Fire Alarm Replacement – Phase 2

RFP SC-25-664

BID DUE DATE: April 30, 2025

The information contained in this Addendum modifies, supplements or replaces information contained in the Bidding Documents dated March 31, 2025 and is hereby made a part of the

Contract Documents.

Acknowledge receipt of this Addendum by inserting its number on the Proposal Form.

Addendum consists of 2 pages.

ADDENDUM INDEX

GENERAL ITEMS None.

APPLICABLE TO THE PROJECT MANUAL: Item #1.

APPLICABLE TO THE DRAWINGS: None.

ADDITIONAL ACCEPTABLE PRODUCTS AND SYSTEMS None.

ATTACHMENTS: None.

GENERAL ITEMS

None.

APPLICABLE TO THE PROJECT MANUAL

ITEM #1 SECTION 28 31 11 – DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

A. CHANGE Paragraph 1.3.A to the following: Reference Division 26 for additional material and installation requirements related to equipment, pathways and wiring. NICET certification identified in Paragraph 1.3.B does not apply to electricians installing conduit and j-boxes under Division

26. NICET certification also does not apply to electricians pulling/terminating wire and installing devices.

B. CHANGE Paragraph 1.3.B to the following: Installer: Company specializing in alarm and detection systems with five years’ documented experience in the installation and maintenance of fire alarm systems.

State of Iowa Fire Alarm System Installer License is required for all JCI workers programming, testing and commissioning the system. NICET II required for all JCI project managers overseeing the installation of the fire alarm system. JCI Foreman/equivalent shall possess a NICET II and shall have a thorough understanding of this specification and follow all

BBS 24044 / April 29, 2025 ADDENDUM NUMBER 002

Fire Alarm Replacement – Phase 2

Ames National Laboratory specification requirements. NICET Level I required for all JCI workers performing the installation.

THE DRAWINGS

None.

ADDITIONAL ACCEPTABLE PRODUCTS AND SYSTEMS

ATTACHMENTS:

END OF ADDENDUM 002

Issued April 29, 2025